CENTRAL SYSTEM
CITY
CE400
USER INSTRUCTIONS
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
http: www.tecnocontrol.it e-mail: info@tecnocontrol.it
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 2/21
CONTENTS
Introduction ............................................................................................................... 3
Description ................................................................................................................ 3
Central System Monitoring ...................................................................................... 5
Alarms Reset..................................................................................................................................5
Sensor Details Viewing .................................................................................................................6
Enaling – Disabling Sensors.........................................................................................................6
Buzzer Setting ...............................................................................................................................6
Power Supply datas Viewing ........................................................................................................7
Auxiliary Input status Viewing ......................................................................................................7
CE400 INSTALLATION.............................................................................................. 8
Electrical connections...................................................................................................................8
Sensors Connection ............................................................................................... 11
Connection of 2-wires 4÷20mA transmitters ..............................................................................11
Connection of 3-wires 4÷20mA transmitters ..............................................................................11
Auxiliary Input and Output AUX .................................................................................................11
Connection with Normally Open contact devices 11
Auxiliary Power Supply Exit 11
Keyboard Use and General Informations ...................................................................................12
Sensors Setup .............................................................................................................................12
Delete Sensors.............................................................................................................................14
Modifying Sensors Setup............................................................................................................14
Output Setup ...............................................................................................................................15
Battery Selection..................................................................................................... 16
Code Setup (Password).......................................................................................... 16
Backlight.................................................................................................................. 16
Appendix.................................................................................................................. 17
List of anomaly messages and Alarms.......................................................................................17
List of Acoustic and Optical Signals ..........................................................................................17
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 3/21
Introduction
The CE400 gas Central System has been designed to be connected to up to 4 sensors and
represent a useful instrument for monitoring and controlling areas where there might be the
presence of flammable, toxic gases and oxygen.
ALARM
ON ENTER
FAULT
ESC
CITY
Description
The CE400 Central System, designed in a wall mount cabinet 285x230x130mm, is
composed by a front unit for the data processing with keyboard, backlighted graphic display
164x92 pixel, and by a input/output card and power supply. Power supply is 230Vac-50Hz;
the sensors are 20Vcc powerd. The cabinet of the Central System is designed to accept a
12Vcc 7Ah battery to maintain the system powered on in absence of Main power supply.
The CE400 Central System is able to manage up to 4 inputs for 4÷20mA sensors (S1, S2,
S3 ed S4); an auxiliary input for N.O. contacts (AUX) and is able to pilot up to 5 relay output
(AL1, AL2, AL3, AL4 e AUX).
To the Central System can be connected an Expansion Card ES400 to add other 4 inputs
for 4÷20mA sensors (S5, S6, S7 ed S8) and other 4 output relays (AL5, AL6, AL7 e AL8).
• The measurement range of the inputs is divided into the following indications:
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 4/21
FAULT- (<1 mA) - UNDERFLOW (from 1 to 3,5mA) - NORMal (from 3,5 to 21mA), or
PRE1, PRE2, ALLarm, (setup levels) - OVERFLOW (from 21 to 24mA) - FAULT+ (over
the 24mA).
• For each sensor three alarm levels and the fault are available and addressable to
whatever output.
Every output can be configured as follows:
- delay ON up to 250 seconds at the overcoming of the set alarm level.
- delay OFF up to 250 seconds when the input decreases below the set alarm level.
- It can have a time ON for the activation from 0 to 250 seconds, activating for the
selected time and then deactivating only after the selected time has been passed,
whatever the input value is (even if the input remain over the set elerm level).
- It can be memorized (if it has not been set any time ON), so that to stay active even if
the detector that gave the input returns under the alarm level.
- It can be setup with a positive logic (normally activated relay) or with negative logic
(relay in normal position).
• The internal Buzzer can be activated or deactivated in case an AL3 alarm or the AUX
input occur.
• Every detector can be Excluded without phisically disconnecting it from the system or
deleting it from the programm. In this case the current value read from the system about
that detector will be showed as well, with the “ “ symbol on the side of the detector
number, but there will be no activity (alarms and outputs) on that value.
• There is also the possibility (and we suggest to always use it) to protect the configuration
settings by a 4 digits “Code” (Password). To modify the Outputs Configuration, Inputs
Configuration, Code or Battery, you will always need to insert the right password.
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 5/21
Than the Central System will show the situation of the connected 1 0 % LEL NORM
detectors. The Display shows all detectors (max 8). 2 0 ppm NORM
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 6/21
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 7/21
NOTE: the central system CE400 makes a Battery functional test for a minute each 24 hours only if
the Battey has been selected “Installed”. If the Battery is down or in fault, the yellow Led will start
flashing.
