Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
113 views4 pages

Network Analyser Network Analyser: MPR60S / MPR60S-MPR60S / MPR60S

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 4

NETWORK ANALYSER NETWORK ANALYSER

MPR60S / MPR60S-10/20/21/40/41 MPR60S / MPR60S-10/20/21/40/41


Net: (Type of system connection)
CORRECT USAGE and SAFETY PRECAUTIONS INSTALLATION DIAGRAM SETUP The type of system connection is set in this menu.
Failure to abide by the precautions below may result in Important note for making system connection; “Net” To set the connection type;
Setting up Device on the Network and Configuring its Settings:
SERIOUS INJURY or DEATH. First, connect the supply and voltage measurement while in the Instantaneous Values menu;
inputs. Apply energy and measurement voltage to the After connecting the device as mentioned in the user’s manual, supply energy. In order
- Cut all power before connecting the device. Press the ENTER button. (The ENERGY menu is displayed)
device. Observe the existence of three phases from for your measurement and applications to be correct, make the necesarry configurations
- Once the device is online on the network, do not remove the front panel.
in the SETUP menu.
- Do not attempt to clean the device with a solvent or another similar agent. LCD screen. indicators must be seen. Find the “SETUP” menu by scrolling using the UP/DOWN
Only a dry piece of cloth is used.. If indicator (phase sequence is not correct) is “SETUP” To enter to the “SETUP” menu, buttons.
- Check the connections. seen in addition to these indicators, cut the energy while in the Instantaneous Values menu;
- Electrical devices should be repaired only by your authorized seller. and measurement voltage and change the direction of Press the ENTER button.(The Network menu is displayed)
- The device is for panel type installation only. 2 phases. At next step, you can connect current and Press the ENTER button. (The ENERGY menu is displayed)
- The fuse used must be Type FF and the current limit value should be 1A. another connections as mentioned in the installation diagram.
- The production company or the authorized seller is not responsible for the * This box consists of 1 User Manual CD, 1 Installation Guide, 2 clamps and Press the ENTER button.(The CT menu is displayed)
consequences resulting from failure to comply with these precautions. 2 screwed clamps.
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
Warning : 3 Phase with neutral connection only for Find the “Net” menu by scrolling using the UP/DOWN buttons.
- A switch or circuit breaker must be connected between the network and the K L MPR60S-20 MPR60S-40
L1
K L MPR60S-21 MPR60S-41
auxiliary supply input of device. L2 k l
K L
k l
- Connected switch or circuit breaker must be in close proximity to the device.
L3

k l Analog Press the ENTER button.


N

- Connected switch or circuit breaker must be marked as the disconnecting Out RS-485
1 2 3 4 5 6
device for the equipment. Enter the “Net” system connection type by scrolling using the
L1 L2 L3 11 12 13 14 15 16
Standards which are applied to the device: Current Measurement Inputs
The image of screen is at UP/DOWN buttons.(3P4W, ARON, 3P3W)
EN 61000-6-2, EN 61000-6-4, EN 55016-2-1, EN 55016-2-3, EN 55011, GND A B TR side while in this menu
EN 61000-3-2, EN 61000-3-3, EN 61010-1, EN 61000-4-2, EN 61000-4-3, Voltage Measurement Inputs
Analog
Out RS-485 To record the “Net” system connection type, press the ENTER
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11
7
L1
8
L2
9
L3
10
N
11 12 13 14 15 16
GND A B TR
button.

Note: 3P4W : 3 Phase + Neutral (Star connection)


GENERAL INFORMATION 1. Relay 1 2. Relay 2 3. Input 1 4. Input 2
External
Supply
RS-485 3P3W : 3 Phase No Neutral(Delta connection)
Device, based on DSP (Digital Signal Processor), is designed for the purpose of 17 18 19 20 21 22 23 24 25 26 11 12 13 14 15 16 ARON : ARON connection
Sub-menus under the SETUP menu and what these sub-menu settings can be used

1A
L1
measuring all parameters in industry plants and recording these parameters to its Input 1 Input 2
_

Eng: (Energy Calculation)


+
Max:30VDC N GND A B TR for are explained in detail below.
memory. The measured parameters can be displayed on LCD screen which has
If “Tot” menu is selected, device measures the reactive powers of three phases.
dimension of 3.6 inch and can be read easily in dark environments by activating the Figure 1 only for

Back-Light function. Device contains a MODBUS serial interface option.


