Close Loop
Close Loop
net/publication/3267119
CITATIONS READS
80 410
6 authors, including:
Jyh-Cherng Gu
National Taiwan University of Science and Technology
20 PUBLICATIONS 486 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
single-phase three-wire power flow solution for a modern home premises wiring systems View project
All content following this page was uploaded by Wei-Tzer Huang on 21 August 2014.
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
CHEN et al.: UPGRADING PRIMARY FEEDERS FROM RADIAL AND OPEN-LOOP TO NORMALLY CLOSED-LOOP ARRANGEMENT 1309
B. Basic Considerations
Fig. 1. Schematic diagram of three possible arrangements for forming a In general, the characteristic of an open-loop feeder is the
normally closed-loop feeder.
same as that of a radial feeder, except during the load transfer pe-
riod. For simplicity, only the upgrading from radial to normally
The impacts on the existing systems and customers while up- closed-loop arrangement has been discussed in this paper.
grading should be evaluated in a detailed manner, especially Many factors should be considered while upgrading the
during feasibility study. This paper deals with the upgrading feeder arrangement to a normally closed loop by tying the ends
techniques and impacts. Four feeders fed from two distribution of two existing radial feeders together, such as:
substations of Taipower in downtown Taipei were used as the • the short-circuit currents, capacities and voltage levels of
sample feeders. To explore the impacts of system upgrading, the substations;
some detailed analyzes have been performed in addition to the • the ratings, impedances, loadings, and load characteristics
basic engineering analyzes. Based on the basic and extra engi- of the substation transformers;
neering analyzes, the impacts can therefore be explored and the • the size, length, loading, load distribution, and load char-
required supporting measures can be drawn. acteristics of the feeders.
In this upgrading project, the fundamental and most impor- Not only the qualities of these factors, but also their vari-
tant consideration is the impact on the original system and cus- ations in different operation conditions, are important. These
tomers. The customer outage costs and the cost of replacing factors affect, considerably, both normal and abnormal opera-
all the LBSs with CBs and constructing a feeder automation tions of closed-loop feeders. The capacities of substation trans-
system with high speed communications between the protec- formers, the ampacities of conductors, the voltage profiles along
tive relays at each CB were all considered before the project the feeders, the ratings and settings of protective devices, etc.
was conducted. But the detailed economic analysis and relia- should all be examined to make sure the entire system is well de-
bility assessment will not presented in this paper. The resulting signed while operated in a normally closed-loop arrangement.
reliability improvement from implementing closed-loop feeder On this basis, the feasibility of system-type upgrading is dis-
arrangements is quite obvious, therefore, no information about cussed in detail as follows.
the reliability assessment was presented in this paper. 1) Type I: In Fig. 1, two radial feeders F#1 and F#2 fed by
the same power transformer were tied together at their ends to
II. UPGRADING OF FEEDER ARRANGEMENT form a typically normally closed-loop feeder, classified as type
I in this paper. The factors affecting this kind of upgrading are:
A. Feeder Arrangements
• the conductor sizes of the feeders;
A normally closed loop can be formed by tying the ends of • the lengths of the feeders;
two radial feeders together. Fig. 1 illustrates a schematic di- • the loadings of the feeders;
agram of three possible normally closed-loop feeder arrange- • the distribution of the loads along the feeders;
ments [8]. This figure shows that all the closed-loop circuits • the characteristics of the loads along the feeders.
have two sources. The major difference between these three ar- Hence, the natures of feeders are the key factor for success-
rangements is just the two sources. The closed-loop arrange- fully upgrading a system type from radial to type I closed-loop
ments are classified as follows. arrangement.
Type I: The two feeders for forming a closed loop were In general, primary feeders are classified as thermally lim-
fed by the same power transformer. ited feeders (TL feeders) and voltage-drop-limited feeders (VD
Type II: The two feeders for forming a closed loop were feeders). The feeders serving the customers in urban or suburban
fed by two different transformers located in the areas, having short lengths and high load densities, therefore,
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
1310 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 3, AUGUST 2004
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
CHEN et al.: UPGRADING PRIMARY FEEDERS FROM RADIAL AND OPEN-LOOP TO NORMALLY CLOSED-LOOP ARRANGEMENT 1311
TABLE IV
LUMPED-SUM LOADS FOR THE OTHER FEEDERS
TABLE III
DEMANDS OF HIGH-VOLTAGE AND LOW-VOLTAGE CUSTOMERS
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
1312 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 3, AUGUST 2004
Fig. 4. Current profiles along feeders ZH#54 and ZH#55. Fig. 7. The loadings of substation transformers #1 and #2.
Fig. 5. Voltage profiles along feeders ZH#54 and ZH#55. Fig. 8. Current profiles along feeders ZH#55 and ZH#61.
B. Type II
The feeder pair, ZH#55 and ZH#61, fed by two different
power transformers that are located in the same substation,
makes up a normally closed loop of type II.
