8 Sheath Fault Location
8 Sheath Fault Location
8 Sheath Fault Location
Sheath testing,
Sheath fault location
and
Location of earth faults
Table of Contents
1. Introduction .............................................................................................................3
2. Why Sheath testing ................................................................................................3
2.1 Sheath test devices ..........................................................................................4
2.2 Norms and regulations for sheath testing .........................................................5
2.3 User definitions .................................................................................................5
2.4 Conducting the test...........................................................................................6
2.5 Safety ...............................................................................................................7
3. Sheath fault prelocation ..........................................................................................8
3.1 Prelocation with the comparison or voltage drop method .................................9
3.1.1 Bipolar Measurement of the voltage drop ................................................11
3.1.2 Advantages and disadvantages of the voltage drop method ...................11
3.2 Prelocation with a measuring bridge...............................................................12
3.2.1 Prelocation ...............................................................................................12
3.2.2 Prelocation with MVG 5 ...........................................................................12
3.2.3 Two wire measurement according to Murray ...........................................13
3.2.4 Three wire measurement according to Graaf ...........................................13
3.2.5 Advantages and disadvantages of bridge methods .................................14
4. Sheath fault pinpointing ........................................................................................15
4.1 The different methods.....................................................................................15
4.2 Voltage gradients............................................................................................15
4.3 The DC Method ..............................................................................................16
4.3.1 Pulsed DC and current limits....................................................................18
4.3.2 Power .......................................................................................................18
4.3.3 Specialties of the DC - Method ................................................................19
4.3.4 Influences ................................................................................................19
4.3.5 Advantages and disadvantages of the DC - Method ................................19
4.4 Surge Method .................................................................................................20
4.5 Localisation of earth contacting faults in LV plastic insulated MV systems..... 20
4.6 Audio frequency methods ...............................................................................21
4.7 Equipment combination FL 50 with Step voltage Probe DEB 3-10 .................22
4.8 Audio Frequency Method with 4,8 Hz and SFL2 A-Frame .............................22
4.9 Localisation of earth contacting faults in LV and illumination systems............24
5. Wording ................................................................................................................25
2010-07-13 2
1. Introduction
Since many years the main reason of faults in cables with plastic insulated outer
sheath is the damage of this sheath. This permits the penetration of water into
the cable and as a consequence it enhances the growth of „Water Trees“ and
other corrosion based damages in power cables. Water trees are one of the
primary reasons of cable faults.
In communication cables the ingress of water significantly reduces the
transmission quality which is in today’s high performance data transmission
requirements almost equal to a loss of the line.
In cables, which are not protected against longitudinal water migration there is
the additional danger of joint faults due to water spreading though the
conductors into the joints.
The following article describes the different test procedures for plastic insulated
and the prelocation and pinpointing of sheath faults.
A perfect, non disturbed operation of a cable system requires in addition to the stated
requirements for data transmission and energy transfer, good insulation values
between the conductors as well as between conductors and shield. Prerequisite for
this is also the intact outer sheath (Jacket), which is today mostly consisting of PE.
The damage statistics of cable faults published in the recent years, especially for
medium voltage cables, indicated a significant amount of sheath faults, which were
obviously the triggering cause for a breakdown of the cable.
Resulting the sheath testing permits in a certain context also a diagnostic information
about the condition, resp. the expectable state of the cable
Additionally the sheath test is one oft he most important tools in combination with all
diagnostic technologies, since a diagnostic evaluation of a cable requires that the
cable to be tested has to be in a good and faultless condition
A diagnose without a
combined sheath test is a
relatively unreliable
valuation of the cable
condition, since entering
water as a result of a
sheath fault and the
following damages result
in a fast decrease of the
condition quality.
2010-07-13 3
The test of the integrity of the outer sheath provides almost the ideal condition for the
early detection of damages and provides the possibility of an early elimination of
beginning cable faults.
With a simple insulation and voltage breakdown test between cable shield and outer
soil, it is already possible to conduct a commissioning
test directly after laying and to confirm the integrity Sheath
of the outer plastic sheath.
Semicon layer
With regular tests, especially in areas with high
construction activities, it is possible to detect
Shield
damages of the outer sheath at an early stage,
where an immediate repair will prevent further Insulation
damages, and where it is still possible to locate
the cause of the damage and to claim an Semicon layer
according compensation.
