Professional Documents
Culture Documents
Electric Power Systems Research: Aushiq Ali Memon, Kimmo Kauhaniemi
Electric Power Systems Research: Aushiq Ali Memon, Kimmo Kauhaniemi
a r t i c l e i n f o a b s t r a c t
Article history: One of the main technical issues in the practical implementation of a Microgrid is the design of the proper
Received 8 December 2014 protection scheme. The scheme must be capable to meet the basic protection requirements of selectiv-
Received in revised form 27 May 2015 ity, sensitivity and reliability not only in grid-connected mode but also in islanded mode of operation.
Accepted 9 July 2015
Since the introduction of Microgrid concept, many researchers have introduced various new protection
Available online 1 August 2015
schemes to be incorporated in medium and low voltage Microgrids. Most of the researchers agree that
the conventional protective devices usually based on overcurrent principle are inadequate to provide
Keywords:
complete protection for Microgrids during both grid-connected and islanded mode of operation, hence
AC Microgrid
Protection issues
new protection techniques based on other principles must be developed. The new protection schemes
Protection schemes should be not only adaptable according to operational modes of Microgrid but also sensitive enough to
Islanded mode detect and clear the lowest possible fault currents within Microgrid quickly ensuring minimum supply
Grid-connected mode disruption to consumers. This paper briefly reviews protection issues in AC Microgrids and presents state
of the art protection schemes for AC Microgrids developed and proposed so far. It also gives a critical
analysis of each proposed method and categorizes the protection issues and schemes on the basis of
operational modes of AC Microgrid. At the end, it has been concluded that more effort is still needed to
overcome the limitations of proposed protection schemes and to improve reliability of communication
system for adaptive protection schemes or provide alternate means to cope with communication failures.
Moreover, protection against cyber-attacks is crucial for safe and secure operation of future Microgrids.
© 2015 Elsevier B.V. All rights reserved.
Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2. Protection issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.1. Protection coordination (selectivity) with DG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.2. Protection issues in Microgrids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.2.1. Selection of protection device/switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.2.2. Spurious separations or false trips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.2.3. Re-synchronisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.2.4. Events/faults during grid-connected mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.2.5. Events/faults during islanded mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.2.6. Anti-islanding protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.2.7. Role of Microgrid control architecture in protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3. Protection schemes for Microgrids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.1. The protection schemes for only grid-connected mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.2. The protection schemes for only islanded mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.3. The protection schemes for both grid-connected and islanded mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
http://dx.doi.org/10.1016/j.epsr.2015.07.006
0378-7796/© 2015 Elsevier B.V. All rights reserved.
24 A.A. Memon, K. Kauhaniemi / Electric Power Systems Research 129 (2015) 23–31
protection must be to disconnect the faulty portion from the rest of of noise in voltage/current signal may further degrade the per-
system as quick as possible and how it is done depends on the fea- formance of proposed relay and the setting of threshold values is
tures and complexity of Microgrid and the protection strategy used not clearly mentioned. The potential application of synchronised
[2]. There may be some non-fault cases resulting in low voltages phasor measurements using phasor measurement units (PMUs)
at PCC like voltage unbalances and non-fault open phases which and global positioning system (GPS) at either side of PCC for Loss-
are difficult to be detected and may potentially create hazards of-Mains detection is mentioned in [25]. The high capital cost of
for sensitive loads, microsources etc. Therefore, some protection PMUs makes this scheme uneconomical [25]. Moreover, possibility
mechanisms must be developed to avoid such situations [1]. of GPS signal loss or impairment causing clock drift consequently
make PMUs less accurate (or function incorrectly) and less reli-
2.2.5. Events/faults during islanded mode able, therefore PMUs with back-up clock functionality will be
When Microgrid operates in islanded mode, the nature of prob- required [29].
lems becomes completely different from that of grid-connected
mode. In grid-connected mode, the fault currents of higher mag-
2.2.7. Role of Microgrid control architecture in protection
nitudes (10–50 times the full load current) are available from the
Microgrid configuration may change due to various control
utility grid in order to activate conventional OC protection devices.
actions like load-shedding in peak-hours or increase in local gen-
On the contrary, for a stand-alone Microgrid the fault current of
eration for export to grid for optimum and economical operation of
about five times the full load current is available [1]. When a large
Microgrid. Therefore, adaptive protection system will be required
number of converter-based DERs are connected in Microgrid, the
to change protection relay settings dynamically according to chang-
fault currents of only 2–3 times the full load current (or even less
ing configuration of Microgrid. Adaptive protection scheme can be
depending on control method of converter [22]) are available [23].
