ATS-PLC Ver1.

PROGRAMMABLE TOUCH-SCREEN
AUTOMATIC TRANSFER SWITCH
CONTROL UNIT
OPERATOR’S MANUAL

Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung, TAIWAN
Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw
ATS-PLC Automatic Transfer Switch

TABLE OF CONTENTS

Section Page

SECTOIN 1 : INTRODUCTION
1.1 Preliminary Comments and Safety Precautions .............................................................................. 3
1.2 Overview .......................................................................................................................................... 3
1.3 Product Overview ............................................................................................................................. 3
1.4 Functions / Features ........................................................................................................................ 3
1.5 Electrical Characteristics .................................................................................................................. 4
1.6 Exterior Overview ............................................................................................................................. 5
1.7 ATS-PLC quickly start ...................................................................................................................... 6

SECTOIN 2 : TOUCH SCREEN PANEL OVERVIEW


2.1 Status Icons ..................................................................................................................................... 8
2.2 Start-Up Screen ............................................................................................................................... 8
2.3 Auto Mode ........................................................................................................................................ 9
2.4 OFF Mode ...................................................................................................................................... 10
2.5 Manual Mode ................................................................................................................................. 11
2.6 Test Mode ...................................................................................................................................... 12
2.7 Program Mode ............................................................................................................................... 13

SECTOIN 3 : KCU-XX COMMUNICATION MODULE CONFIGURATION

SECTOIN 4 : SPECIFICATION AND INSTALLATION


4.1 General Specification ..................................................................................................................... 26
4.2 Unit Dimension and Installation Reference .................................................................................... 26

SECTION 5 : TYPICAL WIRING


APPENDIX 01: TOUCH SCREEN SENSITIVITY CALIBRATION
APPENDIX 02: DOWNLOAD START-UP SCREEN

______________________________________________________________________________________
2
ATS-PLC Automatic Transfer Switch

SECTION 1 : INTRODUCTION The multi parameter setting ranges enables the


controller to operate on all kinds of ATS transfer
1.1 Preliminary Comments and Safety Switches and the customizable features to fulfill the
operator’s needs. All configurations are stored in the
Precautions internal program memory to prevent loss of data or
The manual covers installation, operation and important settings during a power outage.
maintenance of the ATS-PLC Automatic Transfer
Switch Controller. This manual is for use by 1.4 Functions / Features
authorized and qualified personnel only.
● Microcomputer program control, compact size
and easy installation.
WARNING ● 5.7” inch color LCD touch-screen.
High voltages can kill. ● Program and function setting via touch-screen
operation.
● Voltage, current, frequency and KVA readings for
1.2 Overview normal and standby power and current time
display.
Transfer switches protect critical electrical loads
against loss of power. A standby (emergency) ● Voltage, current and frequency readings displayed
generator backs up the normal grid power. The digitally in numeric or gauge type display.
transfer switch connects either the normal or the ● Normal and standby power full phase voltage
standby supply to the load. When power is lost from monitoring and protection.
the grid, the transfer switch transfers the load to the ● Normal and standby power frequency monitoring
standby source. Eventually after the grid is and protection.
restoration, the ATS connects the load back to the ● Normal and standby reverse phase sequence
grid. protection.
● Normal and standby overload or short circuit trip
monitoring and protection.
● Optional exercise with or without load.
● Optional 1 to 4 weeks automatic scheduled
exercise / testing.
● Pre-alert warning signal output for scheduled
automatic Exercise / testing.
● Transfer failure alarm.
● Full compatibility with all types of ATS switches.
● Optional USB / RS485 / Ethernet remote (mobile
proxy) communication functions.
● Program on-site or from remote (mobile) device
(PC, Smart Phone).
1.3 Product Overview ● Program on-site or from remote (mobile) device
(PC, Smart Phone).
The ATS-PLC is a programmable multifunction
● Permanent stored configuration, prevent loss of
touch-screen automatic transfer switch control unit data during power outage.
with built in 5.7” inch color touch screen. The
● Front panel display provides source status and
compact design easily replaces the general
fail alarm indications.
conventional ATS controlling circuit board and
controllers. The interface is user friendly with plenty ● Built-in 40 sets of event log.
of preferred settings and configuration to suit user ● Built-in 4 digits password protection.
preference. Suited for single phase/3 phase 3 wires/ ● Multiple language support (Traditional Chinese /
3 phase 4 wires systems. English / Spanish).

