Network Analyser Network Analyser: MPR60S / MPR60S-MPR60S / MPR60S
Network Analyser Network Analyser: MPR60S / MPR60S-MPR60S / MPR60S
Network Analyser Network Analyser: MPR60S / MPR60S-MPR60S / MPR60S
- Connected switch or circuit breaker must be marked as the disconnecting Out RS-485
1 2 3 4 5 6
device for the equipment. Enter the Net system connection type by scrolling using the
L1 L2 L3 11 12 13 14 15 16
Standards which are applied to the device: Current Measurement Inputs
The image of screen is at UP/DOWN buttons.(3P4W, ARON, 3P3W)
EN 61000-6-2, EN 61000-6-4, EN 55016-2-1, EN 55016-2-3, EN 55011, GND A B TR side while in this menu
EN 61000-3-2, EN 61000-3-3, EN 61010-1, EN 61000-4-2, EN 61000-4-3, Voltage Measurement Inputs
Analog
Out RS-485 To record the Net system connection type, press the ENTER
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11
7
L1
8
L2
9
L3
10
N
11 12 13 14 15 16
GND A B TR
button.
1A
L1
measuring all parameters in industry plants and recording these parameters to its Input 1 Input 2
_
L2
k l K L
L2
k l
K L
K L
of alarm warnings). k l
DATE
L3 L3
k l
k l
Find the SETUP menu by scrolling using the UP/DOWN buttons.
8- The existence of 3 phases can be displayed as VL1 ,VL2 ,VL3 on the
1 2 3 4 5 6 1 2 3 4 5 6
right corner of the device at any time. L1 L2 L3 L1 L2 L3 Date:
..(DD/MM/YY)
9- The values of the current and voltage total harmonics (THD) can be observed Current Measurement Inputs Current Measurement Inputs Press the ENTER button. (The Network menu is displayed) It records to its memory the measurement value assigned parameters in
on the left side of the screen.
Voltage Measurement Inputs
Analog
Out RS-485 Voltage Measurement Inputs
Analog
Out RS-485
Press the ENTER button. (CT is displayed) the Datalog Menu with date and time.For this reason, it is important to set
10- Outputs can be observed on the LCD screen to see which ones are active. 7 8 9 10 11 12 13 14 15 16 7 8 9 10 11 12 13 14 15 16
L1 L1
Press the ENTER button. (The ENERGY menu is displayed)
_ Input 1 Input 2
_
Input 1 Input 2
Max:30VDC N Max:30VDC N
Figure 2 Figure 3
Wall 79.3mm To record the new CT value, press ENTER button.
70mm
PC CONNECTION Find the SETUP menu by scrolling using the UP/DOWN buttons.
VT: (Voltage transformer ratio):
A MAX. OF 31 DEVICES CAN BE CONNECTED TO THE SAME LINE. The voltage transformer ratio can be programmed between 1,0...4000,0 Transformer
90mm
MAX. 1200 mt. RS485/RS232 or RS485/USB ratio can set in 0.1 step.
91mm
CONVERTER Please pay attention that voltage transformer ratio is entered directly instead of primary Press the ENTER button. (The Network menu is displayed)
voltage value.
B
Type 19
A PC
91mm GND VT To set the VT voltage transformer ratio; Find the Date menu by scrolling using the UP/DOWN
Type 19 (96x96) While in Instantaneous Values menu; buttons.
50mm
1. The device fits into a Type 19 square cut out (91 mm x 91 mm). TR B A GND TR B A GND TR B A GND
Press the ENTER button.
2. Remove the thumbscrews, then slide out the securing brackets from the rear panel. Press the ENTER button. (The ENERGY menu is displayed)
MPR60S-xx -31 MPR60S-xx -2 MPR60S-xx -1
3. Place the device through the panel cut-out, then slide the securing brackets
back into the slots on each side of the device. BY USING A REPEATER, 247 DEVICES CAN BE CONNECTED TO Find the SETUP menu by scrolling using the UP/DOWN buttons. Press the ENTER button.
THE SAME LINE.
4. Tighten the thumbscrews so that the securing brackets bear on the rear of the RS485/RS232 or RS485/USB
MAX. 1200 mt. MAX. 1200 mt.
panel into which the device has been placed. CONVERTER Press the ENTER button. (The Network menu is displayed)
2
5. The current and voltage connectors are designed for cables up to 2.5 mm , but B Enter the Date by scrolling using the UP/DOWN buttons.
