Radial Fans
Radial Fans
Radial Fans
USER INFORMATION
RADIAL FANS
SERIES VRE 100 ... 560
direct driven
Issue 09/06
Radial fans of plastic materials
Series VRE VRE 100 ... 560
direct driven
Application in all ranges of ventilation
base
motor fastening
elastic connection adapter ring
hub protection cap
with tensioning tape impeller fastening vibration absorbers
casing
condensate drain
APPLICATION
High resistance to corrosion resulting from the use of high-quality plastic materials makes the radial fans of type VRE
suitable in particular for process exhausting devices in the chemical and pharmaceutical industries, for ventilating
laboratories, battery rooms, pickling and washing plants, galvanic and agricultural facilities etc.
TECHNICAL DESCRIPTION
Main components of the fans are the impeller, spiral casing, casing connections, base, and driving motor. The motor is
flange-connected directly to the base and completely separated from the flowing medium. The impeller has been arranged
on the motor shaft and is driven directly. Steel components - such as screws, hub and hub connections - are made of acid-
resistant steel or protected against corrosion by plastic coverings.
The aerodynamic design of the fans is state-of-the-art so that high efficiency, low sound levels, and high performance
density can be achieved.
Every fan is supplied as a complete assembly unit ready for use. Vibration absorbers matched in size and quantity, elastic
connections on the pressure and suction sides, and a condensate drain bore with closing cap are elements of the standard
range of delivery.
Design features
Impeller: There are two impeller designs covering a wide range of performance:
Type 731 with vanes curved backward
Type 734 with vanes curved forward
Special impellers are used for special applications. Impellers with vanes in radial arrangement, for instance,
are advantageous if the medium conveyed contains intensely sticking substances.
The impellers are made of single components and assembled with progressive joining methods. Dynamic
balancing complies with ISO 1940.
Materials: PVC, PPs, PVDF, FRP (for high demands), electrically conductive plastic material (explosion-proof fans)
Casing: The casings are made of deep-drawn half shells (sizes 100 … 250 made of PVC or PPs) or even side walls
and a jacket which are tightly welded. The connection diameter on the suction side is in any case identical with
the nominal size of the fan. The casing can be opened on the suction side for cleaning. A condensate drain has
been arranged in deepest position.
Sealness of the shaft lead-through that is sufficient for many applications results from the vanes with far end
arrangement. Higher demands on sealness are met by an additional seal between impeller and casing (see
section Shaft seal).
A shatter guard or an additional FRP reinforcement should be arranged for cases of high demands on safety.
A wide range of casing connections is available for connecting ventilation lines.
Note: Connected plant components must not load the fan mechanically.
Materials: PVC, PPs, PVDF, FRP (for high demands), electrically conductive plastic material (explosion-proof fans)
Base: Robust welded design of zinc-coated sheet steel, optionally available: varnished or of stainless steel.
Motors: Standard motor: 3 ~ 400 V/ 50 Hz, degree of protection IP 54, design B 5 (in special cases B 14 or B 3)
Single-phase motors 230 V/ 50 Hz, motors with special voltages and different degree of protection, pole-
changing and explosion-proof motors
i_vre_en (09/06)
Motors with thermal winding protection (PTC resistor) --> special design TS
Motors with integrated frequency inverter --> special design MFU
03
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic materials
Series VRE direct driven
Technical explanation
CONDITIONS OF USE
permissible ambient temperature: -30 °C … 40 °C (EX motors -20 °C ... 40 °C)
permissible temperature of medium conveyed: -30 °C … 40 °C
Higher temperatures depend on the design size, material, and speed rate and are subject to consultation with the
manufacturers.
The applied materials have good chemical resistance against many substances. It should be considered, however, that
evens plastic materials are attacked by certain chemicals. This depends on the following items:
Chemical composition and concentration of medium conveyed
Temperature and time of action
Mechanical loading and residual stress resulting from processing
Many applications in fields such as laboratories and stockrooms for chemicals, in agriculture and damp-loaded processes
led to good results with "standard materials" such as PVC or PPs that can be used without any problem in most cases.
