SLC Signaling Line Circuit
SLC Signaling Line Circuit
SLC Signaling Line Circuit
SLC
Wiring Manual
G
Document 51253
11/29/2005 Rev:
P/N 51253:G ECN 05-473
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capability—can provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), manufacturer's same room as the control panel and in rooms used by the sys-
recommendations, State and local codes, and the recommen- tem for the connection of alarm transmission wiring, communi-
dations contained in the Guide for Proper Use of System cations, signaling, and/or power. If detectors are not so
Smoke Detectors, which is made available at no charge to all located, a developing fire may damage the alarm system, crip-
installing dealers. A study by the Federal Emergency Man- pling its ability to report a fire.
agement Agency (an agency of the United States government) Audible warning devices such as bells may not alert people
indicated that smoke detectors may not go off in as many as if these devices are located on the other side of closed or
35% of all fires. While fire alarm systems are designed to pro- partly open doors or are located on another floor of a building.
vide early warning against fire, they do not guarantee warning Any warning device may fail to alert people with a disability or
or protection against fire. A fire alarm system may not provide those who have recently consumed drugs, alcohol or medica-
timely or adequate warning, or simply may not function, for a tion. Please note that:
variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control panel. It is essential to use only equip-
• Smoke particles may be drawn into air returns before ment listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of NFPA 72 shall be
izing-type sensing chambers tend to detect fast-flaming fires followed. Environments with large amounts of dust, dirt or
better than smoldering fires. Because fires develop in different high air velocity require more frequent maintenance. A main-
ways and are often unpredictable in their growth, neither type tenance agreement should be arranged through the local man-
of detector is necessarily best and a given type of detector ufacturer's representative. Maintenance should be scheduled
may not provide adequate warning of a fire. monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate should be performed by authorized professional fire alarm
warning of fires caused by arson, children playing with installers only. Adequate written records of all inspections
matches (especially in bedrooms), smoking in bed, and violent should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.). Limit-C-9-2005
This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity 93% ± 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27º C/60-80º F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
Acclimate Plus™, HARSH™, NIS™, Notifier Integrated Systems™, NOTI•FIRE•NET™, and ONYXWorks™ are all trademarks; and FlashScan®, NION®,
NOTIFIER®, ONYX®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and
LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©2005 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Please note this email address is for documentation feedback only. If you have any technical
issues, please contact Technical Services.
NOTE: FireWarden-100 SLC devices are not compatible with the Notifier panels in this manual;
refer to the FireWarden-100 SLC Manual P/N 52304.
1. AFC-600 has been discontinued; to service existing installations of this panel, refer to the
original manuals shipped with the panel.
CAUTION:
! Do not program more than 99 addresses on a CLIP-mode SLC loop, because this will slow the
system down and compromise the response time of the panel to display off-normal events.
CAUTION:
! Do not program modules as CLIP and detectors as FlashScan on the same SLC. This combination
does not work.
1.6 Devices
1.6.1 Monitor/Zone Interface Modules
These addressable modules allow the control panel to monitor entire circuits of conventional alarm
initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and
supervisory devices.
• FMM-1 Monitor Module; FlashScan or CLIP mode. (An earlier module named MMX-1 was
CLIP mode only.)
• FDM-1 Dual Monitor Module; FlashScan or CLIP mode.
• FMM-101 Addressable Mini-Monitor Module; FlashScan or CLIP mode. (An earlier module
named MMX-101 was CLIP mode only.)
• FZM-1 Zone Interface Module; FlashScan or CLIP mode. (An earlier module named MMX-2
was CLIP mode only).
• XP5-M - Supervises five Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices. Supports FlashScan or CLIP mode. This module is
capable of participating in degraded mode where supported by the FACP. (See the XP5 Series
Manual)
• XP6-MA Allows an intelligent alarm system to monitor six zones of conventional two-wire
detectors; FlashScan or CLIP mode.
• XP10-M Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices; FlashScan or CLIP mode. This module is capable of
participating in degraded mode where supported by the FACP.
1.6.5 Transponders
• XPIQ An integrated, multiple channel audio amplification and distribution subsystem
remotely controlled by the FACP. It can direct up to four low level audio signals from risers to
up to four audio amplifiers, which are then directed to up to four integrated, continuously
supervised speaker circuits. The XPIQ is FlashScan capable (only).