MPR60S NETWORK If total phase value is inductive, it records values to the inductive area. If total
MPR60S-10 phase value is capacitive, it records values to the reactive area.
In this menu, current transformer ratio, voltage transformer ratio and system connection If “Sprt” menu is selected, device measures the reactive powers of three phases
3. Input 1 4. Input 2 type of device are set. for each phase seperately. If phase value is in the inductive area, it records values
to the inductive reactive area. If phase values is in the capacitive area, it records
FEATURES 3. Pulse A 4. Pulse R
values to the capacitive reactive area. Measurement for each phase seperately
21 22 23 24 21 22 23 24 It has 5 sub-menus.
1- Measurements of parameters given in the parameter table can be displayed can be done for 3P4W (3 Phase with Neutral) systems.
“CT:…..”, “VT:……”, “Net:……”, “Eng:........”, “E.Unit:........”
on LCD screen.
E.Unit: (Energy Unit)
2- Current and voltage transformer ratios can be programmed. Input 1 Input 2
_ Pulse A Pulse R _
+ + CT: (Current transformer ratio) : It is used for determine the units of energy counters.
3- Parameters in 3 phase with neutral, 3 phase without neutral and Aron Max:30VDC Max:30VDC
connection systems can be measured The current transformer ratio is set in this menu. It can be programmed
Counters can be chosen Mega or Kilo.
4- Data communication with PC can be provided by using RS-485 outputs only for only for between 1...5000
MPR60S-10 MPR60S
5- Selected parameters can be recorded onto memory with date and time. for example : If energy counter value is 12345678901 kWh
MPR60S-20 MPR60S-21 “CT” To set the “CT” ratio,
6- Recorded parameters can be transferred to a PC through the software. MPR60S-40 MPR60S-41
while in the Instantaneous Values menu; when “k” is chosen, 45678901 kWh will be displayed or
7- It can assign 3 parameters each to the 1. Relay 1 and 2. Relay 2. If the
parameter values are not within the adjusted limits, the output relay 3 Phase without neutral connection 3 Phase without neutral Aron connection.
Press the ENTER button. (ENERGY is displayed) when “M” is chosen, 12345678 MWh will be displayed.
K L K L
L1
can be made to change contact (These outputs can be used for the purpose L1

L2
k l K L
L2
k l
K L
K L

of alarm warnings). k l

DATE
L3 L3
k l
k l
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
8- The existence of 3 phases can be displayed as “VL1 ,VL2 ,VL3 ” on the
1 2 3 4 5 6 1 2 3 4 5 6
right corner of the device at any time. L1 L2 L3 L1 L2 L3 Date:…..(DD/MM/YY)
9- The values of the current and voltage total harmonics (THD) can be observed Current Measurement Inputs Current Measurement Inputs Press the ENTER button. (The Network menu is displayed) It records to its memory the measurement value assigned parameters in
on the left side of the screen.
Voltage Measurement Inputs
Analog
Out RS-485 Voltage Measurement Inputs
Analog
Out RS-485
Press the ENTER button. (CT is displayed) the Datalog Menu with date and time.For this reason, it is important to set
10- Outputs can be observed on the LCD screen to see which ones are active. 7 8 9 10 11 12 13 14 15 16 7 8 9 10 11 12 13 14 15 16

11- Unauthorized access to the device’s settings can be prevented by setting


L1 L2 L3 N
GND A B TR
L1 L2 L3 N
GND A B TR the date and time correctly.
up a password from the Setup Menu. “Date” To set the date,
External External Press the ENTER button
1. Relay 1 2. Relay 2 3. Input 1 4. Input 2 Supply 1. Relay 1 2. Relay 2 3. Input 1 4. Input 2 Supply while in the Instantaneous Values menu;
DIMENSIONS 17 18 19 20 21 22 23 24 25 26 17 18 19 20 21 22 23 24 25 26
Enter the appropriate “CT” ratio (between 1.....5000) by scrolling
1A
1A

L1 L1
Press the ENTER button. (The ENERGY menu is displayed)
_ Input 1 Input 2
_
Input 1 Input 2

Panel Cut Dimensions using the UP/DOWN buttons.


+ +

Max:30VDC N Max:30VDC N

Figure 2 Figure 3
Wall 79.3mm To record the new “CT” value, press ENTER button.
70mm
PC CONNECTION Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
VT: (Voltage transformer ratio):
A MAX. OF 31 DEVICES CAN BE CONNECTED TO THE SAME LINE. The voltage transformer ratio can be programmed between 1,0...4000,0 Transformer
90mm

MAX. 1200 mt. RS485/RS232 or RS485/USB ratio can set in 0.1 step.
91mm

CONVERTER Please pay attention that voltage transformer ratio is entered directly instead of primary Press the ENTER button. (The Network menu is displayed)
voltage value.
B

Type 19
A PC
91mm GND “VT” To set the “VT” voltage transformer ratio; Find the “Date” menu by scrolling using the UP/DOWN
Type 19 (96x96) While in Instantaneous Values menu; buttons.
50mm
1. The device fits into a Type 19 square cut out (91 mm x 91 mm). TR B A GND TR B A GND TR B A GND
Press the ENTER button.
2. Remove the thumbscrews, then slide out the securing brackets from the rear panel. Press the ENTER button. (The ENERGY menu is displayed)
MPR60S-xx -31 MPR60S-xx -2 MPR60S-xx -1
3. Place the device through the panel cut-out, then slide the securing brackets
back into the slots on each side of the device. BY USING A REPEATER, 247 DEVICES CAN BE CONNECTED TO Find the “SETUP” menu by scrolling using the UP/DOWN buttons. Press the ENTER button.
THE SAME LINE.
4. Tighten the thumbscrews so that the securing brackets bear on the rear of the RS485/RS232 or RS485/USB
MAX. 1200 mt. MAX. 1200 mt.
panel into which the device has been placed. CONVERTER Press the ENTER button. (The Network menu is displayed)
2
5. The current and voltage connectors are designed for cables up to 2.5 mm , but B Enter the “Date” by scrolling using the UP/DOWN buttons.
A PC
can accept cables up to 4 mm2 GND
Press the ENTER button. (CT is displayed)
6. Category 5 cable is suggested for RS-485 input connector
... ... Find the “VT” Menu by scrolling using the UP/DOWN buttons.
TR
B
A
GND

To record the “Date”, press the ENTER button.


Excessive force can damage the device. The thumbscrews only need to be ‘finger- MPR60S-xx -2.
tight’ to hold the device in place. MPR60S-xx -247 REPEATER MPR60S-xx -31. MPR60S-xx -1. Press the ENTER button.