______________________________________________________________________________________
3
ATS-PLC Automatic Transfer Switch

1.5 Electrical Characteristics


System Power
ITEM CONTENT FACTORY PRESET
System Phase 3 Phase 4 Wires / 3 Phase 3 Wires / Single Phase 3 Phase 3 Wires
X/5A (X = Primary Current, 5A = Secondary Ratio)
Current Transformer (CT) X = Not Available/50/100/150/200/250/300/400/500/600/800/ 1000/5A
1000/1200/1500/1600/2000/3000/4000/5000/6000 (A)

Time Delay Setting


ITEM SETTING RANGE UNIT FACTORY PRESET
Time Delay Emergency to Normal (TDEN) 0 ~ 1800 sec 2 sec/unit 10 sec
Time Delay Normal to Emergency (TDNE) 0 ~ 1800 sec 2 sec/unit 10 sec
Timer Delay Engine Start (TDES) 0 ~ 300 sec 2 sec/unit 10 sec
Timer Delay Engine Cooling (TDEC) 0 ~ 1800 sec 2 sec/unit 30 sec
Time Delay OFF position (TDOF) 0 ~ 300 sec 2 sec/unit 4 sec

Protection Setting
ITEM SETTING RANGE UNIT FACTORY PRESET
Normal/ standby Over Voltage Protection 110V ~ 530V 10V/unit 250V
Over Voltage Reset Value -20V ~ 0V 1V/unit -5V
Normal/ standby Under Voltage Protection 80V ~ 470V 10V/unit 180V
Under Voltage Reset Value 0V ~ 20V 1V/unit 5V
Normal/ standby Over Frequency Protection 51Hz ~ 75Hz 1Hz/unit 65Hz
Over Frequency Reset Value -10Hz ~ 0Hz 1Hz/unit -1Hz
Normal/ standby Under Frequency Protection 40Hz ~ 59Hz 1Hz/unit 55Hz
Under Frequency Reset Value 0Hz ~ 10Hz 1Hz/unit 1Hz
Abnormality Confirmation Time Delay 0 ~ 99 sec 1 sec/unit 10 sec
Reverse Phase Sequence Protection Enabled / Disabled Disabled

Brightness Adjustment
ITEM SETTING RANGE UNIT FACTORY PRESET
Brightness Adjustment Level 1 ~ Level 8 1 level Level 6
Screen Saver 2 min ~ 10 min or cancelled 1 minutes 3 min

Communications Transmission
ITEM SETTING RANGE FACTORY PRESET
Remote Operation Enable/Disable Disable
Baudrate 1200 / 2400 / 9600 / 19200 / 38400 / 57600 38400
RS485 Slave Address 00 ~ 99 (Valid value 01 ~ 99;00 Disabled) 00 (Disabled)

______________________________________________________________________________________
4
ATS-PLC Automatic Transfer Switch

1.6 Exterior Overview


Front

Color Touch-Screen

Power on Indicator
LED (Blinking)

Home Button

Press to return to main page at anytime


Press and hold for 10 sec to execute touch screen sensitivity adjustment function

Rear

Removable DIN
terminals

Terminal Number

Communication
Expansion Sockets

Removable DIN
terminal

Mounting Hole

______________________________________________________________________________________
5
ATS-PLC Automatic Transfer Switch

1.7 ATS-PLC Quickly Start


Step1 : Refer to chapter-5 (wiring diagram) for Step5:Select Language. (Refer to 2.7.3.2)
completed wiring.

Step2:Turn on the DC power and set the ATS-PLC


controller under OFF mode.

Step6:Setting system phase and CT rated. (Refer


to 2.7.5.1)

Step3:Into programming mode.

Step7:Select switch type. (Refer to 2.7.5.3)

Step4:Setting current time. (Refer to 2.7.3.1)

______________________________________________________________________________________
6
ATS-PLC Automatic Transfer Switch

Step8:Setting exerciser parameter if needed. (Refer Step11:Operate testing.


to 2.7.5.4)
Manually start the genset and transfer the load from
Normal to Standby source by press touch key.