implemented with centralised or decentralised control approaches,
The conventional OC protection devices are usually set to operate
but each approach requires different communication architecture.
at 2–10 times the full load current. Hence, due to this drastic reduc-
The centralised control architecture for adaptive protection is the
tion of fault level, the time-current coordination of OC protective
conventional method. In this method, a central controller coordi-
devices is disturbed; the high-set instantaneous OC devices and OC
nates the protection settings. However, failure of central controller
devices with extremely inverse characteristics like fuses are most
causes full loss of adaptive protection and therefore, redundancy
likely to be affected [1].
in central controller is required. The centralised communication
architecture is supported by various communication protocols like
2.2.6. Anti-islanding protection
Modbus, DNP3, IEC 60870-5-101/104, IEC 61850 and it can be
Another important consideration for islanding mode of oper-
implemented with serial/bus communication, over PLC (power-line
ation is related with anti-islanding (or Loss-of-Mains) protection
carrier) or via Ethernet network. The decentralised control archi-
of DERs. The deactivation of anti-islanding protection is generally
tecture depends on information exchange between distributed
required if the amount of microsource generation within Microgrid
intelligent electronic devices (IEDs). Each IED acts autonomously
is very high. If anti-islanding protection is kept activated then there
after receiving information from other IED to change its active set-
is chance that it may cause uncontrolled islands within Microgrid
ting group. The decentralised architecture is only feasible when the
due to its fast tripping. Hence, it will be desirable to deactivate
communication protocol allows direct communication between
anti-islanding protection instantly when an isolated Microgrid is
IEDs. Presently, the industry is focused on IEC 61850 as the stan-
detected to be formed, to do that, DERs must have FRT capa-
dard protocol for decentralised communication. The decentralised
bility to cope with voltage and frequency transients caused by
architecture requires a bus or Ethernet network for implementa-
islanding [1,21]. As reported in [1], the most reliable and fast
tion, though it can also be implemented with 4G wireless network
method to deactivate anti-islanding protection of DERs is to send
or over PLC [30].
a trip blocking signal through Microgrid central controller using
The earlier research shows that traditional protection devices
communication link. The fast and reliable method for islanding
with single setting are incompatible with Microgrid protection phi-
detection is necessary for a stable operation of Microgrid. The
losophy which ensures safe and secure operation of Microgrid in
islanding detection methods are generally divided into three cat-
both the grid-connected and islanded mode of operation. Hence
egories: Passive, active and telecom-based [24]. Various passive
it becomes inevitable to look for alternate means and methods
and active Loss-of-Mains detection methods and algorithms have
of faults detection and isolation which can work equally well in
been reported in [25–27]. Passive islanding detection methods
both grid-connected and islanded mode of operation, that is, new
are preferred over active methods due to factors of speed, reli-
protection schemes must be adaptable [1,2,31,32]. The new pro-
ability and power quality, whereas, telecom-based methods are
tection schemes should not only consider the reduction in fault
more complex and costly as compared with passive methods. How-
levels but also consider the chances of bidirectional fault current
ever, some passive islanding detection methods based on measured
flow in some feeders [1]; besides, the new protection schemes
electrical quantities like voltage and frequency may fail or take
should also use communication links to ensure fast and reliable
longer time to detect islanding when generation and loads in
operation.
Microgrid are nearly equal [24,28]. To solve this problem, a new
passive islanding detection method based on pattern recognition
approach for the extracted current and voltage transient signals 3. Protection schemes for Microgrids
(at DG terminals) generated during disconnection of the main grid
is proposed in [28]. The method uses discrete wavelet-transform A critical review of some proposed protection schemes in the
and classification technique (decision-tree (DT) classifier) to extract recent scientific literature is presented in this section. The protec-
current and voltage signal energies (detail coefficients) in various tion schemes are divided into three main categories: the schemes
frequency bands. The transient detector is used to trigger the clas- for only grid-connected mode, the schemes for only islanded mode
sifier after a delay of 0.01 s if the value of the detail coefficient and the schemes for both grid-connected and islanded mode.
exceeds a pre-set threshold value. The performance of the pro- Tables 1 and 2 summarise the protection schemes for only islanded
posed method has been compared with other passive methods in mode and the protection schemes for both grid-connected and
[24]. The response time of the proposed DT relay is (30–48) ms islanded mode respectively with advantages/limitations of each
for various islanding events and DG types. However, high level scheme.
