0100CT1501 Sec-14
0100CT1501 Sec-14
0100CT1501 Sec-14
Overview 14-3
General Purpose Dry Type 600 Volts and Below Overview 14-3
DOE 2016 Energy Efficient Three Phase 14-4
DOE 2016 Energy Efficient Single Phase and Single Phase Watchdog 14-7
Accessories 14-8
Enclosures and Accessories 14-8
Mini Power-Zone Unit Substation 14-10
Sealed, Mini Power-Zone™ Unit Substation 14-10
Resin Encapsulated Three and Single Phase Transformers 14-11
Resin Encapsulated Export Model and Buck Boost Transformers 14-12
Non-Ventilated and Transformer House 14-13
PZC Transformer Enclosures 14-13
Industrial Control 14-14
TRANSFORMERS
08/06/2018
EZ Selector–Selection Assistance LV Transformers EZ Selector–Selection
Assistance
schneider-electric.us
14-2
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Overview Low-Voltage Dry-Type Distribution
Transformers
schneider-electric.us
Distribution transformer means a transformer that (1) has an input voltage of 34.5 kV or
less; (2) has an ouput voltage of 600 V or less; (3) is rated for operation at a frequency of
60 Hz; and (4) has a capacity of 10 to 2500 kVA for liquid-immersed units and 15 to 2500
kVA for dry-type units.
Low voltage dry-type distribution transformer means a distribution transformer that: has
an input voltage of 600 V or less, is air-cooled, and not used oil as a coolant.
The following product offering must comply with the table above:
• Three- and single-phase
• Step up and step down transformers
• General purpose ventilated transformers (isolation transformers)
• Watchdog general purpose ventilated transformers (low temperature rise)
• Transformers designed for harmonic applications (K-rated, harmonic mitigating, data
center transformers, etc.)
• General purpose open core and coil transformers
The following low voltage transformers do not need to comply with the table above:
• Auto-transformers
• Drive isolation transformers
• Non-ventilated transformers
• Resin encapsulated transformers
• Buck boost transformers
• Control transformers (machine tool)
• Medical isolation panel transformers compliance with UL 1047 (tables 30.1 and 30.2)
(SPECIAL IZ — LOW LEAKAGE)
New Three-Phase Offering from Square D — DOE 2016 EX
• Exceed the efficiency levels from 10 CFR 431.196
• Terminals sized to handle wire ranges to match Square D circuit breakers, switches,
panelboards, etc. Located to meet NEC bending radius and layout to simplifiy
connections
• IZ Levels to allow for designing with the minimum AIC Panels available
• In-rush current limited to expand the Square D circuit breaker options at both 125 and
250% sizing
• Sound level at 3 dB for all designs, but up to 6–10 dB below on certain units—QUIET
TRANSFORMERS
QUALITY
• 1/2 in. clearance from the rear and side, UL 1561alcove testing all enclosures to
not exceed 90°C on adjacent walls
• Four product families of the DOE 2016 EX: General purpose, aluminum and copper
windings, 150°C rise; Watchdog, low temperature rise, aluminum and coover
windings, 115 or 80°C rise; Two solutions for harominic loads: K-13 Wye secondary,
harmonic mitigating transformers and K-9 ZigZag secondary, harmonic mitigating
transformers.
Association (NEMA) Standard TP–1–2002, Guide for Determining Energy Efficiency for Distribution Transformers.)
14-3
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Low-Voltage Dry-Type Distribution DOE 2016 Energy Efficient Three Phase
Transformers
Class 7400 / Refer to Catalog 7400CT1501 schneider-electric.us
[2] Not for construction, Contact your local Schneider Electric representative for certified prints.
[3] For enclosure styles, see Table 14.8 Enclosure Dimensions and Accessories, page 14-8
14-4
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
DOE 2016 Energy Efficient Three Phase Low-Voltage Dry-Type Distribution
Transformers
schneider-electric.us Class 7400 / Refer to Catalog 7400CT1501
Table 14.3: EX Three Phase 60 Hz, 240 Vac Delta Secondary; UL Listed
120 Volt Center Tap - Limited to 7.5% Loading, Design for Ground Reference and Light Maintenance Loading.
kVA Catalog No. Minimum Efficiency Full Capacity Taps Degree C Temp. Insulation Class %IZ Sound Weight (lbs) Enclosure[5]
@ 35% 75°C Rise Level dB [4]
480 Vac Delta Primary, Aluminum Windings
15 EX15T6HCT 97.89% 6–2.5%2+4– 150 220 4.9% 42 dB 235 17K
30 EX30T6HCT 98.23% 6–2.5%2+4– 150 220 4.2% 42 dB 405 18K
45 EX45T6HCT 98.40% 6–2.5%2+4– 150 220 4.1% 42 dB 480 18K
75 EX75T6HCT 98.60% 6–2.5%2+4– 150 220 5.8% 47 dB 640 20K
112.5 EX112T6HCT 98.74% 6–2.5%2+4– 150 220 4.5% 47 dB 910 21K
150 EX150T6HCT 98.83% 6–2.5%2+4– 150 220 4.1% 47 dB 1140 22K
225 EX225T6HCT 98.94% 6–2.5%2+4– 150 220 4.5% 52 dB 1820 25J
300 EX300T6HCT 99.02% 6–2.5%2+4– 150 220 5.2% 52 dB 1960 25J
500 EX500T63HCT 99.14% 4–2.5%2+2– 150 220 4.9% 57 dB 3090 30J
750 EX750T63HCT 99.23% 4–2.5%2+2– 150 220 4.9% 61 dB 4120 31J
Watchdog transformers, by design, reduct energy consumption at loads greater than
50% loading, giving fewer BTUs/hour at those loading levels. The life expectancy is
greater than that of 150°C rise General Purpose units.
