Heatload
Heatload
Heatload
Client: CONDITIONS DB WB
Area(sq.ft) 285 Height 17 Outside 110 78
Volume(Cu.ft): 4845 Inside 72
Area(sq.ft) 290.52 Height 10
volume(Cu.ft): 2905
Area(sq.ft) 916 Height 8
Volume(Cu.ft): 7329
Difference 38 XXX
Area or sun gain/
Item Factor Btu / Hour
Qty(Sq.ft) Temp diff
SOLAR GAIN GLASS VENTILATION
Glass(N) 23 0.56 0 15079 Cu.ft 2
Glass(E) 12 0.56 0 60
Glass(W) 163 0.56 0 503
Glass(S) 12 0.56 0 CFM 503
SOLAR & TRANS. GAIN-WALLS & ROOF
wall (N) 204 27 0.35 1928 SENSIBLE HEAT FACTOR
wall (E) 102 41 0.35 1469 RSH 117407
wall (W) 102 35 0.35 1250 RTH 125543
wall (S) 0 39 0.35 0
Roof sun 58 0.5 0 SHF 0.94
Roof insulated 327 58 0.11 2086
TRANS GAIN EXCEPT WALLS & ROOFS ADP 54.13 (From tables/chart)
All glass 38 1.13 0
Partition glass 33 0.8 0 DEHUMIDIFIED AIR
Ceiling 1165 33 0.45 17294 16
Floor 33 0.5 0 DE AIR CFM 6759
Partition 1372 33 0.43 19469
INFILTRATION & OUTSIDE AIR
outside air DB diff BF 1.08
503 38 0.1 1.08 2063
INTERNAL HEAT
People 15 People X 323 4845
HP 15.00 HP 2545 38175
Blower HP 0.3 2545 799
Miscell 0 3.41 0
Lights 2983 Watts 3.41 12716
ROOM SENSIBLE HEAT SUB TOTAL 102093
Supply duct Supply duct Fan HP Safety factor
heat gain% + leak loss % + % + 15% 15314
TOTAL ROOM SENSIBLE HEAT (RSH) 117407
LATENT HEAT
cfm Gr/lb BF
502.6 29 0.1 0.68 991
People 15 People X 427 6405
Steam 0 lb/hr X
Appliances 0
Miscell 0 0
ROOM LATENT HEAT SUB TOTAL 7396
Supply duct Safety
leakage loss % + Factor 10% 740
TOTAL ROOM LATENT HEAT 8136
ROOM TOTAL HEAT(RTH) 125543
OUTDOOR AIR HEAT
Sensible 503 38 0.9 18565
Latent 503 29 0.9 8921
GRAND TOTAL HEAT SUB TOTAL 153029
2% 3061
GRAND TOTAL HEAT 156089
TR 13.01
7/20/2019
%RH Gr/lb
0 93
55 64
XXX 29
NTILATION
X ACPH
E HEAT FACTOR
(From tables/chart)
FIED AIR