LR3D086
TeSys LRD thermal overload relays - 2.5...4 A - class 10A

Download your LR3D086 datasheet

Characteristics | Documents & Downloads

Main Hide

Range TeSys
Product name TeSys LRD
Product or component type Non differential thermal overload relay
Device short name LR3D
Relay application Motor protection
Product compatibility LC1D09...LC1D38
Network type AC
DC
Overload tripping class Class 10A conforming to IEC 60947-4-1
Thermal protection 2.5...4 A
adjustment range
[Ui] rated insulation voltage 600 V power circuit conforming to CSA
600 V power circuit conforming to UL
690 V power circuit conforming to IEC 60947-4-1

Complementary Hide

Network frequency 0...400 Hz


Mounting support Under contactor
Tripping threshold 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
[Ith] conventional free air 5 A for signalling circuit
thermal current
Permissible current 3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational 690 V AC 0...400 Hz
voltage
[Uimp] rated impulse 6 kV
withstand voltage
Phase failure sensitivity Tripping current 130 % of Ir on two phase, the last one at 0
Control type Red push-button stop
Blue push-button for reset mode
Temperature compensation -20...60 °C
Connection pitch 14.5 mm
Connections - terminals Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² -
cable stiffness: flexible - without cable end
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² -
cable stiffness: flexible - with cable end
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² -
cable stiffness: solid - without cable end
Power circuit : lugs-ring terminals
Tightening torque Control circuit : 1.7 N.m - on screw clamp terminals
Power circuit : 2.3 N.m - on lugs-ring terminals screw : M4
Width 45 mm
Depth 70 mm
Product weight 0.124 kg
Environment Hide

Standards ATEX D 94/9/CE


EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 No 14
Product certifications ATEX INERIS
BV
CCC
CSA
DNV
GL
GOST
RINA
UL
LROS
Protective treatment TH conforming to IEC 60068
IP degree of protection IP20 conforming to IEC 60529
Ambient air temperature for -20...60 °C without derating conforming to IEC 60947-4-1
operation
Ambient air temperature for -60...70 °C
storage
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations 6 Gn IEC 60068-2-6
Shocks 15 Gn for 11 ms IEC 60068-2-7
Dielectric strength 6 kV at 50 Hz conforming to IEC 60255-5

Contractual Hide
warranty
Period 18 months