• Aluminum or copper windings
• Two temperature rise options: 115°C rise on 220°C insulation systems (15%
continuous emergency overload capacity); 80°C rise on 220°C insulation systems
(30% continuous emergency overload capacity)
Table 14.4: EX Three Phase 60 Hz, 480Y/277 Vac Secondary; UL Listed
kVA Catalog No. Minimum Efficiency Full Capacity Taps Degree C Temp. Insulation Class %IZ Sound Weight (lbs) Enclosure[5]
@ 35% 75°C Rise Level [4]
480 V Delta Primary, 208Y/120 Secondary, Aluminum Windings
15 EX15T3HF 97.89% 6–2.5%2+4– 115 220 4.5% 39 dB 245 17K
30 EX30T3HF 98.23% 6–2.5%2+4– 115 220 3.5% 39 dB 400 18K
45 EX45T3HF 98.40% 6–2.5%2+4– 115 220 5.1% 39 dB 490 18K
75 EX75T3HF 98.60% 6–2.5%2+4– 115 220 4.3% 44 dB 920 20K
112.5 EX112T3HF 98.74% 6–2.5%2+4– 115 220 4.4% 47 dB 1170 21K
150 EX150T3HF 98.83% 6–2.5%2+4– 115 220 3.8% 49 dB 825 22K
225 EX225T3HF 98.94% 6–2.5%2+4– 115 220 4.5% 49 dB 1825 24J
300 EX300T3HF 99.02% 6–2.5%2+4– 115 220 30.0% 49 dB 1975 25J
500 EX500T68HF 99.14% 4–2.5%2+2– 115 220 4.9% 56 dB 3100 30J
750 EX750T68HF 99.23% 4–2.5%2+2– 115 220 5.0% 58 dB 4125 31J
480 V Delta Primary, 208Y/120 Secondary, Copper Windings
15 EX15T3HFCU 97.89% 6–2.5%2+4– 115 220 4.1% 39 dB 250 17K
30 EX30T3HFCU 98.23% 6–2.5%2+4– 115 220 3.5% 39 dB 410 18K
45 EX45T3HFCU 98.40% 6–2.5%2+4– 115 220 4.3% 39 dB 495 18K
75 EX75T3HFCU 98.60% 6–2.5%2+4– 115 220 4.6% 44 dB 755 20K
112.5 EX112T3HFCU 98.74% 6–2.5%2+4– 115 220 4.1% 47 dB 1025 21K
150 EX150T3HFCU 98.83% 6–2.5%2+4– 115 220 3.9% 49 dB 1270 22K
225 EX225T3HFCU 98.94% 6–2.5%2+4– 115 220 6.8% 49 dB 1545 24J
300 EX300T3HFCU 99.02% 6–2.5%2+4– 115 220 5.0% 49 dB 1975 25J
500 EX500T68HFCU 99.14% 4–2.5%2+2– 115 220 4.8% 56 dB 3705 30J
750 EX750T68HFCU 99.23% 4–2.5%2+2– 115 220 5.3% 58 dB 4400 31J
480 V Delta Primary, 208Y/120 Secondary, Aluminum Windings
15 EX15T3HB 97.89% 6–2.5%2+4– 80 220 4.7% 39 dB 400 18K
30 EX30T3HB 98.23% 6–2.5%2+4– 80 220 3.8% 39 dB 490 18K
45 EX45T3HB 98.40% 6–2.5%2+4– 80 220 3.9% 44 dB 920 20K
75 EX75T3HB 98.60% 6–2.5%2+4– 80 220 5.2% 47 dB 1170 21K
112.5 EX112T3HB 98.74% 6–2.5%2+4– 80 220 4.3% 49 dB 1825 22K
150 EX150T3HB 98.83% 6–2.5%2+4– 80 220 4.2% 49 dB 1825 24J
225 EX225T3HB 98.94% 6–2.5%2+4– 80 220 4.6% 49 dB 1975 25J
300 EX300T68HB 99.02% 4–2.5%2+2– 80 220 4.4% 56 dB 3100 30J
500 EX500T68HB 99.14% 4–2.5%2+2– 80 220 4.9% 58 dB 4125 31J
480 V Delta Primary, 208Y/120 Secondary, Copper Windings
15 EX15T3HBCU 97.89% 6–2.5%2+4– 80 220 4.4% 39 dB 400 18K
30 EX30T3HBCU 98.23% 6–2.5%2+4– 80 220 3.7% 39 dB 495 18K
45 EX45T3HBCU 98.40% 6–2.5%2+4– 80 220 4.4% 44 dB 755 20K
75 EX75T3HBCU 98.60% 6–2.5%2+4– 80 220 3.6% 47 dB 1025 21K
112.5 EX112T3HBCU 98.74% 6–2.5%2+4– 80 220 4.2% 49 dB 1270 22K
150 EX150T3HBCU 98.83% 6–2.5%2+4– 80 220 3.8% 49 dB 1545 24J
225 EX225T3HBCU 98.94% 6–2.5%2+4– 80 220 6.9% 49 dB 1975 25J
300 EX300T68HBCU 99.02% 4–2.5%2+2– 80 220 5.0% 56 dB 3705 30J
500 EX500T68HBCU 99.14% 4–2.5%2+2– 80 220 4.8% 58 dB 4400 31J
TRANSFORMERS
[4] Not for construction, Contact your local Schneider Electric representative for certified prints.
14
[5] For enclosure styles, see Table 14.8 Enclosure Dimensions and Accessories, page 14-8
14-5
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Low-Voltage Dry-Type Distribution DOE 2016 Energy Efficient Three Phase
Transformers
Class 7400 / Refer to Catalog 7400CT1501 schneider-electric.us
DOE 2016 Low Voltage Distribution Transformers designed for applications with
harmonic loads.
Square D offers offers Delta - Wye 30°Phase Shift transformers which reconfigure the
harmonic models and mitigate the harmful effects of triplens. UL Listed with the following
K-ratings to handle excess heat created by harmonic wave forms, K13. Available with
aluminum or copper windings and 150°C or 115°C Rise with 220C insulation system.