• XP Series (XPP-1, XPC-8, XPM-8 & XPR-8) Provides the FACP with an efficient multiplex
subsystem capability. It communicates with the FACP and functions as a data-gathering panel
for alarm Initiating Device Circuits and as a remote switching center for Notification
Appliance Circuits (NAC), telephone circuits or relays. Not FlashScan capable.
For information on connecting these transponders to the SLC, refer to the XP Transponder Manual
or the XPIQ Manual.
FSI-851 Addressable, intelligent smoke detector that incorporates an ionization sensing chamber.
Designed to provide open area protection. FlashScan capable. (An earlier model named FSI-751
was also FlashScan capable. Earlier models named CPX-751 and CPX-551 were CLIP mode
only.)
FSP-851 Analog, addressable intelligent smoke detector that uses a photoelectric sensing chamber.
Listed for use in ducts. Designed to provide open area protection. The FSP-851T adds thermal
sensors that will alarm at a fixed temperature of 135° F (57.2°C). Both models support FlashScan
or CLIP mode. (Earlier versions named FSP-751 and FSP-751T also supported FlashScan or CLIP
mode, but were not listed for use in ducts. Earlier models named SDX-551, SDX-751 and
SDX-551TH were CLIP mode only.)
FST-851 Intelligent thermistor sensing circuit for fast response. Designed to provide open area
protection with 50 foot spacing capability. A fixed temperature sensor with 135°F (57.2°C) fixed
temperature alarm. The FST-851R incorporates a thermal rate of rise of 15°F (8.3°C). The
FST-851H is a high temperature sensor with 190°F (87.8°C) fixed temperature alarm. Both
models models support FlashScan or CLIP mode. (Earlier versions named FST-751 and FST-751R
also supported FlashScan or CLIP mode. Earlier models named FDX-551 and FDX-551R were
CLIP mode only.)
FSD-751P Photoelectric Duct Detector. The FSD-751RP includes an alarm relay. Both models
support FlashScan or CLIP mode.
FSD-751PL Low-flow Photoelectric Duct Detector, with extended speed range of 100–4000 FPM
(0.5 m/s to 20.3 m/s). FSD-751RPL adds a relay. Both models support FlashScan or CLIP mode.
FSH-751 (HARSH™) A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. Supports FlashScan or
CLIP mode. (An earlier model named HPX-751 was CLIP mode only.)
FSL-751 VIEW® An advanced intelligent photoelectric detector that uses a laser diode, special
optics, and signal processing to obtain extremely high sensitivity. Supports FlashScan and CLIP
mode; compatible with AFP-300/AFP-400, NFS-640, and NFS-3030/NFS2-3030 only. LPX-751L
is compatible with AFP-200 and AM2020/AFP1010; CLIP mode only. (An earlier version named
LPX-751 was CLIP mode only and compatible with AFP-300/AFP-400.)
Table 1.2 SLC Circuit Configuration and Performance: Style 4, Style 6, Style 7
NFS-640/E Monitor Module Blinks RED RED continuous Blinks GREEN RED continuous
NFS2-3030, Control Module Blinks GREEN GREEN continuous Blinks GREEN GREEN continuous
NFS-3030 Detector Blinks RED RED continuous Blinks GREEN RED continuous
NOTE: In CLIP mode, the LPX-751 and HPX-751 blink GREEN in standby and stay RED when
activated.
FACP: Recommended
Wire Gauge†
Wire Type and Limitations* Max. Distance
NOTE: Twisted-shielded pair or untwisted unshielded wire is not recommended for use with LIB-200A or LIB-400.
Untwisted, unshielded wire, in conduit 1,000 ft. (304.8 m) 12 to 18 AWG (3.31 mm² to 0.82 mm²)
or outside of conduit.
Note: Twisted-shielded pair is not recommended for use with this panel.
Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to ground) should not
exceed 0.5 microfarads.
Untwisted, unshielded wire, in conduit 1,000 ft (304.8 m) 12 to 18 AWG (3.31 mm² to 0.82 mm²)
or outside of conduit.
Twisted, shielded pair 10,000 ft. (3,048 m) 12 to 18 AWG (3.31 mm² to 0.82 mm²)
† Notifier brand cable is recommended; see the product catalog available from Paige Electric.
