Gas-insulated

ring main units


FB
up to 36 kV

System Configuration

T&D
Power Distribution
Terms of delivery
The General Terms of Delivery, as amended, shall apply.

Illustrations
The illustrations are not binding for delivery.
Introduction

Introduction
Features 4
Mechanical design
Technical description 6
Optional equipment 10
Range of available models
Ring main units, type FBA, FBE, FBT, FBM 11
Selection tables
Performance characteristics of the FBT
ring main units, outgoing feeder cable,
outgoing transformer feeder 13
Performance characteristics of the FBA,
FBE ring main units, outgoing feeder cable,
outgoing transformer feeder 14
Performance characteristics, regulations and
directives, degrees of protection, standard
operating conditions 15
General technical data
Control and operating devices
Data for motor-drive mechanism,
power consumption of motor-drive mechanism,
data for shunt opening release,
data for auxiliary switch 17
Dimensions and weights, SF6 filling 18
Low-voltage wiring 20
HVHBC fuse links 22
Metering panel 24 kV 26
Selection tables for cable fittings 27
Constructional data
Pressure relief (in case of an internal fault) 30
Attachment of gas coolers to switchgear 31
Fastening and flooring ducts 32
Shipping information
Transport of the switchgear 33
Fax query to submit an offer 34

3
Introduction

Features

Straightforward planning

The FBA, FBE ring main units and


the FBT transformer switching blocks
are three-pole enclosed switch-dis-
connector units. SF6 gas is used as
insulating and switching medium.
The gas-insulated switchgear units
are insensitive to environmental in-
fluences, e.g. to humidity, dust and
aggressive gases, and afford maxi-
mum personnel protection. The clear
overall design ensures easy,
straightforward operation. The spa-
cious cable connection area permits
selection of various cable connec-
tion systems.
The FB ring main units have been
designed for rated voltages of up to
36 kV and rated currents up to 630
A; they feature a particularly com- FBA/FBE ring main unit
pact design.

Safe operation

This switchgear station warrants


safe operation: thanks to its high
personnel and operating safety, ex-
tremely reduced space requirements
and independence of environmental 1
2

influences.

The result is a particularly economi-


cal solution with an extremely high
safety standard, especially due to:
– separate switching devices for
load disconnectors and earthing
switches
– fuse/load disconnector combina-
tions
– one separate earthing switch
each upstream and downstream
of the fuse receivers
FBT transformer
switching block

4
The advantages of our gas-insulated Particular features of our series FB
ring main units A/E/T

• All components conducting • Continuity up to 36 kV


medium voltage are insensitive to • Enhanced personnel protection
– air humidity due to separate switching devices
– aggressive atmosphere for load disconnectors and earth-
– dirt ing switches
– dust • Straightforward exchange of
– vermin and rodents cable phases due to horizontal
• SF6 – an insulating gas featuring arrangement of the outside-cone
extremely favourable properties cable bushings (i.e. 3 bushings
– extremely high insulating capacity side-by-side at the same level)
– incombustible • Extremely easy replacement of
– no contact oxidation fuses
• Maximum operating safety due to • No bridging of the isolating dis-
– low gas pressurization tance by insulating material, i.e.
– excellent gas-proofing the condition of the electrical iso-
– high inductive breaking capacity lating distance is maintained for
• Minimum floor space / room re- the entire service life
quirements due to • Spacious cable connection com-
– insulating medium SF6 partment, suited for connection of
– compact design parallel cables or cable connec-
• Maximum personnel safety tion with additional surge arre-
– straightforward and safe opera- sters - possible within the switch-
tion gear boundaries
– comprehensive, powerless inter- • Particularly clearly arranged ope-
locking system rating panel with operator gui-
– tested and approved for beha- dance and switchgear inter-
viour in case of an internal fault locking
(PEHLA tested)
• Zero maintenance for life-time
(approx. 30 years)

Transformer
Low-voltage
section

Medium-voltage section

Other
components

Compact station of concrete

5
Mechanical design

Technical description ting safety, separate switching de-


vices (each switching device has a
The FBA/E ring main unit and the drive of its own) are used on prin-
FBT transformer switching block are ciple for load disconnectors and
mounted on a rugged, hot-galva- earthing switches.
nized supporting structure. The All switching devices are equipped
switching units are housed in a with snap-action drives. As a rule,
shared tank made of corrosion-re- the load disconnectors of the trans-
sistant and non-magnetic chromium- former unit are equipped with an
nickel steel. additional breaking stored-energy
The tank is designed as a "sealed mechanism. Operation

pressure system". Given the climatic In our ring main units, we use tech-
conditions which are normally assu- nical lubricants which do not requi-
med to exist in substations, it has a re any maintenance under normal
service life of approx. 30 years. climatic conditions according to IEC
The service pressure of the insulat- 60298 or DIN/VDE 0670, part 6.
ing gas SF6 is 0.3 bar. A shutter is installed above the ope-
The tank bottom is equipped with rating panel; it can be used to ac-
pressure relief devices which en- commodate short-circuit indicators,
sure, in case of excess pressure, voltage detection systems or – on re-
Pressure relief device
that gases which escape are di- quest – DSA2 and pressure gauges.
verted to the bottom or to the rear.
Spacious cable connection compart-
Switching units ment

The current circuits of the three-pole The cable connection compartments


switching units are arranged side are amply designed. All commerci-
by side; load disconnectors and the ally available systems can be instal-
make-proof earthing switches are led in the ring main units: fully insu-
separate switching devices with se- lated, metal-enclosed terminal sy-
parate drives. The load disconnec- stems, partially insulated terminal Cable connecting sockets
according to DIN 47636
tors are designed as twist switches systems, parallel cables, cables and
and arranged so that the isolating surge arresters or ground cables.
distances are not bridged by insu- Pressure relief
lating material when the unit is
switched off. The pressure relief devices which
are metallically separated from the
Drives cable connection act as rupture
joints for the case of internal excess
The drives for the switching units pressure of the gas-filled cladded
are located on the front end, in a compartment.
separate metal-enclosed chamber,
outside of the gas-filled switching
compartment.
To enhance personnel and opera- Drive unit FBA

6
High-grade steel tank, filled with insu-
lating gas, with switching units, fuse
attachment and drives

Board with indicators

Operat-
Cable connection, ing panel
outgoing feeder cable
Cable connection,
outgoing transformer
feeder

Supporting structure
Cable compartment
and fuse cover

1 Position indicator, load disconnector


“ON”-”OFF”

2 3 4 2 3 4 2
2 Insertion opening for detachable lever
5 5 5 3 4
Load disconnector
1 1 1 3 Position indicator, earthing switch

4 Insertion opening for detachable lever


Earthing switch
6
5 Slide switch for powerless interrogator
Cable 1 Cable 2 Transformer
lock
Earthing switch/load disconnector
Operating panel FBA/FBE 6 Rating plate

