FIRST LETTERS SUCCEEDING LETTERS

MEASURED /
READOUT / PASSIVE OUTPUT / ACTIVE
INITIATING VARIABLE MODIFIER FUNCTION MODIFIER
FUNCTION FUNCTION
VARIABLE
A ANALYSIS ALARM
B BURNER, COMBUSTION USER'S CHOICE USER'S CHOICE USER'S CHOICE
C CONDUCTIVITY CONTROL CLOSE
D DENSITY DIFFERENCE, DIFFERENTIAL DEVIATION

E VOLTAGE SENSOR, PRIMARY ELEMENT


F FLOW, FLOW RATE RATIO
GLASS, GAUGE, VIEWING
G USER'S CHOICE
DEVICE
H HAND HIGH
I CURRENT INDICATE
J POWER SCAN
K TIME, SCHEDULE TIME RATE OF CHANGE CONTROL STATION
L LEVEL LIGHT STATUS LOW
MOISTURE, MANUAL,
M OVERRIDE MIDDLE, INTERMEDIATE
MULTI, MOTOR
N USER'S CHOICE USER'S CHOICE USER'S CHOICE USER'S CHOICE
O USER'S CHOICE ORIFICE OPEN
P PRESSURE, VACUUM POINT (TEST CONNECTION)
Q QUANTITY INTEGRATE, TOTALIZE INTEGRATE, TOTALIZE
R RADIATION, RESTRICTION RECORD RUN
S SPEED, FREQUENCY SAFETY SWITCH STOP
T TEMPERATURE TRANSMIT
U MULTI-VARIABLE MULTIFUNCTION MULTIFUNCTION
VIBRATION, MECHANICAL
V VALVE, DAMPER, LOUVER
ANALYSIS
W WEIGHT, FORCE WELL, PROBE
UNCLASSIFIED, ACCESSORY DEVICES,
X X-AXIS UNCLASSIFIED UNCLASSIFIED
MISCELLANEOUS UNCLASSIFIED
Y EVENT, STATE, PRESENCE Y-AXIS RELAY, COMPUTING DEVICE
DRIVER, ACTUATOR,
Z-AXIS, SAFETY
Z POSITION, DIMENSION UNCLASSIFIED FINAL
INSTRUMENTED SYSTEM
CONTROL ELEMENT
TYPICAL BASIC PROCESS CONTROL SYSTEM ABBREVIATIONS
AE ELEMENT - ANALYZER PV VALVE - CONTROL, PRESSURE
BE ELEMENT - BURNER PCV VALVE - SELF REGULATING
DT TRANSMITTER - DENSITY PG GAUGE - PRESSURE
EIV EMERGENCY ISOLATION VALVE PT TRANSMITTER - PRESSURE
FV VALVE - CONTROL SC CONTROLLER - LOCAL SPEED
FE ELEMENT - FLOW TV VALVE - CONTROL, TEMPERATURE
FFC CONTROLLER - FLOW RATIO TG GAUGE - TEMPERATURE
GB STATUS INDICATION TE ELEMENT - TEMPERATURE
HS SWITCH - HAND VE PROBE - VIBRATION
HV VALVE - CONTROL, HAND VS SWITCH - VIBRATION
I FUNCTION - DCS LOGIC VT TRANSMITTER - VIBRATION
IT TRANSMITTER - CURRENT WT TRANSMITTER - WEIGH SCALE
JT TRANSMITTER - POWER XV VALVE - ON/OFF
KS SWITCH - TIME XY SOLENOID VALVE
LG GAUGE - LEVEL ZSC SWITCH - POSITION CLOSED
LV VALVE - CONTROL, LEVEL ZSO SWITCH - POSITION OPEN
MOV VALVE - MOTOR OPERATED
TYPICAL INSTRUMENTED PROTECTIVE SYSTEM / FIRE & GAS SYSTEM ABBREVIATIONS
FZS SWITCH - FLOW, SAFETY RV VALVE - PRESSURE RELIEF, SAFETY
FZT XMTR - DP, SAFETY TZS SWTICH - TEMPERATURE, SAFETY
HZS SWITCH - HAND, SAFETY TZT TRANSMITTER - TEMPERATURE, SAFETY
IZ FUNCTION - IPF LOGIC, SAFETY XZV VALVE - SHUTDOWN, SAFETY
LZS SWITCH - LEVEL, SAFETY XZY POSITIONER - HART, SAFETY
LZT TRANSMITTER - LEVEL, SAFETY XZY SOLENOID VALVE - SHUTDOWN, SAFETY
PDZT TRANSMITTER - DP, SAFETY ZZSC SWITCH - POSITION CLOSED, SAFETY
PSE BURSTING DISK, SAFETY ZZSO SWITCH - POSITION OPEN, SAFETY
PZS SW - PRESSURE, SAFETY ZZT TRANSMITTER - POSITION, SAFETY
PZT TRANSMITTER - PRESSURE, SAFETY