ACS 753 - ACS 763 - ACS 863: A/C Service Unit
ACS 753 - ACS 763 - ACS 863: A/C Service Unit
ACS 753 - ACS 763 - ACS 863: A/C Service Unit
en Repair instruction
A/C Service Unit
ACS 753, ACS 763, ACS 863 Service Manual
Table of Contents
Safety Warnings.................................................................................................... 4
Introduction........................................................................................................... 8
Introduction......................................................................................................................... 9
Unit Specifications........................................................................................................... 20
Maintenance Schedule..................................................................................................... 22
Diagnostics and Testing..................................................................................... 23
Functional Check.............................................................................................................. 24
Diagnostics and Testing.................................................................................................. 28
Depressurizing the Unit................................................................................................... 40
Troubleshooting............................................................................................................... 41
Error Messages................................................................................................................. 54
Electrical System Operation and Repair........................................................... 57
Electrical System Operation............................................................................................ 58
Electrical System Repair.................................................................................................. 65
Plumbing and Mechanical System Operation and Repair............................... 72
Plumbing and Mechanical System Operation................................................................ 73
Plumbing and Mechanical System Repair..................................................................... 75
Component Application Charts....................................................................................... 85
Flow Diagrams.................................................................................................................. 87
Main Component Descriptions........................................................................ 106
Notes .................................................................................................................. 109
Safety Warnings
Explanation of Safety Signal Words Used in this Manual
DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury.
CAUTION: Used without the safety alert symbol indicates a potentially hazardous situation which,
if not avoided, may result in property damage.
These safety messages cover situations Bosch is aware of. Bosch cannot know, evaluate, or
advise you as to all possible hazards. You must verify that conditions and procedures do not
jeopardize your personal safety.
Wear gloves.
Alternating voltage.
Grounding protection.
USE THE MACHINE AS OUTLINED IN THIS MANUAL. Using the machine in a manner for
which it was not designed will compromise the machine and nullify the protections provided.
TO REDUCE THE RISK OF FIRE, do not use the machine in the vicinity of spilled or open
containers of gasoline or other flammable substances.
TO REDUCE THE RISK OF FIRE, do not use an extension cord. An extension cord may
overheat and cause fire. If you must use an extension cord, use the shortest possible cord
with a minimum size of 14 AWG.
TO REDUCE THE RISK OF FIRE, do not use the machine in the vicinity of flames and
hot surfaces. Refrigerant decomposes at high temperatures, freeing toxic substances to
the environment which are noxious to the user.
TO REDUCE THE RISK OF FIRE, do not use the machine in environments containing
explosive gases or vapors.
TO REDUCE THE RISK OF FIRE, Do not use this machine in ATEX classified zones
or areas. Protect the machine from conditions that may cause electrical failure or other
hazards relating to ambient interaction.
DO NOT USE COMPRESSED AIR TO PRESSURE TEST OR LEAK TEST THE MACHINE
OR VEHICLE AIR CONDITIONING SYSTEM. Mixtures of air and refrigerant can be
combustible at elevated pressures. These mixtures are potentially dangerous and may
result in fire or explosion causing personal injury and/or property damage.
NOTE (R1234yf only): To minimize the risk of ignition, the unit software guided leak check is pe-
riodically performed otherwise the unit will lock. For same purpose, also hardware features such
as ventilation fan monitoring system, suitably located vents on cart bottom (R1234yf is heavier
than air) and sealed power switching circuits are present.
CAUTION: The machine is not intended to operate with oils classified as flammable
or hazardous according to EN 1272/2008 (CLP).
DO NOT USE THIS MACHINE OUTDOORS DURING RAIN OR HIGH HUMIDITY. Protect
the machine from conditions that may cause electrical failure or other hazards relating to
ambient interaction.
DO NOT USE THIS MACHINE IN DIRECT SUNLIGHT. Position the machine far from heat
sources, such as direct sunlight which can cause excessive temperatures. The use of this
machine under normal environmental conditions (10°C to 50°C) keeps pressures under
reasonable limits. Make sure the machine does not exceed the operating temperature
indicated on the technical data plate.
Place the station on a flat surface and in sufficient lighting conditions; lock the front wheels
and do not subject them to vibration.
Further information regarding health and safety may be obtained from the refrigerant
manufacturer.
SP00D00609 2018-03-26 6 Robert Bosch GmbH
ACS 753, ACS 763, ACS 863 Service Manual
Protective devices
The machine is equipped with the following protective devices:
• Over pressure valves.
• A maximum pressure switch stops the compressor when excessive pressure is sensed.
WARNING: Tampering with these protective devices could result in serious injury.
WARNING: Do not modify the pressure relief valve or change the control system
settings. Using the machine in a manner for which it was not designed will compromise
the machine and nullify the protections provided.
CAUTION: Check always the pressure gauges values to ensure that pressures are
maintained within the limits specified in the “Unit specifications” section.
Door switch
Door switch on service rear door disconnects electrical power to the unit when opened.
WARNING: Do not tamper the interlock switch. During normal operation, the rear
service door must always be closed and the above panel in place.
Machine handling
The unit should normally be moved on flat surfaces with a maximum slope of 15 ° and on the four
wheels, avoiding excessive shaking. When stopped then the brake on the front wheels must be
inserted. On slightly irregular surfaces, the unit can be moved by keeping it slightly inclined and
grounded on the two rear wheels by making sure to have a firm grip on the rear handle.
CAUTION: Although heavier components of the unit are installed on the bottom of
the unit in order to lower as much as possible the center of gravity, it’s however not
completely removed the risk of overturning.
I n troducti o n
Introduction..........................................................................................................9
Control Panel Functions................................................................................................. 10
Icon Legend..................................................................................................................... 10
Glossary........................................................................................................................... 11
Setup Menu...................................................................................................................... 11
General Maintenance...................................................................................................... 14
Electrical Protection........................................................................................................ 14
Tank Fill............................................................................................................................ 14
Filter Maintenance........................................................................................................... 15
Internal Refrigerent Identifier Maintenance (ACS 863 only)V��������������������������������������� 16
Vacuum Pump Maintenance........................................................................................... 16
Edit Print Header............................................................................................................. 17
Replace Printer Paper..................................................................................................... 17
Calibration Check............................................................................................................ 18
Scales Reset.................................................................................................................... 18
Pressure Decay Leak Test (R1234yf only)..................................................................... 19
Lockout............................................................................................................................. 19
Unit Specifications.............................................................................................20
Maintenance Schedule.......................................................................................22
Introduction
These units are designed to be compatible with existing service equipment and standard service
procedures. These machines utilize a single-pass system that meets specifications for recycled
refrigerant. Follow recommended service procedures for the containment of refrigerant.