3 4 2 5 3 4

Cable Transformer

Operating panel FBT

7
Standardized cable terminal compo- placement of its fuse links. The fuse
nents links are installed in insulating con-
duits which are integrated into the
The cables are connected via stan- hermetically sealed, gas-filled clad-
dardized outer cone-type compo- ded compartment as required by
nents according to DIN 47636. the system; this has the following
Ring main cable connection: Tee advantages:
screw-type plugs or cable terminal – the electrical field is essentially
systems for outside-cone cable bush- arranged within the SF6 atmos-
ings according to DIN 47 636, phere
part 6, AS36 630 with internal – the fuse handle with its sealing
thread M16x2 must be provided to set is placed in the "shadow" of
this effect. the field intensity
Connection of transformer cables: – no conductive layers (e.g. indu-
The use of right-angle or straight strial or sea atmosphere) can
connectors according to DIN, part settle on the insulating surface of
3, ASL24 250, is recommended for the fuse attachment
this purpose. As an alternative, out- – the area within the gas-filled
side-cone cable bushings AS36 cladded compartment is com- Cable connection

630 according to DIN 47 636, pletely protected


part 6, with internal thread M16x2 – the area of the fuse handle is in-
can be provided to this effect. sensitive - there is especially no
For a precise list, please refer to need to establish "electrical seal-
page 27. ing" conditions (arrangement of
Variable adjustable cable irons per- insulation) with the handle closed.
mit connection of different cable ter-
minal systems. Additional horizon- The stored-energy mechanism and
tally and vertically adjustable sup- the rugged tripping linkage ensure
porting plates for parallel cable that all three phases are switched
boxes or surge arresters can be sup- off on fuse tripping, as provided by
plied with the switchgear as optio- IEC 60 420. Maximum personnel
nal equipment. protection is ensured by the interro-
gator interlock which only enables
opening of the fuse cover if the sy-
Interrogator interlock system stem is correctly grounded. Two
earthing switches arranged upstre-
At ALSTOM Sachsenwerk, person- am and downstream of the fuse
Fuse handle and all-pole
nel and operator safety is of maxi- links enable fuse replacement with-
tripping
mum priority in the development of out insulating tools. Vice versa, the
switchgear. A continuous interroga- earthing can only be cancelled after
tor interlock system has been de- the fuse cover has been closed.
signed to prevent any unauthorized Both earthing switches are make-
operation and to enable access to proof and are switched simulta-
the cable compartment only after it neously via a snap-action drive.
has been grounded as specified.
The following mutual interlocks have
been implemented:
– Load disconnector - earthing
switch
– Earthing switch - cable compart-
ment cover
– Earthing switch - fuse cover

Replacement of the fuse links

An essential advantage of the FB


ring main unit is straightforward re- Interrogator lock Fuse replacement

8
For selection of the fuse links, we the type tests and in several tests Surface protection
recommend to adhere to page 18 during development, thus proving
and to insert standard fuses with their safety. The tests were conduc- The ring main unit fairings are hot-
thermal protection. ted in internal high-capacity test galvanized to protect them against
bays and in neutral institutions, as corrosion. The switchgear front is vi-
e.g. IPH Berlin, KEMA, L.C.O.E. sually enhanced by painting.
Connecting external control lines Spain, LABORATORIUM LISTRIK Standard paint:
Jakarta etc. – Operating panel RAL 1003
External control lines can be (signal yellow)
connected to terminal strips by – Covers painted according to
branches following the standar- Climatic conditions RAL 7044 (silk grey)
dized wiring diagram. – Side panels and supporting struc-
The switchgear is suited for tempe- ture hot-galvanized
ratures between -25 and +60°C as
Auxiliary switches well as for the operating conditions
according to DIN VDE 0670, part 6 Locations for installation
Multi-pole (up to 10) auxiliary (see operating conditions on page
switches can be installed on/in 15). The medium-voltage section The switchgear is suited for installa-
load disconnectors. located in the gas-filled cladded tion in confined electrical operating
Earthing switches can be equipped compartment and a fully insulated areas.
with 2-pole auxiliary switches. The cable connection conforming with
auxiliary switches can also be ad- the system is protected against en-
justed subsequently as break and vironmental influences, such as hu-
make contacts by adjustable cams. midity, dust, aggressive gases etc.
The gas-filled cladded compart-
ments made of chromium-nickel
Tested and approved switchgear steel, the SF6 gas insulation and the
high switching capacity warrant
Our ring main units have satisfied trouble-free operation and a long
the requirements of DIN VDE 0670, service life.
part 6, PEHLA 1-6 or IEC 60298 in

9
Optional equipment 2. Short-circuit indicators which are
directly mounted to the grounded
Zero voltage detection single-conductor cables. To this ef-
fect, the cable compartment covers
The electronic voltage detection sy- must feature inspection ports (optio- – IVIS – the integrated vol-
stem IVIS with integrated indicator tage detection system
nal equipment). – short-circuit indicator
(three lightning flash symbols) indi- The indications of the short-circuit in-
cates zero voltage in a branch and dicator manufacturers must be com-
fully satisfies the requirements of plied with.
VDE 0682, part 415, or of the IEC
publication 61243-5, part 5E.
Cable compartment cover
In the presence of full rated voltage,
IVIS indicates continuous, uninter- The cable compartment covers
rupted lightning flash symbols. serve as a shock-hazard protection
of the cable connection systems and
The lightning flash symbols feature are designed to be arc-resistant.
an integrated malfunction indication The covers are also available with
showing interrupted lightning flash inspection ports on request.
symbols in case of a malfunction. In
this case, the switchgear may re-
Additional interlock Removable cable compart-
main operative, but remedies must ment covers
be co-ordinated with the manufactu- An auxiliary interlock can be pro-
rer. vided for cable testing; it prevents
the load disconnector from being
The IVIS measuring sockets meet the switched on while the earthing
operating conditions for a phase switch is "OFF" and the cable
monitor with N.O. interface. connection compartment is open.

Optionally, zero voltage of the


branch may also be determined via Pressure indication
a constant-voltage indicator. In this
case, the sockets for the constant- The pressure is indicated via a pres- ➀ Green zone
(operating range)
voltage indicator (HO system) are sure gauge which is screwed onto ➁ Filler valve
➂ Pressure gauge
installed in the appliance recess. the filler valve. A pressure gauge coupling
(pressure gauge
can be retrofitted without requiring screw coupling)
➃ Pressure gauge
gas work and without interrupting
Phase comparison the operating condition.

Phase comparison is possible by


means of the phase monitor Mimic diagram
MS 100.
One of the characteristic features of Gas pressure gauge

the FB ring main units is the operat-


Short-circuit indicator ing panel of exemplary design.

