Interface Units
T&D
Energy Automation & Information
MiCOM P59x Series Interface Units
2
Connections to V.35 Connections to X.21 Connections to GPS Antenna
ITU-T V.35 electrical connections to ITU-T X.21 electrical connections to The GPS antenna that is supplied
the P592 interface unit are made the P593 interface unit are made (MOTOROLA GCNAC1121) comes
via a standard female 34 pin ‘M’ via a standard male 15 way complete with 6 metres of cable
block connector on the rear of the D-subminiature connector. terminating in a standard BNC type
device. Since the V.35 signals are coax plug that can be plugged
The use of twisted pairs of 24
either of ±0.55V or ±12V straight into the rear of the P594
AWG (19/0.12mm) stranded
magnitude, the cable connecting the module. Should the extension be
cable, foil shielded, with drain wire
P592 unit and the multiplexer must required this can be requested from
is recommended. Due to the
be properly screened against ALSTOM T&D Ltd Protection and
similarities between RS449 and
electromagnetic noise and Control, at time of order, enabling
X.21, the P593 may also be
interference. up to 20m of cable in total.
suitable for connection to
The interface cable should consist of RS449/RS422 equipment. External connections of the P594
pairs of 24AWG (19/0.12mm), are shown in figure 2d.
External connections of the P593
twisted and shielded, and have a
are shown in Figure 2c.
characteristic impedance of about
100 ohms. The choice of grounding
depends on the local codes and
practices.
It is recommended that the interface
cable shield is connected to the
multiplexer frame ground. The cable
may be connected to the MiCOM
P592 case earth if no earth loop
current is expected.
External connections of the P592
are shown in Figure 2b.
Transmit Signal
data/clock conversion Rx
(to PCM) 4 circuit
Fibre optic
communication
7 (see Note 2)
Receive Signal
data/clock conversion Tx
(to PCM) circuit
8
25 +5V
Auxiliary MiCOM P591
DC supply 26 Optical to G.703
Vx co-directional PCM interface unit
Notes:
Case earth 1. The case earth must be connected to the
(see Note 1) protective earth conductor
2. Optical connections are of BFOC 2.5 type
unless otherwise specified
3
DSR
E
Data set ready
V
Receive timing X Signal
R conversion
Receive data circuit
T
Tx
V.35 loopback
Fibre optic
P loopback Fibre optic
V.35 communication
Transmit data S
communication Signal (see Note 2)
interface U conversion
Terminal timing circuit
W
Y Rx
Transmit timing
AA
Clock
CTS switch
Clear to send D Notes:
(see Note 6) 1. The case earth must be connected to the
CTS off protective earth conductor.
Request to send C
DSR off 2. Optical connections are of BFOC 2.5 type
B unless otherwise specified.
Signal ground OV (see Note 5) V.35 loopback 3. Equipment is normally supplied with OV
Fibre optic loopback common return signal and case earth
+ electrically bonded. Removal of an internal
Auxiliary dc supply Vx Supply healthy soldered link allows electrical isolation if
A required.
V.35 protective ground
MiCOM P592 4. Female V.35 Winchester connector.
Case earth Optical to V.35 communication 5. Auxiliary dc supply terminals.
(see Note 3) interface unit
6. "Request to send" is pulled "on" permanently.
A
2
TXD Signal
9
B conversion
circuit
A Rx
4
RXD Signal Fibre optic
11 conversion communication
B circuit (see Note 2)
A
6
X.21 Clock
communication 13
B Tx
interface
PL1 Normal operation Normal operation
X.21 loopback Fibre optic loopback
A
3
Control See Note 6 Supply healthy Notes:
10
B 1. The case earth ust be connected to the
A Clock
5 protective earth conductor.
Indication X.21 loopback 2. Optical connections are the BFOC 2.5 type
12
B unless otherwise specified.
Fibre optic loopback
Common 3. Equipment is normally supplied with 0V
8 0V
common return signal and case earth
See Note 3 electrically bonded. Removal of an internal
1 soldered link allows electrical isolation if
Case earth required.
(see Note 1) 4. DB 15M X.21 conntect
+ +5V MiCOM P593 optical to X.21
Auxiliary dc supply Vx1 5. Auxiliary dc supply terminals
communication interface unit
0V 6. Control circuit is permanently driven off.
4
MiCOM P594 TX1
GPS timing module
TX2
Fibre optic
1 pulse per
GPS receiver TX3 second output
module
TX4
Healthy
0
1
2
B1 Number of 3
AC or DC satellite
Vx B2 4
aux supply + signals
5
received
6
7
8
Bulkhead jack socket Case
Pin terminal (PCB type) earth
5
High voltage withstand • DC supply interruption Atmospheric environment
• Dielectric withstand IEC 60255-11:1979 • Temperature
IEC 60255-5: 1977 The unit will withstand a 10ms IEC 60255-6:1988
interruption in the auxiliary
2kV rms for 1 minute between Storage and transit
supply, under normal operating
power supply terminals –25°C to +70°C
conditions, without de-energising.
connected together and the case
Operating
earth terminal. • EMC compliance
–25°C to +55°C
2 kV rms for 1 minute between 89/336/EEC
IEC 60068-2-1:1990 Cold
power supply terminals
Compliance with the European
connected together and the IEC 60068-2-2:1974 Dry heat
Commission Directive on EMC is
interface signal terminals • Humidity
claimed via the Technical
connected together.
Construction File route. IEC 60068-2-3:1969
• High voltage impulse
Generic Standards were used to 56 days at 93% RH and 40°C
IEC 60255-5: 1977 establish conformity.
• Enclosure protection
Three positive and three negative EN 50081-2:1994
impulses of 5kV peak, 1.2/50µs, EN 50082-2:1995 IEC 60259:1989
0.5J between power supply IP50 (dust protected)
• Product safety
terminals connected together and
the case earth terminal. 73/23/EEC °Mechanical environment
Three positive and three negative Compliance with the European • Vibration
impulses of 5kV peak, 1.2/50µs, Commission Low Voltage
IEC 60255-21-1:1988
0.5J between power supply Directive.
terminals connected together and Response Class 1
Compliance is demonstrated by
the interface signal terminals reference to generic safety
connected together. standards.
Cases
Three positive and three negative EN 61010-1:1993/A2:1995 The MiCOM P590 Series units are
impulses of 5kV peak, 1.2/50µs, EN 60950: 1992/A11: 1997 housed in cases as shown in
0.5J across the power supply Figure 3.
terminals. • Weight 2.2kg
6
Information required with order
Interface unit
Electrical connections
G.703 1
V.35 2
X.21 3
GPS timing 4
Supply Vx
P591
24 - 48Vdc 4
110 - 250Vdc 5
P592/P593
24 - 250Vdc 6
P594
24 - 125Vdc 7
48 - 250Vdc / 96 - 240Vac 8
Your contact:
7
© 2003 ALSTOM. - 020300 - Electronic file
Publication: P59x/EN BR/Eb
TRANSMISSION & DISTRIBUTION Energy Automation & Information, Le Sextant, 3 avenue André Malraux, 92300 Levallois-Perret. France
Tel: +33 (0) 141 49 20 00 Fax: +33 (0) 1 41 49 24 85 energy-automation.information@tde.alstom.com www.tde.alstom.com
Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70
ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product
referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.