FACP: Recommended
Wire Type and Limitations Max. Distance Wire Gauge*
AFP-100
Twisted, shielded pair, 40 ohms 10,000 ft. (3,000 m) 12 AWG (3.31 mm²)
maximum per length of Style 6 and 7 8,000 ft. (2,400 m) 14 AWG (2.08 mm²)
loops. 40 ohms per branch maximum 4,875 ft. (1,450 m) 16 AWG (1.31 mm²)
for Style 4 loops. 3,225 ft. (980 m) 18 AWG (0.82 mm²)
Untwisted, Unshielded 1,000 ft. (300 m) 12-18 12 to 18 AWG (3.31 mm² to 0.82 mm²)
Note: Twisted-unshielded pair wire is not recommended for use with this panel.
AFP-200
Untwisted, unshielded wire, in conduit 1,000 ft. (304.8 m) 12 to 18 AWG (3.31 mm² to 0.82 mm²)
or outside of conduit
Note: Twisted-unshielded pair wire is not recommended for use with this panel.
Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to earth) should not exceed
0.5 microfarads.
AFP-300/AFP-400
Untwisted, unshielded wire, in conduit 1,000 ft. (304.8 m) 12 to 18 AWG (3.31 mm² to 0.82 mm²)
or outside of conduit.
Note: Twisted-unshielded pair wire is not recommended for use with this panel.
Twisted-shielded pair. Maximum loop 10,000 ft. (3,048 m) 12 AWG (3.31 mm²)
resistance is 40 ohms. Maximum 8,000 ft. (2,438.4 m) 14 AWG (2.08 mm²)
length is 10,000 ft. per channel (NFPA 4,875 ft. (1,485.9 m) 16 AWG (1.31 mm²)
Style 4) or 10,000 ft. total twisted pair 3,225 ft. (982.98 m) 18 AWG (0.82 mm²)
length (NFPA Style 6 and 7). Maximum
loop current is 200 mA (short circuit) or *If the wiring connected to the LIB-200 leaves the building it must be in conduit. It can
100 mA (normal). not exceed 1000 m (1093 yards), must not cross any power lines, and must not be in the
vicinity of any high voltage. These outdoor wiring restrictions do not apply to the
LIB-200A or the LIB-400.
Twisted-shielded pair. Maximum loop 10,000 ft. (3,048 m) 12 AWG (3.31 mm²)
resistance: 40 ohms. 8,000 ft. (2,438.4 m) 14 AWG (2.08 mm²)
Maximum loop voltage: 27.6 VDC. 4,875 ft. (1,485.9 m) 16 AWG (1.31 mm²)
Maximum loop current: 200 mA (short 3,225 ft. (982.98 m) 18 AWG (0.82 mm²)
circuit) or 100 mA (normal operation).
SLC Out
SLC-meas5.cdr
Branch
Segment
Segment
Five
Four
Segment
Segment Segment
SLC-meas2.cdr
Three
One Two
STEP 2
Last Device
SLC Return
Short Point
SLC Out
SLC-meas5.cdr
First Device
STEP 3
SLC Return
Last Device
B+ A+ B- A- TB1 B+ A+ B- A- TB1
LEM320-SLC-TB.cdr
SLC Loop Connections SLC Loop Connections
on Loop Control Modules on Loop Expander Module
nfs640-slc-tb.cdr, LEM320-slc-tb.cdr
SLC1
B+ A+ B- A-
B+ A+ B- A- TB1
TB16
SLC Loop #1 Connections SLC Loop #2 Connections
on FACP’s main circuit board on Loop Expander Module
2.4.3 AFP-100
AFP-100 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TB6.
slc-100.wmf
2.4.4 AFP-200
AFP-200 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TB5.
slc-200.wmf
2.4.5 AFP-300/AFP-400
AFP-300 supports one SLC loop; AFP-400 supports two SLC loops. The loops are CLIP mode
only. SLC loops connect to TB6 on AFP-300; SLC loops connect to TB5 and TB6 on AFP-400.
slc-300.wmf, slc-400.wmf
SLC Loop Connections SLC Loop Connections
on AFP-300 on AFP-400
slc-lib-200a.wmf,slc-lib-400.wmf
Pin 3 SLC Loop Port A- Pin 3 SLC Loop Port A-
LIB-200A LIB-400
slc-aim-200.wmf
Figure 2.11 SLC Connections for AIM-200
NOTE: AFC-600 has been discontinued; to service existing installations of this panel, refer to
the original manuals shipped with the panel.