Critical applications may occur in the process-technological industry - surface refinement, pickling plants, process exhaust
air in microelectronics.
For selection of suitable materials the purpose of use of the fan and the type of medium conveyed should be
specified in requests or orders.
Slightly dust-laden media can also be conveyed but lead to increased wear.
Notes on outdoor use: If possible, fans should not be exposed to intense ultraviolet radiation.
The motor should be protected by a weather hood.
Ambient conditions have to be considered in material selection.
Working range: The fans show stable operation in the entire range of the characteristic shown. Operation with smaller
volume flows is possible but very ineffective. Use with larger volume flows may lead to motor overload
(type 734 in particular) and must be avoided.
Parallel arrangement: of type 731 is possible in any case, of type 734 after consultation with the
manufacturers only.
Series arrangement: requires the manufacturers' agreement (increased casing pressures).
SHAFT SEAL
Radial fans VRE with standard design have vanes in far end arrangement and formed on the rear hub protection cap. This
means permanent intake of external air through the minimized gap of the shaft lead-through if
pressure loss on suction end is greater that one third of total pressure loss.
This is the reason why components with high pressure losses such as washers, filters, separators etc. should be arranged,
whenever possible, before the fan, i.e. on the suction side.
sealing ring This seal is used for high demands on gastightness and in
cases of relatively dry outlet air. It is distinguished by its long
impeller hub service life.
There are various special seals such as gas shutoff seals,
labyrinth seals etc. for very high demands on tightness, in
particular in cases of high humidity and much condensate.
The manufacturers should be contacted for such
applications.
SPECIAL DESIGNS and ACCESSORIES (more details at the end of this brochure)
Cleaning opening, shatter guard, weather hood for motor, various connections for condensate drain, base of stainless
steel, intake and outlet protective grating
i_vre_en (09/06)
Ventilation components: ducts, elbows, flaps, air hoods, pipe and profiled silencers
Electrical accessories: repair switches, motor protection switches, pole changing switches, complete fan controls,
frequency inverters (also with pressure and volumetric flow regulation), air flow monitoring.
04
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic materials
Series VRE direct driven
Technical explanation
EXPLOSION PROTECTION
Guideline 94/9/EG (ATEX) newly regulates explosion protection for non-electrical devices from July 1, 2003. In addition to
observation of design and safety instructions according to DIN EN 14986 and DIN EN 13463, the fan has to be assigned
exactly to the relevant degree of protection and labelled accordingly. The manufacturers have to prove conformity.
Areas with hazard of explosion exist in the chemical industry, in gasworks, coking plants, varnishing units, petrol stations,
sewage and wastewater treatment plants, laboratory systems etc.
Prerequisites of explosion are:
Flammable substances (such as gas, dust),
Oxygen in sufficient quantity of air
Ignition source (sparks, fire, hot surfaces, electrostatic discharges)
The following measures have to be taken if explosions cannot be excluded:
Prevention of explosible atmosphere
Avoidance of ignition sources
Moderation of damaging effects of explosions
An efficient and supervised ventilation system is often a sufficient measure for avoiding ignitable atmosphere and,
consequently, hazard of explosion.
Protection demands on a fan depend on the probability of occurrence of explosible atmosphere in the medium conveyed
or/and in the surrounding. Hazard is classified in three zones:
The plant operator or the relevant board of control has to decide which protection is necessary and which additional
regulations have to be considered. This means that the customer has to specify in the order which kind of protection the fan
has to have.
Fans VRE are supplied for the following types of ignition protection:
Zone 1: II 2G c IIB+H2 T3
Zone 2: II 3G c IIB+H2 T3
temperature class T3 (ignition temperature of gas > 200 °C)
explosion group of gases IIB+H2 (IIA and H2 included, IIC not included)
constructional safety
category (2G = gases of zone 1, 3G = gases of zone 2)
Equipment-group II (use in mining not permissible)
On principle, application in zone 0 is not possible. Gases of explosion group IIC (hydrogen excluded), gases with ignition
temperature below 200 °C, and combustible dusts are likewise impermissible.