The switchgear can be equipped


with short-circuit indicators. On prin- Motor-drive mechanisms
ciple, short-circuit indicators can be
The load disconnectors and earth-
used in two ways:
ing switches are actuated manually
1. Short-circuit indicators within the
via detachable levers. Motor-drive
switchgear front. The conductors L1,
mechanisms for remote control can
L2 and L3 are displayed separately.
be provided for the load disconnec-
The short-circuit indicators can be
tors behind the operating panel.
equipped as follows, on request:
– with manual reset
– with automatic reset
– with remote alarm contact
– with earth-fault indicator

10
Range of available models

Ring main units,


type FBA, FBE, FBT, FBM

The type designations of the type-


tested ring main units and of the
transformer switching block inform
about the design, the rated voltage,
the insulation level and the compo-
nents fitted.

Type designation Explanation

Series FB . . . / . . - . / . . . Switch disconnector units with


load disconnector

Model A, E Gas-insulated ring-main unit


for substations

T Gas-insulated transformer switching


block for mast base stations and
wind converter plants
M Metering panel

Rated peak current 4 Rated peak current 40 kA


5 50 kA
6 63 kA
Rated voltage
/ 12-2 / Rated voltage 12 kV
/ 17-2 / 17.5 kV
/ 24-2 / 24 kV
/ 36-2 / 36 kV

11
Variants Model code Rated voltage Types
kV

12 17.5 24 36 FBT FBA FBE

2011 KT ● ● ● ● ●

3000 KKK ● ● ● ● ● ●

3001 KKT ● ● ● ● ● ●

3002 KTT ● ● ● ●

4000 KKKK ● ● ● ● ● ●

4001 KKKT ● ● ● ● ● ●

4002 KKTT ● ● ● ● ● ●

4003 KTTT ● ● ● ●

5000 KKKKK ● ● ● ● ● ●

5001 KKKKT ● ● ● ● ● ●

5002 KKKTT ● ● ● ● ● ●

5003 KKTTT ● ● ● ● ● ●

5004 KTTTT ● ● ●

Metering ●1) ● ●
panel

1)
on request K=Cable, T=Transformer

12
Selection tables

Performance characteristics of
FBT ring main units (transfor-
mer switching block)
Outgoing feeder cable
Outgoing transformer feeder

Performance characteristics of the switching units


Rated voltage kV 12 17.5 24 36
Service voltage max. kV 12 17.5 24 36
Rated frequency Hz 50/60 50/60 50/60 50
Rated lightning impulse to ground kV 75 95 125 170
withstand voltage across isolating distance kV 85 105 145 195
Rated power to ground kV 28 38 50 70
frequency across isolating distance kV 32 45 60 80
Cable testing voltage (direct voltage) 15 min. kV 48 60 96 108
Rated current A 200 200 200 200
Outgoing feeder cable Rated short-time current 1s kA 16 16 16 16
with earthing switch 3s kA – – – –
Rated peak current kA 40 40 40 40
Rated making current (earthing switch) kA 40 40 40 40
Number of operations with rated 5 5 5 5
making current
Outgoing transformer Rated current A 200 200 200 200
feeder Rated short-time current 1s kA 5 5 5 5
(Earthing switch) 3s kA – – – –
Rated peak current kA 16 16 16 16
Rated making current kA 16 16 16 16
Number of operations with rated making current 5 5 5 5
Rated take-over current
according to IEC 60420 A 3000 800 800 800
Dielectric strength Lightning impulse withstand voltage kV 75 95 125 170
Power frequency withstand voltage kV 28 38 50 70

Dielectric strength at balanced Lightning impulse withstand voltage kV 75 95 95 145


pressure of 0.0 bar SF6 Power frequency withstand voltage kV 28 38 50 70
Rated filling pressure SF6 at 20 °C bar 0.3 0.3 0.3 0.3
Pickup pressure of pressure relief device bar <2 <2 <2 <2
Wall thickness of stainless steel tank mm 3 3 3 3

13
Performance characteristics of
FBA, FBE ring main units
Outgoing feeder cable
Outgoing transformer feeder

Performance characteristics of the switching units


Rated voltage kV 12 17.5 24 36
Service voltage max. kV 12 17.5 24 36
Rated frequency Hz 50/601) 50/601) 50/601) 50
Rated lightning impulse to ground kV 75 95 125 170
withstand voltage across isolating distance kV 85 105 145 195
Rated power frequency to ground kV 28 38 50 70
withstand voltage across isolating distance kV 32 45 60 80
Cable testing voltage (direct voltage) 15 min. kV 48 60 96 108
Outgoing feeder Rated current A 400/630 400/630 400/630 630
cable Rated short-time current 1s kA 16/20/25 16/20/25 16/20/25 16
3s kA 16/20/25 16/20/25 16/20/25 16
Rated peak current kA 40/50/63 40/50/63 40/50/63 40
Rated making current kA 40/50/63 40/50/63 40/50/63 40
Number of operations with rated making current 5 5 5 5
Rated closed-loop breaking current A 400/630 400/630 400/630 630
Rated load breaking current A 400/630 400/630 400/630 630
Number of operations with rated load breaking current 100 100 100 100
Number of mechanical operating cycles 1000 1000 1000 1000
Rated cable-charging and line-charging breaking current A 160 160 160 80
Inductive breaking current2)
Rated cable-charging breaking current under
earth-fault conditions A 160 160 160 160
Rated breaking current under
earth-fault conditions A 600 600 600 300

Outgoing transformer Rated current A 200 200 200 200


feeder with fuses Rated short-time current 1s kA 5 5 5 5
(Earthing switch) 3s kA 3 3 3 3
Rated peak current kA 16/20 16/20 16 16
Rated making current kA 16/20 16/20 16 16
Number of operations with rated making current 5/2 5/2 5 5
Rated take-over current
according to IEC 60420 A 3000 800 800 800
Dielectric strength Lightning impulse withstand voltage kV 75 95 125 170
Power frequency withstand voltage kV 28 38 50 70

Dielectric strength at balanced Lightning impulse withstand voltage kV 75 95 95 145


pressure of 0.0 bar SF6 Power frequency withstand voltage kV 28 38 50 70
Rated filling pressure SF6 at 20 °C bar 0.3 0.3 0.3 0.3
Pickup pressure of pressure relief device bar <2 <2 <2 <2
Wall thickness of stainless steel tank mm 3 3 3 3

1)
Rated making current 63 kA at 60 Hz on request
2)
No-load current of transformers up to 1250 kVA

14
Performance characteristics
Regulations and directives
Degrees of protection
Standard operating condi-
tions

Regulations and directives VDE IEC

Design and execution VDE 0670, part 6; VDE 0670, part 1000 IEC 60298; IEC 60694
Type testing, routine testing
Load disconnector – switching units VDE 0670, part 301 IEC 60265-1
Fuse/load disconnector combination VDE 0670, part 303 IEC 60420
Earthing switch VDE 0670, part 2 IEC 60129
Behaviour in case of an internal fault VDE 0670, part 6 Appendix AA criteria 1-6, 1s IEC 60298 with Appendix AA
Operation, operator control and work
in the vicinity of live components VDE 0105, part 1000
Installations, building dimensions, room type Indoor switchgear, utilization according to VDE 0101 in confined electrical operat-
ing areas: rooms or locations which are exclusively used for the operation of electri-
cal equipment, which are kept closed and which are only accessible to persons
having undergone electrotechnical training. Access by untrained persons is only
permitted in the presence of specialist electricians or persons having undergone
electrotechnical training.