A PC
can accept cables up to 4 mm2 GND
Press the ENTER button. (CT is displayed)
6. Category 5 cable is suggested for RS-485 input connector
... ... Find the VT Menu by scrolling using the UP/DOWN buttons.
TR
B
A
GND
Find the SETUP menu by scrolling using the UP/DOWN buttons. Find the SETUP menu by scrolling using the UP/DOWN
Press the ENTER button.(Network menu is displayed)
Press the ENTER button.(The ENERGY menu is displayed) buttons.
Press the ENTER button. (Network menu is displayed)
Find the RS-485 menu by scrolling using the UP/DOWN buttons. Press the ENTER button.(Network menu is displayed)
Find the SETUP menu by scrolling using the UP/DOWN
Find the Time menu by scrolling using the UP/DOWN buttons. buttons.
Press the ENTER button.(Addr menu is displayed)
Find the Datalog menu by scrolling using the UP/DOWN
Press the ENTER button. buttons.
Press the ENTER button.(Network menu is displayed)
Press the ENTER button. Find Prt menu by scrolling using the UP/DOWN buttons.
Find the Datalog menu by scrolling using the UP/DOWN Press the ENTER button.(Per: menu is displayed)
Enter the Time by scrolling using the UP/DOWN buttons. Press the ENTER button. buttons.
Find the Event menu by scrolling using the UP/DOWN
Enter Prt settings (None, Odd, Even) by scrolling using the UP/DOWN buttons.
To record the Time, press the ENTER button. buttons. Press the ENTER button. (Per: menu is displayed)
To record the Prt settings press the ENTER button. Press the ENTER button Press the ENTER button
NOTE: Even if the ENERGY is interrupted, Date and Time informations of
device is saved and operated during 72 hours. Enter Event (On-No) by scrolling using the UP/DOWN
Enter Per value (Off - 5...32000 sec) by scrolling using the buttons.
RS-485 UP/DOWN buttons.
RS-485 (PC Communication Settings)
Device has a MODBUS RTU communication protocol. Parameters measured by DATALOG To record Event, Press the ENTER button.
device can be transferred to a PC through the software. Using this software, all To record the Per val , press the ENTER button.
Datalog Menu
settings of device can be configured by means of PC. Event (Emergency Recording)
It is necesarry to set the Baud Rate, Address and Parity values to the device Device contains memory in order to record desired parameters with date and
in order to communicate with a PC. Note: If off is selected record off. If it is desired to record outside of the adjusted period as well,
time.Recorded parameters and the process about recording are set in the Datalog
Event : On option should be selected.
RS-485 has 3 sub-menus menu.These recordings can also be displayed on a PC screen. The memory is not
Addr: ... , Bd: ..., Prt: ...
effected from power cuts.
Addr: (Address Information)
PARAMETER TABLE
The Datalog menu has 30 sub-menus.
Addr To enter the address information, Pr1:... Pr2:... ....... Pr28:... , Per:... , Event:... *V L1, L2, L3 (Phase Voltage) Imp.(KWh) (Import Active Energy) Hr. (Hour)
while in the Instantaneous Values menu; Pr1: ... Pr2: ... ........ Pr28:... (Parameter Menus) *V L12, L23, L31 (Phase-Phase Voltage) Ind. (KVArh) (Inductive Reactive Energy) Min. (Minute)
Press the ENTER button. (The ENERGY menu is displayed) A total of 28 parameters can be assigned to these menus with one parameter per L
*V N (Average) (Total Phase Voltage Average) Cap.(KVArh) (Capacitive Reactive Energy) Sec. (Second)
each menu: These parameter values are recorded on to device memory. *V LL (Average) (Total Phase-Phase Voltages Average) *THD V% L1, L2, L3 (Total Harmonic Values for Voltages) Day (Day)
The parameters that can be see in parameter tables (See page 4). *Freq. (Hz) (Frequency) *THD I% L1, L2, L3 (Total Harmonic Values for Currents) Mo. (Month)
Find the SETUP menu by scrolling using the UP/DOWN buttons.