Classification generally differentiates between inside (medium conveyed) and outside (surrounding). Every zone of hazard
requires its special design. Explosion-proof electrical devices (motors, switches etc.) and electrically conductive materials
(preferably conductive and flame retardant polypropylene --> PPsX) are employed. General classification is as follows:
Motors with increased safety EEx e II must not be used in inverter operation. Motors EEx de with flameproof enclosure can
be employed in inverter mode if they are equipped with special winding protection (special design TS15). Standard motors
can be used and operated in inverter mode if the surrounding is not an EX zone and the fan meets certain design demands.
05
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic materials
Series VRE direct driven
Technical explanation
Impeller type
731 - curved backward
734 - curved forward
(special disigns of impeller types)
Direct drive
Material (casing/impeller)
PERFORMANCE PARAMETERS
All performance parameters are determined on MIETZSCH-own test racks. The design corresponds to DIN 24 163. The
volumetric flow is determined from the differential pressure by means of a measuring nozzle according to EN ISO 5167 .
In cases of radial fans that are destined to be arranged within a plant, the total pressure difference ∆pt results from
∆pfa = ∆pt - ρ/2 * cD2 (to designate it static pressure difference is incorrect)
06
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic materials
Series VRE direct driven
Technical explanation
3000
VRE 731
2900 U/min
2000 1450 U/min
impeller with backward
950 U/min curved vanes
710 U/min
315
560
1000
500
250
∆pt / Pa
450
400
200
500
400
160
200
100
ße
100
g rö
nn
Ne
30 .
50 100 200 300 500 1000 2000 3000 5000 10000 20000 30000 V / m³/h
4000
3000
VRE 734
400
200
2000
2900 U/min impeller with forward
1450 U/min
950 U/min
560 curved vanes
315
710 U/min
160
500
1000 450
250
∆pt / Pa
100
500
400
ße
300
nn
Ne
200
100
i_vre_en (09/06)
80 .
50 100 200 300 500 1000 2000 3000 5000 10000 20000 30000 V / m³/h
07
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 100 / 731
Impeller with backward curved vanes
PERFORMANCE
1400 Working range
1000
- stable regime in entire characteristic
range
- casing
=0
100
1450
- motor outside the flow conveyed
- robust sheet metal base, zinc-coated
- vibration absorbers in range of
50
delivery
--> MIETZSCH-CD
240
198 204
20
08
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 100 / 734
Impeller with forward curved vanes
PERFORMANCE
1400 Working range
1000
- stable regime in entire characteristic
range
300
Design features
ax
ηm
--> MIETZSCH-CD
240
198 204
20
09
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 160 / 731
Impeller with backward curved vanes
PERFORMANCE
1400 Working range
,78
400
manufacturers
=0
ax
300
ηm
Design features
1450 - welded impeller with 8 vanes curved
200
backward
- casing
deep-drawn for PVC or PPs
welded for special materials
100 950
- motor outside the flow conveyed
- robust sheet metal base, zinc-coated
- vibration absorbers in range of
50
delivery
max.810
PRINCIPAL DIMENSIONS
266
(made of PVC or PPs )
The principal dimensions refer to elastic Ø 160 179 192
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
315
--> MIETZSCH-CD
310 274
20
10
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 160 / 734
Impeller with forward curved vanes
PERFORMANCE
3000 Working range
- stable regime in entire characteristic
2000 range
- operation with larger volumetric flows
may lead to motor
2900 U/min
- parallel and series connection
,69
1000
possible after consultation with the
=0
manufacturers
∆pt / Pa
ax
ηm
Design features
500
- welded impeller with 35 vanes curved
400 forward
300 - casing
1450 deep-drawn for PVC or PPs
welded for special materials
200
- motor outside the flow conveyed
- robust sheet metal base, zinc-coated
- vibration absorbers in range of
100
950 delivery
- variant connectors of casing
ρ = 1,2 kg/m³
60
.