Enter a “VT” value (between 1.0...4000.0) by scrolling using the


Note: For 3 phase with neutral connection (Figure1) the neutral must be connected; UP/DOWN buttons.
otherwise the device will not function.
To record the “VT” value, press the ENTER button.
1 2
NETWORK ANALYSER NETWORK ANALYSER
MPR60S / MPR60S-10/20/21/40/41 MPR60S / MPR60S-10/20/21/40/41
Prt: (Parity Settings) Emergency: Power cuts, switching of one of the output relays, etc.
TIME Per: (Period Menu)
“Prt” To set the Prt settings,
Time: (Hour / Minute / Seconds) “Event” To set Event,
while in the Instantaneous Values menu; Device records data for desired time periods
while in the Instantaneous Values menu;
“Time” To set the time, Press the ENTER button. (The ENERGY menu is displayed)
while in the Instantaneous Values menu; “Per” To set time period,
Press the ENTER button. (The ENERGY menu is displayed)
Press the ENTER button. (The ENERGY menu is displayed) while in the Instantaneous Values menu;
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.

Find the “SETUP” menu by scrolling using the UP/DOWN buttons. Find the “SETUP” menu by scrolling using the UP/DOWN
Press the ENTER button.(Network menu is displayed)
Press the ENTER button.(The ENERGY menu is displayed) buttons.
Press the ENTER button. (Network menu is displayed)
Find the “RS-485” menu by scrolling using the UP/DOWN buttons. Press the ENTER button.(Network menu is displayed)
Find the “SETUP” menu by scrolling using the UP/DOWN
Find the “Time” menu by scrolling using the UP/DOWN buttons. buttons.
Press the ENTER button.(Addr menu is displayed)
Find the “Datalog” menu by scrolling using the UP/DOWN
Press the ENTER button. buttons.
Press the ENTER button.(Network menu is displayed)
Press the ENTER button. Find “Prt” menu by scrolling using the UP/DOWN buttons.
Find the “Datalog” menu by scrolling using the UP/DOWN Press the ENTER button.(Per: menu is displayed)
Enter the “Time” by scrolling using the UP/DOWN buttons. Press the ENTER button. buttons.
Find the “Event” menu by scrolling using the UP/DOWN
Enter “Prt” settings (None, Odd, Even) by scrolling using the UP/DOWN buttons.
To record the “Time”, press the ENTER button. buttons. Press the ENTER button. (Per: menu is displayed)

To record the “Prt” settings press the ENTER button. Press the ENTER button Press the ENTER button
NOTE: Even if the ENERGY is interrupted, Date and Time informations of
device is saved and operated during 72 hours. Enter “Event (On-No)” by scrolling using the UP/DOWN
Enter “Per” value (Off - 5...32000 sec) by scrolling using the buttons.
RS-485 UP/DOWN buttons.
RS-485 (PC Communication Settings)
Device has a MODBUS RTU communication protocol. Parameters measured by DATALOG To record “Event”, Press the ENTER button.
device can be transferred to a PC through the software. Using this software, all To record the “Per” val , press the ENTER button.
Datalog Menu
settings of device can be configured by means of PC. Event (Emergency Recording)
It is necesarry to set the Baud Rate, Address and Parity values to the device Device contains memory in order to record desired parameters with date and
in order to communicate with a PC. Note: If “off” is selected record off. If it is desired to record outside of the adjusted period as well,
time.Recorded parameters and the process about recording are set in the Datalog
“Event : On” option should be selected.
RS-485 has 3 sub-menus menu.These recordings can also be displayed on a PC screen. The memory is not
‘‘Addr: ...’’ , ‘‘Bd: ...’’, ‘‘Prt: ...’’
effected from power cuts.
Addr: (Address Information)
PARAMETER TABLE
The “Datalog” menu has 30 sub-menus.
“Addr” To enter the address information, “Pr1:...” “Pr2:...” ....... “Pr28:...” , “Per:..”. , “Event:...” *V L1, L2, L3 (Phase Voltage) Imp.(KWh) (Import Active Energy) Hr. (Hour)
while in the Instantaneous Values menu; “Pr1: ...” “Pr2: ...” ........ “Pr28:...” (Parameter Menus) *V L12, L23, L31 (Phase-Phase Voltage) Ind. (KVArh) (Inductive Reactive Energy) Min. (Minute)
Press the ENTER button. (The ENERGY menu is displayed) A total of 28 parameters can be assigned to these menus with one parameter per L
*V N (Average) (Total Phase Voltage Average) Cap.(KVArh) (Capacitive Reactive Energy) Sec. (Second)
each menu: These parameter values are recorded on to device memory. *V LL (Average) (Total Phase-Phase Voltages Average) *THD V% L1, L2, L3 (Total Harmonic Values for Voltages) Day (Day)
The parameters that can be see in parameter tables (See page 4). *Freq. (Hz) (Frequency) *THD I% L1, L2, L3 (Total Harmonic Values for Currents) Mo. (Month)
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
If no parameter is desired to be assigned to the menu, 'Off' option must be selected. *I L1, L2, L3 Year (Year)
(Phase Currents) *Max.VLN (Maximum Phase Voltages)
15000 recording can be stored in memory on the condition that the total 28 * I CTR (Current Transformer Ratio)
Press the ENTER button.(Network menu is displayed) (Total Phase Currents) *Min. VLN (Minimum Phase Voltages)
parameters from Pr 1 to Pr 28 are saved as one recording. VTR (Voltage Transformer Ratio)
*P L1, L2, L3 (W) (Active Power) *Max. Demand IL (Max. Demand of Phase Currents)
At 15001st recording, the first 1000 recordings are cleared automatically. And now, IOS (Relay Position)
*Q L1, L2, L3 (VAr) (Reactive Power *Min. Demand IL (Min. Demand of Phase Currents)
Find the “RS-485” menu by scrolling using the UP/DOWN buttons. last record will be 14001th recording not 15001th recording. * In (Neutral Current)
*S L1, L2, L3 (VA) (Apparent Power) *Max. Demand I (Max. Demand of Total Phase Currents)
Note: Max. Demand W (Max. Demand of Total Active Powers)
Press the ENTER button. (The Addr menu is displayed) * P. (W) (Total Active Power) *Min. Demand I (Min. Demand of Total Phase Currents)
Whether parameters are assigned to the menu or not, the memory is separated for Max. Demand VAr (Max. Demand of Total Reactive Powers)
Press the ENTER button. * Q. (VAr) (Total Reactive Power) *Demand IL (Demand of Phase Currents)
28 parameters and for every record it allocates an area of 28 parameters. Max. Demand VA (Max. Demand of Total Apparent Powers)
* S. (VA) (Total Apparent Power) *Demand IL (Demand of Total Phase Currents) Min. Demand W (Min. Demand of Total Active Powers)
For example:
*COS jL1, L2, L3 (Displacement Power Factor) *Demand W (Demand of Total Active Powers) Min. Demand VAr (Min. Demand of Total Reactive Powers)
Enter “Addr” information (1..247) by scrolling using the UP/DOWN buttons.
You can find below how a parameter is assigned to (Pr 12) step by step. *PF L1, L2, L3 (Power Factor) *Demand VAr (Demand of Total Reactive Powers) Min. Demand VA (Min. Demand of Total Apparent Powers)
“Pr12” To set the parameter menu, P. F (Total Power Factor) *Demand VA (Demand of Total Apparent Powers)
To record “Addr” information, press the ENTER button.
while in the Instantaneous Values menu; Exp.(KWh) (Export Active Energy)
Bd : (Baud Rate Value)
“Bd” To set the Bd value,
while in the Instantaneous Values menu; Press the ENTER button.(The ENERGY menu is displayed)
1. RELAY 1 / 2. RELAY 2
Press the ENTER button. (The ENERGY menu is displayed) 1. Relay 1 and 2. Relay 2 :
Device contains two output relays (NO Normally open). 1.Relay 1 and 2.Relay 2 are used for alarm output. Active relays can be seen on LCD.
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
Press the ENTER button.(Network menu is displayed)
Press the ENTER button. (The Network menu is displayed) Relay 1 is
Relay 2 is
switched on
switched on
Find the “Datalog” menu by scrolling using the UP/DOWN buttons.
Find the “RS-485” menu by scrolling using the UP/DOWN buttons.