If no parameter is desired to be assigned to the menu, 'Off' option must be selected. *I L1, L2, L3 Year (Year)
(Phase Currents) *Max.VLN (Maximum Phase Voltages)
15000 recording can be stored in memory on the condition that the total 28 * I CTR (Current Transformer Ratio)
Press the ENTER button.(Network menu is displayed) (Total Phase Currents) *Min. VLN (Minimum Phase Voltages)
parameters from Pr 1 to Pr 28 are saved as one recording. VTR (Voltage Transformer Ratio)
*P L1, L2, L3 (W) (Active Power) *Max. Demand IL (Max. Demand of Phase Currents)
At 15001st recording, the first 1000 recordings are cleared automatically. And now, IOS (Relay Position)
*Q L1, L2, L3 (VAr) (Reactive Power *Min. Demand IL (Min. Demand of Phase Currents)
Find the RS-485 menu by scrolling using the UP/DOWN buttons. last record will be 14001th recording not 15001th recording. * In (Neutral Current)
*S L1, L2, L3 (VA) (Apparent Power) *Max. Demand I (Max. Demand of Total Phase Currents)
Note: Max. Demand W (Max. Demand of Total Active Powers)
Press the ENTER button. (The Addr menu is displayed) * P. (W) (Total Active Power) *Min. Demand I (Min. Demand of Total Phase Currents)
Whether parameters are assigned to the menu or not, the memory is separated for Max. Demand VAr (Max. Demand of Total Reactive Powers)
Press the ENTER button. * Q. (VAr) (Total Reactive Power) *Demand IL (Demand of Phase Currents)
28 parameters and for every record it allocates an area of 28 parameters. Max. Demand VA (Max. Demand of Total Apparent Powers)
* S. (VA) (Total Apparent Power) *Demand IL (Demand of Total Phase Currents) Min. Demand W (Min. Demand of Total Active Powers)
For example:
*COS jL1, L2, L3 (Displacement Power Factor) *Demand W (Demand of Total Active Powers) Min. Demand VAr (Min. Demand of Total Reactive Powers)
Enter Addr information (1..247) by scrolling using the UP/DOWN buttons.
You can find below how a parameter is assigned to (Pr 12) step by step. *PF L1, L2, L3 (Power Factor) *Demand VAr (Demand of Total Reactive Powers) Min. Demand VA (Min. Demand of Total Apparent Powers)
Pr12 To set the parameter menu, P. F (Total Power Factor) *Demand VA (Demand of Total Apparent Powers)
To record Addr information, press the ENTER button.
while in the Instantaneous Values menu; Exp.(KWh) (Export Active Energy)
Bd : (Baud Rate Value)
Bd To set the Bd value,
while in the Instantaneous Values menu; Press the ENTER button.(The ENERGY menu is displayed)
1. RELAY 1 / 2. RELAY 2
Press the ENTER button. (The ENERGY menu is displayed) 1. Relay 1 and 2. Relay 2 :
Device contains two output relays (NO Normally open). 1.Relay 1 and 2.Relay 2 are used for alarm output. Active relays can be seen on LCD.
Find the SETUP menu by scrolling using the UP/DOWN buttons.
Find the SETUP menu by scrolling using the UP/DOWN buttons.
Press the ENTER button.(Network menu is displayed)
Press the ENTER button. (The Network menu is displayed) Relay 1 is
Relay 2 is
switched on
switched on
Find the Datalog menu by scrolling using the UP/DOWN buttons.
Find the RS-485 menu by scrolling using the UP/DOWN buttons.
Find the Pr1 menu by scrolling using the UP/DOWN buttons Press the ENTER button. (The ENERGY menu is displayed) I/0 Status Register from
5-24V 4.Pulse R
max 30V Output
1 t (msec)
Press the ENTER button Find the SETUP menu by scrolling using the UP/DOWN buttons. 3.Input-1 / 4.Input-2 Dur
Bits (Duration)
0 Time
Each time the consumed energy increases by an increment of Prm, a pulse as
Enter Pr1 parameter marked with an * in the parameters table Press the ENTER button.(Network menu is displayed) long as the Dur value entered (msec) is produced in the Pulse Outputs.
by scrolling using the UP/DOWN buttons.
Find the 1. Relay1 menu by scrolling using the UP/DOWN 3.Input-1 / 4.Input-2
buttons. Find the 3. Pulse A menu by scrolling using the UP/DOWN buttons.
Dly1: (Delay value for the 1st parameter)
Input: 5-24V DC
For switching on the Relay 1, value of parameter which is assigned to this output, max. 30V DC
Press the ENTER button. (Cfg is displayed)
must exceed determined intervals and this event must continue for a time period Find Prm / Dur menu by scrolling UP/DOWN buttons. Press ENTER
Time button for selection.
which is entered at the Dly1 menu. min. 50 msec.