3.1 Overview
This section shows the proper termination of the shield, if used.
Shielding of the SLC is recommended for use with AFP-100, AFP-200, AFP-300/400, LIB-200,
and AIM-200. Proper termination of the shield depends on the type of conduit used:
• Section 3.2, “No Conduit”.
• Section 3.3, “Full Conduit” (Canadian requirement).
• Section 3.4, “Partial Conduit”.
Shielding of the SLC is not recommended for use with NFS-640/E, NFS-3030/NFS2-3030,
LCM-320, LEM-320, LIB-200A or LIB-400. If twisted-shielded wire is used in one of these
installations, use a floating shield to terminate the wire as shown in Section 3.5, “Floating Shield”,
on page 27.
Use of good wiring practice consistent with local electrical codes is expected.
3.2 No Conduit
For use with AFP-100, AFP-200, AFP-300/400, LIB-200, and AIM-200 only
Scrape the paint on the cabinet to bare metal to provide a good electrical connection. Fold the foil
and drain wire back over the cable jacket. Slide the cable into the connector clamp and secure. The
drain wire should be connected to the connector screw. Do not allow the shield drain wire or foil to
enter the system cabinet.
Connector Screw
Shield Drain Wire
Cabinet
Foil
SLC-swterm1.cdr
Conduit
Shield2.wmf, SLC-swterm2a.wmf
Cabinet Foil Tape over foil.
NOTE: For Style 6 or Style 7 SLC wiring, connect one end of the shield to the
reference/negative side of the respective channel
Cabinet
SLC-swterm3.cdr
Conduit
Tape
SLC-swterm4.cdr
NOTE: Using shielded wire in applications where it is not recommended will reduce the maximum
SLC length. If shielded wire must be used where not recommended, failing to float the ends will
reduce the maximum SLC length even further.
4.1 Overview
This chapter concerns itself with the two styles of circuits that do not require isolation devices:
• NFPA 72 Style 4
• NFPA 72 Style 6
Addressable Module
T-tapped Circuits
B+ B–
SLC-style4.cdr
Control Panel
SLC
SLC Out
Addressable Module
SLC Return
B+ B– A– A+
SLC-style6.cdr
Control Panel
SLC
NOTE: T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.
5.1 Overview
There are two isolator devices used to protect critical elements of the FlashScan-mode or
CLIP-mode SLC loop from faults on other SLC branches or segments.
• Fault Isolator Module ISO-X
• Isolator Detector Base B224BI
A Fault Isolator Module on both sides of a device, or the combination of an Isolator Base and
Isolator Module are required to comply with NFPA Style 7 requirements.
CAUTION:
! If relay or sounder bases are not used, a maximum of 25 addressable devices can be connected
between Isolator Modules and/or Bases. When relay or sounder bases are used, the maximum
number of addressable devices that can be connected between Isolators is reduced to seven.
Isolator modules will not function properly when these limits are exceeded.
When more than 100 Isolator Modules and/or Isolator Bases are connected from the AFP-300 or
AFP-400 to an SLC loop, the address capacity of the loop is reduced by two (2) addresses for every
isolator device in excess of 100.
The address capacity of the loop is reduced by two (2) addresses for every isolator device in excess
of 200 when the Isolator Modules and/or Isolator Bases are connected to the SLC loop from the
NFS2-3030, NFS-3030, NFS-640/E, AFP-100 or AFP-200.
Continuation
of the SLC
IN
IN
OUT
OUT
SLC-isowire.cdr
SLC Isolated branch
of theSLC
Detector 1 X Detector 2
Y
Detector 5 Z
Detector 4 Detector 3
SLC Out SLC Return
SLC-isowork.wmf
Control Panel
Isolator Base Non-Isolating Device Short-circuit path
NOTE: For information on wiring an isolator base, refer to Figure 9.3, “Wiring an Isolator Base”
on page 55.
Isolator Module
Two-wire Addressable Detector
Isolated Branch
Isolator Module
Isolated Branch
Isolator Module
Isolated Branch
B– B+
SLC-style4iso.cdr
Control Panel
SLC
Isolator Isolator
Module Module
Section B
Two-wire
Addressable Section C
Detector
Addressable
Pull Station
Section A
The first isolator module on SLC Out and SLC Return is not
Isolator required for AFP-300, AFP-400, NFS-640/E, or Isolator
Module NFS-3030/NFS2-3030 because the panels provide the Module
functionality.