Press the ENTER button.(Per: menu is displayed)


Press the ENTER button.(Addr menu is displayed) 1. Relay 1
3 parameters can be assigned to this output. “Hi” High and “Lo” low value desired for each selected parameter can be adjusted. If the measurement value
Find the “Pr12” menu by scrolling using the UP/DOWN buttons. of any parameter exceeds the setting value, the output relay activates
Find the “Bd” Menu by scrolling using the UP/DOWN buttons. Relay 1 has 16 sub-menus.
Press the ENTER button Cfg: By this parameter, relays can be configured as “Alarm Output” (Cfg: Alarm) or as “Digital Output” (Cfg: Dout).
Press the ENTER button. Menus of 1st Parameter
“Pr1:...”, “Hi1:...”, “Lo1:...”, “Hs1:...”, “Dly1:...”
Enter the “Pr12” parameter by scrolling using the UP/DOWN buttons. Menus of 2nd Parameter
Enter a “Bd” value (1200, 2400, 4800, 9600, 19200, 38400bps) by “Pr2:...”, “Hi2:...”, “Lo2:...”, “Hs2:...”, “Dly2:...”
scrolling using the UP/DOWN buttons. Menus of 3rd Parameter
To record the new “Pr12” parameter, press the ENTER button. “Pr3:...”, “Hi3:...”, “Lo3:...”, “Hs3:...”, “Dly3:...”
To record the “Bd” value, press the ENTER button. 4
3
NETWORK ANALYSER NETWORK ANALYSER
MPR60S / MPR60S-10/20/21/40/41 MPR60S / MPR60S-10/20/21/40/41
Pr1: (1st Parameter)
This is the menu in which the 1st parameter is assigned to the Relay 1. The Press the ENTER button
DIGITAL INPUTS (only for MPR60S-10/20/40) PULSE OUTPUTS (only for MPR60S/MPR60S-21/41)
parameters that can be set are marked with an * in parameter tables. Digital Inputs Pulse Outputs (For Energymeters)
If no parameter is desired to be assigned to the menu, “Off” option must be selected. Device has 2 pulse outputs.
Device has 2 digital inputs. User can monitor the applied voltage to the input It is possible to see which one of these outputs generate pulse from the LCD screen
“Pr1” To set Pr1, while in the Instantaneous Values menu;
Enter a “Lo1” value by scrolling using the UP/DOWN buttons. on the LCD display. at any time.
Press the ENTER button. (The ENERGY menu is displayed) Energy