Step9:Setting all the necessary protections for both


Normal and Standby source. (Refer to 2.7.5.5)
Step12 : Manually transfer the load go back to
Normal Source and stop the genset by press touch
key.

Step10:Power on Normal side AC volt input and set


the ATS-PLC under Manual mode.
Step13:Repeat Step 11 & 12 to make sure the ATS
works or not.

Step14:Set the ATS-PLC on AUTO mode and


finished the quick start procedure.

______________________________________________________________________________________
7
ATS-PLC Automatic Transfer Switch

SECTOIN 2 : TOUCH SCREEN PANEL OVERVIEW


2.1 Status Icons
Icon Function Icon Function

Normal power / Grid Engine remote start

TDEN/TDNE/TDEC/TDES
Emergency power / Standby
Time delay countdown
Return to last page (Modification will
Load
not be saved if pressed in setting
mode)
Power source connected
Enter / Save
Power source not connected
Increase
Connecting failure
Decrease
Overload or trip warning
Move right
Reverse phase sequence warning
Move left
ATS failure
Event logs erase
Incorrect operation
Mute
Incorrect password entered. System
locked (Please contact with dealer)

2.2 Start-up Screen

Start-up Screen
Displays for 3 sec then
enters operation mode

Press to skip start-up


screen

Attention! Start-up screen is customizable by user, for details please refer to APPENDIX 02.

______________________________________________________________________________________
8
ATS-PLC Automatic Transfer Switch

2.3 Auto Mode

2.3.1 Pointer Gauge Meter Mode Main Screen

Connection Status Message Area


Normally shows the time
& any Warning when
failure occurs
Phase Indication (Note 01)
Press to see another phase Pointer Analog Mode
Green = Normal Range
Volt / Amp / Hz (Note 02) Red = Abnormal Range
Press to change display from
Press to change display
Volt > Amp > Hz
mode to digital display

Normal Source Data Standby source Data

Programming Buttons

Range In AUTO

【Note 01】3 Phase 3 Wires selection sequence = L12 > L23 > L31.
3 Phase 4 Wires selection sequence = L12 > L23 > L31 > L1N > L2N > L3N
【Note 02】Volt / Amp / Frequency display sequence = Volt > Amp > Hz

2.3.2 Numerical Meter Mode Main Screen

Connection Status
Press to change back to
analog display
Normal Source
Readings

Standby source
Readings

______________________________________________________________________________________
9
ATS-PLC Automatic Transfer Switch

2.4 OFF Mode

2.4.1 OFF Mode Display Screen

Press to Enter Event Log

Warning Message
Current Time Display Area

Current Date

From OFF, Press


In “OFF” PROG to Enter System
Programming

2.4.2 Event Log Display Screen

Press to Erase Events

Failure Events Display Time of Failure


Max. Of 40 entries Listed in order of occurrence

Move up Move down

Return to last page Home Key


Press to Return to OFF Screen

Attention! If controller left untouched or no entries being selected in 60 seconds the screen will automatically
return to OFF screen.

______________________________________________________________________________________
10
ATS-PLC Automatic Transfer Switch

2.5 Manual Mode

2.5.1 Manual Mode Display Screen (Normal Source Supplying)

Standby Source Manual


Connect Button
ATS Connection Status

Engine Start / Stop button

Normal Source Data Standby Source Data


Display Area Display Area

In MANUAL

2.5.2 Manual Mode Display Screen (Standby Source Supplying)

ATS Connection Status


Normal Source Manual Engine Start /
Connect Button Stop Button

______________________________________________________________________________________
11
ATS-PLC Automatic Transfer Switch

2.6 TEST Mode

2.6.1 With Load / Without Load Selection

Button Illuminates Button Illuminates


When Selected When Selected

Test With Load Test Without Load


Botton Button

In TEST Mode

Attention! When executing Test while emergency source is connected, system will bypass “ With Load /
Without Load Selection ” and exercise testing with load.