Isolator
Module
Two-wire Isolator
Detector Base
Isolator Isolator
Module Module
Addressable
Pull Station
Addressable
Detector
Isolator Isolator
Module Module
6.1 Description
These addressable modules monitor conventional contact-type alarm initiating devices. You can
configure module circuits as NFPA Style B (Class B) or Style D (Class A) Initiating Device
Circuits (IDC). There is no limit to the number of contact-type devices installed on a monitor
module IDC.
For more information on the individual module specifications refer to the Installation Instructions
that are provided with this device. For information on transponders, refer to the specific
transponder manual.
Rotary
Switches
IDC Return 9
IDC Return 8 SLC–
SLCModule-simplified.wmf
IDC Out 7 SLC+
24 VDC –
IDC Out 6
24 VDC +
} Zone interface modules only.
On addressable monitor modules in
FlashScan mode with NFS-640/E,
NFS2-3030, and NFS-3030, pins 3 & 4 can
Areas used to record the device be jumpered to enable the fire panel’s
address and SLC number. Communication Loss (Degraded mode)
feature.
Rotary
Switches
Address +1 { 9 H–
8 H+ SLC–
SLCDualMod-simplified.wmf
SLC+
Base Address { 7L+
6L–
FMM-101.cdr
IDC (-) Yellow
Rotary 6 7 8 9 10
Switches 5
4 11 Breakaway Tab - Modules come
3 12 with a raised breakaway tab on the
2 13
SLC-setadd.cdr, SLCbrktabs.cdr
1 0 1514 TENS rotary switch. This tab must
TENS
be removed when the module is on
an FACP that uses more than 99
addresses.
6789
5
4
3
2
10
ONES
From Supply
24 VDC
Four-wire 24 VDC Power
Detector Base Filtered, Regulated,
Resettable
Manual pull
station
To Next IDC
or
47K ELR Supervision Device
(supplied
with module)
Heat SLC
detector
FMM-1
SLC-idcB1.wmf
IDC
From
Supply
24 VDC
Four-wire
Detector Base 24 VDC Power
Filtered, Regulated,
Resettable
Manual pull
station
To Next IDC
or
Supervision Device
SLC
Heat
detector FMM-1
SLC-idcD1.cdr
IDC
NFS-640/E, NFS2-3030, and
NFS-3030 (FlashScan® only):
Jumper terminals 3 and 4 to enable
the fire panel’s Communication Loss
(Degraded mode) feature.
Manual
Pull
Station
47K
ELR 47K
ELR
SLC
Heat
Detector
FDM-1
Base +1 Address
SLC-idcB3fdm1.wmf
Two-wire
smoke
detectors 3.9K ELR
(supplied with module)
SLC
FZM-1
IDC
90 mA
External
SLC-idcB2.wmf
24 volt supply
required
3.9K ELR
Two-wire (supplied with module)
smoke
detectors
SLC
FZM-1
IDC
90 mA
External
24 volt supply
required
SLC-idcD2.wmf
Figure 6.9 Typical Style D IDC Wiring with the Zone Interface Module
7.1 Description
The FCM-1 module is an addressable module that can be used for monitoring and switching 24
VDC Notification Appliance Circuit (NAC) power for NFPA Style Y (Class B) and NFPA Style Z
(Class A) circuits. It can also be used for audio/voice applications and fire-fighters telephone; these
two types of applications are documented separately. For UL 9th edition audio applications, refer
to the Digital Voice Command Manual and the Digital Audio Amplifiers Manual. For UL 8th
edition audio applications, refer to the Voice Alarm System Manual or FireVoice 25/50 Manual.
The module has a resistor on the back (refer to Figure 7.2) that must be removed when it is used on
an FFT-7 or FFT-7S telephone circuit.
For more information on the module specifications refer to the Installation Instructions provided
with this device.
SLCModule-simplified.wmf
24 VDC Nonresettable Power (+)*
FMM-1back.cdr
then place a piece of the Addressable Control
tape over the Module Without Relay”).
recessed area.
NOTE: When using NFS2-3030/NFS-3030 and the Control type ID, do not cut this resistor.
FCM-1
SLC-nacY.wmf
Module polarities are shown in alarm condition
24 VDC Nonresettable power
NAC Return
A power supervision relay
is required only on the last
NAC Out module of the power run.