Table 14.5: EX Three Phase 60 Hz, 30° Phase Shift, 480 Delta to 208Y/120; UL Listed, K-13
kVA Catalog No. Minimum Phase Full Capacity Taps Degree C Insulation Class %IZ Sound Weight (lbs) Enclosure[7]
Efficiency @ 35% Shift Temp. Rise Level [6]
75°C
480 Delta Primary, 208Y/120 Secondary, Aluminum Windings, 150°C Rise, 220C Insulation, K13 Listed
15 EX15T3HNLP 97.89% 30° 6–2.5%2+4– 150 220 1.90% 39 dB 400 18K
30 EX30T3HNLP 98.23% 30° 6–2.5%2+4– 150 220 2.60% 39 dB 490 18K
45 EX45T3HNLP 98.40% 30° 6–2.5%2+4– 150 220 3.10% 44 dB 920 20K
75 EX75T3HNLP 98.60% 30° 6–2.5%2+4– 150 220 2.80% 47 dB 1170 21K
112.5 EX112T3HNLP 98.74% 30° 6–2.5%2+4– 150 220 3.30% 49 dB 1825 22K
150 EX150T3HNLP 98.83% 30° 6–2.5%2+4– 150 220 3.00% 49 dB 1825 24J
225 EX225T3HNLP 98.94% 30° 6–2.5%2+4– 150 220 3.30% 49 dB 1975 25J
480 Delta Primary, 208Y/120 Secondary, Copper Windings, 150°C Rise, 220C Insulation, K13 Listed
15 EX15T3HCUNLP 97.89% 30° 6–2.5%2+4– 150 220 1.90% 39 dB 400 18K
30 EX30T3HCUNLP 98.23% 30° 6–2.5%2+4– 150 220 3.00% 39 dB 495 18K
45 EX45T3HCUNLP 98.40% 30° 6–2.5%2+4– 150 220 3.00% 44 dB 755 20K
75 EX75T3HCUNLP 98.60% 30° 6–2.5%2+4– 150 220 2.80% 47 dB 1025 21K
112.5 EX112T3HCUNLP 98.74% 30° 6–2.5%2+4– 150 220 3.00% 49 dB 1270 22K
150 EX150T3HCUNLP 98.83% 30° 6–2.5%2+4– 150 220 4.60% 49 dB 1545 24J
225 EX225T3HCUNLP 98.94% 30° 6–2.5%2+4– 150 220 3.80% 49 dB 1975 25J
480 Delta Primary, 208Y/120 Secondary, Aluminum Windings, 115°C Rise, 220C Insulation, K13 Listed
15 EX15T3HFNLP 97.89% 30° 6–2.5%2+4– 115 220 1.80% 39 dB 400 18K
30 EX30T3HFNLP 98.23% 30° 6–2.5%2+4– 115 220 2.50% 39 dB 490 18K
45 EX45T3HFNLP 98.40% 30° 6–2.5%2+4– 115 220 3.00% 44 dB 920 20K
75 EX75T3HFNLP 98.60% 30° 6–2.5%2+4– 115 220 2.80% 47 dB 1170 21K
112.5 EX112T3HFNLP 98.74% 30° 6–2.5%2+4– 115 220 3.30% 49 dB 1825 22K
150 EX150T3HFNLP 98.83% 30° 6–2.5%2+4– 115 220 3.00% 49 dB 1825 24J
225 EX225T3HFNLP 98.94% 30° 6–2.5%2+4– 115 220 3.30% 49 dB 1975 25J
480 Delta Primary, 208Y/120 Secondary, Copper Windings, 115°C Rise, 220C Insulation, K13 Listed
15 EX15T3HFCUNLP 97.89% 30° 6–2.5%2+4– 115 220 1.70% 39 dB 400 18K
30 EX30T3HFCUNLP 98.23% 30° 6–2.5%2+4– 115 220 2.80% 39 dB 495 18K
45 EX45T3HFCUNLP 98.40% 30° 6–2.5%2+4– 115 220 3.00% 44 dB 755 20K
75 EX75T3HFCUNLP 98.60% 30° 6–2.5%2+4– 115 220 2.70% 47 dB 1025 21K
112.5 EX112T3HFCUNLP 98.74% 30° 6–2.5%2+4– 115 220 2.90% 49 dB 1270 22K
150 EX150T3HFCUNLP 98.83% 30° 6–2.5%2+4– 115 220 4.60% 49 dB 1545 24J
225 EX225T3HFCUNLP 98.94% 30° 6–2.5%2+4– 115 220 3.70% 49 dB 1975 25J
14
TRANSFORMERS
[6] Not for construction, Contact your local Schneider Electric representative for certified prints.
[7] For enclosure styles, see Table 14.8 Enclosure Dimensions and Accessories, page 14-8
14-6
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
DOE 2016 Energy Efficient Single Phase Low-Voltage Dry-Type Distribution
and Single Phase Watchdog Transformers
schneider-electric.us Class 7400 / Refer to Catalog 7400CT0601
TRANSFORMERS
[10] For enclosure styles, see Table 14.8 Enclosure Dimensions and Accessories, page 14-8
14-7
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Low-Voltage Dry-Type Distribution Accessories
Transformers
schneider-electric.us
Style D and H—Type 2 Rated Style K—Type 1 Rated Style J—Type 1 Rated
Converts to Type 3R with Weathershield Converts to Type 2 with Drip Shield Converts to Type 2 with Drip Shield
Converts to Type 3R with Weathershield Converts to Type 3R with Weathershield
[11] These dimensions are not for construction. Contact your local Schneider Electric.
[12] Wall mounting brackets are used with units weighing no more than 700 lbs.
[13] Ceiling mounting brackets are used with units weighing no more than 1200 lbs.
14-8
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Accessories Low-Voltage Dry-Type Distribution
Transformers
schneider-electric.us
Schneider Electric Low Voltage Transformers have been qualified to the site-specific
requirements of the following listed model building code and/or standard. (International
Building Code, California Buildling Code, Uniformed Building Code). Qualification based
on tri-axial shake table test results conduced in accordance with the AC156 test
protocol3 (Acceptance Criteria for Seismic Qualification Testing of Nonstructural
Components).
• Enclosure 1A to 11A, 12C to 16C, 12B to 15B (Resin Encapsulated Transformers)
• Enclosure 17D to 31D, 17H to 18H, 17K to 22K, 25J to 31J (Ventilated Transformers)
• Enclosure 17K to 20K with wall mounting bracket (Ventilated Transformres)
• Enclosure 17E to 31E (Non-ventilated Transformers)
• Enclosure MPZ A, AA, B, BB, C, CC (MPZB)
Product is Listed for installation in Hospitals State of California–OSHPD Special Seismic
Certification Preapproval OSP-0023-10.