2.6.2 With Load Testing Screen Display

Blue Represents the


Currently Displayed
Parameter for
Standby Source

______________________________________________________________________________________
12
ATS-PLC Automatic Transfer Switch

2.7 Program Mode (PROG)


Attention! Prior to execute system parameter configuration / Programming (PROG), first set system to OFF
Mode then press PROG to enter program configuration, otherwise a operation failure message will
be displayed. (See illustration in 2.7.2 MANU Mode Procedure Error Warning).

Programming Map

System Clock

Chinese

Language English

Spanish
System Setup
Set New Passcode

Passcode Change Passcode

Disable Passcode

Set Brightness
Brightness
Screen Saver

En/Dis Communication

Comm. Interface Baudrate

Communication RS485 Slave Address

Download Image

System Phase
System Power
CT Setting

Program Mode TDEN

TDNE

Time Delay TDES

TDEC

TDOF

MCCB Type (1 Motor)

MOT Type (2 Motors)

ACB Type
Switch Type
Kutai TS Type

Double Throw (1 Coil)

Double Throw (2 Coils)


System Parameter Exerciser OV/UV Setting

Normal OV/UV Setting OV/UV Reset

Time Delay

OF/UF Setting

Normal OF/UF Setting OF/UF Reset

Time Delay

OV/UV Setting

Protection Setup Standby OV/UV Setting OV/UV Reset

Time Delay

OF/UF Setting

Standby OF/UF Setting OF/UF Reset

Time Delay

Reverse Phase Sequency

Normal V Calibration

Calibrated V/A Reading Load A Calibration

Factory Setting Standby V Calibration

______________________________________________________________________________________
13
ATS-PLC Automatic Transfer Switch

2.7.1 Program Mode Display Screen

Communication Setting
Refer to Chapter 2.7.4
System Settings Refer to
System Setting Chapter 2.7.5
Refer to Chapter 2.7.3

Current Mode“PROGRAM”

Home Key
Press to Return to OFF
Screen Display

Attention! If controller left untouched or no entries being selected in 60 seconds the screen will automatically
return to OFF mode display screen.

2.7.2 Enter Program Mode Procedure Error Warning

Error Message

Mute

Attention! The error message is displayed for 5 seconds only, and then automatically returns to previous
screen.

______________________________________________________________________________________
14
ATS-PLC Automatic Transfer Switch

2.7.3 System Setup

Set Time

Language Selection Description

Password Setting

Brightness Adjustment

Return to Previous Page

2.7.3.1 System Clock Setting

Decrease
When selected the
background turns blue

Increase

Return to last page button


(Modification are not Enter and Save
saved if pressed)

Attention! The adjustment of system clock directly affects the automatic exerciser test and event log records,
therefore it is vital to setup the correct current time and date when install the unit for the first time.

______________________________________________________________________________________
15
ATS-PLC Automatic Transfer Switch

2.7.3.2 Language Setting


Currently ATS-PLC operating language only support traditional English and Spanish.

When selected the back


ground turns blue When selecting the
language it turns blue

2.7.3.3 Passcode Setting

Return to last page


button (Modification are
not saved if pressed)

Correct Enter and Save

Attention! The Passcode protects only the authority to change or adjust the parameter setting, will not affect
the operation of the controller’s functions.

______________________________________________________________________________________
16
ATS-PLC Automatic Transfer Switch

2.7.3.4 Change or Disable Passcode


Once passcode is set, to change or disable the passcode, enter “System Setup” and click “Passcode”.

Change Passcode Disable Passcode

2.7.3.5 Brightness Adjustment

Brightness Backlight
adjustment buttons

Screen Saver time.


Brightness Adjustment When set to maximum, the
screen saver mode will be
cancelled.

______________________________________________________________________________________
17
ATS-PLC Automatic Transfer Switch

2.7.4 Communication Setup


In this setting, user can choose to run the remote communication interface settings and download
personalization of the startup screen function.

Communication Interface
Setting
General Description
Download Startup Screen

Attention! For Startup Screen download program, please refer to Appendix 02.

