Data Sheet: Pro Eco 120W 24V 5A
Data Sheet: Pro Eco 120W 24V 5A
Data Sheet: Pro Eco 120W 24V 5A
Data sheet
PRO ECO 120W 24V 5A Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data www.weidmueller.com
Temperatures
Operating temperature Storage temperature -40 °C...+85 °C
Input
AC current consumption 1.2 A @ 230 V AC / 2.4 A AC input voltage range 85…264 V AC (Derating @
@ 115 V AC 100 V AC)
Connection system [Input] DC current consumption 0.4 A @ 370 V DC / 1.2 A
Screw connection @ 120 V DC
DC input voltage range 80…370 V DC (Derating @ Frequency range AC
120 V DC) 47...63 Hz
Input frequency 47...63 Hz Input fuse (internal) Yes
Inrush current Recommended back-up fuse 4 A / DI, safety fuse
6 A, Char. B, circuit breaker
3...5 A, Char. C, circuit
max. 40 A breaker
rated input voltage 100...240 V AC (wide-
range input)
output
Connection system [Output] Screw connection Output voltage 24 V
Output voltage 22...28 V DC (einstellbar Overload protection
über Potentiomenter in der
Front) Yes
Parallel connection option yes, max. 5 Powerboost @ 24 V DC, 60 °C 3.6 A for 1 min, ED = 5 %
Protection against inverse voltage Yes Ramp-up time ≤ 100 ms
Rated (nominal) output current @ UNom 5 A at 55 °C continous output current @ 24 V DC 5 A @ 55 °C
rated output voltage 24 V DC ± 1 % residual ripple, breaking spikes < 50 mVSS @ 24 V DC, IN
General data
AC failure bridging time @ INom > 100 ms @ 230 V AC / > Degree of efficiency
20 ms @ 115 V AC 88%
Earth leakage current, max. 1 mA Housing version Metal, corrosion resistant
MTBF > 500,000 h acc. to IEC Max. perm. air humidity (operational)
1709 (SN29500 5 %…95 % RH
Mounting position, installation notice Horizontal on TS35 Operating temperature
mounting rail, with 50 mm
of clearance at top and
bottom for air circulation.
Can be mounted side
by side with no space in
between.
Protection against over-heating Yes Short-circuit protection Yes
Weight 0.6 kg
Technical data www.weidmueller.com
Insulation coordination
Class of protection I, with PE connection Insulation voltage, inpututput 3 kV
Pollution severity 2
Signalling
Contact load (NO contact) max. 30 V DC / 0,5 A Floating contact Yes
Relay onff Output voltage > 21.6 V /
< 20.4 V
Classifications
eClass 6.2 27-04-90-04
Approvals
ROHS
Conform
Drawings www.weidmueller.com
Electric symbol