To record “Lo1”, press the ENTER button. A pulse


A pulse
A pulse has been
has been
Find the “SETUP” menu by scrolling using the UP/DOWN buttons. applied to has been generated
Hs1: (Hysteresis value for the 1st parameter) 3.Input-1 applied to
from
4.Input-2
3.Pulse A
When the interval is exceeded which is limited with Hi and Lo values,for releasing
Press the ENTER button.(Network menu is displayed) Output
Relay 1 which is already switched on:
If the warning is caused due to exceeding the Hi value, it is required that the value Prm
Find the “1. Relay1” menu by scrolling using the UP/DOWN In order to configure Input-1 function, in H 0165 register on communication:
must decrease as much as Hs (hysteresis) value.
buttons. - “0” has to be entered for Real Time and t (msec)
3.Pulse A /
If the warning is caused due to becoming less than the Lo value, it is required that - “1” has to be entered for Latch. 4.Pulse R
Press the ENTER button. (Cfg is displayed) the value must increase as much as Hs (hysteresis) value. In order to configure Input-2 function, in H 0166 register on communication: A pulse
- “0” has to be entered for Real Time and
”Hs1” To set the Hs 1 value, while in the Instantaneous Values menu; has been
- “1” has to be entered for Latch. generated

Find the “Pr1” menu by scrolling using the UP/DOWN buttons Press the ENTER button. (The ENERGY menu is displayed) I/0 Status Register from
5-24V 4.Pulse R
max 30V Output
1 t (msec)
Press the ENTER button Find the “SETUP” menu by scrolling using the UP/DOWN buttons. 3.Input-1 / 4.Input-2 Dur
Bits (Duration)
0 Time
Each time the consumed energy increases by an increment of “Prm”, a pulse as
Enter “Pr1” parameter marked with an * in the parameters table Press the ENTER button.(Network menu is displayed) long as the “Dur” value entered (msec) is produced in the Pulse Outputs.
by scrolling using the UP/DOWN buttons.

Find the “1. Relay1” menu by scrolling using the UP/DOWN


3.Input-1 / 4.Input-2
3. PULSE A (only for MPR60S/MPR60S-21/41)
To record the new “Pr1”, press the ENTER button. buttons. 3. Pulse A (Import Active Energy Pulse Output)
Input: 5-24V DC
max. 30V DC A pulse is generated in 3. Pulse A proportional to the import active energy value.
Hi1: (Highest value for the 1st parameter) For example, a pulse for every increase of 10 KWh.
Press the ENTER button. (Cfg is displayed) Time
3. Pulse A has 2 sub-menus.
It is the highest value the 1st parameter is desired to reach.When the “Prm: ...” , “Dur: ...”
min. 50 msec.
measured value is over the adjusted value, Relay 1 activates. Prm: (The Value of the Import Active Energy Value to Set for 1 Pulse)
Real Time function operation A pulse is generated from 3. Pulse A output for each increase of the Prm value by
“Hi 1” To set the Hi 1 value, while in the Instantaneous Values menu; Find the “Hs1” Menu by scrolling using the UP/DOWN buttons a desired amount (1kWh... 50.0 MWh).
In order to reset input registers, which are set in latch Dur: (Pulse Duration in Miliseconds)
Press the ENTER button. (The ENERGY menu is displayed) function, “0” bit has to be written in I/0 status register. A pulse is generated for the desired duration in (100...2500 msec).
Press the ENTER button Press the ENTER button. (The ENERGY menu is displayed)
I/0 Status Register
Write “0” to I/O Status Register Bit

Find the “SETUP” menu by scrolling using the UP/DOWN buttons.


Enter a “Hs1” value by scrolling using the UP/DOWN buttons. 1
3.Input-1 / 4.Input-2
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
Bits

Press the ENTER button.(Network menu is displayed) 0 Time


To record “Hs1”, press the ENTER button. Press the ENTER button. (Network menu is displayed)

Find the “1. Relay1” menu by scrolling using the UP/DOWN 3.Input-1 / 4.Input-2

buttons. Find the “3. Pulse A” menu by scrolling using the UP/DOWN buttons.
Dly1: (Delay value for the 1st parameter)
Input: 5-24V DC
For switching on the Relay 1, value of parameter which is assigned to this output, max. 30V DC
Press the ENTER button. (Cfg is displayed)
must exceed determined intervals and this event must continue for a time period Find Prm / Dur menu by scrolling UP/DOWN buttons. Press ENTER
Time button for selection.
which is entered at the Dly1 menu. min. 50 msec.