A.A. Memon, K. Kauhaniemi / Electric Power Systems Research 129 (2015) 23–31 27
Table 1
Protection schemes for only islanded mode.
No. Protection scheme Applied methods/functions Test system features Faults Advantages/limitations
1. Harmonic content THD and frequency C-DGs Constant MVA OHL radial 11/0.48 kV LLG Difficult to assess THD
based protection measurement of converter threshold values for different
scheme [39] voltages, communication fault types, possibility of relay
link between relays trip failure when more
dynamic loads are connected
or if some DGs with pure
voltage output, sensitivity
problems with varying fault
impedances
2. Voltage based abc-dq0 transformation of C- DGs Constant MVA OHL radial 11/0.48 kV LLL, LL, LG Single-pole tripping and high
protection scheme DGs output voltages and impedance faults are not
[40] communication link considered, trip decision
between relays. depends on communication
link
3. Symmetrical OC relays, static switch at C- DGs kW - 0.48 kV LG, LL No use of communication link
component and PCC, zoning principle. and provides full protection
residual current from LG and LL faults.
based scheme [41] However, three phase and high
impedance faults and single
pole tripping not considered
4. Adaptive IEDs (voltage, current, C- DGs Constant MVA OHL radial 20 kV – Adaptable to operational
protection scheme directional OC modes of Microgrid but highly
[21] measurements with dependent on communication
interlocking), high speed link, detailed simulation
communication link, results for particular types of
zoning. faults are not discussed
3.1. The protection schemes for only grid-connected mode 3.2. The protection schemes for only islanded mode
A protection coordination scheme based on OC principle and A protection scheme based on monitoring of harmonic con-
time dependent characteristics of current to prevent high fault tent of C-DGs in an islanded Microgrid is proposed in [39]. In this
clearing times and maximizing DG connection to MV distribution scheme the total harmonic distortion (THD) of the voltage at the
networks is presented in [33]. This strategy provides extra benefit converter terminal of the DG is continuously monitored by the pro-
of running extensive radial networks with directly-coupled DGs (D- tection relay and when THD exceeds a threshold value during a
DGs) or closed-loop networks with converter-based DGs (C-DGs). fault, the converter gets a shutdown by the relay. The variation
However, this scheme is unclear about high impedance faults (HIF) of the amplitude of fundamental frequency of the faulted phase
and is more effective with increased number of relays. An adap- is used to detect the fault type (the frequency of faulted phase is
tive overcurrent pickup strategy for MV feeder with C-DGs and dropped as compared to sound phase) and comparison of THD of
radial overhead line (OHL) has been proposed in [18]. This scheme voltage between sound and faulted phase is used to identify the
updates the OC relay minimum pickup current on the basis of the fault location (faulted phase has greater THD than sound phase).
fault analysis of the system. However, this scheme is more effec- The relay with more THD is considered to be in fault zone or nearer
tive when some of DGs are disconnected. A protection strategy to the fault location and has to trip in order to clear the fault. How-
using conventional OC relays with definite time grading for a LV ever, for correct relay to trip, relays must be synchronised using
Microgrid with both D-DGs and C-DGs connected to OHL and cable communication link.
network has been presented in [34]. The proposed scheme does A voltage based protection scheme for islanded Microgrids con-
not use any communication link and can be applied without any taining C-DGs is proposed in [40]. The scheme monitors the output
modification of existing protection system, hence it is economical. voltages of DGs and transforms them into dc quantities using d–q
An intelligent agent based protection scheme for radial OHL dis- frame of reference. Any type of disturbance in DGs output voltages
tribution system without DG and for closed loop system with DG due to network faults is reflected as a disturbance in d–q quantities.
is proposed in [35]. The scheme assumes peer to peer communica- The scheme utilizes the concept of zones and uses communication
tion between IEDs. The scheme provides higher speed of back up link between relays in order to discriminate between the faults
protection as compared to conventional protection, autonomous inside and outside of the zone. The considered scheme has been
system monitoring and adjustment of parameters, but needs high verified with the help of simulations for different types of faults at
speed communication. various locations. However, HIF and single-pole tripping have not
In [36,37], it has been proposed to use a fault current limiter been taken into account.