Each unit includes a high-vacuum pump for fast, thorough evacuation. The compressor first pulls
the A/C system to -0.4 bar; the compressor then works with the vacuum pump to pull a vacuum
to an absolute pressure of less than 1.0 bar.
NOTE: Refrigerant systems require special oils. Refer to the A/C system manufacturer’s service
manual for oil specifications.
1 23
abc
def
ghi
15
jkl
mno
pqrs
tuv
wxyz
14
16
13 4 23 17
12 18
11 5
10 19
9 6
20
7
8
21
22
Figure 1-1. Description of machine
1. Gauge low pressure (LP) 15. N2H2 or N2 inlet port max 14 bar (1.4 MPa)
2. Visual alert 16. Flush port (high pressure*)
3. Gauge high pressure (HP) 17. Flush port (low pressure*)
4. 2 x USB 2.0 slot 18. Service hose port (high pressure*)
5. Identifier Filter 19. Service hose port (low pressure*)
(ACS 863 only) 20. Contaminant recovery outlet port
6. Master switch (ACS 863 only)
7. Circuit breaker 21. Front wheels with locking brake
8. Power supply socket 22. Rear wheels
9. UV dye bottle 23. Hoses wraping support
10. Fresh oil bottle 2 (POE) (*) max 25 bar (2.5 MPa)
11. Fresh oil bottle 1 (PAG)
12. Used oil bottle
13. Printer
14. Display and control panel (HMI)
3.544 kg
ARROW UP moves selection of a Refrigerant
7.34 bar
• The machine displays amount of filter ca- Model Replacement filter at: 150 kg
pacity remaining until the machine locks R1234yf (alert 138 kg)
down. This message may occur at anytime
during the course of an A/C system main-
tenance action.
5. Select OK icon to change the filter; Select
ESC icon to resume using the machine.
Replace the Filter
1. If OK icon was selected to change the filter,
the unit will clear the filter, then prompts for
the new filter code to be entered: 1
ENTER NEW FILTER SERIAL NUMBER
NOTE: If SERIAL NUMBER WRONG is
displayed, the serial number has been incorrectly
entered or the filter has already been used in this
machine. Figure 1-4. Filter Location
2. Use the keypad to enter the serial number
that appears on the new filter and select OK O-rings
icon to continue.
• The machine clears the existing filter and
displays:
TURN POWER OFF
AND REPLACE FILTER Figure 1-5. O-ring Location
every 10 days (for R1234yf only). 1. Turn the Lockout lever (1) counterclockwise
1. Follow the on-screen prompts to connect (CCW).
the hose service couplers to the storage 2. Insert a padlock or other item through the
connectors on the side of the machine. aligned holes so the lever cannot be turned
Open the hose couplers by turning the col- clockwise (CW) to start the machine.
lars clockwise.
2. Select OK icon to start the test.
3. The machine performs a self-recovery and 1
displays:
RECOVER IN PROGRESS
4. The machine performs a 30-second vacuum
test and displays:
VACUUM CHECK IN PROGRESS
• If the vacuum test fails, the machine will
prompt to check for leaks.
5. Once the machine passes the vacuum test, Figure 1-10. Lockout
a controlled pressure is applied to its internal
components. The machine displays:
PRESSURE CHECK IN PROGRESS
6. Pressure is held for five minutes and moni-
tored for decay. Minutes and seconds count
down on the display.
• If an acceptable pressure decay is de-
tected, the machine recovers refrigerant
and returns to the Functions Menu, ready
for normal operation.
• If an unacceptable pressure decay is de-
tected, the machine will prompt to check for
leaks. Take the machine to an authorized
service center for repair.
UNIT SPECIFICATIONS
ACS 763 ACS 863 ACS 753
Refrigerant R1234yf R1234yf R134a
ISV total capacity (water 22 l 22 l 22 l
capacity)
Internal Vessel Maximum 19.655 kg of R1234yf 19.655 kg of R1234yf 21.671 kg of R134a
Storage Capacity (kg of (17.4 kg manageable (17.4 kg manageable (19.4 kg manageable
refrigerant) by operator) by operator) by operator)
Fluid Maximum Working 25 bar (2.5 Mpa) 25 bar (2.5 Mpa) 25 bar (2.5 Mpa)
Pressure (PS)
Fluid Operating Tempera- -10 °C ÷ +120 °C -10 °C ÷ +120 °C -10 °C ÷ +120 °C
ture Range (TS)
Maximum Recovery Speed - - -
(liquid phase)
Overall Leak Rate <80g/year <80g/year <80g/year
Power Supply 230 Vac/1 50/60 Hz 230 Vac/1 50/60 Hz 230 Vac/1 50/60 Hz
Overvoltage category II II II
Power Consumption 1100 W 1100 W 1100 W
Unit Storage Temperature -20 °C ÷ +60 °C -20 °C ÷ +60 °C -20 °C ÷ +60 °C
Range
Unit Operating Tempera- +10 °C ÷ +50 °C +10 °C ÷ +50 °C +10 °C ÷ +50 °C
ture Range
Humidity (non-condensing) 32.2°C (90°F), 86% 32.2°C (90°F), 86% 3°C (90°F), 86% RH
RH RH
Maximum Altitude 2000 m (6561.66 ft) 2000 m (6561.66 ft) 2000 m (6561.66 ft)
IP Protection Rating IP20 IP20 IP20
Pollution dregree 2 2 2
Noise <70 dB(A) <70 dB(A) <70 dB(A)
Dimensions 105 x 75 x 77 cm 105 x 75 x 77 cm 105 x 75 x 77 cm
with HMI on shipping with HMI on shipping with HMI on shipping
position position position
Weight 112 kg 112 kg 112 kg
(empty tank + accessories)
Display 7in. TFT WVGA 7in. TFT WVGA 7in. TFT WVGA
(800x480) color LCD (800x480) color LCD (800x480) color LCD
with LED backlight with LED backlight with LED backlight
Filter 700 cc dessicant 700 cc dessicant 700 cc dessicant
Manometer Ø 100 mm Ø 100 mm Ø 100 mm
EN 837-1 Class 1 EN 837-1 Class 1 EN 837-1 Class 1
Bottles (Oils and Dye) 3 x 250 ml 3 x 250 ml 3 x 250 ml
sealed sealed sealed
Service hoses 250 cm / SAE J2888 250 cm / SAE J2888 250 cm / SAE J639
Quick Couplers For R1234yf, For R1234yf, For R134a,
SAE J2888 SAE J2888 SAE J639
MAINTENANCE SCHEDULE
MAINTENANCE TASK RECOMMENDED INTERVAL
After (SEE TABLE) of refrigerant has
been filtered. Refer to Filter Change in the
Maintenance section of this manual.