Degree of protection VDE 0470, part 1 IEC 60529

for the main circuits IP 64


for the drive mechanisms IP 2X
for the cable connection compartment IP 3X
(operator side with cable compartment cover,
side panels)

Standard operating conditions Indoor conditions according to


VDE 0670, part 1000 IEC 60694

Options
Temperature of Maximum value 40 °C 50 °C to 60 °C1)
ambient air Average value over 24 h 35 °C 45 °C to 55 °C1)
Minimum ”indoor” value minus 5 °C minus 25 °C
Installation altitude up to 1000 m higher installation altitudes on request
above sea level
Rated filling pressure (gas pressure) at 20 °C
1)
at reduced rated current – refer to diagram, page 16

15
Admissible number of operations of Continuous current carrying capacity as a function of the ambient temperature for FBA
the load disconnectors 750

Type FBA, FBE and FBT switchgear


700
units are maintenance-free for their

Continuous current [A]


entire service life.
650
FBA 630 A
The admissible number of opera- rated current
tions is so ample that it is normally 600
at 40 ºC
not reached within the service lives. Testing point
550

Should, however, the admissible


number of operations be reached in 500

20

25

30

35

40

45

50

55

60
exceptional cases, please contact
the manufacturer. Ambient temperature [ºC]

Mains cable outgoing feeder Mains cable outgoing feeder


Rated current 400 A Rated current 630 A
1 000 1 000

500 500
Breaking current n

Breaking current n

100 100

50 50

10 10
10

50

10

50
100

400
500

1000

5000

100

500

1000

5000
630

Breaking current n Ia (A) Breaking current n Ia (A)

Outgoing transformer feeder Outgoing transformer feeder


Series FBA, FBT 12 kV Series FBA, FBT 24 kV
Take-over current 3000 A Take-over current 800 A
1 000 1 000

500 500
Breaking current n
Breaking current n

100 100

50 50

20

10 10
10

50

10
3000

50
100

500

1000

5000

100

500

1000

5000

Breaking current n Ia (A) Breaking current n Ia (A)

Diagrams indicating the admissible number of operations


16
General technical data

Control and operating


devices

Technical data for motor-drive mechanism


Drive mechanism type Outgoing transformer feeder Mains cable outgoing feeder
Stored-energy mechanism SF Snap-action drive SFU
Rated voltage [kV] 12 17.5 24 36 12 17.5 24 36
Closing time
(for motor actuation) [s] ≤6 ≤3
Opening time
(for motor actuation) [s] ≤ 0.7 ≤3
Opening time for release 160 W [ms] ≤ 34 ≤ 45 –
Minimum command time ”OFF” for release 160 W [ms] ≤ 20 –
Arcing time (max. value) [ms] 18 15
Opening time T [ms] 38 –
°
Motor charging time ”ON” [s] ≤6 ≤3
Motor charging time ”OFF” [s] – ≤3
Motor (power consumption) [W/VA] 150 170 150 170

Power consumption for motor drive in case of SF and SFU drive mechanisms
Rated voltage [VDC] [VAC]
24 48 60 110 125 220 120 230
Starting current [A] 13.3 12.1 8.4 4.7 4.1 2.5 6.8 3.7
Rated current [A] 5.5 2.8 2.2 1.2 1.1 0.6 2.2 1.2

Technical data for shunt opening release


Power consumption of solenoid (160 W) of shunt opening release (SF drive)
Rated voltage [VDC] [VAC]
24 48 60 110 125 220 120 230
Coil current [A] 6.3 3.2 2.6 1.3 1.2 0.7 0.9 0.5

Technical data for auxiliary switch


DC voltage Alternating
[V] voltage
[V]
24 48 60 110 220 120 220
Switching capacity in [A] 8 4 3 2 1 10 10
Rated short-time current 100 A up to 30 ms
Time constant T = L/R ≤ 20 ms –

17
Dimensions, weights and
SF6 filling

FBT 2011 FB 3001

Width Width Depth Depth

127,5

Height
Height

65–-107

h
M12 M12

m
g
85
85

k l

L1 L2 L3 L1 L2 L3 L1 L2 L3

M12 M12
120

120

L1 L2 L3 L1 L2 L3

a f f af f
f f b f f
b
c f f

FB 4002 FB 5003

Width Width
Height
Height

M12 M12
85
85

L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3
M12 M12
120

120

L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3

d e

18
Model Up Width Height Depth a b c d e f g h k l m Weight
kV kg
FBT 2011 12/17.5/24 690 – 220 to 235
FBA 3000 12/17.5/24

FBA 3001 12/17.5/24 1010 – 300 to 350


FBA 3002 2) 12/17.5/24 –
FBA 4000 12/17.5/24

FBA 4001 12/17.5/24 400 to 465


1330
FBA 4002 12/17.5/24 1315 725 90 410 730 95 75 – 435 700 470 541.5 373
FBA 4003 2) 12/17.5/24 (1045) 1) (60 –170)1) (430)1) (103)1)

FBA 5000 12/17.5/24 1050 – 480


FBA 5001 12/17.5/24 510
FBA 5002 12/17.5/24 1650 1370 530
FBA 5003 12/17.5/24 555
FBA 5004 2) 12/17.5/24 580

1) optional Dimensions in mm

2) this model not available in optional switchgear height 1045

Model Up Width Height Depth a b c d e f g h k l m Weight


kV kg
75 – 665 975 698
FBT 2011 36 990 1700 (1400)1) – (25 –465)1) (675)1) (398)1) 460
FBE 3000 36 510
1460
FBE 3001 36 1700 – 75–665 975 698 560
FBE 4000 36 – 600
75 – 665 975 698
FBE 4001 36 1930 1700 (1400)1) 865 135 605 1075 (25 –465)1) (675)1) 475 646.5 (398)1) 650
FBE 4002 36 125 700
FBE 5000 36 1545 700
FBE 5001 36 75–665 975 698 750
2400 2015
FBE 5002 36 800
FBE 5003 36 850

