Type Test Report
Serial No.:
Customer:
Customer ref .:
Rating:
V Hz kW r/min A cos j Duty
3~Motor 690 Y 50 30,0 1474 32,8 0,83 S1
Insul.cl.F 400 D 50 30,0 1474 56,5 0,83 S1
IP55 415 D 50 30,0 1477 55,7 0,81 S1
400 D 50 30,0 1776 50,3 0,84 S1
Ef f class IE2 460 D 60 30,0 1777 48,6 0,83 S1
Thermal test ( 100% load ) 194,2 400 D 50 56,5 32,65 30,00 1476 0,83 91,88
Ambient Temperature : 21 2
These tests have been carried out on motor no. 3GV1110790499001, on date 2012-02-21
which is identical in electrical design with the above.
Manuf actured and tested in accordance with rules of IEC 60034-1 and IEC 60034-2-1.
PLL determined f rom residual loss.
On behalf of customer