The document provides technical specifications and heat load calculations for an HVAC system for a building area.

Details provided include the dimensions and volumes of different areas, glass surfaces, wall and roof compositions, occupancy information, and factors considered in calculating the total heat load.

Factors included are solar and transmission gains through walls and roof, internal heat from people and equipment, and supply duct heat gain.

Summer AHU-XX Date: 7/20/2019

Client: CONDITIONS DB WB
Area(sq.ft) 285 Height 17 Outside 110 78
Volume(Cu.ft): 4845 Inside 72
Area(sq.ft) 290.52 Height 10
volume(Cu.ft): 2905
Area(sq.ft) 916 Height 8
Volume(Cu.ft): 7329
Difference 38 XXX
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 23 0.56 0 15079 Cu.ft 2
Glass(E) 12 0.56 0 60
Glass(W) 163 0.56 0 503
Glass(S) 12 0.56 0 CFM 503
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 204 27 0.35 1928 SENSIBLE HEAT FACTOR
wall (E) 102 41 0.35 1469 RSH 117407
wall (W) 102 35 0.35 1250 RTH 125543
wall (S) 0 39 0.35 0
Roof sun 58 0.5 0 SHF 0.94
Roof insulated 327 58 0.11 2086
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.13 (From tables/chart)
All glass 38 1.13 0
Partition glass 33 0.8 0 DEHUMIDIFIED AIR
Ceiling 1165 33 0.45 17294 16
Floor 33 0.5 0 DE AIR CFM 6759
Partition 1372 33 0.43 19469
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
503 38 0.1 1.08 2063
INTERNAL HEAT
People 15 People X 323 4845
HP 15.00 HP 2545 38175
Blower HP 0.3 2545 799
Miscell 0 3.41 0
Lights 2983 Watts 3.41 12716
ROOM SENSIBLE HEAT SUB TOTAL 102093
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 15314
TOTAL ROOM SENSIBLE HEAT (RSH) 117407
LATENT HEAT
cfm Gr/lb BF
502.6 29 0.1 0.68 991
People 15 People X 427 6405
Steam 0 lb/hr X
Appliances 0
Miscell 0 0
ROOM LATENT HEAT SUB TOTAL 7396
Supply duct Safety
leakage loss % + Factor 10% 740
TOTAL ROOM LATENT HEAT 8136
ROOM TOTAL HEAT(RTH) 125543
OUTDOOR AIR HEAT
Sensible 503 38 0.9 18565
Latent 503 29 0.9 8921
GRAND TOTAL HEAT SUB TOTAL 153029
2% 3061
GRAND TOTAL HEAT 156089
TR 13.01
7/20/2019
%RH Gr/lb
0 93
55 64

XXX 29

NTILATION
X ACPH

E HEAT FACTOR

(From tables/chart)