Due to normal wear and tear, these units require regular maintenance to ensure safe operation
and optimum performance. The above chart provides a schedule of the minimum recommended
maintenance tasks.
FUNCTIONAL CHECK
Prior to performing a functional or diagnostic 14. The unit will go through a file updating pe-
check, make sure the software version is riod (it can take several minutes) to finalize
current. This is especially true if the control the entire update procedure, then will dis-
and/or power boards have been replaced. If play the Main Menu.
the software version is not current, corrupt, Install Current Software with WiFi
or unknown, follow the procedure in Updating Once WiFi connection has been established
System Software Instruction. select Wi-Fi Update (Call up the Main Menu and
Updating System Software Instruction select Next " Menu " Settings " Firmware
update " Wi-Fi Update).
To upgrade the firmware through a USB stick 1. Manual path:
or via WiFi (see Firmware update in the Setup Select Wi-Fi Update and check the new
Menu function section). software availability then select HELP
Download and install current Software icon to look into release note or OK icon
with USB stick to start the update procedure that is
Equipment Requirements: composed by the following steps:
(1) USB stick • Downloading compressed software pack-
This item may be purchased from most retail age.
office supply/electronics stores or from any • Decrypt the software package and vali-
online retailer that carries computer accessories. date it to be sure that is a not corrupted.
In case of Firmware update with USB stick • Decompress the content.
follow the instruction: • Install all new files.
• Request user to reboot unit and complete
1. Insert the USB stick to your computer. the install procedure.
2. Format as FAT32. • When the unit reboot confirm the instal-
3. Download the current software from: lation procedure by press <Yes> button
\EDIS\software\systemsw\acs6xx_7xx\. when the bootloader black and white
4. Put the zip package as is into the root folder screen is shown.
of the USB stick. • The unit will go through a file updating
5. Insert the USB stick into the USB port on period (it can take several minutes) to
the unit. finalize the entire update procedure, then
6. Turn ON the unit. will display the Main Menu.
7. Call up the Main Menu. 2. Automatic path:
8. Select NEXT icon. After the connection to internet network is
9. Select MENU icon. available, when the ACS unit is switched
10. Select Settings " Firmware update and on, it’s automatically connect to the same
USB Update. network and immediately (before to show
11. Allow the unit to install the software com- the Main Menu) it will search for new soft-
pletely and then remove the USB stick, this ware is available of not, if yes it will show
operation may requires several minutes. a message to process as above (point 1).
12. Wait the screen that ask to reboot the unit at
the end of the update process and so recyle
the unit power.
13. When the unit reboot confirm the installation
procedure by press <Yes> button when the
bootloader black and white screen is shown.
NOTE: Refer to Scale Calibration at 11. 2 th stage recovery. Unit perform special
Replacement Scale Assembly/Magnet in the deep recovery function where pump and
Electrical section, if necessary. compressor are working togheter to intake all
refrigerant small parts still in the A/C vehicle
The Recover and Charge function tests must be system. Deep recover min tiem is 5 minutes.
performed sequentially, in the order presented Then Oil drain process to evacuate the
here. accumulator from used oil recoverd by vehicle.
12. After the oil drain is complete, a summary
of the amount of refrigerant recovered and
Recover Function oil drained is displayed. The unit displays:
During the Recover process, the system will
initiate a filter check, service data entry, and
inlet pressure check.
1. Empty the oil drain bottle before starting a
recovery.
2. Connect the high-side (red) and/or low-side
(blue) hoses to the test tank.
3. Open the coupler valves on the hoses by
turning the collars clockwise.
4. Select the RECOVER icon from the main
menu.
5. The screen will message display: “Connect Or:
both service hoses to AC system being
serviced and open both coupler valves”.
6. Select OK icon and unit perform:
• inlet pressure check.
• A/C unit internal clearing process.
• 1st recovery stage.
• 2 st recovery stage (deep recover).
7. Select OK icon to continue or ESC icon to
cancel.
8. The machine (ACS 863 only) checks the
refrigerant in the source tank to verify it
is R1234yf and not contaminated. The
machine displays the following screens: 13. Select Print icon to print out recovery
information and pre-recover diagnostics or
INITIALIZING REFRIGERANT IDENTIFIER
select OK icon to return the main menu.
ANALYZING REFRIGERANT SAMPLE
The displayed recovered weight can vary
REFRIGERANT PURITY PASSED
depending on ambient conditions and
9. The unit will run low-side clearing then enter should not be used as an indicator of
into a 1st stage Recovery. scale accuracy. The amount of oil that was
10. When the system has recovered to removed from the A/C system is the amount
-0.4 bar, the vacuum pump starts and runs of new oil that can be charged into the A/C
until recover is complete. system after evacuation is complete.
• Use only new oil to replace the oil removed
during the recycling process.
• Dispose of used oil according to government
laws and regulations.
Recovery is complete.
WARNING: Never change the default settings unless directed by the factory.
Otherwise the unit may fail to operate properly.
• To perform any of the checks in the Service All units include load cell scales: ISV Load Cell,
Menu, use the up and down arrows to scroll Drain Load Cell, PAG Load Cell, POE Load Cell
to the desired test listed and select OK icon. and Dye Load Cell.
• To exit the Service Menu, select BACK icon. ISV Load Cell Calibration
1. After selecting Calibrate Load Cell from
the Service Menu by pressing OK icon, the
following displays:
Offset Failure:
Slope Failure:
2. Select OK icon to enter the PAG Load Cell 2. Select OK icon to enter the POE Load Cell
calibration menu. The following displays: calibration menu. The following displays:
3. Select OK icon to begin the calibration. 3. Select OK icon to begin the calibration.
Selecting ESC icon returns to the Calibrate Selecting ESC icon returns to the Calibrate
Load Cell service menu. Load Cell service menu.
Follow all remaining calibration instructions Follow all remaining calibration instructions
displayed. displayed.
• First point calibration without nothing. • First point calibration without nothing.
• Second point calibration with 500 g (edit- • Second point calibration with 500 g (edit-
able). able).
• Check with 250 g (not editable) and con- • Check with 250 g (not editable) and con-
firm with OK icon. firm with OK icon.
