Operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
DANGER NOTE
Missing safety device and non-functioning safety device Transport of device
If there is no safety device, you could be seriously injured, for → Transport the device in its original packaging only.
example if you reach into the running device or your hands are → Secure the device so that it does not slip, e.g. by using a
sucked into it. clamping strap.
→ Operate the device only with a fixed and isolating safety
protection and a fixed guard grille. 1.10 Storage
The guard must withstand the kinetic energy of a fan blade ; Store the device, partially or fully assembled, in a dry and
detaching at maximum speed. weatherproof manner in the original packing in a clean environment.
→ The device is a built-in component. You, the owner/ ; Protect the device from environmental impacts and dirt until the final
operator, are responsible for providing adequate protection for installation.
the device.
; We recommend storing the device for a maximum up to one year to
→ Shut down the device immediately if you detect a guarantee proper operation and longest possible service life.
missing or ineffective protective feature.
; Even devices explicitly suited for outdoor use are to be stored as
1.6 Mechanical movement described prior to being commissioned.
; Maintain the storage temperature, see
DANGER chapter 3.6 Transport and storage conditions.
Rotating device
; Please make sure that all screwed cable glands are fitted with
Body parts that come into contact with the rotor and impeller
dummy plugs.
can be injured.
Translation of the original operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
2. PROPER USE
The device is exclusively designed as a built-in device for moving air
according to its technical data.
Any other or secondary use is deemed improper and constitutes a
misuse of the device.
Installations on the customer's side must meet the mechanical, thermal
and service life-related stresses that can occur.
Proper use also includes:
● Use the device in power systems with earthed neutral (TN/TT power
systems) only.
● Only using the device in stationary systems.
● Carrying out all maintenance.
● Moving air with a density of 1.2 kg/m³.
● Using the device in accordance with the permitted ambient
temperature, see chapter 3.6 Transport and storage conditions and
chapter 3.2 Nominal data.
● Operating the device with all protective features in place.
● Minding the operating instructions.
Improper use
Using the device in the following ways is particularly prohibited and
may cause hazards:
● Operating the device with an imbalance, e.g. caused by dirt deposits
or icing.
● Operation in medical equipment with a life-sustaining or lifesaving
function.
● Operation with external vibrations.
● Moving solids content in flow medium.
● Painting the device
● Connections (e.g. screws) coming loose during operation.
● Opening the terminal box during operation.
● Moving air that contains abrasive particles.
● Moving highly corrosive air, e.g. salt spray mist. Exceptions are
devices that are intended for salt spray mist and protected accordingly.
● Moving air that contains dust pollution, e.g. suctioning off saw dust.
● Operating the device close to flammable materials or components.
● Operating the device in an explosive atmosphere.
Translation of the original operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
3. TECHNICAL DATA
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
4. CONNECTION AND START-UP → Make sure that the cable end is connected in a dry
environment.
4.1 Connecting the mechanical system Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.
CAUTION
Cutting and crushing hazard when removing the fan
4.2.1 Prerequisites
from the packaging
→ Carefully remove the device from its packaging, only ; Check whether the data on the type plate agree with the connection
touching the guard grille. Make sure to avoid any shock. data.
→ Wear safety shoes and cut-resistant safety gloves. ; Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.
CAUTION ; Only use cables designed for current according to the type plate.
Heavy load when taking out the device For determining the cross-section, follow the basic principles in
Bodily harm, e.g. back injuries, are possible. accordance with EN 61800-5-1. The protective earth must have a
→ Two people should remove the device out of its packaging cross-section equal to or greater than the outer conductor cross-
together. section.
; Check the device for transport damage. Damaged devices must no We recommend the use of 105°C cables. Ensure that the minimum
longer be installed. cable cross-section is at least
; Do not make any modifications, additions or renovations to the AWG26/0.13 mm².
device. Replacing the terminal box is not permitted. Earth wire contact resistance to EN 61800-5-1
; Install the undamaged device according to your application. Compliance with the impedance specifications to EN 61800-5-1 for the
protective earth circuit must be verified in the end application.
4.2 Connecting the electrical system
Depending on the installation situation, it may be necessary to install an
DANGER additional protective earthing conductor via the additional protective earth
Electric voltage on the device connection point available on the device.
Electric shock The protective earth connection point is located on the housing and has
a protective earth symbol and a bore hole.
→ Always install a protective earth first.