100 200 300 400 500 1000 2000 3000 V. / m³/h
0,03 0,05 0,1 0,2 0,3 0,4 0,5 1,0 V / m³/s
max.810
PRINCIPAL DIMENSIONS
266
(made of PVC or PPs )
The principal dimensions refer to elastic Ø 160 179 192
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
315
--> MIETZSCH-CD
310 274
20
11
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 200 / 731
Impeller with backward curved vanes
PERFORMANCE
1400 Working range
2900 U/min
- stable regime in entire characteristic
1000
range
,79
=0
500 - parallel connection possible, series
ax
connection after consultation with the
ηm
400
manufacturers
1450
300
Design features
200
- welded impeller with 8 vanes curved
backward
950 - casing
deep-drawn for PVC or PPs
welded for special materials
100
- motor outside the flow conveyed
710
- robust sheet metal base, zinc-coated
- vibration absorbers in range of
50
delivery
--> MIETZSCH-CD
370 306
20
PERFORMANCE
3000 Working range
- stable regime in entire characteristic
2000 2900 U/min range
,70
- operation with larger volumetric flows
=0
may lead to motor
ax
ηm
1000
- parallel and series connection
possible after consultation with the
manufacturers
∆pt / Pa
Design features
500
1450 - welded impeller with 35 vanes curved
400 forward
300 - casing
deep-drawn for PVC or PPs
welded for special materials
200
- motor outside the flow conveyed
950
- robust sheet metal base, zinc-coated
- vibration absorbers in range of
100 delivery
710
- variant connectors of casing
ρ = 1,2 kg/m³
60
.
200 300 400 500 1000 2000 3000 5000 V. / m³/h
0,1 0,2 0,3 0,4 0,5 1,0 V / m³/s
max.855
PRINCIPAL DIMENSIONS
294
(made of PVC or PPs )
The principal dimensions refer to elastic Ø 200 224 240
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
365
--> MIETZSCH-CD
370 306
20
PERFORMANCE
Working range
2000 2900 U/min - stable regime in entire characteristic
range
- fan can be operated beyond
characteristic specified
,80
1000
=0
- parallel connection possible, series
∆pt / Pa
ax
connection after consultation with the
ηm
manufacturers
500 1450
Design features
400
- welded impeller with 8 vanes curved
backward
300
speed 2900rpm with FRP-impeller
950 - casing
200 deep-drawn for PVC or PPs
welded for special materials
- motor outside the flow conveyed
710
100 - robust sheet metal base, zinc-coated
- vibration absorbers in range of
delivery
ρ = 1,2 kg/m³
50
. - variant connectors of casing
300 400 500 1000 2000 3000 5000 10000 V / m³/h
.
0,1 0,2 0,3 0,4 0,5 1,0 2,0 V / m³/s
max.1015
PRINCIPAL DIMENSIONS
328
(made of PVC or PPs )
The principal dimensions refer to elastic Ø 250 280 298
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
415
--> MIETZSCH-CD
480 332
25
PERFORMANCE
3000 Working range
- stable regime in entire characteristic
2000 range
- operation with larger volumetric flows
may lead to motor
- parallel and series connection
1000
possible after consultation with the
manufacturers
,70
∆pt / Pa 1450 U/min
=0
ax
Design features
ηm
500
- welded impeller with 35 vanes curved
400 forward
--> MIETZSCH-CD
480 332
25
15
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 315 / 731
Impeller with backward curved vanes
PERFORMANCE
4000 Working range
2900 U/min
3000 - stable regime in entire characteristic
range
,80
=0
- parallel connection possible, series
connection after consultation with the
ax
ηm
1000
manufacturers
1450
Design features
∆pt / Pa
- welded impeller with 8 vanes curved
500 backward
speed 2900rpm with FRP-impeller
400
950 - welded spiral casing
300
- motor outside the flow conveyed
- robust sheet metal base, zinc-coated
200 710
- vibration absorbers in range of
delivery
- variant connectors of casing
100
ρ = 1,2 kg/m³
.