Find the Hi1 menu by scrolling using the UP/DOWN buttons To set the Dly 1 value, while in the Instantaneous Values menu; Latch function type operation.
Enter Prm value between 1kWh... 50.0 MWh or Dur value between
Address : H 004C 100...2500 msec by scrolling using the UP/DOWN buttons.
Press the ENTER button. (The ENERGY menu is displayed)
Press the ENTER button 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
To record Prm / Dur, press the ENTER button.
0 0 0 0 0 0 0 0 0 0 0 0 Input2 Input1 Relay2 Relay1
Find the SETUP menu by scrolling using the UP/DOWN buttons.
Enter a Hi1 value by scrolling using the UP/DOWN buttons.
(Hi1 value must be greater than Lo1 value) Input 1 and Input 2 register bits show inputs status.
4. PULSE R (only for MPR60S/MPR60S-21/41)
4. Pulse R (Inductive Reactive Energy Pulse Output)
Press the ENTER button.(Network menu is displayed) A pulse is generated from 4. Pulse R which is related with inductive value of the
To record Hi1, press the ENTER button.
3.INPUT-1/4.INPUT-2 (only for MPR60S-10/20/40) reactive energy. For example, one pulse for every increase of 10 KVArh energy.
Lo1 (Lowest value for the 1st parameter) Pulse-R has 2 sub-menus. Prm: ... , Dur: ...
Fn: Function Setting
Find the 1. Relay1 menu by scrolling using the UP/DOWN Prm: (The Value of the Inductive Reactive Energy Value to set for 1 Pulse)
It is the lowest value that the 1st parameter is desired to reach.When the measured buttons. A pulse is generated from 4. Pulse R for each increase of the Prm value by a
Press the ENTER button. (The ENERGY menu is displayed)
value is under the adjusted value, Relay 1 activates. desired amount (1kVArh... 50.0 MVArh).
Lo1 To set the Lo 1 value, while in the Instantaneous Values menu; Dur: (Pulse Duration in Miliseconds)
Press the ENTER button. (Cfg is displayed) Find the SETUP menu by scrolling using the UP/DOWN buttons. A pulse is generated for the desired duration in (100...2500 msec).
Press the ENTER button. (The ENERGY menu is displayed)
Press the ENTER button. (The ENERGY menu is displayed)
Find the Dly1 Menu by scrolling using the UP/DOWN buttons
Press the ENTER button. (Network menu is displayed)
Find the SETUP menu by scrolling using the UP/DOWN buttons.
Find the SETUP menu by scrolling using the UP/DOWN buttons.
Press the ENTER button
Find the 3. Input-1 or 4. Input-2 menu by scrolling using the
Press the ENTER button.(Network menu is displayed) UP/DOWN buttons. Press the ENTER button. (Network menu is displayed)
Enter a Dly1 value by scrolling using the UP/DOWN buttons.
Find the 1. Relay1 menu by scrolling using the UP/DOWN Press the ENTER button. (Fn menu is displayed) Find the 4. Pulse R menu by scrolling using the UP/DOWN buttons.
buttons.
To record Dly1, press the ENTER button.
Press the ENTER button.
Press the ENTER button. (Cfg is displayed) Note: Find Prm / Dur menu by scrolling UP/DOWN buttons. Press ENTER
button for selection.
The 2nd and 3rd parameter settings of Relay 1 such as Hi, Lo, Hs, Dly values can Enter a Fn value (Real time or Latch) by scrolling using the UP/DOWN
buttons.
be adjusted like the 1st parameter. Enter Prm value between 1kVAr... 50.0 MVArh or Dur value between
Find the Lo1 menu by scrolling using the UP/DOWN buttons
100...2500 msec by scrolling using the UP/DOWN buttons.
To record Fn, press the ENTER button.
To record Prm / Dur, press the ENTER button.
5 6
NETWORK ANALYSER NETWORK ANALYSER
MPR60S / MPR60S-10/20/21/40/41 MPR60S / MPR60S-10/20/21/40/41
Press the ENTER button. (The ENERGY menu is displayed) INFO TECHNICAL DATA
DISPLAY INFO: In this menu, the information about the memory of the device and the Operating Voltage (Un) : Please look behind the device.