1) optional Dimensions in mm

SF6 filling
Rated voltage 12 kV 17.5 kV 24 kV 36 kV

Type Volume of SF6 gas tank

2011 230 l; 1.8 kg 510 l; 4.0 kg


3000 250 l; 1.9 kg 530 l; 4.2 kg
3001 310 l; 2.4 kg 650 l; 5.1 kg
3002 370 l; 2.9 kg –
4000 330 l; 2.6 kg 680 l; 5.3 kg
4001 390 l; 3.0 kg 790 l; 6.2 kg
4002 450 l; 3.5 kg 900 l; 7.0 kg
4003 510 l; 4.0 kg –
5000 410 l; 3.2 kg 820 l; 6.4 kg
5001 470 l; 3.7 kg –
5002 530 l; 4.1 kg 1060 l; 8.3 kg
5003 590 l; 4.6 kg 1180 l; 9.2 kg
5004 650 l; 5.1 kg –

19
Auxiliary circuits

Wiring diagram – Mains cable outgoing feeder

Item of apparatus

1st branch 2nd branch 3rd branch 4th branch 5th branch Function
–H11 –H12 –H13 –H14 –H15 Short-circuit indicators (terminals 8-12: optional equipment)
–M11 –M12 –M13 –M14 –M15 Motor on load disconnector
–Q11 –Q12 –Q13 –Q14 –Q15 Load disconnector
–Q81 S51/52 –Q82 S51/52 –Q83 S51/52 –Q84 S51/52 –Q85 S51/52 Auxiliary contact on earthing switch control element
–Q81 –Q82 –Q83 –Q84 –Q85 Earthing switch
–S11 –S12 –S13 –S14 –S15 Auxiliary switch on load disconnector
–S81 –S82 –S83 –S84 –S85 Auxiliary switch on earthing switch

The devices appearing in the


boxed-in area are installed in the
switchgear unit, depending on the
order, and are wired up to the ter-
minal strip.
Devices outside of the boxed-in
areas are not included in the scope
of supplies. The free contact ele-
ments of the auxiliary switch (S11)
have been factory-set as shown in
the circuit diagram. However, inde-
pendently of the factory setting,
each contact element of the auxili-
ary switch can be adjusted as
break contact, make contact or
passing contact.

20
Wiring diagram – Outgoing transformer feeder with integrated fuse installation

-Q13

-Q83

Item of apparatus

1st branch 2nd branch 3rd branch 4th branch 5th branch Function
–F12 –F13 –F14 –F15 Shunt opening release
–M12 –M13 –M14 –M15 Motor on load disconnector
–Q12 –Q13 –Q14 –Q15 Load disconnector with fuse attachment
–Q12 S31/32 –Q13 S31/32 –Q14 S31/32 –Q15 S31/32 Initiator on fuse attachment
–Q82 S51/52 –Q83 S51/52 –Q84 S51/52 –Q85 S51/52 Auxiliary contact on earthing switch control element
–Q82 –Q83 –Q84 –Q85 Earthing switch
–S12 –S13 –S14 –S15 Auxiliary switch on load disconnector
–S82 –S83 –S84 –S85 Auxiliary switch on earthing switch

The devices appearing in the


boxed-in area are installed in the
switchgear unit, depending on the
order, and are wired up to the ter-
minal strip.
Devices outside of the boxed-in
areas are not included in the scope
of supplies. The free contact ele-
ments of the auxiliary switch (S13)
have been factory-set as shown in
the circuit diagram. However, inde-
pendently of the factory setting,
each contact element of the auxili-
ary switch can be adjusted as
break contact, make contact or
passing contact.

21
1. HVHBC fuse links Fusing table and standards High ambient temperature

Selection and supply by The fusing table on page 23 has The fusing table also applies to a
ALSTOM Sachsenwerk GmbH been designed for normal applica- max. ambient temperature of 50 °C,
tion of the switchgear units and tak- e.g. for the switchgear within the
ing account of all appropriate stan- housing of a packaged substation
These projecting notes represent re- dards. according to IEC 61330, VDE
commendations by the manufacturer 0670, part 611, for very hot cli-
in accordance with the requirements These standards are: mate conditions.
of the appropriate standards. The – Protection of distribution transfor-
user is enabled to select ALSTOM mers according to IEC 60787,
HVHBC fuse links or – on his own VDE 0670, part 402, transformer Temperature-rise limit
responsibility – fuse links of other connection group Dy5
types and from other manufacturers – Fuse links according to The fusing table takes account of
based on the specified data. IEC 60282-1, VDE 0670, part 4, the temperature rise limits in the en-
model I, or DIN 43625 closure of the switchgear.
– Specificiations in IEC 60420,
Switchgear types / HVHBC fuse VDE 0670, part 303
links – Max. ambient temperature for
switchgear 40°C according to
For utilization in the FBA, FBE, FBT IEC 60694, VDE 0670, part
gas-insulated ring main units, for the 1000, identical to max. ambient
protection of distribution transfor- temperature for the switchgear
mers, we recommend ALSTOM within the housing of a packaged
HVHBC back-up fuse links with inte- substation according to IEC
grated thermal cut-outs according to 61330, VDE 0670, part 611
the fusing table on page 23. – No transformer operation under
In case of overload of the HVHBC overload conditions
fuses, the thermal cut-outs cause the – The LVHBC fuse links gTr accord-
load disconnectors to switch off the ing to VDE 0630, part 22, are
unit in case of selective vis-à-vis the HVHBC fuse
– overload currents, links
– fuse links which had been da- – The LVHBC fuse links can handle
maged previously due to tran- 1.3 times the rated transformer
sients. current for min. 10 hours
This avoids thermal overload of the In the case of 1.5 times the rated
switchgear. transformer current, the unit is
switched off within two hours.

Ordering data

The following ordering data must be


specified in the order:
– Transformer rated capacity
– Transformer service voltage
– Rated current of the selected
HVHBC fuses

22
HVHBC fuse links

Fusing table
ALSTOM Sachsenwerk GmbH

Service Rated voltage Dimension D (”e”) Type of Transformer rated capacity in kVA Remarks
voltage of range of of HVHBC switchgear
transformer HVHBC fuse link
fuse link

250 315 400 500 630 800 1000 –


uk = 4 % uk = 5 % –
Max. admissible short-circuit duration = 2 s

kV kV mm Rated current in A of the HVHBC fuse links

6 6/12 292 FBA, 12 kV 50 63 80 100 125 160 1) 1)

FBT, 12 kV

10 6/12 292 FBA, 12 kV 31.5 40 50 63 80 100 125 1)

FBT, 12 kV

15 10/24 442 FBA, 24 kV 25 31.5 31.5 40 50 63 1) 1)

FBT, 24 kV

20 10/24 442 FBA, 24 kV 16 25 25 31.5 40 63 63 1)

FBT, 24 kV

30 20/36 537 FBE, 36 kV


FBT, 36 kV 16 20 25 25 31.5 40 40 2)

HVHBC Rated capacity in kVA


fuse link (of the transformer to be protected)

0.4 0.4/0.5 kV NH-gTr kVA 250 315 400 500 630 800 1000 –
(A) (361) (455) (577) (722) (909) (1155) (1443) –

Rated short-circuit voltage uk and maximum admissible short-circuit duration according to VDE 0532, part 5/05.84 (= IEC 6076-5:1976)
This selection table must be used in case of ambient temperatures ≤ +50°C without overload.