A sheath damage, if not associated with a direct Conductor
damage of the cable insulation, will seldom lead to
a fast breakdown and failure of the cable installation. Fig 2: Cable construction details
From the moment of damage until the appearance of
the real breakdown, many months or even years can pass
If the sheath is damaged by a manual impact or a by penetrating stone, the shield
beneath can be driven more or less through the semiconducting layer into the
insulation. In this location the homogenous field distribution is distorted and partial
discharge sources develop. This partial discharge will then, depending on its intensity,
destroy the insulation and lead to a breakdown
2010-07-13 4
2.2 Norms and regulations for sheath testing
The testing of cable sheaths is regulated in different norms, IEEE, IEC 60229, VDE 0276 part
620 and part 632, also their Harmonised document HD 60602 and 60632
The VDE specifies the following details:
Here it has to be observed, that an increased amount of joints, the ageing and other influences
will have a direct impact on the measured current. This means the values shown in [Fig 3.] are
to be considered for a new installation, with typically one joint per 500 m.
For aged installations, the condition must be considered in the evaluation of the current.
Requirement for a sheath test is a continuous insulation of the shield through the sheath
against the surrounding soil. Earth contacting joints and armatures are not permitted, since
these will conduct the test voltage to earth.
The insulation condition or the electric strength of a shield resp. sheath against earth is easily
determined and requires no extensive test instruments. Depending on the insulation material
of the cable, but also according to the above described factory rules, DC voltages from 3 to 5
kV (partially 10 kV and more) are connected between the metallic shield and operational earth
and the measured leakage current or the insulation resistance is evaluated
In many international applications, voltages up to 10 kV are already standard.
This value depends also on the construction of the cable sheath, where in some cases, for
example in HV Cables with a thick sheath, the common 5 kV are insufficient to bridge the thick
outer sheath of high voltage cables.
2010-07-13 5
2.4 Conducting the test
The test voltage is connected in such a way, that the negative potential is connected to the
shield, and the positive will be connected to earth. Even if polarisation effects are rather rare it
is recommended, to maintain this polarity to enable the reproducibility of the measurements.
An exception is the bipolar measurement of the new MFM 10.
The typical recommended test duration is 10 minutes. Are the measured current values above
the described values, and resulting, the insulation resistance values below the permitted limits,
the cable should be investigated more detailed or at lest tested in sorter, regular intervals to
check for changes.
After the connection oft he sheath test set, the test voltage is slowly (maximum 1 kV per
second) increased to the typical test end value of 3 resp. 5 kV.
During the increase, it is very important to observe the charging current of the shield. Sudden
changes or just one single fast increase of the current are a clear indication of a sheath fault
After reaching the nominal test voltage level, single flashovers during the 10 minutes test
duration are not always detected, since the observation of an analogue measuring instrument
requires a lot of concentration
Some of the flashovers happen only once, due to the fact that one single flashover will already
interrupt the fault or will dry it up, causing it to appear like an intact cable sheath. This will
happen especially in long cables where the charged cable capacity contains sufficient energy,
to dry up the fault during the flashover.
Here sheath test systems are preferable, which indicate a single flashover also in the case,
where the unit discharges the shield and switches off after the preset test duration.
For this purpose, the new MFM 10 will automatically record and indicate all these events in the
test protocol
2010-07-13 6
2.5 Safety
The discharge and grounding of the sheath test system and the connected shield should
receive special attention.
The shield capacity, fully charged, contains a dangerous energy and can provide a high
personal hazard.
A shield capacity of app. 1200 pF / m results for a cable lengths of 1000 m in a complete
shield capacity of 1.2 µF. This is a charge of 15 Joules, an energy amount that has to be
considered as highly dangerous when touched.
C
[1] P =U 2 J or Ws
2
On the other side, this charge is too small to cause further damages at the fault position.
Also for operation within these specific applications, there is the same potential danger and
resulting the same safety rules as for any operation will apply.
For the sheath testing, prelocation or pinpointing of sheath faults it is required to disconnect
the cable shield on all ends of the cable. Since a cable shield may carry a dangerous voltage
potential, it is important to perform the connection (As well as the disconnection) only on a
discharged and grounded shield.
The sheath tester must be only powered up, after all connections have been performed!
Like for any other operation in high voltage environment the 5 safety rules apply!
1. Disconnect power
2010-07-13 7
3. Sheath fault prelocation
To avoid a long time duration for the pinpoint location procedure, especially on longer cables
and solid surfaces, it is always recommended to do a prelocation. Without prelocation the time
for the location can consume quite some time, thus also extending the thermal load by on the
fault which includes the risk of drying it op, before it has been located.