→ Check the protective earth. 4.2.2 Residual current operated device
DANGER Only pulse-current sensitive and/or universal RCD protective
Incorrect insulation devices (Type A or B) are permitted. Like frequency inverters,
Risk of fatal injury from electric shock RCD protective devices cannot provide personal safety while
→ Use only cables that meet the specified installation operating the device.
requirements for voltage, current, insulation material, load etc.
4.2.3 Voltage control
→ Route cables such that they cannot be touched by any
rotating parts. With open loop speed control using transformers or electronic
DANGER voltage regulators (e.g. phase angle control), excessive current
Electrical load (>50 µC) between mains wire and may occur.
protective earth connection after switching of the supply In addition, noises can occur with phase angle control
when switching multiple devices in parallel. depending on the mounting situation.
Translation of the original operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
Δ Delta connection
Y Star connection
L1 = V1 = blue
L2 = U1 = black
L3 = W1 = brown
W2 yellow
U2 green
V2 white
TOP 2 x grey
PE green/yellow
Translation of the original operating instructions
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
4.5 Open additional screwed cable glands 4.8 Switching off the device
You have the ability to break a second cable gland opening through on ; Disconnect the device from the supply voltage at the main switch for
the terminal box. the supply line.
WARNING ; When disconnecting, be sure to disconnect the earth wire connection
In event of a fault, the screwed cable gland is under last.
electrical voltage
Electric shock
→ Do not use metal cable glands for plastic terminal
boxes.
; Screw the cable gland into the pre-cut thread using a screwdriver.
When doing so, note the tightening torques, see chapter 3.1 Product
drawing.
; Remove the plastic tab that falls off when the wire is pressed through
into the terminal box.
WARNING
Hot motor housing
Fire hazard
→ Ensure that no combustible or flammable materials are
located close to the fan.
; Inspect the device for visible external damage and the proper function
of the protective features before switching it on.
; Check the air flow paths of the fan for foreign objects and remove any
that are found.
; Apply the nominal voltage to the voltage supply.
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
S4D560-AB01-01
Operating instructions
WARNING
Terminals and connections have voltage even with a 5.1 Cleaning
unit that is shut off
Electric shock NOTE
→ Wait five minutes after disconnecting the voltage at all poles Damage to the device during cleaning.
before opening the device. Malfunction possible
→ Do not clean the device using a water jet or high-pressure
CAUTION
washer.
The motor restarts automatically when operating voltage
is applied, e.g. after a power failure. → Do not use any cleaners containing acids,
Danger of injury bases or solvents.
→ Keep out of the danger zone of the device. → Do not use any pointed or sharp-edged objects to clean.
→ When working on the device, switch off the mains 5.2 Safety test
supply voltage and secure the latter from being switched on
again. What has to How to test? Frequency Which
→ Wait until the device stops. be tested? measure?
→ Insert the brought-out thermal overload protector into the Check the Visual inspection At least every Repair or
control circuit so that the cooled off motor does not switch on protective 6 months replacement of
independently after a fault. casing against the device
accidental
If the device remains out of use for some time, e.g. when in
contact for
storage, we recommend switching the device on for at least
damage and to
two hours to allow any condensate to evaporate and to move
the bearings. ensure that it is
intact
Malfunction/error Possible cause Possible remedy Check the Visual inspection At least every Replacement
Impeller running Imbalance in rotating Clean the device; if device for 6 months of the device
roughly parts imbalance is still damage to
evident after blades and
cleaning, replace the housing
device. Mounting the Visual inspection At least every Fasten
If you have connection lines 6 months
attached any weight Mounting of Visual inspection At least every Fasten
clips during cleaning, protective 6 months
make sure to earth connection
remove them Check the Visual inspection At least every Replace wires
afterwards.
Translation of the original operating instructions
insulation of 6 months
Motor does not turn Mechanical blockage Switch off, de- the wires for
energise, and damage
remove mechanical Tightness of Visual inspection At least every Retighten,
blockage. screwed cable 6 months replace if
Mains supply Check mains supply gland damaged
voltage faulty voltage, Condensate Visual inspection At least every Open bore holes
restore power discharge 6 months
supply. holes for
Faulty connection De-energise, correct clogging, as
connection, see necessary
connection diagram. Weld seams Visual inspection At least every Replace device
Thermal overload Allow motor to cool for crack 6 months
protector responded off, locate and rectify formation
cause of error, if
necessary cancel
restart lock-out
Unacceptable Check operating point
operating point