Testing Procedures: CT Test Format
Testing Procedures: CT Test Format
Equipment Required
1. Insulation Resistance tester: Megger
mit1020.
2. CT Analyzer
3. Multimeter.
4. Primary Injection Kit: ODEN AT
Insulation Tester
CT Analyzer
Insulation Resistance Test
Use Megger mit1020 to measure insulation resistance.
Insulation Resistance Tests to be done:
o Primary winding - Ground (Apply 5000V for 1 minute)
o Primary winding - Secondary winding (Apply 2500V for 1 minute)
o Secondary winding - Secondary winding (Apply 2500V for 1 minute)
o Secondary - Ground (Apply 1000V for 1 minute)
CT Characteristics Test
Use CT Analyzer to test CT Characteristics.
Connection on CT Analyzer will be same as the shown
figure.
Repeat the test for the other phases and the other secondary
cores.
Refer to CT Analyzer User Manual to find how to use CT
Analyzer & how to enter CT Data.
Connection
CT Loop Resistance Test
Measure CT resistance from CT terminal blocks (CT Side).
Measure Loop resistance from CT terminal blocks (Load Side).
Measure the Total Loop resistance (CT resistance + Load resistance + wiring
resistance).