1) Transformer Loadings: Fig. 7 shows the loading va-
rieties of the correlative transformers. The loadings of Tr#1
and Tr#2 will become more balanced when the tie breaker is
closed because the two correlative transformers share not only
Fig. 6. The short-circuit capacities at buses along feeders ZH#54 and ZH#55.
the loads of the feeder pair but also the loads connected to
these two correlative transformers. The redistribution of the
in the line segments of the relatively heavier loading side of complex power of Tr#1 and Tr#2 caused Tr#2, with relatively
the loop will decrease while those on the lighter loading side lighter loading, to deliver extra complex power through feeders
increase. There is a current of 89 A flowing through the tie line ZH#61 and ZH#55 to the loads on the secondary side of Tr#1,
from feeder ZH#55 to ZH#54. This fact results in the currents with relatively heavier loading. This fact results in the loading
in each line segment along the feeder circuit becoming more of Tr#1 decreasing and Tr#2 increasing.
uniform after the tie breaker is closed. That is, the operating In addition, while the line segment 4–11 was isolated due to a
condition is changed from A to B. feeder fault, Tr#1 serves all the loads of the feeder pair of Type
In condition C, assuming that the line segment 3–6 is iso- II.1 arrangement. However, for the Type II.2 arrangement the
lated due to a fault occurring at that feeder segment, the loading two power transformers will still share not only the loads of the
will change dramatically and the directions of currents in some feeder pair but also the loads connected to the secondary buses
line segments may also change. For example, the current flow of the two transformers because the tie breaker is closed. There-
through bus 3–9 was increased to 433 A, this may overheat the fore, the loadings of these two transformers will not change
feeder conductor. much.
3) Voltage Profiles: The average node voltages along the 2) Current Profiles: Fig. 8 illustrates the variations of the
feeder circuit will be slightly increased. The voltages along the currents in each line segment. For Type II.1 arrangement, the
feeder ZH#54 were slightly increased while those along the variations are significant. The directions of currents in some line
feeder ZH#55 were slightly decreased, as shown in Fig. 5. Since segments of feeder ZH#55 were reversed. The current flowing in
the load diversity of the feeder pair is large, the variations of the tie line, between buses 13 and 10, is pretty high, 103 A. It is
the line currents are therefore significant. Accordingly, the more directly proportional to the loading difference of the two correl-
load difference between the two feeders, the more line current ative transformers. Therefore, if the loading difference of these
and voltage variations rise. two transformers is large, the feeder pair may act as a transmis-
4) Short-Circuit Capacities: The short-circuit capacities sion line to transfer mass power between the secondary buses of
along the feeder circuit are shown in Fig. 6. The variations of these two transformers. This may lead to the feeder pair being
the short-circuit capacities under three operating conditions overloaded. This phenomenon should be avoided. Nevertheless,
are small. Generally, the farther the bus from the tie point, the if more than one feeder pair between these two transformers are
less the increasing rate of short-circuit capacity obtains. For tied to form more closed loops, these loops will share the power
example, the short-circuit capacity of bus 8 was increased 12% need been transferred. Therefore, the impacts will be lessened.
when the two feeders were tied together as a closed loop. For Type II.2 arrangement, the varieties of line currents have the
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
CHEN et al.: UPGRADING PRIMARY FEEDERS FROM RADIAL AND OPEN-LOOP TO NORMALLY CLOSED-LOOP ARRANGEMENT 1313
Fig. 10. The short-circuit capacities at buses along feeders ZH#55 and ZH#61.
same trends as those of Type I after the tie breaker was closed,
as shown in Fig. 8.
3) Voltage Profiles: Fig. 9 depicts the voltage profiles of the
nodes along the feeder pair. It is obvious that the node voltages
along the feeder ZH#61 are descending while those along the Fig. 13. Voltage profiles along feeders ZH#61 and SU#74.
feeder ZH#55 are ascending. This trend is similar to that of a
Type I arrangement. formers are not enormous. However, if the voltage levels of the
4) Short-Circuit Capacities: Fig. 10 shows the short-circuit primary sides of the two correlative distribution substations are
capacities of nodes along feeders ZH#55 and ZH#61. The trends different, for example, one is 161 kV and another one is 69 kV,
of variations of the short-circuit capacities are similar to those then the transformer loading may vary significantly even if the
of Type I. When two radial feeders are tied, the short-circuit difference of the loads connected to the two correlative trans-
capacities of the buses along the feeders are almost doubled. formers is not great. In this case, it is possible that mass power
However, the increasing rates of short-circuit capacities after the may flow from one transformer to the secondary bus or even
tie breaker being closed are much larger than those of Type I. back feed to the primary side of the other transformer, through
The reason is that the fault current at each bus comes from two the feeders that are tied at their ends normally. This condition is
sources when the feeder pair is tied together. In addition, the definitely undesirable.