For the prelocation of sheath faults on cables, high voltage measuring bridges of different type
in varying connections can be used. But these measuring bridges and their methods require
voltage proof technologies, because the measurement can go up to 10 kV.
Usual bridges operate with voltages up to a maximum of some 100 Volts, a voltage level,
which is for the location of sheath faults only seldom sufficient. Another method is the
comparison of the ratio measurement, which evaluates the current, voltage and resistance
before and after the fault position and converts this ratio to the cable length
For this method, the voltage drop of both cable parts and its according partial test current is
measured.
Due to the very high resistive Measurement, the measuring current can be comparatively low,
which makes the complete measurement almost independent from resistances in the
measuring path. Due to this low current, the risk of changing the fault or drying it up is
negligible.
The following described Voltage-Drop-Method in a specific circuit version proved its
performance in many thousands of measurements during the past years.
This method does not require any complex measuring instruments or technologies and
characterises itself by a most simple calculation process. A modern version determines the
fault distance already automatically as soon as the cable length is entered.
UN UF
IN IF
RN RF
LN LF
2010-07-13 8
3.1 Prelocation with the comparison or voltage drop method
According to Figure 5, a constant current source G is connected between shield and ground.
For this procedure, the shield at both ends of the cable to be tested must be disconnected!
The current flow is though the fault resistance Rfault via the surrounding soil back to the
generator ground.
The current flowing in the route part LN (Cable begin to Fault position) results in a voltage UN in
the size of some millivolts on the shield resistance.
For “test leads” it is possible to use the core of the “faulty” cable and/or core and shield of a
second cable of the same system.
L N , UN , I N , R N LF , UF , I F , RF
White
G
! !
Green
Faulty Sheath
Black ! !
Rfault
Yellow
The voltage drops on the resistance of these” test leads” and the contact resistances of the
connection points are negligible, since the measurement system has a high resistive
measuring input, and do not need to be included into the calculation of the fault distance.
This one of the major advantages of the voltage drop method in comparison with bridge based
procedures.
In a second measurement, the constant current source is now connected though one of the
auxiliary lines through the shield at the far end and the fault resistance Rfault via the
surrounding soil back to the generator ground. The voltage UF is now measured at the shield
resistance of the route part LF. The two partial voltages have the same ratio as the two
distances LN to LF.
According to the following equation [ 2 ] the fault distance LN can be calculated as follows.
UN
[2]...LN = L
U N +U F
2010-07-13 9
The only requirement of the voltage drop method is a constant, identical current for both
measurements. Small deviations between the two test currents will reduce the accuracy
For this there are two solutions available.
The first is solved with the state of the art electronic supply, which provides an accuracy of the
regulated constant currents, much higher than required for the stated accuracy.
The second additional solution is the use of calculated resistance values instead of the voltage
drop only. By converting the voltage drop into resistance by simultaneous measuring of current
and voltage at the shield of the cable, the resistances of the partial sections can be calculated.
The equation for this process is as follows.
RN
[3]...LN =
R N + RF
A requirement for small measuring deviations are low resistive connection at the cable ends,
since contact resistances will add to the line resistances and may cause deviations in the
measuring results.
In case of several sheath faults at the same cable, error measurements are likely, but
field test have shown that a careful increase of the test voltage locates the fault with the lowest
breakdown voltage first. After the location of this fault the further increase of the voltage will
then allow a second sheath fault location. In this case the result will show the distance
between the two faults, which very often is an average of the complete cable length.
Therefore, special attention is required if the measured fault distance is similar to 50% of the
complete cable length.
White
G
! !
Green
Virtual Fault Spot
Black ! !
Rfault1 Rfault2
Yellow
2010-07-13 10
R1 1 R1
R1 = R2 10
R2 10 R2
A B C
Rfault1 Rfault2
10 100
R1 10 10
1 1
R2
0,1 0,1
0,0 0,01
A B C
Disadvantages:
- No direct detection of multiple faults
2010-07-13 11
3.2 Prelocation with a measuring bridge
3.2.1 Prelocation
In opposition to the voltage drop method, in bridge measurements the resistance value is used
for the evaluation.
For plain resistance measurements it is required to eliminate any external influence. Important
is a very good contact between measuring bridge and test object. The contacts points have to
be carefully cleaned and the contact itself should be done with screw clamps, and not with
clips.