LCD Display Settings producer are obtained. Frequency : 50/60 Hz
Press the ENTER button. (Will enter the ENERGY menu) Information menu has three sub-menus. Power Consumption : < 6 VA
In this menu, LCD display settings are configured. It has 3 sub-menus. Log.Rec..... Eng. Rec.......Producer-Production Information..... Burden : < 1 VA (Current Burden)
: < 0.5 VA (Voltage Burden)
Loop: ... , Cont: ... , BL: ...
PASSWORD Vin : 1 - 300 VAC 50/60 Hz. (L-N)
: 2 - 500 VAC (L-L)
Loop:
Energy value can be monitored by scrolling using Password Menu : (Menu for setting up a user password) Iin : 0.005 - 5.5 A~
In this menu, the duration of displaying instantaneous value is adjusted automatically, In this menu, a user password is set and activated. Measurement Ranges : 1,0...400,0 kV
while in the Instantaneous Values menu. The Loop duration can be adjusted between the UP/DOWN buttons. : 0.005...10000 A
In order to prevent the devices SETUP, DEMAND and ENERGY menus from
1... 600 in terms of seconds. unauthorized access, it is necesarry to set up a 3 digit user password and then : 0-99 999 999 kWh, kVArh or MWh, MVArh
For example; DEMAND activate it. Measurement Category
Accuracy
: CAT III
The Loop duration is set 10sec. In the Instantaneous Values menu, if any button Set Psw: (Menu for setting up a user password) Voltage, Current : 0.5%±2 digit
DEMAND To see the DEMAND Menu; While in the Instantaneous Values Menu, Active Power : 1%±2 digit
is not pressed during 10 sec, the Instantaneous values are displayed in sequence
Press the ENTER button (The ENERGY menu is displayed.) Reactive, Apparent Power : 2%±2 digit
for 10 seconds periods. Demand : It shows the averages which arise on power and current during demand
time. Voltage Transformer Ratio : 1.0 ... 4000.0
By using this function all instantaneous values can be observed one after the other Current Transformer Ratio : 1...5000
without pressing any buttons. min. value : It shows the min. value different from zero that measured on voltages.
max. value : It shows the max. value that measured on voltages. Find the SETUP Menu scrolling UP/DOWN buttons. Connection Type : 3P4W, 3P3W, ARON
This function can be cancelled by selecting No option in the Loop Menu. Relay Outputs : 2 NO, 5A 1250 VA
This is the menu in which it is possible to observe the below values; Demand Time : 15 minutes
*max. VL-N (Max. voltages between Phase-Neutral) Serial Interface : MODBUS RTU (RS 485)
*min. VL-N (Min. voltages between Phase-Neutral) Press the ENTER button (The Network menu is displayed.) Baud Rate : 1200-38400 bps
INSTANTANEOUS VALUES *max. Demand IL
*min. Demand IL
(Max. demand values of phase currents)
(Min. demand values of phase currents)
Address : 1-247
Parity : None, Even, Odd Parity
Observing the Measured Parameters *Demand IL (Demand values of phase currents)
Find the Set Psw menu by scrolling using the UP/DOWN buttons. Data Logging
In this menu, instantaneous values of parameters are displayed. *max. Demand SI and min. Demand SI (Total max. and min. demand values of phase current) Parameters to record : Choosen 28 parameters with date and time
This menu is the last menu that is reached by pressing ESC button while in any *Demand SIL (Demand value of total phase current) Record Size : 15000 record lines
menu. *Demand SP, Demand SQ and Demand SS (Demand values of total power values) Log Duration
max. Demand SP, max. Demand SQ and max. Demand SS (Max. demand values Press the ENTER button. New 000 is displayed. (time interval between 2 records) : Off, 5 - 32.000 seconds
Instantaneous values menu is the main menu of device. If you wait a while without of total powers) Energy Record : 1000 record lines (1 record in ever minutes)
pressing any buttons in any menu, the Instantaneous value menu automatically min. Demand SP, min. Demand SQ and min. Demand SS (Min. demand values Event : Yes, No
comes back. of total powers) Memory : 1 MB Internal Memory
Enter the new 3 digit password by using the UP/DOWN and ENTER Digital Inputs (2 pcs)
When a device is energized for the first time, the device is in the Instantenous values Observed minimum, maximum and demand values can be cleared one by one or buttons. (Dont enter the new password as 000) only for
Functions : Real Time / Latch
menu and shows the instantaneous values. at once. Input Pulse Width : Min. 50 ms
MPR60S-10
MPR60S-20
The display is seen as below. Press the ENTER button. The Chg Psw menu is displayed. (For cancel Operation Voltage : 5...24 V DC, max. 30 V DC MPR60S-40
ANALOG OUTPUT (only for MPR60S-20/21/40/41) the password enter as Chg Psw: 000). The new pasword is saved to
the SETUP, DEMAND and ENERGY menus.