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 8/21
IMPORTANT REMARK
INSTRUCTIONS CONTAINED IN THE MANUAL BELOW INCLUDE INSTALLATION AND
SYSTEM SETUP PROCEDURES TO BE EXECUTED ONLY BY QUALIFIED AND
AUTHORIZED PEOPLE.
CE400 INSTALLATION
The CE400 is a wall mount central system, it has to be fixed with 3 little blocks in the wall through the
3 holes of the metallic base of the case. We suggest you to mark and fix the central hole first, then
you can mark the other two holes keeping the central system horizontal.
To open the cover of the central system, unscrew the 4 frontal screws. Pay attention in opening the
cover because it is connected with a flat wire to the electronic board fixed on the back side. To easier
install it on the wall, disconnect the flat wire, disconnecting it from the connector. (See Fig.2).
Opening the two tongues on their external side the connector slip automatically out.
To connect it again it is necessary to slip it into the polarized connector to avoid any possibile error,
and push it till when the two tongues will close. Then fix the cover again srewing the 4 screws down.
230
95
30
130 285
255
Fig 1 – Dimensions and wall mounting template
Electrical connections
All electrical connections have to be made in the metallic base of the central system.
Mains Power Supply “230Vac” has to be connected on the power supply terminal “L, N and Ground”
(Fig.4).
The 12V 7Ah Battery (if present) has to be connected to cables “B+” (Red) and “B-” (Black) (Fig.4).
On the cisrcuit placed in the metallic base you can find all terminals for the inputs and outputs
connection. Terminals (Fig.3) have a polarized clutch (1); we suggest to use lugs adequate to the
conductors (2) and to fix the wires to the box structure to avoid excessive stress to the circuits and to
the terminals. Use a screwdriver (3) of the right dimensions.
Connection diagrams showed in Fig.5 e 6, to simplify, are always indicated with all sensors.
Inputs: keep into consideration that the Central System CE400 disposes of 4 inputs 4÷20mA only
(from S1 to S4) and 1 input for Normally Open contacts (AUX). To get other 4 inputs (from S5 to S8),
it is necessary to add the Expansion Card ES400 (On the right of the drawing). Inputs “S1, S2….etc.”
accept any 4-20mA linear current signal, coming from 2-wires or 3-wires transmitters. (See chapter
Sensors Connections). “AUX” input accepts only Normally Open contacts, free from voltage.
Output: The Central System CE400 disposes of all exchange contacts relay outputs free from
voltage. Contacts current carrying capacity is 3A at 250Vac. The Central System CE400 has 5 exits
(AUX and from AL1 to AL4), Expansion Card ES400 has other 4 exits (from AL5 to AL8).
Each relay output contacts are indicated with “C” (common), “NC” (normally closed) and “NA”
(normally open). This indication is referred to relays in “not powered” position, this means normally
deactivated = Negative Logic.
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 9/21
AUX S1 S2 S3 S4
S5 S6 S7 S8
ES400
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 10/21
Fig 5 - 2-wires transmitters series TS210E and TS220E Connection Diagram Expansion Card ES400
S5 S6 S7 S8
S1 S2 S3 S4
Auxiliary + - + - + - + -
+ - + - + - + -
Input
Terminal
AUX
+ - S + - S + - S + - S
S - + + - S + - S + - S + - S
NC NA C NC NA C NC NA C NC NA C
NC NA C NC NA C NC NA C NC NA C NC NA C
Fig 6 - 3-wires transmitters series TS210E and TS220E Connection Diagram Expansion Card ES400
S5 S6 S7 S8
S1 S2 S3 S4
Auxiliary + - S + - S + - S + - S
Input + - S + - S + - S + - S
Terminal
AUX
+ - S + - S + - S + - S
S - + + - S + - S + - S + - S
NC NA C NC NA C NC NA C NC NA C
NC NA C NC NA C NC NA C NC NA C NC NA C
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 11/21
Sensors Connection
Connection of 2-wires 4÷20mA transmitters
Connection of 2-wires 4÷20mA transmitters has to be made (Fig.5) between the “+” and “-” terminals
of the transmitter and the correspondant “+” and “S” terminals of the Central System inputs card.