Accessory Lables–required for Building Inspection–OSHPD
OSP Label Catalog Number Products Enclosure Style
7400CAOSHPDABC Resin encapsulated, buck boost Style A, B, C
transformers
7400CAOSHPDDH Ventilated Type EE, drive isolation, Style D, H
auto-transformers
7400CAOSHPDF Low voltage 750 and 1000 kVA Type Style F
EE
7400CAOSHPDJ Ventilated Type EX Style J
7400CAOSHPDK Ventilated Type EX Style K
7400CAOSHPDKO Ventilated Type EX, wall-mounted Style K with WMB
using Square D brackets
7400CAOSHPDMPZB Mini Power Zone Bolt-on A, AA, B, BB, C, CC
TRANSFORMERS
14
14-9
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Low-Voltage Dry-Type Distribution Mini Power-Zone Unit Substation
Transformers
Class 7440 / Refer to Catalog 7440CT0901 schneider-electric.us
14-10
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Resin Encapsulated Three and Single Low-Voltage Dry-Type Distribution
Phase Transformers Transformers
schneider-electric.us Class 7400 / Refer to Catalog 7400CT9601
[15] Not for construction, Contact your local Schneider Electric representative for certified prints.
[16] For enclosure styles, see Table 14.8 Enclosure Dimensions and Accessories, page 14-8
[17] For enclosure styles, see Table 14.17 Enclosure Dimensions, page 14-12
14
Table 14.16: Single-Phase—110/220 Vac Secondary; 50/60 Hz; cULus Listed (240 x 480 Vac Primary to 120/240 Vac Secondary - 60 Hz
only)
kVA 220 x 440 Primary Weight (lbs)[19] Enclosure[20] Full Capacity Taps Degree C Insulation
Catalog No. Temperature Class
Rise
1 1S67F 21.2 7A 190/200/208/220 x 380/400/416/440 115 180
2 2S67F 39.1 9A 190/200/208/220 x 380/400/416/440 115 180
3 3S67F 55.2 10A 190/200/208/220 x 380/400/416/440 115 180
5 5S67F 135 13B 190/200/208/220 x 380/400/416/440 115 180
7.5 7S67F 165 13B 190/200/208/220 x 380/400/416/440 115 180
10 10S67F 165 13B 190/200/208/220 x 380/400/416/440 115 180
Fingersafe™ terminal block cover kits for encapsulated transformers can be used to
meet touch-safe requirements.
Enclosure Kit Catlog Number Description
7A (1 kVA) 7400ENT9 Terminal Block H1, H2, H3, H4, H5, H6, H7, H8, H9, H10 and X1, X2, X3, X4
9A (2 kVA) 7400ENT11 Terminal Block H1, H2, H3, H4, H5, H6, H7, H8, H9, H10 and X1, X2, X3, X4
10A (3 kVA) 7400ENT11 Terminal Block H1, H2, H3, H4, H5, H6, H7, H8, H9, H10 and X1, X2, X3, X4
13B (5–10 kVA) 7400ENT13 Terminal Block H1, H2, H3, H4, H5, H6, H7, H8, H9, H10 and X1, X2, X3, X4
[19] Not for construction, Contact your local Schneider Electric representative for certified prints.
[20] For enclosure styles, see Table 14.17 Enclosure Dimensions, page 14-12
14-12
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Non-Ventilated and Transformer House Low-Voltage Dry-Type Distribution
Transformers
schneider-electric.us
PZC transformer enclosures are shipped separately from transformers so they can be
pre-installed on the job site.
Four standard enclosures of each type material are available for installation of
transformer enclosure types D and H.
Drawings are in the Classic Technical Library. Search by catalog number, which is the
same as the drawing number.
Table 14.21: Stainless Steel Option Table 14.22: Painted Galvanized Option
Catalog No. L W H Weight Enclosure Catalog No. L W H Weight Enclosure
7400SS3R-001 3'-8" 3'-4" 4'-9" 450 lbs 17D, 17H, 18D, 18H, 19D, 20D, 21D, 7400PG3R-001 3'-8" 3'-4" 4'-9" 450 lbs 17D, 17H, 18D, 18H, 19D,
22D 20D, 21D, 22D
7400SS3R-002 4'-6" 3'-9" 6'-0" 500 lbs 24D, 25D, 26D, 36D, 37D 7400PG3R-002 4'-6" 3'-9" 6'-0" 500 lbs 24D, 25D, 26D, 36D, 37D
TRANSFORMERS
7400SS3R-003 5'-8" 4'-1" 7'-0" 550 lbs 28D, 29D, 30D, 38D 7400PG3R-003 5'-8" 4'-1" 7'-0" 550 lbs 28D, 29D, 30D, 38D
7400SS3R-004 6'-4" 4'-9" 7'-10" 600 lbs 31D, 45D 7400PG3R-004 6'-4" 4'-9" 7'-10" 600 lbs 31D, 45D
[23] For enclosure styles, see Table 14.20 Enclosure Dimensions and Accessories, page 14-13
14-13
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Industrial Control Type T and Type TF
Class 9070 / Refer to Catalog 9070CT9901
schneider-electric.us
Selection Guide
1. Determine the inrush and sealed VA of each coil in the control circuit and the VA of
all other components.
2. Total the sealed VA of all operating coils and the VA of all other loads. (This
determines the minimum VA size required for the circuit.)
3. Total the inrush VA of all coils that are starting at the same time and all loads and
coils that are running.
4. Locate a value in the VA column ofTable 14.23 Regulation Chart for Type T, page
14-14, shown below, that is equal to or greater than the value calculated in step 2.
5. In the VA row selected in step 4, find the inrush value under the appropriate voltage
regulation column ofTable 14.23 Regulation Chart for Type T, page 14-14, shown
below. If this value is greater than the calculated value from step 3, this is the
correct transformer VA rating.