Find the “Hi1” menu by scrolling using the UP/DOWN buttons To set the Dly 1 value, while in the Instantaneous Values menu; Latch function type operation.
Enter “Prm value between 1kWh... 50.0 MWh” or “Dur value between
Address : H 004C 100...2500 msec” by scrolling using the UP/DOWN buttons.
Press the ENTER button. (The ENERGY menu is displayed)
Press the ENTER button 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
To record “Prm / Dur”, press the ENTER button.
0 0 0 0 0 0 0 0 0 0 0 0 Input2 Input1 Relay2 Relay1
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
Enter a “Hi1” value by scrolling using the UP/DOWN buttons.
(Hi1 value must be greater than Lo1 value) Input 1 and Input 2 register bits show inputs status.
4. PULSE R (only for MPR60S/MPR60S-21/41)
4. Pulse R (Inductive Reactive Energy Pulse Output)
Press the ENTER button.(Network menu is displayed) A pulse is generated from 4. Pulse R which is related with inductive value of the
To record “Hi1”, press the ENTER button.
3.INPUT-1/4.INPUT-2 (only for MPR60S-10/20/40) reactive energy. For example, one pulse for every increase of 10 KVArh energy.
Lo1 (Lowest value for the 1st parameter) Pulse-R has 2 sub-menus. “Prm: ...” , “Dur: ...”
Fn: Function Setting
Find the “1. Relay1” menu by scrolling using the UP/DOWN Prm: (The Value of the Inductive Reactive Energy Value to set for 1 Pulse)
It is the lowest value that the 1st parameter is desired to reach.When the measured buttons. A pulse is generated from 4. Pulse R for each increase of the Prm value by a
Press the ENTER button. (The ENERGY menu is displayed)
value is under the adjusted value, Relay 1 activates. desired amount (1kVArh... 50.0 MVArh).
“Lo1” To set the Lo 1 value, while in the Instantaneous Values menu; Dur: (Pulse Duration in Miliseconds)
Press the ENTER button. (Cfg is displayed) Find the “SETUP” menu by scrolling using the UP/DOWN buttons. A pulse is generated for the desired duration in (100...2500 msec).
Press the ENTER button. (The ENERGY menu is displayed)
Press the ENTER button. (The ENERGY menu is displayed)
Find the “Dly1” Menu by scrolling using the UP/DOWN buttons
Press the ENTER button. (Network menu is displayed)
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
Find the “SETUP” menu by scrolling using the UP/DOWN buttons.
Press the ENTER button
Find the “3. Input-1” or “4. Input-2” menu by scrolling using the
Press the ENTER button.(Network menu is displayed) UP/DOWN buttons. Press the ENTER button. (Network menu is displayed)
Enter a “Dly1” value by scrolling using the UP/DOWN buttons.
Find the “1. Relay1” menu by scrolling using the UP/DOWN Press the ENTER button. (Fn menu is displayed) Find the “4. Pulse R” menu by scrolling using the UP/DOWN buttons.
buttons.
To record “Dly1”, press the ENTER button.
Press the ENTER button.
Press the ENTER button. (Cfg is displayed) Note: Find Prm / Dur menu by scrolling UP/DOWN buttons. Press ENTER
button for selection.
The 2nd and 3rd parameter settings of Relay 1 such as Hi, Lo, Hs, Dly values can Enter a “Fn” value (Real time or Latch) by scrolling using the UP/DOWN
buttons.
be adjusted like the 1st parameter. Enter “Prm value between 1kVAr... 50.0 MVArh” or “Dur value between
Find the “Lo1” menu by scrolling using the UP/DOWN buttons
100...2500 msec” by scrolling using the UP/DOWN buttons.
To record “Fn”, press the ENTER button.
To record “Prm / Dur”, press the ENTER button.
5 6
NETWORK ANALYSER NETWORK ANALYSER
MPR60S / MPR60S-10/20/21/40/41 MPR60S / MPR60S-10/20/21/40/41
Press the ENTER button. (The ENERGY menu is displayed) INFO TECHNICAL DATA
DISPLAY INFO: In this menu, the information about the memory of the device and the Operating Voltage (Un) : Please look behind the device.
LCD Display Settings producer are obtained. Frequency : 50/60 Hz
Press the ENTER button. (Will enter the ENERGY menu) Information menu has three sub-menus. Power Consumption : < 6 VA
In this menu, LCD display settings are configured. It has 3 sub-menus. Log.Rec..... Eng. Rec.......Producer-Production Information..... Burden : < 1 VA (Current Burden)
: < 0.5 VA (Voltage Burden)
“Loop: ...” , “Cont: ...” , “BL: ...”
PASSWORD Vin : 1 - 300 VAC 50/60 Hz. (L-N)
: 2 - 500 VAC (L-L)
Loop:
Energy value can be monitored by scrolling using Password Menu : (Menu for setting up a user password) Iin : 0.005 - 5.5 A~
In this menu, the duration of displaying instantaneous value is adjusted automatically, In this menu, a user password is set and activated. Measurement Ranges : 1,0...400,0 kV
while in the Instantaneous Values menu. The Loop duration can be adjusted between the UP/DOWN buttons. : 0.005...10000 A
In order to prevent the device’s SETUP, DEMAND and ENERGY menus from
1... 600 in terms of seconds. unauthorized access, it is necesarry to set up a 3 digit user password and then : 0-99 999 999 kWh, kVArh or MWh, MVArh
For example; DEMAND activate it. Measurement Category
Accuracy
: CAT III
The Loop duration is set 10sec. In the Instantaneous Values menu, if any button Set Psw: (Menu for setting up a user password) Voltage, Current : 0.5%±2 digit
“DEMAND” To see the DEMAND Menu; While in the Instantaneous Values Menu, Active Power : 1%±2 digit
is not pressed during 10 sec, the Instantaneous values are displayed in sequence
Press the ENTER button (The ENERGY menu is displayed.) Reactive, Apparent Power : 2%±2 digit