NOTE: DO NOT DISTURB unit during weight NOTE: DO NOT DISTURB unit during weight
calibration. calibration.
OUTPUT TEST
Air Purge Solenoid S1
3. Select OK icon to begin the calibration. PAG Solenoid S2
Selecting ESC icon returns to the Calibrate Oil Drain Solenoid S3
Load Cell service menu. Low-Side Inlet Solenoid S4
High-Side Inlet Solenoid S5
Follow all remaining calibration instructions
displayed. High-Side Charge Solenoid S6
• First point calibration without nothing. Low-Side Charge Solenoid S7
• Second point calibration with 500 g (edit- Recycle Solenoid S8
able).
Vacuum Solenoid S9
• Check with 250 g (not editable) and con-
firm with OK icon. Recover Solenoid S11
Deep Recover Solenoid S12
NOTE: DO NOT DISTURB unit during weight Oil Return Solenoid S13
calibration.
POE Solenoid S14
Dye Solenoid S15
Identifier solenoid S17
N2H2 inlet solenoid S19
N2H2 vent solenoid S20
3. Check :
Placeholders X and Y represent numbers • Unit is with covers.
displayed during this test. A list of the sensors • Fun is clean and running.
and devices and what the values represent 4. Select OK icon, and wait unit is performing
follows: calibration automatically.
5. If Ok unit come back to service menu. 5. The vacuum pump should turn on and the
6. If failed unit ask to retry. time begins to count down (5 minutes).
To pause at any point during the process
A/C unit internal clearing select PAUSE icon. At the Pause function,
The A/C unit internal clearing is used to the Service Vacuum can either be resumed
evacuate service hoses, distillator and dryer or cancelled.
filter (after compressor discharge pressure is
still in). Components ON:
1. LS inlet Solenoid S4.
2. HS Inlet Solenoid S5.
3. Recover Solenoid S11.
4. Compressor.
Service Vacuum
Service vacuum is a manually operated test
used to pull a vacuum on the machine to
remove air from the manifold and ISV prior to
refilling the ISV after service. The inlet pressure should stay below 0.35 bar
1. From the Service Menu, scroll to Calibrate throughout the Service Vacuum. The Vacuum
air flow. Pump, Vacuum Solenoid, HS Charge Solenoid,
2. Select OK icon. The following displays: Oil Return Solenoid, LS Inlet Solenoid, Tank
Liquid Solenoid and Recover Solenoid will turn
ON during this test.
6. When the vacuum Time Remaining falls
to 00.00, the outputs will turn OFF and the
following displays:
The second line of the display, above, represents 7. Scroll to the next desired Maintenance
the item to be reset. Counter. If none is desired, select BACK
6. Select OK icon to reset the amount. Select icon to return to the Service Menu.
ESC icon to leave the amount current and
return to the Service Menu.
10 Days Leak Test (R1234yf only) Default Precharge Leak Test Time
The 10 Days Leak Test is used to enable/ The Default Precharge Leak Test Time is
disable periodical leak test. editable (default 5 min).
TROUBLESHOOTING
Grounding, Noise, and Power Issues Power Issues
The power applied to the unit must be from
To provide proper protection and maximize a stable, low-impedance source. Long-term
system reliability, it is important to consider stability must be within ±10% of the nominal
grounding, shielding, and AC and DC power voltage. For a nominal 230 V line, the limits are
supply issues. 207 V to 253 V. The unit will operate above and
Grounding Issues below the voltage limits. However, problems
Grounding must be looked at first, for without in operation may appear if the voltage drops
a low-impedance ground; all noise protection (sags) below or rises above (surges) these
measures built into the electronic components limits. The life expectancy of the components
and assemblies are rendered useless. in the unit may be shortened significantly.
Grounding equipment is done for two reasons. The impedance controls the ability of the line to
The first and most important is safety. To meet supply a constant voltage with a changing load.
safety requirements, any exposed conductive Noting the line voltage with the unit off, then
surface of the equipment must be within the noting the voltage with the unit on, a technician
safe touch-voltage range of under 30 Volts can determine the impedance of the line from
RMS. Any voltage greater may result in a life the unit to the power transformer. If there is a
threatening electrical shock, under the right greater than 10% change, the line has too much
conditions. resistance or the load is too great. The solution
is a dedicated line.
The second reason is the process by which
the case and any extensions of the case are The line cord must be wired correctly. When
connected to earth ground. If the ground is replacing the line cord, make sure the terminals
open or has a high resistance, electrical noise at the plug have the high, neutral, and ground
will not be shorted to ground and can radiate connections in their proper location. A ground
into the unit. circuit tester can be used to test wiring.
Will Not Power Up, No Display 4. Connect the unit to a proper AC power
source and place the unit power switch on.
1. Verify the unit is connected to a known good The display should illuminate. If the unit
power source with a good ground and not is still inoperative, perform the following
through an extension cord. voltage checks.
2. Verify the power cable is wired correctly a. Measure the voltage at the output of the
and the connector has not been damaged. power supply from PSJ2 pin 2 (+) to pin
Replace or repair as required. 3 (-). Voltage should be 12 VDC.
3. If unit does not power up, check to make • If 12V is not present, go to step 5.
sure the circuit breaker hasn’t tripped. • If 12V is present, replace control board.
4. Turn on the main power switch. 5. Connect the unit to a proper AC power
5. If the display does not activate, verify line source and place the unit power switch on.
voltage is present at the input and output a. Disconnect the cable from power board
terminals of the switch. PBP4.
• If line voltage is not present at power b. Measure the voltage at PBP3 pins 2
switch input, check connections between and 3.
the power switch and AC connector. • Voltage should be 230 VAC (nominal).
• If line voltage is present at power switch If voltage is correct, replace power
input, but not at output with switch turned supply.
on, replace the power switch. • If voltage is less than 207 VAC, replace
• If line voltage is present at both input and power board.
output of switch, proceed to next step.
Circuit Breaker Tripped
Circuit Breaker Not Tripped 1. Place unit power switch off and reset the
1. Turn off unit and disconnect AC power cord circuit breaker.
from receptacle. 2. Place unit power switch on. If the circuit
2. Check the circuit breaker for continuity. breaker remains engaged, the unit should
• If there is no continuity, replace circuit operate normally and no further action is
breaker. required. Otherwise, proceed to step 3.
• If there is continuity, continue to next step. 3. If the circuit breaker trips again after being
NOTE: Before replacing any component, make reset, place the power switch off.
sure the interconnecting harnesses are in good 4. Disconnect PBP3 and perform continuity
condition and proper electrical contact is made checks of the power switch. If no faults are
between the connectors. found, replace the circuit breaker.