600 1000 2000 3000 5000 10000 20000 V / m³/h
.
0,2 0,3 0,4 0,5 1,0 2,0 3,0 4,0 5,0 V / m³/s
max.1155
PRINCIPAL DIMENSIONS 369
The principal dimensions refer to elastic 353 376
Ø 315
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
729
710 490
25
GfK - impeller made of fibre reinforced plastic (FRP) LA3m = A - weighted sound pressure level at distance of 3 m
LWA = A - weighted sound power level in duct
16
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 315 / 734
Impeller with forward curved vanes
PERFORMANCE
3000 Working range
- stable regime in entire characteristic
2000 range
- operation with larger volumetric flows
,71
may lead to motor
1450 U/min
=0
1000 - parallel and series connection
ax
possible after consultation with the
ηm
manufacturers
∆pt / Pa
Design features
500 950
- welded impeller with 35 vanes curved
400 forward
ρ = 1,2 kg/m³
60
.
500 1000 2000 3000 5000 10000 20000 V. / m³/h
0,2 0,3 0,4 0,5 1,0 2,0 3,0 4,0 5,0 V / m³/s
max.1155
PRINCIPAL DIMENSIONS 369
The principal dimensions refer to elastic 353 376
Ø 315
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
729
710 490
25
17
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 400 / 731
Impeller with backward curved vanes
PERFORMANCE
2000 Working range
- stable regime in entire characteristic
1450 U/min range
,80
∆pt / Pa
=0
- parallel connection possible, series
ax
950 connection after consultation with the
ηm manufacturers
500
max.1335
PRINCIPAL DIMENSIONS 409
The principal dimensions refer to elastic 446 479
Ø 400
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
867
830 720
40(33)
18
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 400 / 734
Impeller with forward curved vanes
PERFORMANCE
4000 Working range
3000 - stable regime in entire characteristic
range
,72
- operation with larger volumetric flows
=0
2000 1450 U/min may lead to motor
ax
ηm
- parallel and series connection
possible after consultation with the
1000 manufacturers
950
∆pt / Pa Design features
- welded impeller with 35 vanes curved
500 forward
710
400 - welded spiral casing
- motor outside the flow conveyed
300
- robust sheet metal base, zinc-coated
max.1335
PRINCIPAL DIMENSIONS 409
The principal dimensions refer to elastic 446 479
Ø 400
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
867
830 720
40(33)
19
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 450 / 731
Impeller with backward curved vanes
PERFORMANCE
3000 Working range
- stable regime in entire characteristic
2000 range
1450 U/min
- fan can be operated beyond
characteristic specified
,80
- parallel connection possible, series
1000
=0
connection after consultation with the
ax manufacturers
∆pt / Pa 950
ηm
Design features
500
- welded impeller with 8 vanes curved
400 710 backward
speed 1450rpm with FRP-impeller
300
- welded spiral casing
- motor outside the flow conveyed
200
- robust sheet metal base, zinc-coated
- vibration absorbers in range of
delivery
100
- variant connectors of casing
ρ = 1,2 kg/m³
60
.
2000 3000 5000 10000 20000 30000 V. / m³/h
0,5 1,0 2,0 3,0 4,0 5,0 10,0 V / m³/s
max.1375
PRINCIPAL DIMENSIONS 454
The principal dimensions refer to elastic Ø 450 503 539
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
974
884 790
40(33)
GfK - impeller made of fibre reinforced plastic (FRP) LA3m = A - weighted sound pressure level at distance of 3 m
LWA = A - weighted sound power level in duct
20
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 450 / 734
Impeller with forward curved vanes
PERFORMANCE
Working range
- stable regime in entire characteristic
range
3000
- operation with larger volumetric flows
may lead to motor
2000
- parallel and series connection
possible after consultation with the
,72
manufacturers
=0
ax
1000 950 U/min Design features
ηm
max.1375
PRINCIPAL DIMENSIONS 454
The principal dimensions refer to elastic Ø 450 503 539
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
974
884 790
40(33)
21
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 500 / 731
Impeller with backward curved vanes
PERFORMANCE
3000 Working range
- stable regime in entire characteristic
2000
1450 U/min range
- fan can be operated beyond
,80
characteristic specified
=0
- parallel connection possible, series
1000
ax
950 connection after consultation with the
ηm
manufacturers
∆pt / Pa
Design features
500 710
- welded impeller with 8 vanes curved
400 backward
speed 1450rpm with FRP-impeller
300
- welded spiral casing
200
- motor outside the flow conveyed
- robust sheet metal base, zinc-coated
- vibration absorbers in range of
delivery
100
- variant connectors of casing
ρ = 1,2 kg/m³
70
.