2.7.4.1 Remote Communication Interface Setting

Enable / Disable
ATS-PLC Remote
Communication
Baud Rate Setting

RS485 Address Setting

______________________________________________________________________________________
18
ATS-PLC Automatic Transfer Switch

2.7.5 System Parameter Setting

System Parameter Setting General Description

2.7.5.1 System Power Setting

System Power Setting

Phase Selection

CT Setting
Range : 50 ~ 6000 / 5A

______________________________________________________________________________________
19
ATS-PLC Automatic Transfer Switch

2.7.5.2 Time Delay Setting

Current Setting (Red)

Time Delay Setting

Adjustable Rang
(Black)

Attention! All time delay setting is 2 seconds per Unit.

2.7.5.3 Transfer Switch Type Setting

Transfer Switch type


Selection
Blue represents the type
Transfer Switch selected
Type Setting

Attention! When inconsistent transfer Switch is selected, may cause the ATS fails to operate.

______________________________________________________________________________________
20
ATS-PLC Automatic Transfer Switch

2.7.5.4 Scheduled Automatic Testing / Exerciser Setting

Exerciser Disabled

Attention! When Exerciser is disabled, All corresponding adjustments are omitted.

Exerciser Enabled
Day : 1 = MON, 2 = TUE

Hour : 24hrs
Exercise with / without load
Minutes : 00 to 59
Schedule Interval
Exercise Duration : 0 to 120
Range: 1 to 4 weeks
Unit : Minute

______________________________________________________________________________________
21
ATS-PLC Automatic Transfer Switch

2.7.5.5 Voltage, Frequency Protection and Voltage and Current Reading Adjustment

Normal OV/UV/OF/UF

Standby OV/UV/OF/UF General Description

Reverse Phase

Voltage and
Current Reading
Adjustment

Voltage and Current Adjustment

Load Current
Adjustment

Normal Source Standby Source


Voltage Adjustment Voltage Adjustment

______________________________________________________________________________________
22
ATS-PLC Automatic Transfer Switch

Normal Source Voltage Adjustment

Phase to Phase Phase to Neutral


Voltage Adjustment Voltage Adjustment

Attention! This screen is displayed in 3 Phase 4 Wire system voltage setting only.

2.7.5.6 Reset to Factory Setting / Default

Factory Reset
Resetting Parameters Confirmation
to Factory Default

Attention! When execute factory reset, all modified system parameters will be override to factory preset /
default setting.

______________________________________________________________________________________
23
ATS-PLC Automatic Transfer Switch

SECTION 3 : KCU-XX COMMUNICATION


MODULE SETTING The installation for the KCU-XX communication
By installing the KCU-XX modules (EX:KCU-01, module on the ATS-PLC controller is fairly simple.
KCU-02, KCU-03.... etc.) to the ATS-PLC, user can
operate or monitor the generator remotely. Step 1 : Remove slot cover from the back of
controller.
● KCU-01 – USB communication module
● KCU-02 – RS-485 communications module
● KCU-03 – Ethernet communications module

WARNING
A remote start signal can activate the
ATS-PLC and the engines can start at
anytime without warning. Place a “Danger”
warning sign next to the generator, stating
that this generator can start at anytime!” also
install a warning buzzer or a flash light.
Unexpected engine starts can result in
serious injury or death. When performing
service or maintenance, always disconnect Step 2 : Insert KCU-XX into the ATS-PLC
he remote start signal input. communication slot.

WARNING
When servicing or operating near the vicinity
of the generator, Always make sure the
remote communication setting is turned off,
to ensure the safety of the servicing
personnel nearby.

If the KCU-03 Ethernet module installed on the


ATS-PLC you can remotely monitor and operate the
ATS and generator using the IPhone and Android
mobile phones. Free App software is available for
Apple iOS5.1 system or above and android
operating system 2.3.3 or above. Free software can Step 3:Tighten the screw.
be downloaded from App Store or Google Play by
simply key in “Kutai” and hit search.

For corresponding remote communication settings


please refer to Section 2.7.4.1 and KCU-XX user
manuals and software user manuals.

WARNING
ATS-PLC with KCU-02 module constitutes a
closed LAN network. Each controller address
can be set from 1 to 99 and not to be
repeated. Same transmission rate is a must !!