varieties of the short-circuit capacities due to the line segment In addition, the loadings and the differences of loadings of
4–11 being isolated are pretty different for Type II.1 and II.2, correlative transformers and feeders will also govern the vari-
as shown in Fig. 10. Hence, upgrading the protective devices is ations of correlative transformer loadings. In other words, the
usually required for both the distribution feeders and customers variations of transformer loading are directly proportional to the
connected to them when upgrading the system type from radial factors just mentioned above. Consequently, if the primary sides
to closed loop. of the correlative distribution substations are at the same voltage
level, and the feeder loads and transformer loads are well bal-
C. Type III anced, then, the variations of transformer loading will be minor.
The feeder pair, ZH#61 and ZH#74, fed by two different The given conditions for Type III are the same as for the other
power transformers located in different substations, makes up two types in this paper, so the loading variations are similar to
a normally closed loop of type III. those of Type II.1, but are more sensitive to the loading differ-
1) Transformer Loadings: Fig. 11 shows the loading varia- ences of the two correlative transformers and voltage differences
tions of the two correlative transformers, Tr#2 and Tr#3 under of the secondary buses of these two transformers.
specific system conditions. For Type III arrangement, the trans- 2) Current Profiles: Fig. 12 illustrates the variations of cur-
former loadings may total differently in different cases because rents flowing in each line segment under specific system con-
they are sensitive to system conditions, such as the loading dif- ditions. Similarly, the current variations may total differently in
ference between two correlative transformers, the voltage dif- other cases. The reasons are the same as those for the trans-
ference between two correlative substations, and the difference former loads. In the given conditions, the currents flowing in the
in the short-circuit capacities between those two correlative sub- feeder ZH#61 were increased after the tie breaker was closed,
stations. For example, if the voltage levels of the primary sides and the current flowing in the tie line, line segment 13–16, was
of the two correlative distribution substations are the same, the 41 A.
transformer loading variations are usually insignificant, if the 3) Voltage Profiles: Fig. 13 depicts the voltage profiles
difference of the loads connected to these two correlative trans- along the feeder under specific system conditions. Similarly,
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
1314 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 3, AUGUST 2004
TABLE V
IMPACTS ON THE ORIGINAL SYSTEMS AND CUSTOMERS
Fig. 14. The short-circuit capacities at buses along feeders ZH#61 and SU#74.
D. Discussion
Based on the simulation results, the impacts on the distribu-
tion systems and customers due to the upgrading of system type
can be drawn, as shown in Table V. The impacts of Type I are
the least among the three types of feeder arrangements. Hence,
the type I arrangement is the easiest to use while upgrading a
existing radial or open-loop system. This type has been used
by Taipower to upgrade an existing radial system to a normally
closed-loop system in metropolitan Taipei.
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
CHEN et al.: UPGRADING PRIMARY FEEDERS FROM RADIAL AND OPEN-LOOP TO NORMALLY CLOSED-LOOP ARRANGEMENT 1315
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
1316 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 3, AUGUST 2004
Guan-Chih Pu was born in Taiwan, R.O.C., in 1962. He received the B.Sc. Tzong-Yih Guo (M’92) received the B.S. degree in electrical engineering from
and M.Sc. degrees in electrical engineering from the National Taiwan Institute, National Cheng Kung University, Taiwan, R.O.C., in 1977, the M.S. degree
Taiwan, and the Ph.D. degree from tje National Taiwan University of Science in power system engineering from National Tsing Hua University, Taiwan, in
and Technology, Taiwan. 1979, and Ph.D. degree in power system engineering from Michigan State Uni-
Since 1989, he has been with the Taiwan Power Company Research Insti- versity, Ann Arbor, in 1992.
tute. His research interests include power system analysis, SCADA systems, He joined Taiwan Power Company in 1982, where he was a Power System
and electric power quality. Specialist in the System Planning Department until November 1994. From 1994
to 2002, he was the Manager of the Electric Power Research Laboratory at the
Power Research Institute. He was appointed Deputy Director of the System
Planning Department in June 2002. His current research interests include power
Yen-Feng Hsu was born in Taiwan, R.O.C., in 1962. He received the B.Sc. de- system dynamical stability assessment, applied nonlinear system theory, elec-
gree in electrical engineering from National Taiwan Institute, Taiwan, the M.Sc. tric power quality, and real-time measurement and parameter identification.
degree in electrical engineering from National Tsing Hua University, Taiwan,
and the Ph.D. degree from the National Taiwan University of Science and Tech-
nology, Taiwan.
Since 1989, he has been with the Taiwan Power Company Research Institute.
His research interests include power system analysis and electric power quality.
Authorized licensed use limited to: Chienkuo Technology University. Downloaded on April 15,2010 at 07:25:15 UTC from IEEE Xplore. Restrictions apply.
View publication stats