(FCL) in series with DG unit in order to limit the fault current con- A protection scheme based on the principle of symmetrical com-
tribution from DG during fault and thus return the system to its ponents and residual current measurement for islanded operation
original state as if no DG was connected. In this way original direc- of Microgrid is proposed in [41]. In the paper the term “differ-
tional OC relay settings can be used without disconnection of DG. ential current” is applied, but the principle is same as in the
The use of TCSC (thyristor controlled series capacitor) as an FCL common residual current devices. The proposed scheme uses resid-
has been proposed in [38]. The FCLs offer many advantages like no ual current devices as primary protection of LG faults for the zones
DG disconnection, use of original relay settings, avoid upgrading upstream the faults and zero sequence current as primary protec-
of equipment for handling large currents. But impedance of FCL tion of LG faults for the zones downstream of the fault. The negative
increases with increase in individual DG capacity hence its cost sequence current is used as primary protection for LL faults. I2 t pro-
increases. Moreover transient response of FCL is another concern. tection is used as primary backup for both LG and LL events and
28
Table 2
Protection schemes for both grid-connected and islanded mode.
1. Adaptive Numerical directional D-DGs Constant MVA Cable radial 6/0.4 kV LLL, LL, LG High implementation cost,
directional OC relays with simulation results only for
overcurrent directional interlocking D-DGs, HIF not considered,
protection [42] capability Centralized control is used for
protection settings, needs
A.A. Memon, K. Kauhaniemi / Electric Power Systems Research 129 (2015) 23–31
communication
2. Differential OC relays and C-DGs and D-DGs – OHL and cable, MV LG, LLL Economical (traditional OC
protection communication link radial relays and existing
scheme[47] communication link), but
ineffective when loads are
unbalanced
3. Current travelling Bus bar voltages for – – – 10/0.4 kV – Unaffected by power flow, fault
waves based faults detection and current, load unbalance,
scheme [54] current travelling plug-and-play generators and
waves for fault location independent of Microgrid
operational mode but no
simulation results
4. Multi-agent Network zoning, IEDs, D-DGs Constant MVA OHL radial 24.9 kV LG, LLG-HIF No central data processor, no
protection schemes communication link, voltage transformers, no time
[43] wavelet coefficients of synchronized measurements,
transient current for less computation, effective for
fault location all types of faults including HIF,
but requires means to
differentiate between fault and
switching transients to avoid
false trips, needs high speed
communication
5. Inverse-time Inverse–time C-DGs Constant MVA OHL radial and 11 kV LLL, LL, LG, LLG No use of communication link,
admittance- based admittance relay, closed loop slow tripping for high
protection scheme directional element, impedance faults and higher
[51] zoning DG infeed, measurement errors
due to fundamental extraction
because of harmonics,
transients and decaying dc
components
6. Pattern recognition Time-frequency C-DGs and D-DGs Constant MVA OHL radial and 25 kV LLL, LL, LG, LLG, More robust than current
based scheme transform closed loop LLLG HIF differential scheme, immune to
[52,53] (S-transform), spectral noise and less sensitive to
energy contours, synchronisation error, uses
calculation of both time and frequency
differential energy information (more data for
decision making), proposed for
wide area protection
A.A. Memon, K. Kauhaniemi / Electric Power Systems Research 129 (2015) 23–31 29
under-voltage as secondary protection if I2 t protection fails due to multi-agent approach has been proposed for MV smart grid. The
insufficient current levels. proposed method is adaptable and is based on distributed intelli-
An adaptive protection scheme based on telecommunication gence but can be made adaptable through centralised intelligence.
and modern protection relays or IEDs for Microgrid with C-DGs A comparison between directional OC protection and distance
is presented in [21]. The scheme has been applied to MV feeder protection with the help of PSCAD simulations has been presented
divided into four protection zones and between each zone a cir- in [45]. It is concluded that distance protection performs better than
cuit breaker is installed which is controlled by an IED, the DG units directional OC protection. Therefore, an adaptive protection based
are also provided with IEDs. The IEDs are provided with voltage on directional OC protection for the grid-connected and distance
and currents measurements as well as directional OC protection protection for the islanded mode of Microgrid has been suggested.
function and are connected with each other through high speed
communication links. The proposed method uses voltage measure- 3.3.2. Differential protection schemes
ments for fault detection and current direction for fault location. One differential protection scheme using communication-
In the proposed method, complete system selectivity and speed is assisted digital relays working on the principle of synchronised
obtained through transfer of fault direction and interlocking infor- phasor measurements has been suggested in [46] for MV Micro-
mation between IEDs using communication based on IEC 61850. grids embedded with both D-DGs and C-DGs. Instantaneous
differential protection is used as the primary protection and
adjacent relays are used as backup in case of breaker failure. Com-
3.3. The protection schemes for both grid-connected and islanded parative voltage protection is used as tertiary protection in case
mode of relay or communication failure. The suggested scheme is also
capable of detecting HIF. However, the proposed scheme is uneco-
3.3.1. Adaptive protection schemes nomical to implement and assumes advanced technical features
An adaptive protection scheme based on the principle of net- that are still not available in the present state-of-the-art equipment
work zoning is presented in [13]. Zoning of the feeders is done like high performance relays and breakers as well as high sensitive
in a way that each zone has appropriate balance DG and load current transformers.