2000 3000 5000 10000 20000 30000 V. / m³/h
0,5 1,0 2,0 3,0 4,0 5,0 10,0 V / m³/s
max.1435
PRINCIPAL DIMENSIONS 471
The principal dimensions refer to elastic 562 596
Ø 500
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
1079
957 860
40(33)
GfK - impeller made of fibre reinforced plastic (FRP) LA3m = A - weighted sound pressure level at distance of 3 m
LWA = A - weighted sound power level in duct
22
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 500 / 734
Impeller with forward curved vanes
PERFORMANCE
Working range
- stable regime in entire characteristic
range
3000
- operation with larger volumetric flows
may lead to motor
2000
- parallel and series connection
2
0,7
possible after consultation with the
=
manufacturers
ax
950 U/min
1000 ηm Design features
- welded impeller with 35 vanes curved
∆pt / Pa 710 forward
- welded spiral casing
500
- motor outside the flow conveyed
400
- robust sheet metal base, zinc-coated
300
- vibration absorbers in range of
ρ = 1,2 kg/m³ delivery
200
.
2000 3000 5000 10000 20000 30000 V
. / m³/h
- variant connectors of casing
max.1435
PRINCIPAL DIMENSIONS 471
The principal dimensions refer to elastic 562 596
Ø 500
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
1079
957 860
40(33)
23
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 560 / 731
Impeller with backward curved vanes
PERFORMANCE
4000 Working range
3000 - stable regime in entire characteristic
1450 U/min range
,80
=0
- parallel connection possible, series
ax
connection after consultation with the
950
ηm
manufacturers
1000
Design features
∆pt / Pa
710 - welded impeller with 8 vanes curved
500 backward
speed 1450rpm with FRP-impeller
400
- welded spiral casing
300
- motor outside the flow conveyed
- robust sheet metal base, zinc-coated
200
- vibration absorbers in range of
delivery
max.1505
PRINCIPAL DIMENSIONS 508
The principal dimensions refer to elastic 629 668
Ø 560
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
1151
1060 1050
40
GfK - impeller made of fibre reinforced plastic (FRP) LA3m = A - weighted sound pressure level at distance of 3 m
LWA = A - weighted sound power level in duct
24
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 560 / 734
Impeller with forward curved vanes
PERFORMANCE
Working range
- stable regime in entire characteristic
range
3000
- operation with larger volumetric flows
may lead to motor
2
0,7
2000
- parallel and series connection
=
ax
950 U/min possible after consultation with the
ηm
manufacturers
max.1505
PRINCIPAL DIMENSIONS 508
The principal dimensions refer to elastic 629 668
Ø 560
connectors on inlet and outlet and for
housing position 90R.
Height of axis is identical for all housing
positions.
Further dimensions see page 27.
1151
1060 1050
40
25
MIETZSCH GmbH Lufttechnik Dresden Großenhainer Str. 137 01129 Dresden Fax (0351) 8 58 00 74 http://www.mietzsch.de
Radial fans of plastic material
VRE 100 ... 250 (PVC, PPs)
Dimensions
MAIN DIMENSIONS
Casings of sizes 100 … 250 made of PVC or PPs consist
of two deep-drawn half shells welded together.
The dimension sketch shows housing position 090R.
For other positions the manufacturers turn the casing
around the fan axis.
The smooth connection on the suction and pressure sides
has diameter d = nominal diameter.