(...) = Rated current in A


1)
In the case of relatively high transformer rated voltages, project engineering is to follow section 2.
2)
In the case of a transformer rated capacity of 1250 kVA at 30 kV, a fuse rated current of 50 A is possible.
In the case of a transformer rated capacity of 1600 kVA at 30 kV, a fuse rated current of 63 A is possible.
Circuit-breakers must be used on the low-voltage end.
The selectivity between the high voltage and the low voltage end must be checked by the user.

23
2. HVHBC fuse links, Dimensions for fuse links Back-up fuses
selection data
Switchgear for the following dimen- When using back-up fuses without
„ – unless selection is based on sec- sions "D" or "e" of the fuse links: integrated, temperature-limiting stri-
tion 1” ker tripping, the following standard
Type designation Fuse gauge „D” or „e” requirements must be satisfied:
in mm – at overload currents, the unit is
Fuse links FBA./12-2/... 292 switched off by the LVHBC fuse
FBA./17-2/... 442 links, as specified on page 22;
FBA./24-2/... 442
Fuse links must correspond to: – in case of switchgear in exposed
FBE./36-2/... 537
– VDE 0670, part 4, or IEC-60 FBT./12-2/... 292
locations, in which fuse links may
publication 282-1 with dimensions FBT./17-2/... 442 have suffered previous damage
according to the data sheet I FBT./24-2/... 442 due to transients (e.g. lighting
(model I) or DIN 43 625. FBT./36-2/... 537 impulse currents), all fuse links
– Striker type "medium" with initial must be replaced at regular ser-
tripping force of max. 80 N. Refer also to the operating instruc- vicing intervals.
tions, chapter "Replacement of
fuses" (replacing short fuse links in If these requirements are not satis-
the case of switchgear with fuse fied, only HVHBC back-up fuse links
gauge "D" or "e" = 442 mm) with integrated, thermal cut-out-type
striker tripping may be used in the
gas-insulated switchgear FBA, FBE
and FBT to protect them against
38 max. thermal overload.
e
The following series of the suppliers
ø 20 max.

of HVHBC fuse links with integra-


ø 45±1

ted, thermal cut-out-type striker tripp-


ing are admitted:

Striker
ø 88 max.

Series Supplier
ø 88 max.
ø 50 min.

HVHBC fuse links with ALSTOM Sachsen-


33+2 33+2 thermal cut-out werk GmbH
HVHBC fuse links with SIBA
thermal cut-out
Dimensions in mm HVHBC back-up fuses EFEN
with overload release
(thermal protection)
HVHBC fuse links, JEAN MÜLLER
type IKUS, with thermo-striker
HVHBC fuse links, type H220 Driescher-
or 221 Sta. with thermal Moosburg
protection ”FGS”

24
HVHBC fuse links

Selection data

General-purpose fuses

General-purpose fuses are recom-


mended in the exceptional cases
when load disconnectors are to be
designed with snap-action drive
SFU (instead of stored-energy me-
chanism SF), meaning that no all-
pole fuse tripping is possible.

For detailed information on selec-


tion of the fuse links, refer to the
brochure:
Selection of HVHBC fuse links for
distribution transformers
no. 531 400

25
Metering panel,
FBM 24 kV 1)

FBA -/24 - 2 / 3001 FBM - /24 - 2/.... FBA -/24 - 2 / 3000 FBM - /24 - 2/....

Consumer part EVU Consumer part EVU

Combination examples

900 700

1315
480
M12
85

260 260
Straight
cable connector
(downwards) Due to the minimum cable bending radius,
it may be necessary to use a trailing cable

22
856
ø15

Flooring duct
580
700

for cable entry and


615

pressure relief
400
75
60

820 40

900

Possible configuration of switchgear


1)
Metering panel, FBM 12 kV available on request

26
Selection tables for cable The standard switchgear model is Other variants are available from
fittings equipped with outer cone-type the manufacturer on request.
appliance couplers:
• Mains cable outgoing feeder for The selection table on page 28 and
Cable connection FBA up to 24 KV: 29 contains a number of common
FBE 36 kV: connection systems.
The cable connection compartment FBT up to 36 kV:
is so designed that it enables Appliance coupler The use of Tee plugs is recommen-
connection of DIN EN 50181 for 630 A ded for connection of the ring
– fully insulated female-thread screw-type contact mains, and the use of straight or
– metal-enclosed M16 right-angle connectors is recommen-
or • Outgoing transformer feeder for ded for the connection of transfor-
– partially insulated FBA/FBT up to 24 kV: mer cables.
connection systems or ground ca- Appliance coupler
bles. DIN EN 50181 for 250 A
(plug-in contact 7.9 + 0.02/0.05 mm)
• Outgoing transformer feeder for
FBA/FBT 36 kV:
Appliance coupler
DIN EN 50181 for 400 A
(plug-in contact 14 + 0/– 0.04 mm)

max. max.
445 mm 445 mm

Earth Connec-
connection, tor shell
Cu cable
shield

Mains cable connection* Double connection* Surge arrester with separate


earthing bar *

* for FBE/36 kV available on request

Position of
cable iron
with straight
connector

Outgoing transformer feeder with


right-angle connector (cable iron
replaceable)

27
Selection table I: Outgoing transformer feeder (Subject to modifications. Updated 03/96)

Examples of cable fittings (right-angle or straight connectors) for outgoing transformer cable, plug-in contact

Cable type Connector Manufacturer Rated 12 kV 24 kV 36 kV


type current Connector for cross- Connector for cross- Connector for cross-
type section type section type section
A mm2 mm2 mm2
Plastic Right-angle KABEL 250 AGW 10/250 25...95 AGW 20/250 35...95
cable, connector RHEYDT AGWL 20/250 35...95
fully insulated EURO- 250 158 LR 16...120 K158 LR 16...120
system MOLD 400 M 400 LR 35...185
F&G 250 ASW 10/250 25...120 ASW 20/250 25...120
ABB Kabel 250 SEHDW 11.1 25...70 SEHDW 21.1 25...70
& Draht 400 SEHDT 32 70...500
RAYCHEM 250 RSES..R 25...120 RSES..R 16...120
PIRELLI 250 FMCE-250 16...120 FMCE-250 25...120
400 FMCE-400 25...240
Straight KABEL- 250 AGG 10/250 25...95 ASG 20/250 35...95
connector RHEYDT AGGL 20/250 35...95
EURO- 250 151 SR 16...120 K 151 SR 25...120
MOLD 152 SR 16...120 K 152 SR 25...120
ABB Kabel 250 SEHDG 11.1 25...70 SEHDG 21.1 25...70
& Draht
PIRELLI 250 FMCS-250 16...120 FMCS-250 25...120
400 FMCS-400 25...300
RAYCHEM 250 RSSS...R 25...120 RSSS...R 16...120