The section of the connection cables between Sensors series TS210E and TS220E
sensors and central system has to be calculated in Distance Cable Type
function of the distance as indicated in the table. From 0 to 100 meters 3x0,5 mm2 Shielded
Transmitters series TS210E and TS220E need a From 100 to 200 meters 3x1 mm2 Shielded
shielded cable. The braiding has to be connected to From 200 to 500 meters 3x1,5 mm2 Shielded
the "-" of the input sensor terminal. From 500 to 1000 meters 3x2,5 mm2 Shielded
The section of the connection cables between Sensors series TS292K, TS293K and TS293P
sensors and central system has to be calculated in Distance Cable Type
function of the distance and the used sensor, as From 0 to 300 meters 3x1.5 mm2
indicated in the table. Sensors series TS292K, From 300 to 600 meters 3X2.5 mm2
TS293K and TS293P don’t need shielded cables.
Transmitters Use
PAY ATTENTION: Transmitters calibration is made with calibrated gases, sealed trimmers can be
regulated only by authorized and trained people or by our technicians using calibrated gases.
See the specific Users Instructions of the Treansmitters.
Please note that transmitters series TS292K, TS293K and TS293P for flammable gases, need a
warm-up time, in clean air, for about 20 seconds. After this time they are able to detect gases, but
they reach optimal stability after about 3 hours of continuous work, tests with sample gas should be
done after this time.
Transmitters series TS210E and TS220E reach the optimal stability conditions, in clean air, after
about 1-2 hours of continuous work.
Auxiliary Input and Output AUX
Connection with Normally Open contact devices
Connection to devices (Relay contact detectors, Smoke detectors, Normally Open buttons etc)
disposing of a “not powered” and Normally Open contact, is made (Fig.5) to “S” e “-” terminals of the
AUX input on the Central System.
Auxiliary Power Supply Exit
To the AUX terminal (between “-“ and “+”) it is also available an auxiliary output, about 12Vdc
(11÷16Vcc), for a maximum charge of 12W. Pay attention: we suggest to protect this power supply
with a fuse if the connected device doesn’t have one.
Auxiliary Exit
12Vcc / 12W
-
+
S - +
AUX Auxiliary Terminal
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 12/21
After having entered the firs sensor setup, the software is configured to propose this setup as the
standard for all others sensors, in this case, if you are entring more sensors with the same setup, all
operations will be much more easy and quick.
Sensors Setup NO SENSORS
CONFIGURED
If no sensors have been already configured, the following message
Press ESC key to
will be displaied:
configure.
Pressing the ESC key, you enter in the setup menu.
Mains ON ¯
The cancelled note symbol “ ¯
” showed on the bottom right
SETUP
position of the display shows you that the Buzzer is OFF.
Sensors
At the start-up configuration you will have access to all functions; but Exits
if you will insert a password code, at the second setup change the Battery
system will ask the access code before entering the setup. Code
Then, the minimum underflow is displayed, (the Default value is Zero ZERO : 0.00 _
which is the beginning of the scale).
press key ENTER to confirm.
Enter the overflow of the sensor you are setting up (the maximum ZERO : 0.00 _
selectable value is 9999), (See Appendix Setup 4÷20mA RANGE: _ _ _ _ _
transmitters Table), then press key ENTER
to confirm.
Example: if you are setting up a TS293Px, with the keys
you move the cusrsor and with keys and you select the
number 100.0, and then press ENTER
to confirm.
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 13/21
Select the sensor measurement unit with key , (ppm, LEL, or %), ZERO : 0.00 _
RANGE: 100.0 _
then press ENTER
to confirm. Unit: ppm
Example: if you are setting up a TS293Px, select LEL with key ,
then press ENTER
to confirm.
With the key select if the alarm is Increasing or Decreasing. This ZERO : 0.00 _
setup defines if alarms will start when the signal from the sensor RANGE : 100.0 _
increases or decreases (normally you need to select “increasing”, only Unit : LEL
for Oxygen it is necessary to choose “Decreasing” to start the alarms Alarm : Increasing
when Oxygen concentration is getting down). Press key ENTER
to
confirm.
With the key select the value of the first alarm start (AL1), tehn
Alarm 1: _ _ _ _ _ _ _
press ENTER to confirm.
Example: if you are setting up a TS293Px, select the number 6 with
the key , then press ENTER to confirm.
NOTE: a value has to be entered.
Alarm 1: 6 _ _ _
Select the value of the first alarm start (AL1), then press ENTER to Exit 1: _ _ _ _
confirm. Alarm 2: _ _ _ _
Example: if you are setting up a TS293Px, select the number 10
with the key , then press ENTER to confirm.
NOTE: a value has to be entered.