for 10 seconds periods. Demand : It shows the averages which arise on power and current during demand
time. Voltage Transformer Ratio : 1.0 ... 4000.0
By using this function all instantaneous values can be observed one after the other Current Transformer Ratio : 1...5000
without pressing any buttons. min. value : It shows the min. value different from zero that measured on voltages.
max. value : It shows the max. value that measured on voltages. Find the “SETUP” Menu scrolling UP/DOWN buttons. Connection Type : 3P4W, 3P3W, ARON
This function can be cancelled by selecting “No” option in the Loop Menu. Relay Outputs : 2 NO, 5A 1250 VA
This is the menu in which it is possible to observe the below values; Demand Time : 15 minutes
*max. VL-N (Max. voltages between Phase-Neutral) Serial Interface : MODBUS RTU (RS 485)
*min. VL-N (Min. voltages between Phase-Neutral) Press the ENTER button (The Network menu is displayed.) Baud Rate : 1200-38400 bps
INSTANTANEOUS VALUES *max. Demand IL
*min. Demand IL
(Max. demand values of phase currents)
(Min. demand values of phase currents)
Address : 1-247
Parity : None, Even, Odd Parity
Observing the Measured Parameters *Demand IL (Demand values of phase currents)
Find the “Set Psw” menu by scrolling using the UP/DOWN buttons. Data Logging
In this menu, instantaneous values of parameters are displayed. *max. Demand SI and min. Demand SI (Total max. and min. demand values of phase current) Parameters to record : Choosen 28 parameters with date and time
This menu is the last menu that is reached by pressing ESC button while in any *Demand SIL (Demand value of total phase current) Record Size : 15000 record lines
menu. *Demand SP, Demand SQ and Demand SS (Demand values of total power values) Log Duration
max. Demand SP, max. Demand SQ and max. Demand SS (Max. demand values Press the ENTER button. ‘‘New 000’’ is displayed. (time interval between 2 records) : Off, 5 - 32.000 seconds
Instantaneous values menu is the main menu of device. If you wait a while without of total powers) Energy Record : 1000 record lines (1 record in ever minutes)
pressing any buttons in any menu, the Instantaneous value menu automatically min. Demand SP, min. Demand SQ and min. Demand SS (Min. demand values Event : Yes, No
comes back. of total powers) Memory : 1 MB Internal Memory
Enter the new 3 digit password by using the UP/DOWN and ENTER Digital Inputs (2 pcs)
When a device is energized for the first time, the device is in the Instantenous values Observed minimum, maximum and demand values can be cleared one by one or buttons. (Don’t enter the new password as 000) only for
Functions : Real Time / Latch
menu and shows the instantaneous values. at once. Input Pulse Width : Min. 50 ms
MPR60S-10
MPR60S-20
The display is seen as below. Press the ENTER button. The Chg Psw menu is displayed. (For cancel Operation Voltage : 5...24 V DC, max. 30 V DC MPR60S-40
ANALOG OUTPUT (only for MPR60S-20/21/40/41) the password enter as Chg Psw: 000). The new pasword is saved to
the SETUP, DEMAND and ENERGY menus.
Energy Pulse Outputs (2 pcs)
only for
Switch Period : Min. 1 sec.
Current and Voltage Analog Output: You can press the ESC button to return to instantaneous values menu. Pulse Width : 100-2500 ms MPR60S
MPR60S-21
In device, this feature gives the possiblity that observing the measured values by Chg Psw: (Menu for changing user password) Operation Current : Max. 50 mA MPR60S-41
Operation Voltage : 5-24 V DC max. 30 V DC
L3 other devices with converting these values in to 0/4-20 mA (only for MPR60S-40
Press the ENTER button (The ENERGY menu is displayed.) Analog Voltage Output : 0-10 V or 2-10 V only for
L2 and MPR60S-41) current data or 0/2-10 V (only for MPR60S-20 and MPR60S-21) Load Resistance : ³5 kW MPR60S-20
MPR60S-21
L1 voltage data. Response Perriod : 1 sec.
Find the “SETUP” Menu scrolling UP/DOWN buttons. Analog Current Output : 0-20 mA or 4-20 mA only for
The below parameters can be set as analog output : “SETUP “ menu is displayed. Load Resistance : £500 W MPR60S-40
Response Perriod : 1 sec. MPR60S-41
VL1, L2, L3 (V) (Phase Voltage) PL1, L2, L3 (W) (Active Power)
VL12, L23, L31 (V) (Phase-Phase Voltage) QL1, L2, L3 (VAr) (Reactive Power) Press the ENTER button (Psw: 000 is displayed.) Ambient Temperature : -5°C; +50°C
V. LN (Average) (Average of the total phase voltages) SL1, L2, L3 (VA) (Apparent Power) Display : 3.6” LCD with Backlight
V. LL (Average) (Average of the total phase-phase voltages)
Dimensions : PR-19
I. (A) (Total Phase Currents) Equipment Protection Class : Double Insulation-Class II ( )
Frequency (Hz) (Frequency) P. (W) (Total Active Power) Enter the old 3 digit password using the UP/DOWN Box Protection Class : IP 40
IL1, L2, L3 (A) (Phase Currents)
and ENTER buttons (ie Psw:999). Terminal Block Protection Class : IP 00
Q. (VAr) (Total Reactive Power)
At the bottom of the screen, which sub-menu you are in and the instantanous values THD %VL1, L2, L3 (Total Harmonic Values for Voltages) Box Material : Non-flammable
S. (VA) (Total Apparent Power) Press the ENTER button (Network menu is displayed.) Installation : Flush mounting with rear terminals
belonging to this menu are displayed. Each bar on the left side of screen shows THD %I L1, L2, L3 (Total Harmonic Values for Currents)
the ratio between total harmonics amount of current or voltage for one phase to Wire Thickness for Voltage Connection : 2.5 mm2
Wire Thickness for Current Connection : 4.0 mm2