28
Selection table II: Cable branch line (Subject to modifications. Updated 03/96)

Examples of cable fittings (Tee plugs) for mains cables, screw-type contact

Cable type Manufacturer Rated 12 kV 24 kV 36 kV


current Connector for cross- Connector for cross- Connector for cross-
type section type section type section
A mm2 mm2 mm2
Plastic Fully KABEL 400 AGT 10/400 25...240 AGT 20/400 35...240
cable insulated RHEYDT AGTL 20/400 35...240
system EURO- 400 400 TBS 70...300 K 400 TBS 35...300 M 400 TBS 35...185
MOLD
F&G 400 AST 10/400 25...240 AST 20/400 25...240
630 ASTS 10/630 25...240 ASTS 20/630 25...240
AST 10/630 240...500 AST 20/630 240...500 AST 30/630 240...500
ABB Kabel 630 SEHDT 13.1 70...240 SEHDT 23.1 25...240
& Draht SEHDT 13 50...500 SEHDT 23 25...500 SEHDT 33 70...500
PIRELLI 630 FMCTs-400 95...300 FMCTs-400 35...300 FMCTs-400 25...300
RAYCHEM 630 RSTI... 25...300 RSTI... 25...300
Partially F&G 630 AWK 10/6301) 25...240
insulated AWKS 10/6301) 25...240 AWKS 20/6301) 25...240
system RAYCHEM 400/ RICS...with 25...300 RICS...with 25...300
630 cable box cable box
IXSU-F...for single- IXSU-F...for single-
conductor cables conductor cables
RICS...with 25...300 RICS...with 25...300
cable box cable box
IXSU-F...for three- IXSU-F...for three-
conductor cables conductor cables
Ground Partially KABEL- 400 ESEK 20 W 25...300Cu ESEK 20 W 25...300Cu
cable insulated RHEYDT single-conductor and 25...240Al single-conductor and 25...240Al
system three-conductor cables three-conductor cables
F&G 400 AWM 10/4001) 50...240 AWM 20/4001) 25...150
with cable box with cable box
SKV 10 GKV 20
ABB Kabel 400 MEHW 22 single- 25...150
& Draht conductor and three-core
separately sheathed cables
RAYCHEM 400/ RICS...with 16...300
630 cable box
UHGK...for
quality cables
RICS...with 50...300 RICS...with 35...240
cable box cable box
IDST...for paper in- IDST...for paper in-
sulated single con- sulated single con-
ductor and three-core ductor and three-core
separately sheathed cables separately sheathed cables

1)
Right-angle connector

29
Constructional data

Pressure relief
(in case of an internal fault)

1. Pressure relief into pressure relief The rear panel and the gas cooler
compartment and via rear side of are necessary if the conditions ac-
switchgear (the data and illustra- cording to criteria 1 to 6 are met.
tions are also applicable for stations Criteria 1 to 6 refer to the opera-
with control aisle). tor's side.

with wall
! ventilation louvres in the
front door essential!

with/
with with half-level
wall wall wall/
without
pressure wall
pressure relief
relief pressure
relief

gas cooler*
gas cooler* gas cooler*
connection
duct
(to be pro-
vided by
customer)
pressure-proof pressure-proof pressure-proof
for ≥ 0.2 bar for ≥ 0.2 bar for ≥ 0.2 bar

V ≥ 0.8m3 at 20 kA V ≥ 0.8m3 at 20 kA V ≥ 0.8m3 at 20 kA


V ≥ 0.6m3 at 16 kA V ≥ 0.6m3 at 16 kA V ≥ 0.6m3 at 16 kA
*with 5 expanded metal layers *with 5 expanded metal layers *with 5 expanded metal layers
e.g. 6 x 3.4 x 1 x 0.5 e.g. 6 x 3.4 x 1 x 0.5 e.g. 6 x 3.4 x 1 x 0.5
and seal between switchgear
and wall of building

Installation example with wall Installation example without wall Installation example with clearance
clearance (with connection duct) clearance (cable branch line) to wall and ceiling ≥ 150 mm
(cable branch line)
(Pressure relief completely or
partially into the switchgear room)

30
2. Pressure relief into pressure relief (the data and illustrations are also Points of attachment of
compartment / false floor only applicable for stations with control gas coolers to rear wall of
aisle) switchgear

! only admissible for rated short-


time currents of 16 kA/1s

with/ with
half-level/ wall Threaded pin
without min. M6 x15( optional)
wall switchgear

35
height
pressure
relief pressure
relief
closed rear
panel Cable
without
rear panel

B
Trans-
former*

40
gas cooler* gas cooler*
g a

17.5
h b
pressure-proof pressure-proof i c
for ≥ 0.2 bar for ≥ 0.2 bar
k d
V ≥ 0.8m3 at 20 kA ll e
V≥ 0.8m3 at 20 kA
V ≥ 0.6m3 at 16 kA m f
V ≥ 0.6m3 at 16 kA
*Cross section of duct A C
≥ 0.3 m2 at 20 kA *Cross section of duct
≥ 0.2 m2 at 16 kA ≥ 0.3 m2 bei 16 kA *Mounting to rear panel necessary in case
with 5 expanded metal layers. with 5 expanded metal layers. of straight connectors in outgoing trans-
e.g.: 6 x 3.4 x 0.5 e.g.: 6 x 3.4 x 0.5 former feeder

Installation example with wall Installation example without wall Rear side of switchgear
clearance (cable branch line) clearance (cable branch line) (for dimensions, refer to table)

Dimension table for gas cooler attachment

Model Dim. A Dim. B for switchgear height of Dim. C Dim. a Dim. b Dim. c Dim. d Dim. e Dim. f Dim. g1) Dim. h1) Dim. i1) Dim. k1) Dim. l1) Dim. m1)
1315 1045 1700 1400
FBA 2011 316 319 314 81 221 – – – – 51 251 – – – –
FBA 3000 – 319 950 81 471 861 – – – 51 251 – – – –
FBA 3001 316 319 634 81 541 – – – – 51 251 – – – –
FBA 3002 636 – 314 81 221 – – – – 51 571 – – – –
FBA 4000 – 319 1270 81 541 721 1181 – – – – – – – –
FBA 4001 316 319 954 81 471 861 – – 51 251 – – – –
FBA 4002 636 589 319 – – 634 81 541 – – – – 51 571 – – – –
FBA 4003 956 – 314 81 221 – – – – 51 438 891 – – –
FBA 5000 – 319 1590 81 438 795 1152 1509 – – – – – – –
FBA 5001 316 319 1274 81 447 813 1179 – – 51 251 – – – –
FBA 5002 636 319 954 81 471 861 – – – 51 571 – – – –
FBA 5003 956 319 634 81 541 – – – – 51 438 891 – – –
FBA 5004 1276 – 314 81 221 – – – – 51 438 795 1152 – –