If the inrush value on the selected VA row is not greater than the calculated value
from step 3, use the next higher transformer VA rating, that is, the rating on the next
row.
If your supply voltage is stable and fluctuates less than 5%, Schneider Electric
recommends you use the 90% secondary voltage column. If your supply voltage is not
stable and fluctuates more than 10% we recommend you use the 95% secondary
voltage column. We recommend that you never use the 85% secondary voltage column
since magnetic devices lose life expectancy if they are continuously started at 85% of
rated voltage.
14-14
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Type T and Type TF Industrial Control
Class 9070 / Refer to Catalog 9070CT9901
schneider-electric.us
Table 14.24: 240 x 480 V Primary, 120 V Secondary; 230 x 460 V Primary, 115 V Secondary; 220 x 440 V Primary, 110 V Secondary
VA Type T Type TF Weight Height Width Depth Acceso-
Type T Type TF ry
Finger-
UL/CSA/NOM CE Catalog No. in. mm in. mm in. mm in. mm safe
Covers
25 25 9070T25D1 9070TF25D1 2.5 2.58 66 4.00 102 3.00 76 3.09 79 FSC1
50 50 9070T50D1 9070TF50D1 2.5 2.58 66 4.00 102 3.00 76 3.09 79 FSC1
75 75 9070T75D1 9070TF75D1 3.8 2.89 73 4.18 106 3.38 86 3.34 85 FSC1
100 100 9070T100D1 9070TF100D1 3.8 2.89 73 4.18 106 3.38 86 3.34 85 FSC1
150 150 9070T150D1 9070TF150D1 5.5 3.20 81 4.50 114 3.75 95 3.59 91 FSC1
200 200 9070T200D1 9070TF200D1 5.5 3.20 81 4.50 114 3.75 95 3.59 91 FSC1
250 160 9070T250D1 9070TF250D1 7.1 3.20 81 4.50 114 3.75 95 5.30 135 FSC2
300 200 9070T300D1 9070TF300D1 8.5 3.84 98 5.13 130 4.50 114 4.74 120 FSC2
350 250 9070T350D1 9070TF350D1 10.5 3.84 98 5.13 130 4.50 114 5.11 130 FSC2
500 300 9070T500D1 9070TF500D1 11.9 3.84 98 5.13 130 4.50 114 5.49 139 FSC2
750 500 9070T750D1 9070TF750D1 11.0 4.51 115 5.80 147 5.25 133 5.61 143 FSC2
1000 630 9070T1000D1 9070TF1000D1 20.6 4.51 115 5.80 147 5.25 133 6.30 160 FSC2
1500 1000 9070T1500D1 9070TF1500D1 34.0 6.17 157 7.46 190 7.06 179 5.92 150 FSC2
2000 1500 9070T2000D1 9070TF2000D1 47.0 6.17 157 7.46 190 7.06 179 7.17 182 FSC2
3000 2000 9070T3000D1 — 60.0 8.75 222 — — 9.00 229 7.24 184 FSC2
5000 3000 9070T5000D1 — 89.0 8.75 222 — — 9.00 229 9.15 232 FSC2
[1] TF units are design for line to line voltages on the primary, 277 Vac is a line to neutral voltage.
14-15
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Industrial Control Type T and Type TF
Class 9070 / Refer to Catalog 9070CT9901
schneider-electric.us
Table 14.28: 240 x 480 V Primary, 120/240 V Secondary; 230 x 460 V Primary, 115/230 V Secondary; 220 x 440 V Primary, 110/220 V
Secondary
VA Type T Type TF[2] Weight Height Width Depth Acceso-
Type T Type TF ry
Finger-
UL/CSA/NOM CE Catalog No. in. mm in. mm in. mm in. mm safe
Covers
25 25 9070T25D31 9070TF25D31 2.5 2.58 66 4.00 102 3.00 76 3.09 79 FSC1
50 50 9070T50D31 9070TF50D31 2.5 2.58 66 4.00 102 3.00 76 3.09 79 FSC1
75 75 9070T75D31 9070TF75D31 3.8 2.89 73 4.18 106 3.38 86 3.34 85 FSC1
100 100 9070T100D31 9070TF100D31 3.8 2.89 73 4.18 106 3.38 86 3.34 85 FSC1
150 150 9070T150D31 9070TF150D31 5.5 3.20 81 4.50 114 3.75 95 3.59 91 FSC1
200 200 9070T200D31 9070TF200D31 5.5 3.20 81 4.50 114 3.75 95 3.59 91 FSC1
250 160 9070T250D31 9070TF250D31 7.1 3.20 81 4.50 114 3.75 95 5.30 135 FSC2
300 200 9070T300D31 9070TF300D31 8.5 3.84 98 5.13 130 4.50 114 4.74 120 FSC2
350 250 9070T350D31 9070TF350D31 10.5 3.84 98 5.13 130 4.50 114 5.11 130 FSC2
500 300 9070T500D31 9070TF500D31 11.9 3.84 98 5.13 130 4.50 114 5.49 139 FSC2
750 500 9070T750D31 9070TF750D31 11.0 4.51 115 5.80 147 5.25 133 5.61 143 FSC2
1000 630 9070T1000D31 9070TF1000D31 20.6 4.51 115 5.80 147 5.25 133 6.30 160 FSC2
1500 1000 9070T1500D31 9070TF1500D31 34.0 6.17 157 7.46 190 7.06 179 5.92 150 FSC2
2000 1500 9070T2000D31 9070TF2000D31 47.0 6.17 157 7.46 190 7.06 179 7.17 182 FSC2
3000 2000 9070T3000D31 — 60.0 8.75 222 — — 9.00 229 7.24 184 FSC2
5000 3000 9070T5000D31 — 89.0 8.75 222 — — 9.00 229 9.15 232 FSC2
[2] TF designed for line to line primary and line to neutral secondary. If secondary connected in series, fuse block should be disconnected.
