PRODUCT SPECIFICATION

FORBES-BRYAN Low Corrosion TRAY TYPE


DEAERATOR – 5MW to 400MW

Supply and install tray type deaerator, which shall be manufactured in Australia using skilled labour and
proven materials, for optimum life and efficiency and will comply with the following Australian Standards:
ENGINEERING DATA - FORBES and HUNT BOILERS SAMPLE AUSTRALIAN PRODUCT SPECIFICATION

AS1200-2000 Pressure Equipment


AS1210-2010 Pressure Vessels
AS1657-1992 Fixed platforms, walkways, stairways and ladders – Design, construction and installation
AS1271-2003 Safety valves, other valves, liquid level gauges and other fittings for boilers and unfired
pressure vessels
AS3000-2007 Electrical Installations
AS3920.1-1993 Assurance of Product Quality – Pressure Equipment Manufacture
AS3992-1998 Pressure equipment – Welding and brazing qualification
AS4037-1999 Pressure equipment – Examination and testing
AS4343-2005 Pressure equipment – Hazard levels
AS4458-1997 Pressure Equipment – Manufacture

DEAERATOR

The deaerator shall be of Forbes and Hunt Boilers manufacture or equal approved and must comply with the
following performance and construction criteria:

Construction

The deaerator storage vessel and tray vessel will be manufactured from carbon steel and have adequate
storage capacity to provide 120% of the rated capacity of the steam plant that it feeds.

The deaerator shall be fitted with individual replaceable trays, which will be manufactured from stainless steel
to ensure protection from the effects of corrosion.

The deaerator trays will be housed within a sealed stainless steel chamber, such that all corrosive gasses
extracted from the water are vented to atmosphere without contacting any carbon steel surfaces.

Steam shall enter the deaerator first coming into contact with the hottest water, which is leaving the last row
of trays and then proceed upwards through the tray stack.

The deaerator shall be designed for a maximum Working Pressure of 350 kPa and Operating Pressure of
300 kPa.

The deaerator will be provided with an adequate number of inspection openings to facilitate internal
inspection, tray replacement and cleaning.

Water Entry

The water for deaeration shall enter the vessel through a spay tube(s) which will be manufactured from
stainless steel to minimize corrosion effects.
The spay tube(s) shall disperse the water evenly across the trays where it will be controlled for suitable
deaeration to take place.

Version 1211.1 Page 1 of 3

ADELAIDE MELBOURNE (Hunt Boilers) SYDNEY (Hunt Boilers)


599 Port Road, West Croydon SA 5008 11 Helen Kob Drive, Braeside Vic 3195 4/38 Powers Road, Seven Hills NSW 2147
Ph: 61 8 8268 8877 Fax: 61 8 8347 1311 Ph: 61 3 9580 9377 Fax: 61 3 9580 9411 Ph: 61 2 9674 1255 Fax: 61 2 9674 1877

BRISBANE (Hunt Boilers) PERTH (Hunt Boilers)


10/37 Mortimer Road, Acacia Ridge Qld 4110 1/14 Baling Street, Cockburn Central WA 6164
Ph: 61 7 3277 4730 Fax: 61 7 3277 9730 Ph: 61 8 9414 8787 Fax: 61 8 9414 8383
PRODUCT SPECIFICATION
FORBES-BRYAN Low Corrosion TRAY TYPE
DEAERATOR – 5MW to 400MW

Gas Venting

All gases removed through the deaeration process shall be vented through a stainless steel vent condenser
ENGINEERING DATA - FORBES and HUNT BOILERS SAMPLE AUSTRALIAN PRODUCT SPECIFICATION

pipe, which extends through a stainless steel tray box.

No undeaerated water or removed gasses shall come into contact with any carbon steel surfaces within the
deaerator vessel(s)

Deaerator Trays

All deaeration trays shall be manufactured from stainless steel and be suitable for replacement without the
need for specialised tools or welding.

All trays will have a controlled overflow and retention such that effective gas removal occurs, after which
deaerated water shall naturally fall into the storage area.