FBE 2011 467 537 462 96 370 – – – – 96 370 – – – –


FBE 3000 – – 1400 96 337.6 579.2 820.8 1062.4 1304 – – – – – –
FBE 3001 467 537 932 96 344 593 841 – – 96 370 – – – –
FBE 4000 – – 1870 96 336 576 816 1056 1296 94 334 – – – –
FBE 4001 467 – – 837 537 1402 96 339 582 825 1068 1311 96 370 – – – –
FBE 4002 937 – 932 96 344 593 841 – – 96 344 592 840 – –
FBE 5000 – – 2340 96 334.6 573.2 811.8 1050.4 1289 96.6 335.2 573.8 812.4 – –
FBE 5001 467 – 1872 96 344 593 841 1035 1289 96 370 – – – –
FBE 5002 937 – 1402 96 339 582 825 1068 1311 96 344 592 840 – –
FBE 5003 1407 – 932 96 314 593 841 – – 96 338.8 581.6 824.4 1068.2 1310
1)
Dimensions not valid for switchgear height of 1045 (fastening not possible)

31
Fastening and flooring ducts

for right-angle connectors for right-angle connectors


in the outgoing transformer feeder in the outgoing transformer feeder

22
F back
optional

G
G

in case of max. cross-

H
400
beam width of 80
75
60

60
required
E screw coupling: D
35 min. M10 35
ø15

Required wall cutout in case of


right-angle connectors

Model U Dim. D Dim. E Dim. F Dim. G Dim. H


kV
12
FBT 2011 to 620 300 646 590 615
24
12
FBA 3000 to 940 940 966 590 615
24
12
FBA 3001 to 940 620 966 590 615
24
12
FBA 3002 to 940 320 966 590 615
24
12
FBA 4000 to 1260 1260 1286 590 615
24
Rear panel
12
attachment FBA 4001 to 1260 940 1286 590 615
24
L3 L2 L1
n

12
FBA 4002 to 1260 620 1286 590 615
24
12
FBA 4003 to 1260 320 1286 590 615
24
q FBA 5000
12
1580 1580 1606 590 615
p to
24
12
Back of switchgear FBA 5001 to 1580 1260 1606 590 615
24
Required wall cutout in case of 12
FBA 5002 to 1580 940 1606 590 615
right-angle 24
12
FBA 5003 to 1580 620 1606 590 615
– FBA/T FBE/T 24
U (kV) 12/17.5/24 36 12
FBA 5004 to 1580 320 1606 590 615
Dim. n 120 170 24
Dim. p 30 75
FBT 2011 36 920 520 946 745 745
Dim. q 310 370
FBE 3000 36 1390 1390 1416 745 770
FBE 3001 36 1390 955 1416 745 770
FBE 4000 36 1860 1860 1886 745 770
FBE 4001 36 1860 1425 1886 745 770
FBE 4002 36 1860 955 1886 745 770
FBE 5000 36 2330 2330 2365 745 770
FBE 5001 36 2330 1895 2356 745 770
FBE 5002 36 2330 1425 2356 745 770
FBE 5003 36 2330 955 2356 745 770

Dimensions in mm

32
Shipping information

Transport of switchgear Transport to the site of installation

When transporting the switchgear, The switchgear must be stored at


make sure that the transport unit the conditions admissible for opera-
does not slip or tip over (if neces- tion.
sary, nail transport pallet to loading Condensation must be avoided.
platform). Leave transport unit
packed as far as possible. Parts For transport, lateral parallel dis-
which have been unpacked for in- placement of the switchgear must
spection must be re-packed for fur- be ruled out (if necessary, by using
ther storage. Use the original stabilisers).
packaging material. Transport of switchgear with pallet
For transport to the site of installa-
tion, it is important to remember
Packing the switchgear unit that the main weight is in the top
area of the switchgear. The centre
> 45°
• In the case of truck-worthy of gravity is marked with a label on
packing, the switchgear is de- the side face of the switchgear.
livered on a pallet with PE pro-
tective film. Two plastic belts Transport using a forklift truck:
serve to fasten the switchgear. The switchgear may only be trans-
• In the case of sea-worthy export, ported on pallets.
the switchgear is packed in
sealed aluminium film with de- Transport without pallet: Transport of switchgear without pallet
siccant and a closed crate with Attach crane suspension gear into
sealed wooden bottom. transport eyelet of switchgear.
• In the case of air freight, the Angle of crane suspension gear:
switchgear is packed in a > 45°.
wooden crate with closed
wooden bottom and with bubble--
pack-type plastic packaging film
as dust protection, or in a
wooden crate, also with closed
wooden bottom.

33
Fax query to submit an offer

To Sender

ALSTOM Sachsenwerk GmbH Company:


Rathenaustraße 2 Address:
Dept. SW V6 Postal Code/City:
Contact:
D-93055 Regensburg Name/first name:
Department:
Our FB team: Phone:
Phone: +49 (0)9 41/46 20-186 V61 Mr. Hillinger Telefax:
-122 V61 Mr. Ettinger
-481 V61 Mr. Kiesewetter
-371 V61 Mr. Cavus
-275 V61 Ms. Schmidt
-530 V61 Ms. Kopf
Telefax: +49 (0)9 41/46 20-227

Please submit to us your offer regarding the items ticked off herebelow:
Please call us back for clarification of details
Number of following pages

FBA/E/T . / . . –2 / . . . .

Rated current . . . A

Rated short-time current . . kA

Attachments:

Auxiliary switch on switch-disconnector, 4-pole

Auxiliary switch on switch-disconnector, 6-pole

Auxiliary switch on earthing switch, 2-pole

PEHLA 1-6 / 1 sec.

Short-circuit indicator

Motor drive on switch-disconnector

34
Telephone +49 (0)9 41/46 20-0 · Telefax +49 (0)9 41/46 20-4 18
ALSTOM Sachsenwerk GmbH · Rathenaustraße 2 · D-93055 Regensburg · P.O.B. 10 01 55 · D-93001 Regensburg
SW.06.31 / 0201 EN Printed in the Federal Republic of Germany The technical details and product characteristics described correspond
to the state of the art at the time of printing and can be subject to change.

You might also like