Waste Gas Burner with Touch Screen Control Panel

97300T Waste Gas Burner with Touch Screen Control Panel


Designed for complete automatic operation of the
entire Flare System, The S&J 97300T Waste Gas Burner
and Touch Screen Control Box are designed to combust
biogases generated in fermentation processes. It
efficiently incinerates low BTU gases from anaerobic
digesters, lagoons, and municipal landfills, minimizing
odors and VOC’s. The stoichiometric pilot ensures that
a proper air to fuel mixture is maintained throughout
the wide range of pressure and BTU fluctuations. A
continuous burning pilot in the flame area provides
stable, controlled, nonsmoking, combustion.

The 97300T is designed to withstand wind speeds up


to 150mph as well as seismic zone 4 loads. Its stainless
steel components endure the severest of process
environments. The burner tip is designed with swirl
inducers that create a cyclonic effect producing
an efficient air/fuel mixture and maximizes flame
retention. The wind shroud induces sufficient air to the
flare tip for proper mixing and combustion throughout

Features
the operating range.

Paired with a touch screen control box, the flare is


designed for automatic operation and gives the • High Performance Stoichiometric
operator more flexibility in controlling the system. The
Control Box can also be connected to a local PLC.
Pilot

The Pilot Control Box utilizes state of the art electronics • No Flame Front Burn-out of Pilot Gas
and instrumentation for safe operation. Pilot controls
are enclosed in a NEMA 4, carbon steel, electrical During Ignition
enclosure (NEMA 4X, 304 or 316 optional). For
automatic operation, the flare’s pilot can be designed
to operate only during initial startup or continuously. • Sizes 2” Through 12”
The Pilot Control Box includes a dry contact input
for Remote Start from a SCADA system or a pressure
switch. It also includes Contact Status outputs for Alarm
• Touch Screen Control Panel
and Flame Proven.

The auto-ignition sequence is started by the closing of


• Burns High Flow, Low BTU “Wet”
the remote start contact or pressure switch contact. Methane
This will indicate that the gas pressure limit has been
reached and flaring of excess gas should begin. The
operation of the burner will continue until the contact • No Venturi Maintenance
opens.
• State-of-the-Art Digital Control

• Fully Automated Pilot: Continuous or


Intermittent While Flaring

• Provides Alarm Outputs


5911 Butterfield Road Hillside, IL 60162 • tel: (708) 236-6000 • fax: (708) 236-6006
Rev: 97300T-3D
sales@ljtechnologies.com • www.ljtechnologies.com • ISO 9001:2015 Certified

1
97300T
Waste Gas Burner with Touch Screen Control Panel

Specifications:
Sizes: Stack Materials:
2”, 3”, 4”, 6”, 8”, 10” & 12” Stack with Shroud: 304L Stainless Steel
316L Stainless Steel (Optional)
Stack Burner Connection: Piping: 304L Stainless Steel
ANSI 150 lb. Raised Face Flange 316L Stainless Steel (Optional)

Contact Outputs: Biogas Criteria Composition:


Alarm SPST, 120 VAC 1 Amp 50%-70% CH4, 50%-30% CO2, with trace amounts of
Flame Proven SPST, 120 VAC 1 Amp H2S, Inert Gases and Air
Other Status Outputs Available
Moisture Content:
Saturated (100% Humidity)
Power Requirements:
120 VAC 4 Amp, 240 VAC 2 Amp (Optional) Pilot Gas:
Natural Gas
Controller: Propane (LPG)
Temperature Range: -20 to 150 degrees F Waste Gas (500 BTU/ Cubic Foot Minimum)
Enclosure: NEMA 4, Steel; NEMA 4X,
Stainless Steel Pilot Gas Pressure:
Functions: Manual Start, Remote Start 12” W.C. - 10 PSIG
Automatic Sequencing
Continuous Pilot or
Intermittent Pilot

Functions:
Manual Start:
The operator puts selector to manual and initiates ignition by depressing start on the touch screen control
panel.

Remote Start:
Remote ignition is performed by placing selector switch in the auto position and closing the remote location
dry contact to initiate the operation of the waste gas burner.