(NFS2-3030 and
NFS-3030 only: If using
one of the
NFS2-3030/NFS-3030’s
FlashScan type IDs that
provide built-in power
supervision, no relay is
SLC-nacZ.wmf
required.)
Compatible UL-listed
24 VDC releasing device 9 0
6 7 8 9 10
5
8
4
3
11
12 1 Non-resettable
– 7
2
TENS
1 0 1514
13
2 24 VDC Power
6789
–
Relconn-fcm.cdr
5
Brown Red 6 4
3 3
+ 5
2
10
4
+
REL-47K ONES
ADDRESS
LOOP
(Use with Type Code
Rel Ckt ULC, N.C. Supervision
or see Circuit
Relay Contact Power Supervision
Requirement 3.)
Part of EOLR-1 Relay (EOLR-1)
FCM-1
Figure 7.5 Typical Connection of a 24 VDC Releasing Device to the FCM-1 Module
Circuit Requirements. When connecting a releasing device to the FCM-1 module, note the
following:
1. For NFPA 13 and 15 applications, disable the Soak Timer (Soak=0000).
For NFPA 16 applications, set the Soak Timer (0600-0900 seconds).
Refer to your FACP’s Programming Manual for instructions.
2. For applications using power-limited circuits:
a) Use an End-of-Line device (P/N REL-47K) with the FCM-1 module. Connect the
End-of-Line device as shown in Figure 7.5.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
3. For applications not requiring power-limited circuits –
a) End-of-Line devices (P/N REL-47K) are not required; however, the releasing device circuit
is not supervised against shorts.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit.
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.
The FCM-1 module must be programmed with the correct releasing type code listed in your
FACP’s Programming Manual.
8.1 Description
The FRM-1 module is an addressable module that provides two isolated sets of Form-C relay
contacts.
Ratings for the dry relay contacts on a Form-C module are:
• Resistive – 2 amps @ 30 VDC (e.g. Electronic devices and strobes)
• Inductive – 1 amp @ 30 VDC (0.6pF) (e.g. Mechanical bells and horns)
• Pilot Duty – 0.5 amp @ 125 VAC (0.35pF) (e.g. Using a smaller relay to trip another relay)
For more information on the module specifications refer to the Installation Instructions provided
with this device. For information on transponders, refer to the specific transponder manual.
FRM-1
C
NC
NO
C
NC NO
SLC-frmC.wmf
9.1 Description
The B501 and B710LP Detector Bases, the B224RB plug-in relay detector base, and the B501BH
sounder base provide the connection between the SLC and a variety of intelligent detectors. Use the
B710HD Detector Base with all HARSH™ detectors.
For more information refer to the Installation Instructions documents provided with these devices.
SLC
To next device
on SLC
For connection of
cable shield
RA400Z
SLC-B501wire.wmf
Remote LED
Annunciator
(Optional)
NOTE: The B710LP base wiring is identical to the B501, except there is no shield terminal.
Figure 9.2 shows typical wiring of a B710HD detector base (for use with a HARSH™ detector)
connected to an SLC. An optional RA400Z Remote LED Annunciator is shown connected to the
base.
SLC
To next device
on SLC
For connection of
cable shield
Power to next
To compatible device
UL Listed
Power Supply
RA400Z
Remote LED
Annunciator
(Optional)
B710HD.wmf
NOTE: Use a spade lug to wire the Remote LED Annunciator (–) to Terminal 2 (–).
SLC In
Conduit
SLC-224BIwire.wmf
ISO-X
Isolator Module
To next device
on SLC
For connection of
cable shield
3 Relay Common
2 Normally Open
1 Normally Closed
SLC
b224rb.wmf
OUT
+4 –5
4 5
3 21
IN External supply
-3 – 2 +1
(-) Power
External (+) Power
24V
B501BHWiring.wmf
Supply
UL-listed
Class A Optional Wiring EOL Relay
24V
10.1 Description
The NBG-12LX is an addressable manual pull station with a key-lock reset feature.
For more information refer to the Installation Instructions document provided with this device.
SLC-nbg12.cdr
For NACs:
(Vms - Vom)
Rmax =
(Nb)(Ib)
Where:
Rmax = maximum resistance of the 24 VDC wires
Vms = minimum supply voltage (see Table A.1 below)
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N = total number of detectors on the 24 VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 24 VDC power circuit which must function at the same time in
alarm
Ia = detector current in alarm
Ir = end-of-line relay current
Nb = number of Notification Appliance Devices
Ib = Notification Appliance current when activated
NOTE: This simplified equation assumes that the devices are at the end of a long wire run.