Enter, if required, the number of the relay you want to associate to the Alarm 1: 6 _ _ _
second alarm (AL2), then press ENTER to confirm. Exit 1: _ _ _ _
NOTE: this value can be omitted if not necessary. Alarm 2: 10_ _ _
Exit 2: _ _ _ _
Enter the value of the third alarm (AL3), then press ENTER to confirm. Alarm 1: 6 _ _ _
Example: if you are setting up a TS293Px, senter the number 20 Exit 1: _ _ _ _
Alarm 2: 10_ _ _
with the key , then press ENTER to confirm. Exit 2: _ _ _ _
NOTE: a value has to be entered. Alarm 3: _ _ _ _
Alarm 1: 6 _ _ _
Enter, if required, the number of the relay you want to associate to Exit 1: _ _ _ _
the third alarm (AL3), then press ENTER to confirm. Alarm 2: 10_ _ _
NOTE: this value can be omitted if not necessary. Exit 2: _ _ _ _
Alarm 3: 20_ _ _
Exit 3: _ _ _ _
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 14/21
Enter, if required, the number of the relay you want to use to give Alarm 1: 6 _ _ _
alerm for a fault (Fault), then press ENTER to confirm. Exit 1: _ _ _ _
NOTE: this value can be omitted if not necessary. Alarm 2: 10_ _ _
Exit 2: _ _ _ _
Alarm 3: 20_ _ _
Exit 3: _ _ _ _
Fault: _ _
Select “YES” with the key to confirm all information entered, then Confirm ?
press ENTER
to confirm; the system will go back to the Setup menu. NO
YES
Pressing ESC you exit from the setup menu. Pressing ENTER
you can set
a new sensor up.
Delete Sensors
To delete a sensor it is necessary to select it as described in the Confirm ?
previous chapter, then press ENTER
to scroll all informations entered till NO
you reach the final question: YES
Delete ?
Press ENTER
. Then select “YES” with the key to dolete all the
NO
informations of the selected sensor, pressing again ENTER
you confirm YES
and you go back to the Sensors Setup menu.
Press ESC to exit from the setup menu and to go back to the main
menu.
If you want simply modify some alarm settings or some outputs you can follow the procedure as for
the sensor setup described in the above paragraph.
If you want to change the sensor type it is recommended to delete first the setup of the sensor you
want to change (See Chapter Delete Sensors), then you can setup the new sensor with the new
configuration.
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 15/21
Output Setup
From the Setup menu press to select the Output menu. SETUP
Sensors
Output
Battery
Code
Pressing ENTER
it will appear:
SETUP
With the key enter the number of the output you want to setup
OUTPUT
that corresponds to the relay position on the terminals into the central Number: _
system. After having presed ENTER
to confirm, you go throught the other
parameters. Press directly ENTER
to skip a parameter that you don’t want
to use or enter the information required and press again ENTER
to
confirm.
Delay ON: it is the delay time (max 250 seconds) of the output Delay ON : _ _ _
activation from the moment when the gas concentration overpass the
alarm setting.
Delay ON : _ _ _
Delay OFF: it is the delay time (max 250 seconds) of the output
deactivation from the moment when the gas concentration returns Delay OFF : _ _ _
under the alarm setting.
Time ON: it is the time lenght (max 250 seconds) durino which Delay ON : _ _ _
the output stay active from the moment when the gas Delay OFF : _ _ _
concentration overpasses the alarm setting. When this time has Time ON :_ _ _
elapsed, the output returns to its original status even if the gas
concentration is over the alarm setting
Delay ON : _ _ _
Latched Output: it indicates if you want to keep the output
Delay OFF : _ _ _
active even if the gas concentration returns under the alarm
Time ON :_ _ _
setting. Select “NO” or “YES” pressing the key. The POS: Logic : NO
output will need to be manually deactivated by the operator. Latched Output NO:
Pay attention: this paramenter don’t has to be used if you
have setup a Time ON before, this because there will be a
conflict between the defined output activation time and the
“infinite” time represented by the latched output.
Select “YES” with the key to accept the entered settings. Pressing Confirm ?
the key ENTER you confirm and return back to the Sensors Setup menu. NO
YES
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 16/21
Battery Selection
The Central System needs to know if a Battery has been installed ot not.
This information is needed to start the automatic Battery Test Procedure, it is a one minute test and it
is made automatically once a day. If the battery is fault or doesn’t charge correctly, a yello flashing
Led starts lighting.
SETUP
From the Setup Menu press to select the Battery Menu. Sensors
Exits
Battery
Pressing ENTER it will appear: Code
BATTERY
Select Installed or Not installed with key. Then press ENTER
to Installed
confirm. Not installed
From the setup Menu press to select the Password Menu. SETUP
Sensors
Exits
Pressing ENTER
it will appear: Battery
Password
Use the keys and to digit the Password(max 4 numbers)
New
then press ENTER to confirm. From this point forward all changes will Password : _ _ _ _
be protected by a Password.