Auto Start:
Automatic Start is performed by the sensing of a pressure permissive in the system. The pilot control panel
must be set to “Auto” position for this to be controlled by the pressure switch. When the pressure switch
contacts close, the auto flaring sequence will begin. Once the pressure drops below the pressure switch
set point the contacts will open, halting operation.

Accessories:
A back pressure regulator / deflagration arrester should be installed in the digester line just upstream of
the flare. For automatic operation, the solenoid option must be selected on the back pressure regulator.

5911 Butterfield Road Hillside, IL 60162 • tel: (708) 236-6000 • fax: (708) 236-6006
Rev: 97300T-3D
sales@ljtechnologies.com • www.ljtechnologies.com • ISO 9001:2015 Certified

2
97300T
Waste Gas Burner with Touch Screen Control Panel

Dimensions:

Stack Dimensions Capacity


Dimensions (Inches [mm]) Size
Capacity (FT3/Hr.)
Size A B C (Inches mm])
2 [50] 16 [406] 24 [610] 88 [2235] 2 [50] 4000
3 [75] 18 [457] 24 [610] 92 [2337] 3 [75] 9970
4 [100] 20 [508] 24 [610] 92 [2337] 4 [100] 19150
6 [150] 24 [610] 36 [914] 128 [3251] 6 [150] 44200
8 [200] 24 [610] 48 [1219] 144 [3658] 8 [200] 76800
10 [250] 30 [762] 48 [1219] 176 [4470] 10 [250] 129000
12 [300] 36 [914] 60 [1524] 188 [4775] 12 [300] 218600
Flow specified for gas with 0.8 specific gravity, air at 60o F, and .5” WC
pressure drop

5911 Butterfield Road Hillside, IL 60162 • tel: (708) 236-6000 • fax: (708) 236-6006
Rev: 97300T-3D
sales@ljtechnologies.com • www.ljtechnologies.com • ISO 9001:2015 Certified

3
97300T
Waste Gas Burner with Touch Screen Control Panel

97300T Ordering Guide


Model Number Selection

The model number will have a base number 97300T followed by 8 digit numbers. These digits will represent 8
sets of option tables.

97300T - AB - CD - EF - GH

Table A - Pilot Gas Table E - Control Inputs


Option A Pilot Gas Option E Description
0 Natural 1 1 Dry Contact Input
1 Propane 2-4 Reserved
2 Bio 5 2 Dry Contact Inputs
3 Dual 6 1 4-20MA Analog Input
7 1 4-20MA Analog + 1 Dry Contact Input
Typically Dry Contacts are used for SCADA or pressure switch. Analog for
Table B - Unit Size pressure transmitter.
Option B Unit Size
Table F - Pilot Type
2 2”
3 3” Option F Description
4 4” 1 Continuous (ON while flaring)
5 6” 2 Intermittent (OFF while flaring)
7 8”
8 10”
9 12” Table G - Gas Train
Option G Description
0 Standard*
Table C - Power / P.E. Certificate * Standard regulator pressure is 10 PSIG max
Option C Description
1 120 VAC, 60HZ Table H - Materials of Construction
2 220/240 VAC, 50/60HZ Option H Stack / Piping
3 120 VAC, 60HZ with P.E. 2 304(L) Stainless Steel / 304(L) Stainless Steel
4 220/240 VAC, 50/60HZ with P.E. 4 316(L) Stainless Steel / 316(L) Stainless Steel
5 304(L) Stainless Steel / 316(L) Stainless Steel
6 316(L) Stainless Steel / 304(L) Stainless Steel
Table D - Enclosure Rating / UL NOTE: Pilot Material 316 Stainless Steel
Option D Description
0 NEMA 4 - Carbon Steel
2 NEMA 4X - 304 Stainless Steel
3 NEMA 4X - 316 Stainless Steel
4 NEMA 4 - Carbon Steel (UL 508A)
6 NEMA 4X - 304 SS (UL 508A)
7 NEMA 4X - 316 SS (UL 508A)