Many connection variants are possible to meet customers'
demands.
Design version ELA, vibration isolators, and a
condensate bore with closing cap are elements of the
standard range of delivery. Other versions have to be
Casing connection-pressure side
ordered separately.
Drawings in format dxf --> MIETZSCH-CD F_ rigid connection, round
l3
flange welded on
and undrilled/drilled 1)
Casing connection - suction side
KOF_ elastic connection, round
connecting element of flexible
elastic connection, round
KOF_ elastic connection, round
l2
compensator welded on
flange undrilled/drilled 1)
flange undrilled/drilled 1)
rigid connection, round
compensator welded on
connecting element of
flexible PVC
fastened with band clamp
lmax g6 g4
c g3
Ød Ød
ELA
F_
g5
g2
Ød
g1
l3 l2 l1
h
Housing position
090R
e4 e1
hiso
e6 e5
e3
Fan dimensions
Fan size Ød c e1 e3 e4 e5 g1 g2 g3 g4 g5 g6 h hiso lmax
VRE 100 110 105 204 198 -40 50 144 109 119 120 145 178 240 20 510
VRE 160 160 141 274 310 4 60 222 168 179 194 190 264 332 20 685
VRE 200 200 169 306 370 17 70 278 210 224 240 240 330 395 20 730
VRE 250 250 203 332 480 52 110 346 264 280 298 290 412 460 25 890
1) Flanges (round) and frames (rectangular) are made according to MIETZSCH standard MWS 53030.
Drilling pattern: 0 undrilled (such as FO, KOFO)
i_vre_en (09/06)
h1
and one jacket welded together. R_ rigid connection, rectangular
The dimension sketch shows housing position 090R. a,b
flange welded on
For other positions the manufacturers turn the casing and undrilled/drilled1)
around the fan axis.
KOR_ elastic connection,
h2
The smooth connection on the suction side has diameter
rectangular
d = nominal diameter. The smooth connection on the
compensator welded on
pressure side is rectangular a x b. flange undrilled/drilled 1)
Many connection variants are possible to meet customers' Ød
demands.
RSF_ rigid connection, round
Design version ELA, vibration isolators, and a
h4
transition, flange welded on
condensate bore with closing cap are elements of the
and undrilled/drilled 1)
standard range of delivery. Other versions have to be Ød
ordered separately.
Drawings in format dxf --> MIETZSCH-CD KOF_ elastic connection, round
transition
h6
Casing connection - suction side compensator welded on
flange undrilled/drilled 1)
connecting element of flexible
elastic connection, round
KOF_ elastic connection, round
flange undrilled/drilled 1)
Ød
rigid connection, round
compensator welded on
transition
connecting element of
h5
flexible PVC
fastened with band clamp
lmax g6 g4
c g3
b a
ELA
F_
g5
g2
Ød
g1
l3 l2 l1 h
Housing position
090R
e4 e6 e5 e1
hiso
e3 e2
Fan dimensions
Fan size Ød a b c e1 e2 e3 e4 e5 g1 g2 g3 g4 g5 g6 h hiso lmax
VRE 315 315 288 300 244 425 490 710 120 120 435 324 353 376 354 527 605 25 1030
VRE 400 400 370 380 284 540 720 830 160 130 555 412 446 479 442 666 740 40(33) 1210
VRE 450 450 416 429 329 540 790 884 185 140 624 464 503 539 499 751 845 40(33) 1250
VRE 500 500 455 464 346 580 860 957 202 150 691 514 562 596 554 835 920 40(33) 1310
VRE 560 560 510 517 383 580 1050 1060 229 150 774 576 629 668 626 934 1040 40 1380
h1
conductive materials) casings of sizes 100 … 250 consist R_ rigid connection, rectangular
of two even side walls and one jacket welded together. a,b flange welded on
The dimension sketch shows housing position 090R. and undrilled/drilled1)
For other positions the manufacturers turn the casing
KOR_ elastic connection,
h2
around the fan axis.
rectangular
The smooth connection on the suction side has diameter
compensator welded on
d = nominal diameter. The smooth connection on the flange undrilled/drilled 1)
Ød
pressure side is rectangular a x b. Many connection
variants are possible to meet customers' demands.