with DG capacity slightly larger than load. Moreover, in each zone In [47], a protection strategy based on the principle of differen-
at least the largest DG is equipped with load frequency control tial current and utilizing traditional OC relays and communication
capability. After zoning, some fast operating switches equipped link has been advised for MV Microgrids having both D-DGs and
with synchronisation-check relays and having capability to receive C-DGs. This scheme offers economical implementation, but not
remote signals from sub-station breaker are placed between each of effective during unbalanced load.
two zones. A computer-based relay having high processing power, A differential protection scheme is suggested in [48] as a means
large storage capacity and capability to communicate with zone of primary protection for MV Microgrid with C-DGs and closed loop
breakers and DG relays is installed at sub-transmission sub-station. OHL for both the grid-connected and islanded mode of operation.
This computer-based relay has to perform the functions of online The scheme uses OC and under voltage based protection schemes as
fault detection and isolation of faulted zone by tripping the appro- backup protection in case of breaker or communication link failure.
priate zone breaker and DG connected to that zone. In addition, Current differential relays are used for feeder and bus protection
sub-station relay has to perform the reclosing in case of temporary while DGs are protected using under voltage, reverse power flow,
faults in any of the zones. The scheme is not suitable for systems over voltage and synchronism check relays. This scheme may suffer
with low DG penetration and to a great extent depends on cen- problems due to switching transients and unbalanced loads.
tralised relay and communication links. The need of continuous
synchronised current measurements at each circuit breaker and 3.3.3. Distance protection schemes
DG location with the help of GPS and PMU make this scheme quite A distance protection scheme has been presented in [49] for
expensive. Microgrid with C-DGs. The performance of distance relays with
An adaptive protection scheme employing numerical direc- Mho characteristic has been evaluated in a radial feeder system for
tional OC relays with directional interlocking capability for unbalanced (LG, LL, LLG) faults using PSCAD simulations and MAT-
Microgrid with both D-DGs and C-DGs is proposed in [42]. The LAB calculations. A method of converter control is proposed to limit
scheme is based on Microgrid central controller which updates the the converter current by reducing the voltage in the faulty phase(s)
protection settings according to Microgrid operational mode using while keeping the voltage of healthy phases unaltered. The effects
advanced communication link ensuring fast tripping. of fault resistance and load are considered on the Mho characteris-
A multi-agent based protection scheme using a wavelet trans- tic. It has been observed that the relay downstream to the fault
form technique is presented in [43] for distribution system with operates unnecessarily for ground faults when a star-connected
DGs. The scheme divides the network into several segments and load is connected downstream to the fault and low fault impedance
relay agents are installed at interconnection points between these appears at the fault point. To alleviate this problem the addition
segments. The relay agents detect and isolate the fault through of a directional feature to the distance relay has been suggested.
communication with neighbouring agents. The faulted zone is To solve the same problem, a negative sequence impedance anal-
determined through feedback signals from current transformers ysis has been done at each distance relay location in [50]. It has
(CTs) installed at interconnected branches which measure the cur- been found that reactive part of negative sequence impedance can
rent leaving the node. From the measurement of transient currents, be used to discriminate forward and reverse faults effectively for
wavelet transform coefficients are calculated and on the basis of radial networks with C-DGs.
the sign of the wavelet transform coefficients a fault is assigned An inverse time admittance-based relay is proposed in [51]
to be internal or external. If the wavelet transform coefficients of for radial distribution system with several C-DGs. The proposed
the currents measured at all points have the same sign, the fault is scheme is capable of detecting fault currents even with lower
categorised as internal fault, otherwise considered as an external magnitudes. In this scheme, first of all a normalized admittance
fault. A relay agent diagnoses a fault on its bus bar as an internal is obtained, then this normalized admittance is used to obtain
fault and immediately trips all circuit breakers connected to the bus an inverse time tripping characteristic of relay. The relay trips
bar to clear the fault and communicates its decision to other relay when the normalized admittance becomes greater than 1.0 or
agents. In [44], a new adaptive relay protection concept based on the measured admittance becomes greater than total admittance
30 A.A. Memon, K. Kauhaniemi / Electric Power Systems Research 129 (2015) 23–31
References [30] N. Hatziargyriou, Microgrids: Architectures and Control, John Wiley & Sons,
West Sussex, UK, 2013.