current or voltage in network frequency as a percentage value. Each step shows For example (only for MPR60S-40 and MPR60S-41); Wire Thickness for Pulse or
Find the “Chg Psw” menu by scrolling using the
10%. It is possible to switch between “THD V” and “THD I” by pressing ESC button. Below settings should be fulfilled as like : UP/DOWN buttons. Digital Input Connection : 1.5 mm2
Also, it is possible to see the numerical values of the THD values by going into the RS-485 Connection : Category 5 Cable
Type : 0-20 mA Weight : 0.75 kg
Instantaneous Values Menu. Prm (Parameter) : VL1 Press the ENTER button, previous password
(ie New: 999.) is displayed Installation Category : Class II
THD V : Total Harmonic Distortion of Voltage Lo (Low value) : 0 V Type : PR 19
THD I : Total Harmonic Distortion of Current Hi (High value) : 300 V Package Dimensions : 280x280x265 mm
Enter the new 3 digit password by using the UP/DOWN Package Weight : 6 kg
By scrolling with (UP), (DOWN) buttons while in the Instantaneous Values and ENTER buttons. (Don’t enter the new password as
After above settings completed; Pcs per Package : 8 pcs
Menu, you can observe the below parameters of the network one after the other. 000)
Analog current output’s value will be 0 mA when VL1 value is 0V,
Analog current output’s value will be 20 mA when VL1 value is 300V. Press the ENTER button. The Chg Psw menu is displayed. (For cancel
- Voltage LL - Currents - - Cosj - Active (W)
When VL1 is 220 V analog current output value will be; the password enter as Chg Psw: 000). The new pasword is saved to FRONT PANEL PROPERTIES
Voltage LN P. Factor
(20-0)x(220-0) the SETUP, DEMAND and ENERGY menus. 1 .........Menu (ENTER) button.
Iout= =14,67mA You can press the ESC button to return to instantaneous values menu.
Reactive (VAr) - Apparent (VA) - SPowers - - THD V % - THD I % (300-0) 2 .........Down button.
S P.F.
For example (only for MPR60S-20 and MPR60S-21); 9 10 11 12 13 14 15 16 17 18 19 3 .........Up button.
4 .........ESC button. It is used to exit from a menu.
Freq. (Hz) - Average L
N
- Average LL - SCurrent - Neutral Current (In) Below settings should be fulfilled as like : (THD I and THD V menus are choosed)
Type : 2-10 V MPR60S Network Analyser 5 ......... Menu and Energy line. Shows the present menu. It also shows the
Prm (Parameter) : IL1 energy values.
Note : If there is a “-” symbol before the measured active power, it shows the Lo (Low value) : 100 mA 6 .......... Shows whether the value in the Energy Menu is Export, Import, Inductive
8 or Conductive.
existence of active export power Hi (High value) : 5 A
7 .......... Shows which Output is active.
Note : After above settings completed; 8 .......... Harmonic bars: The total harmonics of the 3 phases are displayed
When ARON connection is choosed, “L2 - - -” symbol is seen at the , Analog voltage output’s value will be 2 V when IL1 value is 100 mA, graphically. The columns represents L1, L2 and L3 phases. Each step
, , , , , , , Analog voltage output’s value will be 10 V when IL1 value is 5 A. 7 shows as percentage scale of 10%. V represents the voltages’ harmonics
, max.IL, min.IL, IL menus. and I represents the currents’ harmonics.
When IL1 is 3.5 A analog voltage output value will be; 20 9 .......... Shows which phase / phase - phase that the measured parameter
Note: When device’s phase voltages exceed 330.0 V, phase-phase voltages exceed (10-2)x(3.5-0.1) belongs to.
530.0 V, phase currents exceed 5.500 A according to upper limits of measurement, Iout = + 2 = 7.551 V 21
10.......... Expresses that the COSj or PF (Power Factor) value of the related
(5-0.1) 6
“HIGH” is displayed on display. for example (only for MPR60S-40 and MPR60S-41); phase.
11 ..........Shows the direction of the value for the related phase. Capacitive
Below settings should be fulfilled as like. or Inductive. (PF, COSj and Reactive Power light up while measuring.)
ENERGY Type
Prm (Parameter)
: 0-20 mA
: PL1
12 ..........Min. and Max. symbols. They light up in the Demand menu.
13 ..........Harmonic symbols. Means that harmonics are displayed on the screen.
Observing The Energy Values: Lo (Low value) : -650 W 14 ..........Total symbol. Shows the total value of the related parameter.
In this menu, energy values are displayed and cleared.In this menu, energy values 15 ..........Phase sequence failure
can be observed which are listed below: Hi (High value) : 350 W
16 ......... Demand symbol. Shows the demand value of the related parameter.
Export Active Energy Import Active Energy 17 ......... PC Communication symbols. Shows the existence of communication
After above settings completed; on the connection line.
Inductive Reactive Energy Analog current output’s value will be 0 mA when PL1 value is -650 W, 22
18 ......... Phase existence symbols.
Capacitive Reactive Energy values Analog current output’s value will be 20 mA when PL1 value is 350 W. 19 ......... Display lines for the measured parameters and their units.
These energy values can be cleared one by one or all at once. When PL1 is -300 W analog current output value will be; (V, kV, MV, A, kA, MA, W, kW, MW, VA, kVA, MVA, VAr, kVAr, MVAr)
5 4 3 2 1 20 ......... 3.6’’ LCD Display
(20-0)x[-300-(-650)] A2922/Rev.6 21 ......... Backlight
Iout= = 7 mA 22 ......... Shows the units of the measured energy values (kWh, kVArh, MWh, MVArh)
[350-(-650)] ver. 1.78
8
7

You might also like