5. Connect PBP3 and disconnect remaining
3. Perform the following continuity checks:
connectors from the power board.
a. Disconnect the cable from power supply
6. Place unit power switch on.
PSJ1.
7. If the reset circuit breaker trips again,
b. Jumper all input power cable pins
replace the power board.
together at the plug end.
8. If the circuit breaker doesn’t trip after being
c. Check for continuity across power
reset, place the power switch off.
supply input cable pins 2 and 3.
9. Connect one connector at a time into the
• If continuity exists, remove jumpers
power board, placing the power switch on
from the input power cable and connect
after each additional connection.
PBP3.
10. Perform step 9 until the circuit breaker trips
• If no continuity, check the power switch
when placing the power switch on.
for proper operation. Repair or replace
11. Check all components associated with the
as required.
last connector to be attached to the power
board when the power switch was placed
on.
10. Verify the oil drain solenoid isn’t leaking Will Not Recover
the vacuum. Place a finger over the end of
the oil drain tube and check for suction. If NOTE: The compressor should be running
a suction is detected, replace the oil drain during this test. If it does not run, refer to
solenoid. Retest. Compressor troubleshooting in the Compressor
11. Disconnect the manifold end of the section of this manual.
compressor oil return line and check for 1. Verify there is pressure reading on the
pressure coming from the manifold (with gauges.
compressor running). If pressure is detected • If pressure is present, the service hoses
at the compressor oil return line connection are connected correctly.
on the manifold, replace the compressor oil • If pressure is absent, the service hoses
return solenoid. Retest. are connected improperly or there is a
12. Verify the accumulator/oil separator bowl is restriction. Clear and reconnect service
tight. Tighten and retest if loose. hoses.
• If not loose, remove the accumulator/oil 2. Display the accumulator pressure (enable
separator bowl and check the condenser display tittle info in maintenance menu).
coil connections to ensure they are tight. • If there is no pressure, inspect inlet
• If loose, tighten, reassemble, and retest. valves, recover solenoid, and check
13. Verify the compressor oil separator bowl is valves.
tight and the O-ring is installed. • I f p r e s s u r e s e e m s n o r m a l a t t h e
• If the compressor oil separator bowl is accumulator, inspect oil return solenoid
loose, retighten and retest. (S13), and compressor.
• If the O-ring is missing, install a new
O-ring, reassemble, and retest. NOTE: The recover solenoid (S11) is controlled
14. Reinstall the condenser coil and compressor to maintain a maximum of 2.5 bar (35 psi) in
oil separator bowl; do not reinstall the the accumulator.
system oil separator bowl. 3. Verify operation of the recover check valve.
15. Access the service menu and select the Replace as needed.
Output Test option. 4. Check the compressor for suction and
16. Scroll to the compressor and turn it on. discharge performance.
Once the compressor is running check the 5. Remove the filter and inspect all fittings
condenser coil connections, condenser coil and gaskets to verify that no obstructions
tubing, and compressor oil separator threads exist. Replace/repair gaskets as needed
for leakage with a soapy water solution or and reinstall filter.
other leak detection fluid. Remove the 6. Verify the accumulator transducer is
leaking component and verify the O-rings functioning properly by attaching a calibrated
are in place and not cut or damaged. gauge to the service port and compare
The O-rings and mating parts should be readings to those on the manual gauge. The
lubricated prior to assembly. Repair any readings should be within the specifications
leaks found and retest. on the transducer ID plate.
NOTE: Limit the amount of time the compressor 7. Check the oil return (S13) solenoid for
is running, as it will be pulling in air and adding bleed-through and proper operation. Repair
it to the ISV. Be sure to purge the air from the as needed.
ISV once the machine is repaired. 8. Check Tank Liquid solenoid, evacuating the
tank with a recovery service unit in advance.
17. If the unit doesn’t complete clearing, test the 9. If problem still exists, check the vacuum (S9)
compressor as reccomended procedure. solenoid, as applicable.
Refer to Compressor Troubleshooting in the
Compressor section of this manual. NOTE: If the compressor fails to operate, refer
to Compressor Troubleshooting.
Compressor Troubleshooting
ss00649
1. Check for proper power source, circuit
breaker, and electrical connectors for
damage or corrosion.
2. Connect the unit directly to a known good
power source. Do not use an extension
cord.
3. Verify the ground wire between the
compressor electrical box and chassis
ground is securely fastened.
4. Check for 230 VAC to the compressor.
• If there is no voltage to the compressor’s
start components, proceed to the next
step.
• If voltage is present at the compressor,
replace the compressor thermal protector
and start relay assembly. If compressor
runs, verify the compressor amp draw is
within specs. If the compressor doesn’t
run and/or is drawing locked rotor amps, Figure 2-1. Compressor Assembly
replace the compressor. 7. Start the compressor.
CAUTION: If using the output step test to 8. The first time the compressor is tested, the
run compressor, the oil return solenoid must gauges may read approximately 7 bar (100
be open before the compressor is started. psi) and 540 mBar (16 in-Hg).
9. Turn off the compressor and release
5. Check for 230 VAC from the power board pressure from manifold.
on connector P6, pins 1 and 2.
• When checking voltage to the compressor, Testing the Compressor a Second Time
it is normal to read a low voltage at the NOTE: Studies have shown the first test may
connector when it’s disconnected and the give false compressor values due to embedded
power to the compressor is off. refrigerant in the oil.
• If voltage is present, check wiring between
1. Close the valves on the manifold and start
the power board and the compressor start
the compressor.
components. Repair as needed.
2. A good compressor will produce 14 bar (200
• If voltage is not present, replace the relay
psi) discharge and 472 mBar (14 in-Hg) on
board.
the suction side, minimum.
6. Perform functional check.
3. Release all pressure and vacuum from the
Compressor Testing Procedure manifold set, close both valves and repeat
1. Remove shrouding from the unit. the test a third time to verify readings.
2. Remove all three lines attached to the 4. If the suction or discharge of the compressor
compressor. is under specifications, replace the
3. Cap off the compressor oil return port. compressor.
4. Connect a manifold set to the compressor,
high side to the compressor discharge and
the low side to the suction port. Remove
hose from center port of manifold.
5. Close both valves on the manifold.
6. Enter the service menu, scroll to the Output
test and select the Compressor test.