The bridge technology requires a very homogenous line resistance, meaning that the
resistance per length unit has to be a constant parameter. For older cables, water ingress and
the resulting changes of the cross section due to corrosion of the cable shield may result in
resistance in-homogenities.
Similar problems appear, if the cable shields of several segments are jointed inside the joint by
a wire with a smaller cross section. Here it has to be as well expected, that the measuring
result is of lower accuracy.
In the case of cables with graphitized outer sheath, (semiconduction sheath) the fault
resistance is typically lower. The return current flow happens primarily via this layer, and not
through the soil.
The prelocation of sheath faults can also be done with a HV Fault location bridge. In this case
a good shield of the system is used for the bridge circuit. The according circuit setup is shown
in the following fig. 8.
In this case the supply for the high voltage can be delivered from any suitable external high
voltage supply.
Reference shield
MVG 5 !
!
Faulty shield
! !
MMG 5
0 - 5 kV DC
After the bridge adjustment, the distance is evaluated from the percentage according to the
equation [ 4 ].
M [%]
[4] l X = 2l g
100
2010-07-13 12
3.2.3 Two wire measurement according to Murray
For longer three phased, single core cables in the kilometre range, the two wire measurement
according to Murray can be used. Strict requirement is, that the specific resistance of the
“good” shield is equal to the on of the fault shield. And the good shield must undamaged
without any sheath faults, which due to practical experience rather seldom.
M [%]
L =L
x 100%
If no good shield is available or if the prelocation is done on three cored cables, the three wire
measurement according to Graf has to be used. In this case the insulation resistance of the
good wire (Help Line) has to 1000 times higher than the faulty line resp. sheath.
1. Help Line
L
Ln Lf
M K 2 − M K1
LX = L
Mk1
Faulty Line / Shield M K 3 − M K1
Mk2
2. Help Line
Mk3
A difference of diameter or resistance parameters between good and faulty line is permitted.
In case of short cables, the test leads will influence the measurement
M K 2 − M K1
LX = L
M K 3 − M K1
If no zero adjustment is possible, the result can be corrected by switching the connections for
Measurement Mk2 or MK3.
Mk3 = 200 - Mk3´ (connection black lead – red lead - 2. help line switched)
2010-07-13 13
In this case the following equation is valid:
200 − M K 2 − M K 1
LX = L
200 − M K 3 − M K 1
Advantages are:
Disadvantages are:
2010-07-13 14
4. Sheath fault pinpointing
- DC Impulse-Method
- Surge Impulse Method
- Audio Frequency method with direct or capacitive coupling
- Audio Frequency method with modulated frequency 4.8 Hz
All methods are based on the evaluation of the voltage gradients within the fault position,
which can be measured with these different methods and their probes. The different methods
have specific advantages as well as disadvantages, which are not so much a question of
quality and accuracy, but more related to the fault area situation, as underground and surface
condition, and the thermal stability of the fault itself and resulting the ability to manage these
influences
Continuing to move further towards the fault will increase the signal.
70% of the signal are measured at
the last third of the distance.
The measured signal strength Fig: Voltage gradients between connection and fault
is proportional to the amount of
voltage gradients between the earth
spikes. The maximum signal is
displayed, when the spike is directly
on to of the fault.
Fig 11: Voltage gradients between the two earth contacts
2010-07-13 15
4.3 The DC Method
The DC source in this case is like for the sheath fault prelocation, a small DC burner down unit
with adjustable current limitation. The maximum output voltage range can be set to1, 2, 5 or 10
kV, depending on the required or allowed test parameters.
The fault location is done as follows
The sheath test device is connected to the screen of the faulty cable and to the operational
earth / ground.
For a higher sensitivity, the distance between the two earth rods can be multiples of 10 m at
the start of the location. Close to the fault the step voltage increases to a maximum with a
defined polarity. Here the distance can be reduced to some decimetres or centimetres. If both
earth rods are inserted in the same distance to the fault, the different polarities of the voltages
compensate each other, resulting in a zero Volte display, indicating, that the fault is exactly in
the centre between the two rods. Then the procedure is repeated in a 90°angle to the cable
route, and by the same procedure a second zero point is measured. The crossing point of
these two measurements is directly on top of the fault. The accuracy of this method is in the
centimetre range, and no other technology can reach this accuracy.