______________________________________________________________________________________
24
ATS-PLC Automatic Transfer Switch

______________________________________________________________________________________
25
ATS-PLC Automatic Transfer Switch

SECTOIN 4 : SPECIFICATION AND INSTALLATION


4.1 General Specification
PARAMETER SPECIFICATION
AC Voltage Measurement Range 50 − 530 Vac 50/60 Hz
Frequency Measurement Range 40 − 75 Hz
Remote Start Contact 7A @ 250 Vac Max
Normal ON Contact 7A @ 250 Vac Max
Emergency ON Contact 7A @ 250 Vac Max
Alarm Output Contact 7A @ 250 Vac Max
Operating Temperature -20 − +70 °C
Storage Temperature -30 − +80 °C
Operating Humidity Maximum 90% relative humidity
Weight 750 g +/- 2%

4.2 Unit Dimension and Installation Reference (Unit: mm)

______________________________________________________________________________________
26
ATS-PLC Automatic Transfer Switch

SECTION 5 : TYPICAL WIRING


5.1 MCCB Type ATS Wiring Diagram (3P/4P)(220VAC) also called the BTS switch

______________________________________________________________________________________
27
ATS-PLC Automatic Transfer Switch

5.2 MCCB Type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
28
ATS-PLC Automatic Transfer Switch

5.3 MOT Type ATS Wiring Diagram (3P/4P)(220VAC) Motor Operated MCCB

______________________________________________________________________________________
29
ATS-PLC Automatic Transfer Switch

5.4 MOT Type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
30
ATS-PLC Automatic Transfer Switch

5.5 Air Circuit Breaker Type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
31
ATS-PLC Automatic Transfer Switch

5.6 Air Circuit Breaker Type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
32
ATS-PLC Automatic Transfer Switch

5.7 Single Coil Double Throw Type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
33
ATS-PLC Automatic Transfer Switch

5.8 Single Coil Double Throw Type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
34
ATS-PLC Automatic Transfer Switch

5.9 Dual Coil Double Throw Type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
35
ATS-PLC Automatic Transfer Switch

5.10 Dual Coil Double Throw Type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
36
ATS-PLC Automatic Transfer Switch

5.11 KUTAI TS-XXX Type ATS Wiring Diagram (3P/4P)(220VAC)

N3

N2
N1
BROWN CN1-1

GREEN CN1-5

WHITE CN1-9
CS1

CS1

CS1
NLS

BLACK CN1-10

BLUE CN1-6
ELS

PINK CN1-11
220V

RED CN1-2
COIL

ORANGE CN1-3
CN1 Connector
CS2

CS2

CS2

RED/WHITE CN1-12

GRAY CN1-8

YELLOW CN1-4
E3

E2
E1

______________________________________________________________________________________
37
ATS-PLC Automatic Transfer Switch

5.12 KUTAI TS-XXX Type ATS Wiring Diagram (2P)(220VAC)

N2
N1
BROWN CN1-1

WHITE CN1-9

CS1

CS1
NLS

BLACK CN1-10

BLUE CN1-6
ELS

PINK CN1-11
220V

RED CN1-2
COIL

CN1 Connector

ORANGE CN1-3
CS2

CS2

RED/WHITE CN1-12

YELLOW CN1-4
E2
E1

______________________________________________________________________________________
38
ATS-PLC Automatic Transfer Switch

5.13 KME WN Type and AICHI WN type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
39
ATS-PLC Automatic Transfer Switch

5.14 KME WN Type and AICHI WN type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
40
ATS-PLC Automatic Transfer Switch

5.15 SOCOMEC ATyS-3S type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
41
ATS-PLC Automatic Transfer Switch

5.16 SOCOMEC ATyS-3S type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
42
ATS-PLC Automatic Transfer Switch

5.17 SOCOMEC ATyS-3e type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
43
ATS-PLC Automatic Transfer Switch

5.18 SOCOMEC ATyS-3e type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
44
ATS-PLC Automatic Transfer Switch

5.19 SOCOMEC ATyS-6 type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
45
ATS-PLC Automatic Transfer Switch

5.20 SOCOMEC ATyS-6 type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
46
ATS-PLC Automatic Transfer Switch

5.21 SOCOMEC ATyS-6e type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
47
ATS-PLC Automatic Transfer Switch

5.22 SOCOMEC ATyS-6e type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
48
ATS-PLC Automatic Transfer Switch

5.23 MITSUBISHI MD type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
49
ATS-PLC Automatic Transfer Switch

5.24 MITSUBISHI MD type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
50
ATS-PLC Automatic Transfer Switch

5.25 MERLIN GERIN MCB type ATS Wiring Diagram (3P/4P)(220VAC)

______________________________________________________________________________________
51
ATS-PLC Automatic Transfer Switch