ERROR MESSAGES
PROCEDURE ERROR/WARNING DESCRIPTION OF ERROR/
WARNING
Calibrate Load Cells Calibration failed! Slope is out Difference between upper and lower
of range. limits is too great. Select RETRY
or ESC icon
Calibrate Load Cells Calibration failed! Verification Weight too high or low.
weight X. XXXYY. Select RETRY or ESC icon.
Calibration Check Calibration failed. Select RETRY icon to return to the
beginning of the calibration check,
or ESC icon to return to the service
menu.
Charge Insufficient vacuum for System vacuum to low to draw in
charge. enough refrigerant. Select AUTO-
MATIC, RETRY or ESC icon.
Charge Insufficient refrigerant Refrigerant in ISV too low. Select
available for charge. ESC icon. May require tank fill.
Charge Leak Test Leak test failed! Check for leaks and retest.
Select ESC icon.
Drain Oil Oil drain halted. Pressure Pressure insufficient to push oil out
error. of separator. Select RETRY or ESC
icon.
Drain Oil Oil drain halted. Flow error. Oil drain timed out. Select RETRY or
ESC icon.
Enter Password Invalid password! Password entered is incorrect. Verify
function password is correct. Select
RETRY or ESC icon.
Fast Charge Charge stalled! Check Check panel valve position and
connections and valves. couplers. Select RETRY or ESC
XX.XXXYY of XX.XXXYY icon.
charged.
Filter Change Invalid serial number! Filter serial number must be different
from any other filter serial number
previously installed. Select RETRY or
ESC icon.
Filter Change Serial number has already Filter serial number must be different
been used. from any other filter serial number
previously installed. Select RETRY or
ESC icon.
Helium Leak Test Transducer error. For production only. Exit test.
Leak Check Pressure test failed. Check Locate and repair any leaks. Select
for leaks. RETRY or ESC icon.
Leak Check Vacuum test failed. Check for Locate and repair any leaks. Select
leaks. RETRY or ESC icon.
P6 J1 1
J1
J2
P7 P1
6
K3 F1
K4 V Adj.
P5 K2 P2 Figure 3-2. 12 VDC Power Supply
J2
P12 7. Communicates with the Power Board
J6
P18
J7
J1
P3 P2 P9 P10 P8
ss01906
P17 J8
Power Socket J2
P12
PS2 PS1
P19
PS3 P2
P13
GND
GRN/YEL CONTROL
J3
BOARD
P6
BLU BRN
Main J7
Switch J1
S/L2 R/L1
POWER 1
P2 J1 SUPPLY J2 P1
6
V/T2 U/T1
V
ADJ.
BLU BRN
Door Switch
GRN/YEL
P2
8 4 3 7
J1
P1
P9
P2
P1
BLU
P8
P7
Circuit Breaker
BRN CB1 POWER P3
BRN BOARD
P6
CB2
P5
P1
P4
P3
Internal Refrigerant
Identifier
ss01904
P3 P4 P2 P5
P17 J8 P7 P11
P15
P12 J2 REFRIGERANT
J6 IDENTIFIER
(ID)
J5 P19
P13 CONTROL
BOARD
J3
P1 P6 P1
P18
P2 AIR FLOW
P5 SENSOR
(AF)
J7
J1
P8
P3 P2 P9 P10
P6
LOW-SIDE
PRESSURE DYE OIL DRAIN POE PAG SCALE
TRANSDUCER LOAD CELL LOAD CELL LOAD CELL LOAD CELL ASSEMBLY
(LSP)
NOTE:
• Air Flow Sensor is disabled on ACS 753 unit only.
• Internal refrigerant indentifier is included on ACS 863 unit only.
ss01905
INJECTION MANIFOLD
ss01907
P2
LED
P17 J8 P7 P11 P1 BOARD
P15 P4
P12 J2
P19
P13
CONTROL
BOARD
J3
P3 PRINTER
P6 ASSEMBLY
P18 P2 P1
J7
J1
P8
P3 P2 P9 P10
P8 P9
P4
P3
P6 J1
P7 P1 P1 VACUUM
^^
PUMP
POWER
BOARD
GND
P5 P2
P4 P3
BRN
BLU
FAN
P2
COMPRESSOR
^^
GND
P8 P9
P4
P3
J1 PBP9
PBP4 P6
P7 P1
PBP8
PBP3
PBJ1
PBP6 P5 P2
PBP1
P17 J8 P11
CBP15
P15
LS1
J2
P12
J6
P19
CBP1 P13
CBP19
J3
P1
P6
P18
CBP6 J7
J1 CBP18
P2
P8
P3 P9 P10
Flow Diagrams........................................................................................................87
Tank Fill................................................................................................................................ 87
Internal Clearing.................................................................................................................. 88
Refrigerant Identification.................................................................................................... 89
Recovery.............................................................................................................................. 90
Deep Recovery..................................................................................................................... 91
Oil Drain................................................................................................................................ 92
Vacuum................................................................................................................................. 93
Vacuum Leak Test............................................................................................................... 94
Air Purge.............................................................................................................................. 95
Oil Inject 1 (PAG)................................................................................................................. 96
Oil Inject 2 (POE)................................................................................................................. 97
UV Dye Inject........................................................................................................................ 98
Pre-charge............................................................................................................................ 99
Charge .................................................................................................................................. 100
Recycle/Power Charge........................................................................................................ 101
Hose Flush........................................................................................................................... 102
Periodic Leak Test............................................................................................................... 103
N2H2 Injection...................................................................................................................... 104
N2H2 Venting....................................................................................................................... 105
Ancillary components and assemblies included Oil Drain Bottle: This bottle provides a
are: reservoir for used oil and must be drained when
the user is instructed to do so by the control
Cooling Fan: The cooling fan is necessary panel. Operators should drain this bottle prior to
to keep the compressor below its maximum each use of the unit to make sure unit operation
ambient operation temperature of 50°C (140°F) is not interrupted.
or less.
High- and Low-Side Gauges: These gauges
Injection Manifold: This assembly serves as monitor the high- and low-side pressures when
the attachment ports for the high- and low-side the unit is operating.
service hoses, as the oil injection point through
PAG Solenoid (S2) and POE Solenoid (S14), High- (Red) and Low-Side (Blue) Service
and as the dye injection point through Dye Inject Hoses: These hoses connect the unit to the
Solenoid (S15). vehicle A/C system.
Flush + N2H2 Manifold: This assembly serves
as the attachment ports for the high- and low-
side service hoses, as the N2H2 or N2 injection
point through N2H2 Inlet Solenoid (S19).