2010-07-13 16
0 0 0
ESG 80
V + - V + - V +
! !
RFault
Fault resistance
At the earth contact
There is not always the possibility to measure directly on top of the cable route, since the road
surface is often insulating, and the earth rods cannot provide a solid earth contact.
(The drilling of holes to make contact is not always permitted and will increase the time for the
locating process).
In this case it is also possible to shift the whole measurement sideways to the unpaved area of
the road, due to the fact, that the significant voltage gradients have range some ten metres.
At the side of the road, there is always chance to use the free accessible soil, gaps between
stones or between plates to determine the centre of the voltage gradients. The longitudinal
coordinate can then be determined by normal tracing with audio frequency locators.
+
0
0
-
V
+
-
V
+
- V +
RF
+
0
2010-07-13 17
4.3.1 Pulsed DC and current limits
When using the DC Method, a periodical interrupt of the current flow has a very positive
effect on the location procedure. External influences of currents in the underground, e.g.
resulting from railway, tram, cathodic protection systems or similar sources will influence the
operation with a straight DC. With a pulsed Signal however, the pointer of the earth fault
probe will show only the capacitive decoupled change of the pulsed signal as a short but
clear directional deflection.
Instead of a zero point, the real fault position will be shown by a change of the polarity. The
pointer can be at any value of the display scale.
The pulsing or duty cycle of the signal, is typically 3 seconds on and 1 second off.
The duty cycle can also be used for receivers without capacitive decoupling, to compensate
for the stray currents and for possible electrolytic effects, which may build up at the probe tips.
For the pinpointing of sheath faults the rule “less is more” applies as well. Large currents will
logically produce larger, better detectable voltage gradients, but the current for the location of
sheath faults performs better between 10 and 100 milliamps. The sheath tester should also
provide the possibility of an automatic current limitation. Both of these limitations have the
purpose to avoid a drying up of the sheath fault due to thermal effects, and will protect other
cable system in the vicinity of the fault. Lower currents will also limit the damage of the sheath
fault which will then allow an easier repair since the inner conductors remain undamaged.
A current limited location procedure has the advantage, that the full power of the sheath tester
is only applied during a short moment, during the change of the fault from high to a low
resistance.
4.3.2 Power
The actual sheath fault location happens only with a low power of some 10 watts. Exact
Details can be taken from the table below. A further reduction of the thermal stress is caused
by the pulsing, which also reduces the duration and following the thermal stress effect of the
current flow through the fault.
2010-07-13 18
4.3.3 Specialties of the DC - Method
For multiple sheath faults, each conductive fault will generate its own voltage gradients.
This will result in so called phantom faults, which cause false measurements
The following Fig. 16 shows such a situation. The correct observation of the polarity changes
during the pinpointing procedure will easily reveal phantom faults by wrong polarity indications
and behaviour.
Phantom fault
+ +
- -
! !
RF
4.3.4 Influences
DC currents in the underground, e.g. resulting from railway, tram, cathodic protection
systems or similar sources will influence the operation with a straight DC. By a capacitor in
series with the input, the DC influence will be blocked, the input signal is differentiated and
the display shows the correct information. An important point is, that always the according
first deflection only indicates the correct direction towards the fault.
Disadvantages are:
Low sensitivity
Low sensitivity in case of multiple faults and in some case no breakdown
Difficult location on solid surfaces
2010-07-13 19
4.4 Surge Method
The application of this method is identical to the DC Method, but is based on the discharge of
a surge generator. The output of a surge generator delivers a signal, which is virtually identical
to a pulsed DC.
Warning!
When using this method, highest caution is required. When using the surge method the
current can reach much higher values even with small pulse widths than for the DC method. A
step voltage of 60 V must not be exceeded. The surge energy should be limited to a maximum
of 100 J.
Disadvantages are:
Error measurements by capacitive coupling
Changes to the fault spot by high energy (drying)
High safety requirements
0 0 0
ESG
V + - V + - V +
! RF !
R Soil
2010-07-13 20
4.6 Audio frequency methods
Instead of a DC generator, a powerful audio frequency transmitter is connected between the
faulty cable shield and earth. Audio frequency units are typically used for cable location,
tracing and for the location of low resistive faults and are therefore in most situations available.
The use of the audio frequency method instead of the DC method has some advantages
despite the limited distance.