The minimum supply voltages produced by Notifier power supplies are listed below:
FACP Vms Power Supply Vms
AFP-100 18.1 FCPS-24/E 19.1
AFP-200 19.4 FCPS-24S6/FCPS-24S8 19.1
NFS-640/E 19.15 MPS-24A/E 19.6
MPS-24B/E 20.1
MPS-400 19.23
ACPS-2406 19.8
AMPS-24/E 20.27
ELR
(Use 47K with FCM-1
or 3.9K with FZM-1) Supervised NAC or IDC
Power Supervision
Relay
(EOLR-1)
SLC-psr.cdr
FCM-1
Power Supervision
Relay
(EOLR-1)
FMM-1
SLC-psr-2address.cdr
Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit
End-of-line
Resistor
FCM-1
Circuit supervised
by control panel
SLC-nacY1.cdr
FCM-1
Circuit supervised
by control panel
SLC-nacZ1.cdr
B.1 Introduction
There are one primary and three secondary UL–listed surge protectors approved for use with the
FACPs listed in this appendix.
Primary Surge Protector:
• 326-2M TII Station Protector
Secondary Surge Protectors:
• DTK-2LVLP-F: Diversified Technology Group, Inc. (DITEK) 1720 Starkey Rd. Largo, FL
33771 (800) 753-2345.
• SLCP-30: EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
• PLP-42N: Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019
(800) 727-9119
NOTE: For detailed information refer to the installation documentation supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs
outside the building.
• Install primary protection only as shown in this document.
• Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional
suppressors in series with the SLC wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring
connected to the surge suppressor input may be routed outside the building as shown below.
Building #2 Building #1
P P
FACP
P = Primary
S = Secondary S
P P S
SLC-ssbuild1.cdr
Surge Suppressor
B.2 Installation
Mounting of the secondary surge suppressor must be inside the FACP enclosure or in a separate
enclosure listed for fire protective signaling use.
• Locate on an available stud and secure with nut.
• Unit is connected in series with the SLC Loop to protect the Control Panel.
• Provide a common ground to eliminate the possibility of a differential in ground potentials.
IN OUT
SLC Terminal Block
2LVLP-F
–
+
SLC-lvlp1.cdr
SLC Loop
IN OUT
PLP-42N Connections
PLP-42N
GRND
L4
L4
Style 6 (Class A)
L3
INPUT
L3
L2
L2
L1
L1
–
GRND
L4
L4
+
OUTPUT
L3
INPUT
L3
L2
L2
SLC-plpn1.cdr
SLC Loop
L1
L1
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to
connect the unit’s ground terminal to equipment ground. Wire length must be minimized to
provide best protection.
SLCP-30 Connections
SLCP-30
IN OUT
SLC Terminal Block
SLCP-30
SLC Loop
–
+
SLC-slcp1.cdr
IN OUT
IN OUT
+
–
SLC-lvlp2.cdr
SLC Loop
IN OUT
PLP-42N Connections
PLP-42N
GRND
L4
Style 6 (Class A)
L3
INPUT
L3
L2
L2
L1
L1
+
GRND
L4
L4
–
OUTPUT
L3
INPUT
L3
L2
SLC-plpn2.cdr
L2
SLC Loop
L1
L1
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to
connect the unit’s ground terminal to equipment ground. Wire length must be minimized to
provide best protection
SLCP-30 Connections
SLCP-30
IN OUT
SLC-slcp2.cdr
IN OUT
SLC-lvlp3.cdr
Return Loop IN OUT
Style 6 (Class A)
NOTE: Do not connect shield (if present) to surge protector or fire panel.
PLP-42N Connections
PLP-42N
L4
OUTPUT
L3
INPUT
L3
SLC Loop
L2
L2
L1
L1
SLC-plpn3.cdr
Optional Four-wire
Return Loop
Style 6 (Class A)
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to
connect the unit’s ground terminal to equipment ground. Wire length must be minimized to
provide best protection. Do not connect shield (if present) to surge protector or fire panel.