RSF_ rigid connection, round
Design version ELA, vibration isolators, and a
h4
transition, flange welded on
condensate bore with closing cap are elements of the
and undrilled/drilled 1)
standard range of delivery. Other versions have to be Ød
ordered separately.
Drawings in format dxf --> MIETZSCH-CD KOF_ elastic connection, round
transition
h6
Casing connection - suction side compensator welded on
flange undrilled/drilled 1)
connecting element of flexible
elastic connection, round
KOF_ elastic connection, round
Ød
flange undrilled/drilled 1)
rigid connection, round
compensator welded on
transition
connecting element of
h5
flexible PVC
fastened with band clamp
lmax g6 g4
c g3
b a
ELA
F_
g5
g2
Ød
g1
l3 l2 l1
Housing position
h
090R
e4 e1
e5
iso
Fan dimensions
Fan size Ød a b c e1 e3 e4 e5 g1 g2 g3 g4 g5 g6 h hiso lmax
VRE 100 110 96 102 105 204 198 -40 50 144 109 119 120 145 178 240 20 510
VRE 160 160 144 152 141 274 310 4 60 222 168 179 194 190 264 332 20 685
VRE 200 200 180 187 169 306 370 17 70 278 210 224 240 240 330 395 20 730
VRE 250 250 226 236 203 332 480 52 110 346 264 280 298 290 412 460 25 890
1) Flanges (round) and frames (rectangular) are made according to MIETZSCH standard MWS 53030.
Drilling pattern: 0 undrilled (such as FO, KOFO)
i_vre_en (09/06)
weather guard
Cleaning opening
Cleaning of the impeller requires the fan to be taken out of Cleaning opening
the plant and the intake socket to be opened. Fan size ØD
An additional cleaning opening (see picture) is advisable for VRE 315 110
reducing maintenance in cases of larger fans and intense
VRE 400 140
soiling.
VRE 450 160
VRE 500 180
How to order: ROE - cleaning opening
VRE 560 225
Ø 22 ØD ØD
i_vre_en (09/06)
Repair switch RS
The repair switch RS is used to disconnect the fan completely from the mains in
cases of repair and maintenance. This excludes the risk of accidents arising from
unauthorized activation. The switch is supplied as a separate unit or fastened and
wired on the fan.
The switch size is determined by the motor power and mains voltage.
Example: Volume flow control with alarming if rated value is fallen below
fan
alarm device
Spiral casing optionally of PVC / PPs, sucking on one side, with condensate drain
Shaft seal: without seal / GD-technical gastight
VRE _ _ _ / _ _ _ W _ _ _ _ - _ _ - _ _ - _ _ _ _ - _ _ _ _
Nominal size
Impeller type
Nominal speed
Special version
Housing position / direction of rotation
Material casing / impeller
Media / use:
Cleaning opening
Repair switch: single / mounted, 3-poles with auxiliary contact / 6-poles with auxiliary switch
Other accessories
no. quantity individual Total
specification price price
EUR EUR
VRE _ _ _ / _ _ _ W _ _ _ _ - _ _ - _ _ - _ _ _ _ - _ _ _ _
Nominal size
Impeller type
Nominal speed
Special version
Housing position / direction of rotation
Material casing / impeller
Media / use:
Repair switch: single / mounted, 3-poles with auxiliary contact, standard / explosion-proof
Motor protection switch: single / mounted, standard / explosion-proof
Other accessories
radial fan VRE 500
standard design
installation on tanks
os scrubbers
special design GAB
Großenhain BERLIN
Moritzburg COTTBUS
BAUTZEN
Dresden-Hellerau exit
Dresden Neustadt
Dresden-Neustadt
exit Dresden-Wilder Mann exit
Hubertusplatz
FRANKFURT A.M.
CHEMNITZ
LEIPZIG