[31] A.R. Haron, A. Mohamed, H. Shareef, A review on protection schemes and coor-
[1] S. Chowdhury, S.P. Chowdhury, P. Crossley, Microgrids and active distribution
dination techniques in Microgrid systems, J. Appl. Sci. 12 (2) (2012) 101–112
networks, in: IET Renewable Energy Series 6, The Institution of Engineering and
(Asian Netw. for Scientific Inf.).
Technology, London, United Kingdom, 2009.
[32] H.J. Laaksonen, Protection principles for future microgrids, IEEE Trans. Power
[2] R. Lasseter, et al., Integration of distributed energy resources, in: The CERTS
Electron. 25 (2010) 2910–2918.
Microgrid Concept, Lawrence Berkeley National Lab, 2002.
[33] J. Jager, T. Keil, L. Shang, R. Krebs, New protection co-ordination methods in the
[3] N. Hatziargyriou, H. Asano, R. Iravani, C. Marnay, Microgrids, IEEE Power Energy
presence of distributed generation, in: Eighth IEE International Conference on
Mag. 5 (2007) 78–94.
Developments in Power System Protection. 1, 2004, pp. 319–322, 2004.
[4] D. Infield, F. Li, Integrating micro-generation into distribution systems—a
[34] N. Jenkins, et al., Large Scale Integration of Micro-Generation to Low Voltage
review of recent research, in: IEEE Power and Energy Society General
Grids, Work Package E, Deliverable DE2, Protection Guidelines for a Micro-
Meeting—Conversion and Delivery of Electrical Energy in the 21st Century,
grid, 2005, pp. 1–370, http://www.microgrids.eu/micro2000/delivarables/
2008, pp. 1–4.
deliverable de2.pdf. (Contract no: ENK5-CT-2002-00610).
[5] R.H. Lasseter, P. Paigi, Microgrid: a conceptual solution, in: IEEE 35th Annual
[35] Y.T. Jin, S.J. Park, S.J. Lee, M.S. Choi, Intelligent agent based protection for smart
Power Electronics Specialists Conference, PESC 04, 2004, pp. 4285–4290, 6.
distribution systems, in: CIRED 21st International Conference on Electricity
[6] IEEE, IEEE Guide for Design, Operation, and Integration of Distributed Resource
Distribution, 6–9 June, 2011, Frankfurt, 2011 (Paper No. 0383).
Island Systems with Electric Power Systems, IEEE Std 1547. 4-2011, 2011, pp.
[36] W. El-Khattam, T.S. Sidhu, Restoration of directional overcurrent relay coor-
1–54.
dination in distributed generation systems utilizing fault current limiter, IEEE
[7] A.P.S. Meliopoulos, Challenges in simulation and design of Grids, in: IEEE
Trans. Power Delivery 23 (2008) 576–585.
Power Engineering Society Winter Meeting, 2002, pp. 309–314, 1.
[37] W. El-Khattam, T.S. Sidhu, Resolving the impact of distributed renewable gen-
[8] R.C. Dugan, Distributed resources and reliability of distribution systems, in:
eration on directional overcurrent relay coordination: a case study, IET Renew.
IEEE Power Engineering Society Summer Meeting, 2002, pp. 105–108, 1.
Power Gener. 3 (2009) 415–425.
[9] F. Katiraei, M.R. Iravani, P.W. Lehn, Micro-grid autonomous operation during
[38] M. Khederzadeh, Application of TCSC to restore directional overcurrent relay
and subsequent to islanding process, IEEE Trans. Power Delivery 20 (1) (2005)
coordination in systems with distributed generation, in: CIRED 20th Interna-
248–257.
tional Conference on Electricity Distribution, 8–11 June, 2009, Prague, 2009
[10] B. Kroposki, R. Lasseter, T. Ise, S. Morozumi, S. Papatlianassiou, N. Hatziargyriou,
(Paper 0041).
Making microgrids work, IEEE Power Energy Mag. 6 (2008) 40–53.
[39] H. Al-Nasseri, M.A. Redfern, Harmonics content based protection scheme
[11] J. Gers, T. Holmes, Protection of Electricity Distribution Networks, second ed.,
for Micro-grids dominated by solid state converters, in: Power System
Peter Peregrinus Ltd, London, 2005.