PAY ATTENTION: we suggest to write down and keep the Password in a safety place. In case
you loose the Password get in contact with out technical support.
Backlight
The display will autamaticaaly switch off, when not used, after 30 seconds; pressing any key it light
back again.
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 17/21
Appendix
List of anomaly messages and Alarms
Intermittent Buzzer One of the sensors has exceeded the alarm 3 level (AL3) or
the AUX input is active.
Symbol ¯ If on the display appears the symbol of the “cancelled Note”
(bottom right corner), it means that the Buzzer is Deactivated.
Green Led Continuosly on Mains power supply ON.
Green Led Blinking Powered by Battery; the Mains is OFF.
Red Led on One of the sensors has exceeded the alarm 3 level (AL3).
Red Led Blinking One of the sensors has exceeded the alarm 1 and 2 levels
(AL1 and AL2); or one of the Latched Output relay has been
activated.
Yellow Led Blinking Battery is fault (Voltage less than 10 Vdc).
Yellow Led on One of the sensors is FAULT+ or FAULT-.
Symbol If on the Display appears the symbol of the “Button” (bottom
right corner); it means that AUX input and output (U) are
active.
Green Led and Display OFF Mains power supply OFF, and battery has powered the
central system till it got down. If the battery voltage get down
under 10,8 Volts, it is automatically disconnected to avoid
damages.
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 18/21
PAY ATTENTION: This procedure has to be made with estreme attention and by
authorized and trained people; because starting this procedure it will start both
Outputs (relays) causing the activation of connected alarm devices and the internal
functions of the central system.
To enter into the Test Program it is necessary to disconnect the battery (if installed) and to switch off
the central system cutting the Mains voltage.
Ower on the central system pressing the key ENTER within 3 seconds, it TEST
Inputs
will appear:
Outputs
Auxiliary
Input Test (Sensors) Power Supply
Press the key to select Inputs. Then press ENTER to confirm. 1: 0164 -> 4.0 mA
All sensors values will appear, even the non configured sensors and 2: 0184 -> 4.5 mA
the sensors of the Expansion Card ES400 (from n° 5 to n° 8). The 3: 0172 -> 4.2 mA
first value is a digital control number* (0÷1024), the second is the 4: 0160 -> 3.9 mA
5: 0000 -> 0.0 mA
mA sensors value read from the central system.
6: 0000 -> 0.0 mA
* = number 0000 corresponds to 0.0mA and number 1024 to 25mA
7: 0000 -> 0.0 mA
8: 0000 -> 0.0 mA
Output test TEST
Press ESC to go back to the Test Menu. Press to select Outputs. Inputs
Outputs
Then press ENTER to confirm.
Auxiliary
From this point it starts a Test sequence that allows to activate (ON) O Alimentazione
utput Test
and deactivate (OFF) all the installed Outputs relays. Output 1 OFF
With the ENTER key you can cheange between OFF and ON and Output Test
vice versa. Output 2 OFF
The key is used to select the next test. Output Test
Output 3 OFF
OUTPUT 1 = Relay 1 (AL1)
Output Test
OUTPUT 2 = Relay 2 (AL2) Output 4 OFF
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 19/21
From this point it starts a Test sequence that allows you to activate
(ON) and deactivate (OFF) the internal functions of the central system. Output Test
Red LED OFF
Red LED
Output Test
Yellow LED Yellow LED OFF
The input will be showed as INACTIVE, closing the AUX input with AUX Input
a “bridge” (between “S” and “-“) it will be showed ACTIVE.
ESC INACTIVE
Press to go back to the Test Menu.
Confirm ?
ESC ESC
Press to go back to the Test Menu, press again and select NO
YES with the key , press ESC
to start again the normal fuctioning YES
of the central system.
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 20/21
Technical Characteristics
TECNOCONTROL S.r.l. - Via Miglioli, 97 20090 SEGRATE (MI) - Tel. +39.02.26 92 28 90 - Fax +39.02.21 33 734
IST-1400.AA01.02 CE400 “CITY” / User Instructions PAG. 21/21
Output Setup
CE400 + ES400
Output (Relay) Number U1 U2 U3 U4 AUX(U9) U5 U6 U7 U8
Delay ON (in Seconds)
Delay OFF (in Seconds)
Time ON (in Seconds)
Positive Logic (NO/YES)
Latched Output (NO/YES)
NOTE:
#--------------------------------------------------------------------------------------------------------------------------------
CODE (Password) Installation Date. Serial Number
PAY ATTENTION: we suggest to write down and store the code (max. 4 numbers)
in a safety place. In case the Code get lost, contact our Service
Dept. That will give an emergency Code.