Energy Pulse Outputs (2 pcs)
only for
Switch Period : Min. 1 sec.
Current and Voltage Analog Output: You can press the ESC button to return to instantaneous values menu. Pulse Width : 100-2500 ms MPR60S
MPR60S-21
In device, this feature gives the possiblity that observing the measured values by Chg Psw: (Menu for changing user password) Operation Current : Max. 50 mA MPR60S-41
Operation Voltage : 5-24 V DC max. 30 V DC
L3 other devices with converting these values in to 0/4-20 mA (only for MPR60S-40
Press the ENTER button (The ENERGY menu is displayed.) Analog Voltage Output : 0-10 V or 2-10 V only for
L2 and MPR60S-41) current data or 0/2-10 V (only for MPR60S-20 and MPR60S-21) Load Resistance : ³5 kW MPR60S-20
MPR60S-21
L1 voltage data. Response Perriod : 1 sec.
Find the SETUP Menu scrolling UP/DOWN buttons. Analog Current Output : 0-20 mA or 4-20 mA only for
The below parameters can be set as analog output : SETUP menu is displayed. Load Resistance : £500 W MPR60S-40
Response Perriod : 1 sec. MPR60S-41
VL1, L2, L3 (V) (Phase Voltage) PL1, L2, L3 (W) (Active Power)
VL12, L23, L31 (V) (Phase-Phase Voltage) QL1, L2, L3 (VAr) (Reactive Power) Press the ENTER button (Psw: 000 is displayed.) Ambient Temperature : -5°C; +50°C
V. LN (Average) (Average of the total phase voltages) SL1, L2, L3 (VA) (Apparent Power) Display : 3.6 LCD with Backlight
V. LL (Average) (Average of the total phase-phase voltages)
Dimensions : PR-19
I. (A) (Total Phase Currents) Equipment Protection Class : Double Insulation-Class II ( )
Frequency (Hz) (Frequency) P. (W) (Total Active Power) Enter the old 3 digit password using the UP/DOWN Box Protection Class : IP 40
IL1, L2, L3 (A) (Phase Currents)
and ENTER buttons (ie Psw:999). Terminal Block Protection Class : IP 00
Q. (VAr) (Total Reactive Power)
At the bottom of the screen, which sub-menu you are in and the instantanous values THD %VL1, L2, L3 (Total Harmonic Values for Voltages) Box Material : Non-flammable
S. (VA) (Total Apparent Power) Press the ENTER button (Network menu is displayed.) Installation : Flush mounting with rear terminals
belonging to this menu are displayed. Each bar on the left side of screen shows THD %I L1, L2, L3 (Total Harmonic Values for Currents)
the ratio between total harmonics amount of current or voltage for one phase to Wire Thickness for Voltage Connection : 2.5 mm2
Wire Thickness for Current Connection : 4.0 mm2
current or voltage in network frequency as a percentage value. Each step shows For example (only for MPR60S-40 and MPR60S-41); Wire Thickness for Pulse or
Find the Chg Psw menu by scrolling using the
10%. It is possible to switch between THD V and THD I by pressing ESC button. Below settings should be fulfilled as like : UP/DOWN buttons. Digital Input Connection : 1.5 mm2
Also, it is possible to see the numerical values of the THD values by going into the RS-485 Connection : Category 5 Cable
Type : 0-20 mA Weight : 0.75 kg
Instantaneous Values Menu. Prm (Parameter) : VL1 Press the ENTER button, previous password
(ie New: 999.) is displayed Installation Category : Class II
THD V : Total Harmonic Distortion of Voltage Lo (Low value) : 0 V Type : PR 19
THD I : Total Harmonic Distortion of Current Hi (High value) : 300 V Package Dimensions : 280x280x265 mm
Enter the new 3 digit password by using the UP/DOWN Package Weight : 6 kg
By scrolling with (UP), (DOWN) buttons while in the Instantaneous Values and ENTER buttons. (Dont enter the new password as
After above settings completed; Pcs per Package : 8 pcs
Menu, you can observe the below parameters of the network one after the other. 000)
Analog current outputs value will be 0 mA when VL1 value is 0V,
Analog current outputs value will be 20 mA when VL1 value is 300V. Press the ENTER button. The Chg Psw menu is displayed. (For cancel
- Voltage LL - Currents - - Cosj - Active (W)
When VL1 is 220 V analog current output value will be; the password enter as Chg Psw: 000). The new pasword is saved to FRONT PANEL PROPERTIES
Voltage LN P. Factor
(20-0)x(220-0) the SETUP, DEMAND and ENERGY menus. 1 .........Menu (ENTER) button.