Conference, 2008. MEPCON 2008. 12th International Middle-East, 2008,
[12] M.H. Aslinezhad, S.M. Sadeghzadeh, J. Olamaei, Overcurrent relays protective
pp. 50–56.
coordination in distribution systems in presence of distributed generation, Int.
[40] H. Al-Nasseri, M.A. Redfern, F. Li, A voltage based protection for micro-grids
J. Tech. Phys. Prob. Eng. (IJTPE) 3 (June) (2011) 40–46.
containing power electronic converters, in: IEEE Power Engineering Society
[13] S.M. Brahma, A.A. Girgis, Development of adaptive protection scheme for dis-
General Meeting, 2006, p. 7.
tribution systems with high penetration of distributed generation, IEEE Trans.
[41] H. Nikkhajoei, R.H. Lasseter, Microgrid protection, in: IEEE Power Engineering
Power Delivery 19 (2004) 56–63.
Society General Meeting, 2007, pp. 1–6.
[14] M.T. Doyle, Reviewing the impacts of distributed generation on distribution
[42] A. Oudalov, A. Fidigatti, Adaptive network protection in microgrids, Int. J. Dis-
system protection, in: IEEE Power Engineering Society Summer Meeting, 2002,
trib. Energy Resour. 5 (2009) 201–226.
pp. 103–105, vol. 1.
[43] N. Perera, A.D. Rajapakse, Agent-based protection scheme for distribution net-
[15] L.K. Kumpulainen, K.T. Kauhaniemi, Analysis of the impact of distributed gen-
works with distributed generators, in: IEEE Power Engineering Society General
eration on automatic reclosing, in: IEEE PES Power Systems Conference and
Meeting, 2006, p. 6.
Exposition, 2004, pp. 603–608, 1.
[44] K. Kauhaniemi, S. Voima, Adaptive relay protection concept for smart grids, in:
[16] J.J. Burke, Power Distribution Engineering: Fundamentals and Applications, CRC
Renewable Efficient Energy II Conference, 21–22 March, 2012, Vaasa, Finland,
Press (MARCEL DEKKER, INC.), New York, 1994, pp. 374.
2012.
[17] H. Zayandehroodi, A. Mohamed, H. Shareef, M. Mohammadjafari, A Compre-
[45] S. Voima, H. Laaksonen, K. Kauhaniemi, Adaptive protection scheme for smart
hensive review of protection coordination methods in power distribution
grids, in: 12th IET International Conference on Developments in Power System
systems in the presence of DG, Przeglad ˛ Elektrotechniczny 8 (2011) 142–148.
Protection (DPSP 2014), 2014, pp. 1–6.
[18] M. Baran, I. El-Markabi, Adaptive over current protection for distribution feed-
[46] E. Sortomme, S.S. Venkata, J. Mitra, Microgrid protection using communication-
ers with distributed generators, in: IEEE PES Power Systems Conference and
assisted digital relays, IEEE Trans. Power Delivery 25 (2010) 2789–2796.
Exposition, 2004, pp. 715–719, 2.
[47] S. Conti, L. Raffa, U. Vagliasindi, Innovative solutions for protection schemes in
[19] H. Laaksonen, K. Kauhaniemi, S. Voima, Protection system for future LV Micro-
autonomous MV micro-grids, in: International Conference on Clean Electrical
grids, in: CIRED 21st International Conference on Electricity Distribution, 6–9
Power, 2009, pp. 647–654.
June, 2011, Frankfurt, 2011 (Paper 0431).
[48] M. Dewadasa, A. Ghosh, G. Ledwich, Protection of microgrids using differen-
[20] N.W.A. Lidula, A.D. Rajapakse, Voltage balancing and synchronization of micro-
tial relays, in: Universities Power Engineering Conference (AUPEC), 2011 21st
grids with highly unbalanced loads, Renewable Sustainable Energy Rev. 31
Australasian, 2011, pp. 1–6.
(2014) 907–920.
[49] J.M. Dewadasa, A. Ghosh, G. Ledwich, Distance protection solution for a con-
[21] S. Voima, K. Kauhaniemi, H. Laaksonen, Novel protection approach for MV
verter controlled microgrid, in: Fifteenth National Power Systems Conference
Microgrid, in: CIRED 21st International Conference on Electricity Distribution,
(NPSC), December, IIT Bombay, 2008, pp. 586–591.