MANIFOLD ASSEMBLY
ss01942
COMPRESSOR
NOTES:
1. Adjust position of ISV liquid and vapor hoses so that the hoses do not contact the center
divider or vacuum pump shelf.
2. Apply Loctite 242 to equivalent to threads.
3. Torque hose fittings to 8.5 ±0.5Nm.
4. Route replacement hoses and tubes in the same positions and places as the original securing
with tie-wraps where appropriate.
ss01940
Sight
Oil drain glass
port
Main Manifold
(Side View)
ISV Assembly
Liquid
Vapor
Main Manifold
(Top View)
Vacuum pump
Injection Manifold
(Reference Only)
NOTE: All wires must be clear of moving parts, pinch points, and sharp edges.
4psi Relief
Check Valve for
Vacuum Pump
Tank Pressure
Transducer (TP)
Oil Drain
Solenoid (S3)
Manifold Assembly
(Side View)
ISV Assembly
(Side View)
Manifold Component Application Chart, ACS 753, ACS 763 and ACS 863
Recycle/ Power
N2H2 Injection
Deep Recover
N2H2 Venting
UV Dye Inject
Identification
Pre-Charge
Hose Flush
Refrigerant
Function
Air Purge
Oil Drain
Clearing
Tank Fill
Recover
Vacuum
Internal
Charge
Charge
Component
Tank Liquid
Liquid Solenoid
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Internal
Recover Check
Tank
ACS 753, ACS 763, ACS 863 Service Manual
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
87
Gauge
Oil Drain
Solenoid
Compressor
Vacuum Pump
FLOW DIAGRAMS
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
SP00D00609
Dye Inject
Bottle
2018-03-26
temperature which can vary depending on the temperature reading from the temperature sensor. When the ISV
of the tank fill solenoid is controlled to maintain 2.4 bar (35 psi) in the accumulator, and is based on the ambient
During the Tank Fill process the compressor, fan, tank fill, and oil return solenoids are activated. The output state
ISV Pressure
Air Transducer
Diffuser
SP00D00609
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
2018-03-26
LS Charge Vapor Relief
ID Orifice
Check Valve Check Valve Temp.
Sensor
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Internal
Plumbing and Mechanical
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
88
Oil Drain
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Compressor
Vacuum Pump
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
During the Internal Clearing process, the compressor is activated. The process continues until -0.45 bar (13 in Hg)
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Internal
Tank
ACS 753, ACS 763, ACS 863 Service Manual
Recover Check
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
89
Oil Drain
Pump Exhaust Solenoid
Check Valve
Compressor
Vacuum Pump
Oil Drain
Bottle
Injection
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
SP00D00609
Low Side High Side
Service Hose High Side Storage Port
Service Hose
2018-03-26
the recovery process, or a “FAIL” message will display. If the refrigerant fails to pass the ID test, the machine will
orifice. After analyzing the refrigerant, the identifier will either send a “PASS” message to the control board to begin
open intermittently, allowing refrigerant to flow to the refrigerant identifier, through the 0.028-inch internal diameter
pressure is verified the machine will initiate identification of the refrigerant. The low side identifier solenoid (S17) will
print the results, and ask if you want to repeat the ID test. If the refrigerant ID test, fails, the test will automatically
When the recover or tank fill function is selected, the machine will check pressures on the service hoses. Once
ISV Pressure
Air Transducer
Diffuser
SP00D00609
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
RECOVERY PROCESS
Solenoid Pressure
2018-03-26
LS Charge Vapor Relief
ID Orifice
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Plumbing and Mechanical
Internal
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
90
Oil Drain
Pump Exhaust Solenoid
Check Valve
Compressor
Vacuum Pump
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
During the first stage of the recovery process, the fan, compressor, high side and low side inlet solenoids are
activated. Recover and oil return solenoids are activated intermittently. Recovery stops when 135 mbar (4 in Hg) is
ISV Pressure
Air Transducer
Diffuser
Tank Liquid
Liquid Solenoid
HS Charge Recycle
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Internal
Recover Check
Tank
ACS 753, ACS 763, ACS 863 Service Manual
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
91
Oil Drain
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
SP00D00609
Bottle
the oil return and power charge solenoids are controlled to maintain 0 to 207 mbar (3 psi) in the accumulator.
Plumbing and Mechanical
During the Deep Recovery process, the recover solenoid is deactivated, high side, and low side inlet solenoids
2018-03-26
remain activated. The vacuum pump, compressor, and deep recover solenoids are activated. The output state of
ISV Pressure
Air Transducer
Diffuser
SP00D00609
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
in the accumulator.
OIL DRAIN PROCESS
LS Charge Main Manifold Vapor
ID Solenoid
Solenoid
2018-03-26
Pressure
LS Charge Vapor Relief
ID Orifice
Check Valve Check Valve Temp.
Sensor
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Plumbing and Mechanical
Internal
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge Oil Drain
92
Solenoid
Pump Exhaust
Check Valve
Compressor
Vacuum Pump
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
there is either a greater than 0.01 bar (0.15 psi) change per second in the accumulator or less than 0.62 bar (9 psi)
During the Oil Drain process, the recyclesolenoid is activated until there is greater than 1.1 bar
(16 psi) in the accumulator. The recycle solenoid is then deactivated and the oil drain solenoid is activated until
ISV Pressure
Air Transducer
Diffuser
Tank Liquid
Liquid Solenoid
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Internal
Recover Check
Tank
Valve
ACS 753, ACS 763, ACS 863 Service Manual
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
93
Oil Drain
Pump Exhaust Solenoid
Check Valve
Compressor
Vacuum Pump
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
SP00D00609
Bottle
2018-03-26
The default vacuum time is 5:00 minutes. When the vacuum process begins, the vacuum pump is activated.
After a 5 second delay, the vacuum, high side and low side inlet solenoids are also activated. When the timer reaches
ISV Pressure
Air Transducer
Diffuser
RI Filter
SP00D00609
Air Purge
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
2018-03-26
Solenoid Pressure
LS Charge Vapor Relief
ID Orifice
Check Valve Check Valve Temp.
Sensor
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Plumbing and Mechanical
Internal
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
94
Oil Drain
Pump Exhaust Solenoid
Check Valve
time, the vacuum leak test will fail (this is not a service menu test.)
Vacuum Pump
Exhaust
Compressor
Vacuum Pump
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
Unit checks low-side transducer for rise in vacuum. If the unit sees a rise of 338 mbar (10 in Hg) within 5 minutes
ISV Pressure
Air Transducer
Diffuser
Tank Liquid
Liquid Solenoid
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Internal
Recover Check
Tank
Valve
ACS 753, ACS 763, ACS 863 Service Manual
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge Oil Drain
95
Solenoid
Pump Exhaust
Check Valve
Vacuum Pump
Compressor
Vacuum Pump
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve
will occur when the machine is on and idle for 5 minutes, and prior to background fill.
Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
SP00D00609
Bottle
The air purge solenoid is activated to release excess pressure from the internal storage vessel (ISV). The air purge
2018-03-26
ISV Pressure
Air Transducer
Diffuser
RI Filter
SP00D00609
Air Purge
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
2018-03-26
Solenoid Pressure
LS Charge Vapor Relief
ID Orifice
Check Valve Check Valve Temp.
Sensor
HS Charge Recycle
Solenoid Solenoid
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Plumbing and Mechanical
Internal
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
96
Oil Drain
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Compressor
Vacuum Pump
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
The oil injection is an automatic process. During the charge setup, the operator must enter the amount of oil wanted
and the machine injects the oil automatically. The system being serviced must have a vacuum to pull oil from the
Tank Liquid
HS Charge Recycle
Solenoid Solenoid
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Internal
Recover Check
Tank
ACS 753, ACS 763, ACS 863 Service Manual
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
97
Gauge
Oil Drain
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Compressor
Vacuum Pump
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
SP00D00609
Bottle
and the machine injects the oil automatically. The system being serviced must have a vacuum to pull oil from the
The oil injection is an automatic process. During the charge setup, the operator must enter the amount of oil wanted
2018-03-26
ISV Pressure
Air Transducer
Diffuser
SP00D00609
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
2018-03-26
Solenoid Pressure
LS Charge Vapor Relief
ID Orifice
Check Valve Check Valve Temp.
Sensor
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Plumbing and Mechanical
Internal
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
98
Oil Drain
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
During the Charge process, the unit activates the dye inject solenoid to inject a preset amount of dye into the vehicle
A/C system to check for leaks. The system being serviced must have a vacuum to pull dye from the dye inject bottle.
Tank Liquid
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Internal
Recover Check
Tank
ACS 753, ACS 763, ACS 863 Service Manual
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
99
Oil Drain
Vacuum Pump
Compressor
Vacuum Pump
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
SP00D00609
Low Side High Side
Service Hose High Side Storage Port
Service Hose
During the pre-charge process (before to perform the charge), the unit charge a little amount of refrigerant in the
2018-03-26
ISV Pressure
Air Transducer
Diffuser
RI Filter
SP00D00609
Air Purge
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
CHARGE PROCESS
LS Charge Main Manifold Vapor
ID Solenoid
2018-03-26
Solenoid Pressure
LS Charge Vapor Relief
ID Orifice
Check Valve Check Valve Temp.
Sensor
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Plumbing and Mechanical
Internal
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
100
Oil Drain
Pump Exhaust Solenoid
Check Valve
Compressor
Vacuum Pump
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
will prompt the user in completing the charge. When the charge process is complete, user must equalize hoses.
During the Charge process, the end user may select either high-side charge, low-side charge, or both. When the
charge process gets close to the programmed weight, the unit slows down. The unit charges by compensation and
tank pressure.
Tank Liquid
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
101
Oil Drain
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Compressor
Vacuum Pump
Oil Drain
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
SP00D00609
Bottle
If the unit does not complete a full charge, the compressor and recycle solenoid are activated, then stop to build
2018-03-26
ISV Pressure
Air Transducer
Diffuser
SP00D00609
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
2018-03-26
Pressure
LS Charge Vapor Relief
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Plumbing and Mechanical
Internal
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
Oil Drain
102
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Compressor
Vacuum Pump
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
previous vehicle serviced. During the Hose Flush Process, the compressor is activated. The high side and low side
Tank Liquid
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Internal
Recover Check
Tank
ACS 753, ACS 763, ACS 863 Service Manual
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
103
Oil Drain
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Vacuum Pump
Compressor
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
SP00D00609
Bottle
charge, high side inlet, low side inlet, recycle, oil return, recover solenoids to check any pressure decay.
Low Side High Side
Service Hose High Side Storage Port
Service Hose
Plumbing and Mechanical
During the periodic leak test process the circuit is pressurized. The unit activates the high side charge, low side
2018-03-26
ISV Pressure
Air Transducer
Diffuser
SP00D00609
Refrigerant Solenoid
Identifier
Tank Liquid
Liquid Solenoid
2018-03-26
Solenoid Pressure
LS Charge Vapor Relief
ID Orifice
Check Valve Check Valve Temp.
Sensor
Low Side
Transducer LS Inlet Recover
Solenoid Solenoid
Service Port
Plumbing and Mechanical
Internal
Recover Check
Tank
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
Oil Drain
104
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
system thru the ACS service hoses. Pressure is monitored by the Low Side Tranducer.
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
Bottle
During the N2H2/N2 injection process, the N2H2 Inlet Solenoid opens to allow the gas flooding the vehicle A/C
Tank Liquid
HS Charge Recycle
Solenoid Solenoid
HS Charge
Check Valve High Pressure
Cutout Swtich
Accumulator
Transducer
Low Side
Transducer LS Inlet Recover
Internal
Recover Check
Tank
ACS 753, ACS 763, ACS 863 Service Manual
Valve
HS Inlet Heat Exchanger /
LS Solenoid Deep Recover Compressor Oil
System Oil
Gauge Solenoid Separator
Separator
Oil Return
Solenoid
Vacuum
Solenoid
HS Filter/Drier
Gauge
105
Oil Drain
Pump Exhaust Solenoid
Check Valve
Vacuum Pump
Exhaust
Oil Drain
Bottle
Injection
Manifold Oil Inject 1
Solenoid
N2H2 Port
Oil Inject 1
Check Valve Oil 1 Inject
Oil Inject 2 Bottle
Solenoid
Contamination
Port
Oil Inject 2 Low Side
Check Valve Pressure Storage Port
Oil 2 Inject Relief
Dye Inject Bottle
Solenoid
N2H2 Inlet
N2H2 Vent Solenoid
Solenoid
N2H2
Dye Inject
Check Valve
Diffuser
Dye Inject
SP00D00609
Bottle
2018-03-26
N2 trapped into the ACS inlet. Vacuum is then performed to remove any possible remained N2H2/N2 after venting.
During the N2H2/N2 injection process (when injection is completed), the N2H2 Vent Solenoid opens to purge N2H2/
Parts and Components ACS 753, ACS 763, ACS 863 Service Manual
Notes
SP00D00609 | 2018-03-26