14-16
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Type T and Type TF Industrial Control
Class 9070 / Refer to Catalog 9070CT9901
schneider-electric.us
Table 14.33: 240/480/600 V Primary, 120 V Secondary; 230/460/575 V Primary, 115 V Secondary; 220/440/550 V Primary to 110 V
Secondary
VA Type T Type TF Weight Height Width Depth Acceso-
Type T Type TF ry
Finger-
UL/CSA/NOM CE Catalog No. in. mm in. mm in. mm in. mm safe
Covers
50 50 9070T50D32 9070TF50D32 3.8 2.89 73 4.18 106 3.38 86 3.34 85 FSC1
75 75 9070T75D32 9070TF75D32 3.8 2.89 73 4.18 106 3.38 86 3.34 85 FSC1
100 100 9070T100D32 9070TF100D32 5.5 3.20 81 4.50 114 3.75 95 3.59 91 FSC1
150 150 9070T150D32 9070TF150D32 5.5 3.20 81 4.50 114 3.75 95 3.59 91 FSC1
200 200 9070T200D32 9070TF200D32 7.1 3.20 81 4.50 114 3.75 95 5.30 135 FSC2
250 160 9070T250D32 9070TF250D32 8.5 3.84 98 5.13 130 4.50 114 4.74 120 FSC2
300 200 9070T300D32 9070TF300D32 10.5 3.84 98 5.13 130 4.50 114 5.11 130 FSC2
350 250 9070T350D32 9070TF350D32 11.9 3.84 98 5.13 130 4.50 114 5.49 139 FSC2
500 300 9070T500D32 9070TF500D32 11.0 4.51 115 5.80 147 5.25 133 5.61 143 FSC2
750 500 9070T750D32 9070TF750D32 20.6 4.51 115 5.80 147 5.25 133 6.30 160 FSC2
1000 630 9070T1000D32 9070TF1000D32 34.0 6.17 157 7.46 190 7.06 179 5.92 150 FSC2
1500 1000 9070T1500D32 9070TF1500D32 47.0 6.17 157 7.46 190 7.06 179 7.17 182 FSC2
2000 1500 9070T2000D32 9070TF2000D32 60.0 8.75 222 — — 9.00 229 7.24 184 FSC2
3000 2000 9070T3000D32 — 89.0 8.75 222 — — 9.00 229 9.15 232 FSC2
Table 14.34: 240/416/480/600 Vac Primary, 99/120/130 Vac Secondary; 230/400/460/575 Vac Primary, 95/115/125 Vac Secondary;
220/380/440/550 Vac Primary, 90/110/120 Vac Secondary; 208/360/416/520 Vac Primary, 85/104/115 Vac Secondary
VA Type T Type TF Weight Height Width Depth Acceso-
Type T Type TF ry
Finger-
UL/CSA/NOM CE Catalog No. in. mm in. mm in. mm in. mm safe
Covers
50 50 9070T50D50 9070TF50D50 4.0 2.89 73 4.19 106 3.38 86 4.43 113 FSC23
75 75 9070T75D50 9070TF75D50 7.2 3.20 81 4.50 114 3.75 95 4.70 119 FSC23
100 100 9070T100D50 9070TF100D50 7.1 3.20 81 4.50 114 3.75 95 4.70 119 FSC23
150 150 9070T150D50 9070TF150D50 8.5 3.84 98 5.14 131 4.50 114 4.74 120 FSC23
200 200 9070T200D50 9070TF200D50 10.5 3.84 98 5.14 131 4.50 114 5.11 130 FSC23
250 160 9070T250D50 9070TF250D50 10.5 3.84 98 5.14 131 4.50 114 5.11 130 FSC23
300 200 9070T300D50 9070TF300D50 11.9 3.84 98 5.14 131 4.50 114 5.49 139 FSC23
350 250 9070T350D50 9070TF350D50 11.0 4.51 115 5.81 148 5.25 133 5.61 143 FSC23
500 300 9070T500D50 9070TF500D50 11.0 4.51 115 5.81 148 5.25 133 5.61 143 FSC23
750 500 9070T750D50 9070TF750D50 20.6 4.51 115 5.81 148 5.25 133 6.3. 160 FSC23
1000 630 9070T1000D50 9070TF1000D50 34.0 6.17 157 7.47 190 7.06 179 5.92 150 FSC23
1500 1000 9070T1500D50 9070TF1500D50 47.0 6.17 157 7.47 190 7.06 179 7.17 182 FSC23
2000 1500 9070T2000D50 9070TF2000D50 60.0 7.63 194 8.93 227 9.00 229 6.38 162 FSC23
Table 14.35: 240 x 480 Vac Primary, 120/24 Vac Secondary (24 Vac limited to 20% of nameplate VA)
VA Type T Type TF Weight Height Width Depth Acceso-
Type T Type TF ry
Finger-
UL/CSA/NOM CE Catalog No. in. mm in. mm in. mm in. mm safe
Covers
50 50 9070T50D15 — 2.5 2.58 66 — — 3.00 76 3.09 79 FSC1
75 75 9070T75D15 — 3.8 2.89 73 — — 3.38 86 3.34 85 FSC1
100 100 9070T100D15 — 3.8 2.89 73 — — 3.38 86 3.34 85 FSC1
150 150 9070T150D15 — 5.5 3.20 81 — — 3.75 95 3.59 91 FSC1
200 200 9070T200D15 — 5.5 3.20 81 — — 3.75 95 3.59 91 FSC1
250 160 9070T250D15 — 7.1 3.20 81 — — 3.75 95 5.30 135 FSC2
300 200 9070T300D15 — 8.5 3.84 98 — — 4.50 114 4.74 120 FSC2
350 250 9070T350D15 — 10.5 3.84 98 — — 4.50 114 5.11 130 FSC2
500 300 9070T500D15 — 11.9 3.84 98 — — 4.50 114 5.49 139 FSC2
TRANSFORMERS
750 500 9070T750D15 — 11.0 4.51 115 — — 5.25 133 5.61 143 FSC2
1000 630 9070T1000D15 — 20.6 4.51 115 — — 5.25 133 6.30 160 FSC2
1500 1000 9070T1500D15 — 34.0 6.17 157 — — 7.06 179 5.92 150 FSC2
2000 1500 9070T2000D15 — 47.0 6.17 157 — — 7.06 179 7.17 182 FSC2
3000 2000 9070T3000D15 — 60.0 8.75 222 — — 9.00 229 7.24 184 FSC2
5000 3000 9070T5000D15 — 89.0 8.75 222 — — 9.00 229 9.15 232 FSC2
14-17
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Industrial Control Type T and Type TF
Class 9070 / Refer to Catalog 9070CT9901
schneider-electric.us
500 300 9070T500D19 11.0 4.51 147 5.25 133 5.61 143 FSC23
750 500 9070T750D19 20.6 4.51 147 5.25 133 6.30 160 FSC23
1000 630 9070T1000D19 34.0 6.17 190 7.06 179 5.92 150 FSC23
14-18
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Transformer Disconnects Industrial Control
Class 9070 / Refer to Catalog 9070CT0301
schneider-electric.us
TRANSFORMERS
14
14-19
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Instrument, 600 Volt Class Voltage and Current Transformers
Class 4210 / Refer to Catalog 4210CT9701
schneider-electric.us
Voltage Transformers
Schneider Electric offers three models of voltage transformers, each suited for a
particular application:
• Model 450R
– Applications requiring accurate voltage measurement within the 0.3% accuracy
class
– Switchboards with 1% instrumentation
• Model 460R
– Applications with less critical accuracy and low burden requirements
– Transducers and other panelboard monitoring
• Model 470R
– Extremely accurate voltage measurement
– Low burden applications, such as PLC modules and similar, high-impedance
electronic devices
Current Transformers
Current transformers are low cost, compact units that offer good electrical performance
in a general purpose transformer.