Deaerator Valves and Mountings

The deaerator shall be supplied complete with valves and fittings including main steam stop valve, safety
valve(s), feed water isolating and check valves, blowdown valve, and water gauges.

Equipment Access

Ladders and galleries shall be provided to the deaerator such that the necessary valves and fittings can be
operated effectively.

Control Overview

The deaerator control panel shall be rated to IP55 and incorporate the necessary controls, switches and
other components to effectively manage the system.

The control panel shall include the display of current operating conditions and fault identification.
Management System

The deaerator management system shall, as a minimum, control and detect the following:

• Automatic feed water control;


• Input pressure reduction control;
• Vacuum breaker;
• Vent valve;
• Pressure and temperature indication;
• Overflow control;
• Low water level control;
• High water level control;

Version 1211.1 Page 2 of 3

ADELAIDE MELBOURNE (Hunt Boilers) SYDNEY (Hunt Boilers)


599 Port Road, West Croydon SA 5008 11 Helen Kob Drive, Braeside Vic 3195 4/38 Powers Road, Seven Hills NSW 2147
Ph: 61 8 8268 8877 Fax: 61 8 8347 1311 Ph: 61 3 9580 9377 Fax: 61 3 9580 9411 Ph: 61 2 9674 1255 Fax: 61 2 9674 1877

BRISBANE (Hunt Boilers) PERTH (Hunt Boilers)


10/37 Mortimer Road, Acacia Ridge Qld 4110 1/14 Baling Street, Cockburn Central WA 6164
Ph: 61 7 3277 4730 Fax: 61 7 3277 9730 Ph: 61 8 9414 8787 Fax: 61 8 9414 8383
PRODUCT SPECIFICATION
FORBES-BRYAN Low Corrosion TRAY TYPE
DEAERATOR – 5MW to 400MW

Deaerator Insulation

The deaerator pressure vessel(s) shall be fully insulated over their complete length using Glasswool or
ENGINEERING DATA - FORBES and HUNT BOILERS SAMPLE AUSTRALIAN PRODUCT SPECIFICATION

Rockwool insulation, selected to be suitable for the continuous operating temperature of the deaerator.

A suitable metal case shall cover over the insulation with all longitudinal and transverse joints lapped by a
minimum of 40mm.

Metal cone downs shall be used at all terminations and transitions on the deaerator and all joints being made
weatherproof with the application of a suitable sealant.

Documentation

The deaerator shall be provided with complete set of documentation as follows:

Design Registration Statement


Design verification Statement
Manufacturer’s Data Report
Copies of all Material Certificates
Copies of all Non-destructive Test Reports
Complete Instruction Manuals (2 sets - electronic)

General Capacity Specification

The deaerator shall be provided as follows:

Model Forbes-Bryan or approved equal

Maximum water volume for deaeration (specifiy) kgs per hour

Minimum deaerated water volume stored (specifiy) Litres

Maximum retained oxygen after deaeration 0.005 cc/l or 7 ppb

Maximum retained carbon dioxide after deaeration Zero (measurable)

Design Temperature 250ºC

Design pressure 350 kPa

Maximum operating pressure 300 kPa

Hydrostatic Test Pressure 525 kPa

AS1200, AS1210, AS3920.1,


Principle Design Standards
AS3992, AS4343 and AS4458

Version 1211.1 Page 3 of 3

ADELAIDE MELBOURNE (Hunt Boilers) SYDNEY (Hunt Boilers)


599 Port Road, West Croydon SA 5008 11 Helen Kob Drive, Braeside Vic 3195 4/38 Powers Road, Seven Hills NSW 2147
Ph: 61 8 8268 8877 Fax: 61 8 8347 1311 Ph: 61 3 9580 9377 Fax: 61 3 9580 9411 Ph: 61 2 9674 1255 Fax: 61 2 9674 1877

BRISBANE (Hunt Boilers) PERTH (Hunt Boilers)


10/37 Mortimer Road, Acacia Ridge Qld 4110 1/14 Baling Street, Cockburn Central WA 6164
Ph: 61 7 3277 4730 Fax: 61 7 3277 9730 Ph: 61 8 9414 8787 Fax: 61 8 9414 8383

You might also like