SLCP-30 Connections
SLCP-30
SLC-slcp3.cdr
Optional Four-wire
Return Loop IN OUT
Style 6 (Class A)
NOTE: Do not connect shield (if present) to surge protector or fire panel.
SLC-lvlp3.cdr
Return Loop IN OUT
Style 6 (Class A)
NOTE: Do not connect shield (if present) to surge protector or fire panel.
PLP-42N Connections
PLP-42N
L4
OUTPUT
L3
INPUT
L3
SLC Loop
L2
L2
L1
L1
SLC-plpn3.cdr
Optional Four-wire
Return Loop
Style 6 (Class A)
NOTE: Use 12 AWG (3.31 mm2) to 18 AWG (0.82 mm2) wire with crimp-on connectors to
connect the unit’s ground terminal to equipment ground. Wire length must be minimized to
provide best protection. Do not connect shield (if present) to surge protector or fire panel.
SLCP-30 Connections
SLCP-30
Optional Four-wire
Return Loop IN OUT
Style 6 (Class A)
NOTE: Do not connect shield (if present) to surge protector or fire panel.
B
F
B224BI, see isolator bases
FACP, see Fire Alarm Control Panels
B501 53
factory preset 39
B710HD 13, 53
FAPT-751 13
B710LP 53
FAPT-851 13
backup alarm, see degraded mode
fault 15, 33, 35
bases 13
fault condition 31
building entry/exit 65
Fault Isolator Module, see isolator module
FCM-1 45, 47, 48, 49, 60, 62, 63
C FCPS-24 59
cabinet 25 FDM-1, see dual monitor module
circuit fault 13 Fire Alarm Control Panels 9, 65
circuit, speaker/telephone 12 Fire alarm service 39, 41, 42, 43, 44
CLIP (Classic Loop Interface Protocol) 11, 16 FlashScan 11, 16, 32
coded output 62, 63 floating segments 27
common ground 66 FMM-1, see monitor module
communications loop 32 FMM-101, see miniature monitor module
conduit, types of 25–27 Form-C contacts 51
connector screw 25 four-wire configuration 48
connectors, crimp-on 66, 67, 68, 69 FSB-200, FSB-200S 13
control modules 12 FSI-751 14
CPX-551 14 FSI-851 14
CPX-751 14 FSL-751 14
FSP-751/T 14
D FSP-851/T 14
FST-751/R 14
DC resistance 19
FST-851/R 14
degraded mode 12, 37, 40, 41
FTM-1 12
R V
RA400Z 53, 54 VIEW® 14
ratings, dry contact 51
relay bases 13, 31 W
relay module 13, 51
wiring 51 Waterflow alarm service, automatic and manual
39, 41, 42, 43, 44
Releasing Device
FCM-1 Connections 49 wire length
four-wire SLC 20
remote switching center 13
two-wire SLC 19
RFX Wireless Interface 14
wire nuts 26
rotary switches 39, 42, 43, 44
wire size 17, 18
wiring
S isolater bases 55
SDRF-751 14 isolator modules 32
Security service 39, 41, 42, 43, 44 NACs 62
shield 69 pull stations 57
shield drain wire 25 relay modules 51
shielded wire 26 SLCs 39, 41, 42, 43, 44
shield-termination 25 wiring pair 65
short circuit 31, 32 wiring style requirements 15
Signaling Line Circuit 11
see also SLC X
SLC
capacity of devices 15 XP Series Transponders 13
performance 15 XP5-C Transponder 12
setting an SLC address 39 XP5-M Transponder 12
terminal block 26
trouble conditions 15 Z
wiring 39, 41, 42, 43, 44 zone interface module 37, 43, 44
SLC-30 65
sounder bases 13, 31
speaker circuit 12
Sprinkler supervision 39, 41, 42, 43, 44
standard bases 13
Style 4, Style 6, Style 7, Style B,Style D, Style Y,
Style Z see NFPA Style 29
supervised circuits 60, 62
supervised devices 60
suppressors, surge 65
surge protector 11, 65
System 5000 with AIM-200 18, 23
T
telephone circuit 12
terminal block, NAC 63
termination of shield 25
transponders 13
trouble conditions 15, 31
trouble warning 33
T-tapping 19, 29, 30, 35, 36
twisted shielded pair wiring 17, 18
twisted unshielded pair wiring 17, 18
twisted-pair wire 26
two-wire configuration 47
two-wire detectors 60
www.notifier.com