• They are very easy to mount on the conductors.
• All current transformers feature permanent polarity marks molded into the case.
The following types of current transformers are available:
• General purpose
• Toroidal (single ratio)
• Rectangle window (single ratio)
• Split core
• Bushing (single ratio) (multi-ratio)
For part numbers, see Section 6 of the Supplemental Digest or see the Schneider
Electric Product Configurator.
Contact your local Schneider Electric representative for other available features.
312R — X 600–4000
4.50 114
202R — X X 100–1000
5.25 133 203R — X — 100–3000
5.75 146 120R — X — 200–3000
6.25 159 210R — X X 200–3000
151R — X 600–4000
6.88 175
152R — X X 50–4000
8.13 206 140R — X X 50–6000
2.12 x 4.25 54 x 108 260R X — — 100–4000
TRANSFORMERS
Table 14.45: New! Standard Efficiency Levels for Liquid Immersed Distribution
Transformers
Power Cast II™
Single Phase Three Phase
kVA Efficiency % kVA Efficiency %
10 98.7 — —
15 98.82 — —
25 98.95 45 98.92
37.5 99.05 75 99.03
50 99.11 112.5 99.11
75 99.19 150 99.16
100 99.25 225 99.23
167 99.33 300 99.27
250 99.39 500 99.35
333 99.43 750 99.4
500 99.49 1000 99.43
667 99.52 1500 99.48
833 99.55 2000 99.51
Liquid Filled Pad Mounted — — 2500 99.53
All Efficiency values are at 50% of nameplate-rated load, determined according to the
DOE Test Procedure 10 CFR 431, Subpart K, Appendix A.
Table 14.46: New! Standard Levels for Medium Voltage Dry Type Distribution
Transformers
kVA Single Phase kVA Three Phase
20-45kV 46-95 kV >/ 96 kV 20-45kV 46-95 kV >/ 96 kV
BIL BIL BIL BIL BIL BIL
Efficiency Efficiency Efficiency Efficiency Efficiency Efficiency
% % % % % %
15 98.1 97.86 — 45 98.1 97.86 —
25 98.33 98.12 — 75 98.33 98.13 —
37.5 98.49 98.3 — 112.5 98.52 98.36 —
50 98.6 98.42 — 150 98.65 98.51 —
75 98.73 98.57 98.53 225 98.82 98.69 98.57
Liquid Filled Substation
100 98.82 98.67 98.63 300 98.93 98.81 98.69
167 98.96 98.83 98.8 500 99.09 98.99 98.89
250 99.07 98.95 98.91 750 99.21 99.12 99.02
333 99.14 99.03 98.99 1000 99.28 99.2 99.11
500 99.22 99.12 99.09 1500 99.37 99.3 99.21
667 99.27 99.18 99.15 2000 99.43 99.36 99.28
833 99.31 99.23 99.2 2500 99.47 99.41 99.33
NOTE: BIL means Basic Impulse Level.
NOTE: All Efficiency values are at 50% of nameplate-rated load, determined
according to the DOE Test Procedure 10 CFR 431, Subpart K, Appendix A.