Iout= =14,67mA You can press the ESC button to return to instantaneous values menu.
Reactive (VAr) - Apparent (VA) - SPowers - - THD V % - THD I % (300-0) 2 .........Down button.
S P.F.
For example (only for MPR60S-20 and MPR60S-21); 9 10 11 12 13 14 15 16 17 18 19 3 .........Up button.
4 .........ESC button. It is used to exit from a menu.
Freq. (Hz) - Average L
N
- Average LL - SCurrent - Neutral Current (In) Below settings should be fulfilled as like : (THD I and THD V menus are choosed)
Type : 2-10 V MPR60S Network Analyser 5 ......... Menu and Energy line. Shows the present menu. It also shows the
Prm (Parameter) : IL1 energy values.
Note : If there is a - symbol before the measured active power, it shows the Lo (Low value) : 100 mA 6 .......... Shows whether the value in the Energy Menu is Export, Import, Inductive
8 or Conductive.
existence of active export power Hi (High value) : 5 A
7 .......... Shows which Output is active.
Note : After above settings completed; 8 .......... Harmonic bars: The total harmonics of the 3 phases are displayed
When ARON connection is choosed, L2 - - - symbol is seen at the , Analog voltage outputs value will be 2 V when IL1 value is 100 mA, graphically. The columns represents L1, L2 and L3 phases. Each step
, , , , , , , Analog voltage outputs value will be 10 V when IL1 value is 5 A. 7 shows as percentage scale of 10%. V represents the voltages harmonics
, max.IL, min.IL, IL menus. and I represents the currents harmonics.
When IL1 is 3.5 A analog voltage output value will be; 20 9 .......... Shows which phase / phase - phase that the measured parameter
Note: When devices phase voltages exceed 330.0 V, phase-phase voltages exceed (10-2)x(3.5-0.1) belongs to.
530.0 V, phase currents exceed 5.500 A according to upper limits of measurement, Iout = + 2 = 7.551 V 21
10.......... Expresses that the COSj or PF (Power Factor) value of the related
(5-0.1) 6
HIGH is displayed on display. for example (only for MPR60S-40 and MPR60S-41); phase.
11 ..........Shows the direction of the value for the related phase. Capacitive
Below settings should be fulfilled as like. or Inductive. (PF, COSj and Reactive Power light up while measuring.)
ENERGY Type
Prm (Parameter)
: 0-20 mA
: PL1
12 ..........Min. and Max. symbols. They light up in the Demand menu.
13 ..........Harmonic symbols. Means that harmonics are displayed on the screen.
Observing The Energy Values: Lo (Low value) : -650 W 14 ..........Total symbol. Shows the total value of the related parameter.
In this menu, energy values are displayed and cleared.In this menu, energy values 15 ..........Phase sequence failure
can be observed which are listed below: Hi (High value) : 350 W
16 ......... Demand symbol. Shows the demand value of the related parameter.
Export Active Energy Import Active Energy 17 ......... PC Communication symbols. Shows the existence of communication
After above settings completed; on the connection line.
Inductive Reactive Energy Analog current outputs value will be 0 mA when PL1 value is -650 W, 22
18 ......... Phase existence symbols.
Capacitive Reactive Energy values Analog current outputs value will be 20 mA when PL1 value is 350 W. 19 ......... Display lines for the measured parameters and their units.
These energy values can be cleared one by one or all at once. When PL1 is -300 W analog current output value will be; (V, kV, MV, A, kA, MA, W, kW, MW, VA, kVA, MVA, VAr, kVAr, MVAr)
5 4 3 2 1 20 ......... 3.6 LCD Display
(20-0)x[-300-(-650)] A2922/Rev.6 21 ......... Backlight
Iout= = 7 mA 22 ......... Shows the units of the measured energy values (kWh, kVArh, MWh, MVArh)
[350-(-650)] ver. 1.78
8
7