5.26 MERLIN GERIN MCB type ATS Wiring Diagram (2P)(220VAC)

______________________________________________________________________________________
52
ATS-PLC Automatic Transfer Switch

5.27 System Voltage different From AC220V wiring Diagram

______________________________________________________________________________________
53
APPENDIX 01: Touch Screen Sensitivity Calibration

* The accuracy and sensitivity is precisely adjusted in factory, unless necessary, please do not recalibrate.

Attention! Never use sharp and pointy objects when Step 4 : 2nd coordinate.
calibrating touch screen. Use standard touch panel
stylus only to prevent damage to the screen.

Step 1 : Power on controller.

Step 2 : Press and hold “Home” key for 10secs to enter


the calibration (As shown in the below illustration).

Step 5 : 3rd coordinate.

Step 3 : first coordinate will first appear in the upper


left-hand corner, aim for the center of the coordinate
and press. Total of 7 coordinates needs to be
calibrated

Step 6 : 4th coordinate.

______________________________________________________________________________________
54
ATS-PLC Automatic Transfer Switch

Step 7 : 5th coordinate. Step 10 : After all 7 coordinates are successfully


calibrated, the screen will display “Saving Calibration
Parameters” to end the sensitivity calibration.

Step 8 : 6th coordinate.

Attention! Once sensitivity calibration begins, all


coordinate must be calibrated, before system is able to
return to normal operation. If accidentally touched the
screen or inaccurate adjustment is made during
calibration, please completed the rest of calibration first
before resuming to step 1 and recalibrate.

Step 9 : 7th coordinate (last calibration).

______________________________________________________________________________________
55
APPENDIX 02: Download Start-up Screen

When powering up the ATS-PLC, the system will display a customizable start-up screen. This chapter will provide you
with the step by step instruction on how to setup customizing start-up screen.

Note 1 : The Start-up Screen picture format is limited to Step 6 : Click on “Link” and select “Connect” to connect
bmp, jpg and png files only with image size 630*390. to the KCU-01 module
The system will proportionally reduce the image size if
image size exceeds the limit.

Note 2 : To download the image from PC to ATS-PLC,


user will need to connect a KCU-01 USB
communication module (optional) to the controller.

KCU-01 USB Module

Step 7 : Select the correct COM Port.


Step 1 : Before connecting the ATS-PLC to the PC,
user must first install the “KCU-01 Modules” and
“ATS-PLC Image Transfer Software” software to the
PC. Drivers are supplied in the supplied software disk
or can be downloaded from Kutai Electronics website
www.kutai.com.tw.
Step 2 : Remove all other communication module(s)
leaving only KCU-01 module installed.

Step 8 : Click “Load Image” and select the image


wishes to upload.

Step 3 : Turn on the DC power.

Step 4 : Connect the USB cable to the KCU-01 and


PC.

Step 5 : Execute the “ATS-PLC Image Transfer


Software”.

______________________________________________________________________________________
56
ATS-PLC Automatic Transfer Switch

Step 9 : Enter Communication Setup and click on Step 12 : The controller will display the follow screen.
“ATS-PLC Communication Interface”.

Step 13 : Click on “Start” on PC screen to begin file


Step 10 : Disable ATS-PLC communication function. download.

Step 11 : Return to Communication Setup and click Step 14 : File downloading.


“Download Image”.

______________________________________________________________________________________
57
Step 15 : Downloading completed.

Step 16 : Click on “OK” to end the downloading


sequence.

Step 17 : Click on “Link” and select “Disconnect” and


remove the USB connection.

Attention! After image is downloaded (Step 15), if user


wishes to change to other image, or download image to
another controller, please remove USB connection
from PC and re-plug it again and retrace back to Step
2.