TRANSFORMERS
14
14-21
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
Energy Efficient, Dry Type 2.4, 5, and 15 kV DOE 2016 Energy Efficient Medium Voltage
Distribution Transformers
Class 7432 schneider-electric.us
Table 14.47: New! EX Three Phase Medium Voltage Transformers Table 14.48: New! Three Phase Voltage Codes
kVA Catalog No. Minimum Weight (lbs) Enclosure kV Class Code Primary Secondary
Efficiency @ 50% 13 2400 Delta 208Y/120
load
14 2400 Delta 480Y/277
2.4 kV and 5 kV Voltage Class 60 Hz 150oC Rise 2.4
15 2400 Delta 240 Delta
112.5 EX112T( )H 98.52 1200 50D 30 kV BIL
16 2400 Delta 480 Delta
150 EX150T( )H 98.65 1400 51D 17 2400 Delta 600 Delta
225 EX225T( )H 98.82 1900 51D 18 4160 Delta 208Y/120
300 EX300T( )H 98.93 2100 52D 19 4160 Delta 480Y/277
500 EX500T( )H 99.09 3000 52D 20 4160 Delta 240 Delta
21 4160 Delta 480 Delta
750 EX750T( )H 99.21 5000 55F
22 4160 Delta 600 Delta
1000 EX1000T( )H 99.28 6000 56F 23 4160Y/2400 240 Delta
1500 EX1500T( )H 99.37 8100 56F 5 25 4160Y/2400 480 Delta
30 kV BIL
2000 EX2000T( )H 99.43 11000 57F 26 4160/2400 600 Delta
2500 EX2500T( )H 99.47 13100 58F 27 4800 Delta 208Y/120
15 kV Voltage Class 60 Hz 150oC Rise 28 4800 Delta 480Y/277
29 4800 Delta 240 Delta
112.5 EX112T( )H 98.36 2000 52D
30 4800 Delta 480 Delta
150 EX150T( )H 98.51 2200 52D 31 4800 Delta 600 Delta
225 EX225T( )H 98.69 2800 53D 32 7200 Delta 208Y/120
300 EX300T( )H 98.81 3300 53D 33 7200 Delta 480Y/277
500 EX500T( )H 98.99 5000 54F 34 7200 Delta 240 Delta
750 EX750T( )H 99.12 6000 55F 35 7200 Delta 480 Delta
36 7200 Delta 600 Delta
1000 EX1000T( )H 99.2 7400 56F
37 12000 Delta 208Y/120
1500 EX1500T( )H 99.3 9000 56F 38 12000 Delta 480Y/277
2000 EX2000T( )H 99.36 11000 57F 39 12000 Delta 240 Delta
2500 EX2500T( )H 99.41 13000 58F 40 12000 Delta 480 Delta
3000 EX3000T( )H — 18000 58F 41 12000 Delta 600 Delta
42 12470 Delta 208Y/120
43 12470 Delta 480Y/277
44 12470 Delta 240 Delta
45 12470 Delta 480 Delta
46 12470 Delta 600 Delta
15
47 12470Y/7200 240 Delta
60 kV BIL
48 12470Y/7200 480 Delta
49 12470Y/7200 600 Delta
50 13200 Delta 208Y/120
51 13200 Delta 480Y/277
52 13200 Delta 240 Delta
53 13200 Delta 480 Delta
54 13200 Delta 600 Delta
55 13200Y/7620 240 Delta
56 13200Y/7620 480 Delta
57 13200Y/7620 600 Delta
58 13800 Delta 208Y/120
59 13800 Delta 480Y/277
60 13800 Delta 240 Delta
61 13800 Delta 480 Delta
62 13800 Delta 600 Delta
All secondary voltages are at 10 KV BIL (BIL means Basic Impulse Level).
2. Insert the voltage code number in place of the ( ) in the catalog number.
Example 1: 1,000 kVA Energy Efficient, 3Ø, 60 Hz, 150oC temp. rise, 60 kV BIL, NEMA sound level, ventilated
indoor enclosure, 13.2 kV delta 480Y/277, with 2-2.5% full capacity taps. 2AN and 2BN = EX1000T51H .
Example 2: 750 KVA Energy Efficient 3Ø, 60 Hz, 80oC temp. rise, 60 kV BIL, NEMA sound level, ventilated indoor
enclosure, 4160 V Delta, 480Y/277, 2-2.5% full capacity taps. 2AN and 2BN = Part number EX750T19HB.
Example 3: 500 kVA Energy Efficient, 3Ø, 60 Hz, 115oC temp. rise, Copper Windings, 60 kV BIL, NEMA sound level,
ventilated indoor enclosure, 12470 Vac delta, 208Y/120, with 2-2.5% full capacity taps. 2AN and 2BN =
EX500T42BCU.
TRANSFORMERS
14-22
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
DOE 2016 Energy Efficient Medium Voltage Energy Efficient, Dry Type 2.4, 5, and 15 kV
Distribution Transformers
schneider-electric.us Class 7432
1,201–15,000 Vac Single-Phase Indoor Transformers
Table 14.49: New! EX Single Phase Medium Voltage Transformers
kVA Catalog No. Minimum Weight Enclosure
Efficiency @ (lbs)
50% load
2.4 kV Voltage Class 60 Hz 150 oC Rise
167 EX167S( )H 98.96 1500 51D
250 EX250S( )H 99.07 2200 52D
333 EX333S( )H 99.14 2500 52D
5 kV Voltage Class 60 Hz 150 oC Rise
167 EX167S( )H 99.07 1500 52D
250 EX250S( )H 99.14 2400 52D
333 EX333S( )H 99.22 3000 53D
15 kV Voltage Class 60 Hz 150 oC Rise
167 EX167S( )H 98.95 2400 52D
250 EX250S( )H 99.03 3400 53D
333 EX333S( )H 99.12 4000 53D
Lugs: Furnished by customer.
Example: 167 kVA Energy Efficient 1Ø 2400/4160Y-120/240 Vac, 1Ø 60 Hz unit is EX167S13H. The unit would be
supplied with 2–2.5% above and 2–2.5% full capacity below normal taps on the primary.
Enclosures
Table 14.51: New! Enclosure Dimensions
Enclosure Number/ Style Height Width Depth Mounting NEMA 3R
in. mm in. mm in. mm
50 D 40.5 1029 36.5 927 21.75 552 Floor n/a consult
factory
51 D 51.5 1308 40.5 1029 26.5 673 Floor n/a consult
factory
52 D 66 1676 50.5 1283 32 813 Floor n/a consult
factory
53 D 80 2032 64 1626 44 1118 Floor n/a consult
factory
54 F 90 2286 72 1829 50 1270 Floor n/a consult
factory
55 F 90 2286 80 2032 50 1270 Floor n/a consult
factory
Style D, NEMA 1 Rated 56 F 90 2286 90 2286 50 1270 Floor n/a consult
factory
57 F 100 2540 100 2540 60 1524 Floor n/a consult
factory
58 F 108 2743 108 2743 60 1524 Floor n/a consult
factory
TRANSFORMERS
These dimensions are not for construction. Contact your local Schneider Electric sales
office for certified prints.
Special outdoor construction required for NEMA 3R applications. Contact your local
Schneider Electric sales office for details.
14-23
© 2018 Schneider Electric
All Rights Reserved
08/06/2018
California Proposition 65 Proposition 65 Message
schneider-electric.us
WARNING: Some of the products listed in this document can expose you to
chemicals which are known to the State of California to cause cancer, birth
defects, or other reproductive harm.
14-24
© 2018 Schneider Electric
All Rights Reserved
08/06/2018