6–9 June, 2011, Frankfurt, 2011 (Paper 0430).
[50] M. Dewadasa, A. Ghosh, G. Ledwich, Line protection in inverter supplied net-
[22] H. Laaksonen, K. Kauhaniemi, Fault type and location detection in islanded
works, in: Australasian Universities Power Engineering Conference (AUPEC’08),
Microgrid with different control methods based converters, in: CIRED 19th
2008, pp. 1–6 (Paper P-053).
International Conference on Electricity Distribution, 21–24 May, Vienna, 2007,
[51] M. Dewadasa, A. Ghosh, G. Ledwich, An inverse time admittance relay for fault
pp. 1–4 (Paper 0372).
detection in distribution networks containing DGs, in: TENCON 2009—2009
[23] T. Loix, T. Wijnhoven, G. Deconinck, Protection of microgrids with a high
IEEE Region 10 Conference, 2009, pp. 1–6.
penetration of inverter-coupled energy sources, in: Integration of Wide-Scale
[52] S.R. Samantaray, G. Joos, I. Kamwa, Differential energy based Microgrid protec-
Renewable Resources into the Power Delivery System, 2009 CIGRE/IEEE PES
tion against fault conditions, in: IEEE PES Innovative Smart Grid Technologies
Joint Symposium, 2009, pp. 1–6.
(ISGT), 2012, pp. 1–7.
[24] N.W.A. Lidula, A.D. Rajapakse, A pattern recognition approach for detecting
[53] S. Kar, S.R. Samantaray, Time-frequency transform-based differential scheme
power islands using transient signals—Part II: Performance evaluation, in: IEEE
for Microgrid protection, IET Gener. Transm. Distrib. 8 (2014) 310–320.
Trans. Power Delivery. July, 2012, pp. 1071–1080, 27.
[54] Shenxing Shi, Bo Jiang, Xinzhou Dong, Zhiqian Bo, Protection of microgrid, in:
[25] M. Geidl, Protection of power systems with distributed generation: state of art,
10th IET International Conference on Developments in Power System Protec-
in: Technical Rep., ETH, Zurich, Switz., 2005.
tion (DPSP 2010), Managing the Change, 2010, pp. 1–4.
[26] P. Naisani, D. Tholomier, T. Yip, G.J. Lloyd, Protection of distributed genera-
[55] M.A. Zamani, T.S. Sidhu, A. Yazdani, A protection strategy and microprocessor-
tion (DG) interconnection, in: 63rd Annual Conference for Protective Relay
based relay for low-voltage microgrids, IEEE Trans. Power Delivery 26 (2011)
Engineers, 2010, pp. 1–17.
1873–1883.
[27] P. Crolla, A.J. Roscoe, A. Dysko, G.M. Burt, Methodology for testing loss of
[56] R.D. Christie, H. Zadehgol, M.M. Habib, High impedance fault detection in low
mains detection algorithms for microgrids and distributed generation using
voltage networks, IEEE Trans. Power Delivery 8 (1993) 1829–1836.
real-time power hardware-in-the-loop based technique, in: IEEE Eighth Inter-
[57] CIGRE Working Group B5.38, The Impact of Implementing Cyber Security
national Conference on Power Electronics and ECCE Asia (ICPE & ECCE), 2011,
Requirements using IEC 61850, Technical Brochure 427, Paris, Aug. (2010).
pp. 833–838.
[58] V. Gurevich, Cyber and Electromagnetic Threats in Modern Relay Protection,
[28] N.W.A. Lidula, A.D. Rajapakse, A pattern recognition approach for detecting
CRC Press, Taylor and Francis Group, FL, 2015.
power islands using transient signals—Part I: Design and implementation, IEEE
[59] V. Gurevich, Susceptibility of modern relay protection: will protection from
Trans. Power Delivery 25 (December) (2010) 3070–3077.
cyber attacks help? Serb. J. Electr. Eng. 11 (2014) 233–241.
[29] www.nerc.com, Extended loss of GPS Impact on Reliability, Prelim-
[60] N. Kush, E. Ahmed, M. Branagan, E. Foo, Poisoned GOOSE: exploiting the GOOSE
inary Special Reliability Assessment Whitepaper, 2014, available at:
protocol, in: Proceedings of the Twelfth Australasian Information Security Con-
http://www.nerc.com/docs/escc/PNT%20-%20Power%20Systems%20V19.pdf
ference (AISC 2014), Auckland, New Zealand, 2014, pp. 17–22, 149.
(accessed on 19.5.2015) 1–8.