Audio Frequency can be selectively amplified by the receiver, which permits a very efficient
suppression or filtering of many types of distortions, for example as a result of electrolytic
voltage sources or from stray currents. Additionally the Audio frequency technology allows the
use of a capacitive voltage measurement. The capacitive voltage measurement provides the
possibility to locate sheath faults in case of solid, poor conducting or insulating surfaces which
prevent the use of a conventional step voltage measurement with earth rods, which have to be
inserted into the ground.
Due to the high capacity of the shield towards earth, the supplying audio frequency generator
has a capacitive load. This may result in a low output voltage in the case of an automatic
impedance matching. In this case it is likely that flash over faults may not ignite and the fault
remains undetectable. The capacitive resistance of the shield and the resulting output voltage
of the generator can be calculated by the following equation.
1
[5] RC =
ωC
[ 6 ] U = PRC
The following table shows the output voltages in respect to different generator power ratings
and frequencies.
2010-07-13 21
4.7 Equipment combination FL 50 with Step voltage Probe DEB 3-10
! !
RFault
RSoil
Fig. 19: Audio Frequency – Step voltage
To increase the sensitivity, the capacitive plates can be exchanged by earth spikes. In this
case, the sensitivity of the receiver has to be adapted.
Capacitive plates allow fault location over all ground surfaces. Spikes require good ground
contact so are best on soft ground, and not hard surfaces unless the condition is improved by
wetting the spike contact areas.
Fig. 20: Audio Frequency with earth spikes (vLoc Pro with A-frame)
2010-07-13 22
Beyond the fault the direction blinking arrow is reversed and active numbers and bargraph
signal strength decreases.
The exact point of the fault is determined by blinking arrows changing direction and minimum
active value, as the voltage between spikes is minimum. The fault is directly under the centre
of the A frame.
Very close to the fault the active number will be almost the same as the reference value. If it is
substantially less, then more than one fault exists.
If this is the case, the best approach is to dig up and clear the fault and resurvey using shorter
interval between measurements.
Fig. 21: Audio Frequency – Step Voltage with frequency modulation using SFL
The Metrotech SFL and i5000 transmitters are ideal for high resistance faults where a higher
current is needed to pass current to ground. Low resistance sheath faults are better located
with the Vloc Pro system.
Bargraph: The arrow indicates the direction toward the fault and the bargraph shows the
signal strength.
Active: Shows the numerical value of the potential difference along the cable route.
(Maximum on top of the largest fault)
Reference: Shows the maximum potential difference that was measured during
synchronisation.
Like for the DC Method, the principle is the same. The display indicates the direction towards
the sheath fault, by measuring the voltage gradients. Also the crossing measurement to
determine the exact location is done the same way.
2010-07-13 23
Fig. 21: Audio Frequency with earth spikes (vLoc Pro with A-frame)
The fault location technique using the Vloc system is similar to SFL system above. The
transmitter is connected across the isolated cable and a grounding point. The transmitter
signal transmits a 4.8Hz low frequency AC and 8 kHz location signal. The Vloc A frame has no
display, so is connected by a cable to the Vloc pro locator, and automatically sets the locator
display to the faultfinding display.
The contact spikes of the A frame are provided with green and red markings, and green and
red arrows on the locator display indicate direction to fault and signal strength dB numbers.
The locator also provides left/right arrows to indicate the cable route.
The fault pinpointing procedure is similar to SFL2 A frame operation.
Final comments
The regular and early testing, detection and location of sheath faults will reduce the amount of
faults, especially in medium voltage cables with extruded outer insulation.
Cable faults can also be located indirectly, since external damages of a cable will often lead
consequentially to real cable faults.
2010-07-13 24
5. Wording
Due to the fact, that especially the area of sheath fault location deals with a huge amount of
different terms, also partially based on local use, we would like to list these words to avoid
confusion among the readers
PILC, Paper Insulated Lead Cable The outer lead sheath will prevent the typical
Sheath fault location due to its continous earth contact.
XLPE, Crosslinked polyethylene Insulation material, also used for the sheath
PVC, Poly vinyl chloride Insulation material, also used for the sheath
Sheath, Jacket, Sleeve Outer cable insulation
Shield, Screen Outer conductor
can be of copper, aluminium, lead
Sometimes made of steel as armour
Semicon Semiconducting filling material between conductors
Insulation, Dielectric The insulating material that insulates the different
conductors from each other
URD Underground Residential Distribution
Secondaries LV Distribution
Primaries MV Distribution
2010-07-13 25