QCVN 09 2017 BXD ENGLISH Unofficial Translation by VGBC
QCVN 09 2017 BXD ENGLISH Unofficial Translation by VGBC
QCVN 09 2017 BXD ENGLISH Unofficial Translation by VGBC
QCVN 09:2017/BXD
Hanoi - 2017
Unofficial Translation by the Vietnam Green Building Council
CONTENTS
2
Unofficial Translation by the Vietnam Green Building Council
INTRODUCTION
QCVN 09:2017/BXD - “National Technical Regulation on Energy Efficiency Buildings” was reviewed by
the Construction Technique Institute (Vietnam Association of Structural Engineering and Construction
Technology) based on the QCVN 09:2013/BXD, submitted by the Department of Science, Technology and
Environment, and enacted by the Ministry of Construction under Circular 15/2017/TT-BXD, dated on
December 28, 2017.
QCVN 09:2017/BXD shall replace the QCVN 09:2013/BXD - “National Technical Regulation on Energy
Efficiency Buildings”, which was enacted by the Minister of Construction in Circular 15 /2013/TT-BXD
dated September 26, 2013.
The National Technical Regulation on Energy Efficiency Buildings was developed thanks to the support of
the Government of Denmark and the contribution of experts from the Vietnam Association of Civil
Engineering Environment, the International Finance Corporation (IFC), and the Pacific Northwest National
Laboratory (PNNL) of the United States Department of Energy.
3
Unofficial Translation by the Vietnam Green Building Council
1. GENERAL REQUIREMENTS
1.1. Scope
1.1.1 The National Technical Regulation on Energy Efficiency Buildings provides mandatory technical
standards in design, construction or retrofit of buildings with a gross floor area of 2,500 m2 or larger
of the following types:
1) Offices;
2) Hotels;
3) Hospitals;
4) Schools;
5) Commercials, services,
6) Residential.
1.1.2 The requirements of this Regulation apply to:
1) Building envelope;
2) Ventilation and air conditioning systems;
3) Lighting systems;
4) Other electrical equipment (electric motors, water heating systems).
NOTE: For retrofit projects of building types within the scope of this Regulation, the mandatory
requirements for building envelope, ventilation and air conditioning systems, lighting systems and
other electrical equipment shall apply to the corresponding systems to be retrofitted.
1.2. Coverage
This Regulation shall apply to all organizations and individuals involved in activities pertaining to
construction of buildings within the scope of this Regulation.
1.3. References
QCXDVN 05:2008/BXD Vietnam Building Code: Dwellings and Public Buildings -
Occupational Health and Safety;
QCVN 12:2014/BXD National Technical Regulation on Electrical Installations of Dwelling
and Public Buildings;
AMCA 205 Energy efficiency classification for fans;
ANSI Z21.10.3 Gas Water Heater, Volume 3, Storage, with Input Ratings above
75,000 Btu/h, Circulating and Instantaneous Water Heaters;
ARI 210/240 Performance rating of unitary air-conditioning and air-source heat
pump equipment;
ARI 340/360 Performance rating of commercial and industrial unitary air-
conditioning and heat pump equipment;
ARI 365 Commercial and industrial unitary air-conditioning condensing units;
ARI 550/590 Performance rating of water-chilling packages using the vapor
compression cycle;
ARI 560-2000 Absorption water chilling and water heating packages;
ASHRAE 90.1-2016 Energy standard for buildings except low-rise residential buildings;
NEMA MG 1-2016 Motors and generators;
4
Unofficial Translation by the Vietnam Green Building Council
NFRC 200-2017 Procedure for determining fenestration product Solar Heat Gain
Coefficients and Visible Transmittance at normal incidence;
ISO 6946-2017 Building components and building elements: Thermal resistance and
thermal transmittance - Calculation method;
ISO 10456-2007 Building materials and products – Hygrothermal properties -
Tabulated design values and procedures for determining declared and
design thermal values
ISO 12759:2010 Fans - Efficiency classification for fans
TCVN 4605:1988 Heating techniques - Insulating components - Design standard
TCVN 5687:2010 Ventilation, Air-conditioning - Design standard;
TCVN 6307:1997 Testing of refrigerating systems;
(ISO 916:1968)
TCVN 6576:2013 Non-ducted air conditioners and heat pumps - Testing and rating for
(ISO 5151:2010) performance;
TCVN 7540:2013 Three-phase asynchronous squirrel cage electrical motors:
Part 1: Energy efficiency (TCVN 7540-1:2013); Part 2: Methods for
determination of energy efficiency (TCVN 7540-2:2013);
TCVN 7830:2015 Non-ducted Air Conditioners - Energy Efficiency;
TCVN 9258:2012 Heat protection for residential buildings - Design guide;
TCVN 10273-1:2013 Air-cooled air conditioners and air-to-air heat pumps - Testing and
(ISO 16358-1:2013) calculating methods for seasonal performance factors - Part 1: Cooling
seasonal performance factor;
5
Unofficial Translation by the Vietnam Green Building Council
6) Thermal Resistance: The inverse of overall heat transfer coefficient U0: R0 = 1/Uo, measured in
m2.K/W;
7) Lamp efficiency: The ratio of rated light output to power consumption, measured in lumen/W;
8) Efficiency of the ventilation & air-conditioning systems: The ratio of output energy (useful energy
at the time of use) to input energy, in consistent unit, for a specific length of time, measured in %;
9) Lighting power density (LPD): The ratio of electric lighting output to the illuminated area,
measured in W/m2;
10) Building envelope: Building envelope or building enclosure consists of opaque or transparent walls,
windows, doors, skylights, among others, that form enclosed spaces within a building.
1.4.2. Symbols, measurement units and acronyms
1) Symbols and measurement units
SHGC Heat gain coefficient (Solar Heat Gain Coefficient) of glazing, published by
manufacturers or determined in accordance with prevailing standards, dimensionless.
In case manufacturers avails of the shading coefficient SC, SHGC = SC x 0.86;
SC Shading Coefficient
R0 Thermal resistance of enclosing assembly, measured in m2.K/W.
Thermal Transmittance U0 = 1/R0, W/(m2.K);
OTTVT Overall thermal transfer value for walls – the mean intensity of the heat flux transferred
through 1 m2 of exterior walls, W/m2;
OTTVM Overall thermal transfer value for roofs – the mean intensity of the heat flux transferred
through 1 m2 of roofing, W/m2;
WWR Window to Wall Ratio, measured in %;
2) Acronyms
AHU Air Handling Unit;
AMCA Air Movement and Control Association International, Inc.;
ANSI American National Standards Institute;
ARI Air Conditioning and Refrigeration Institute;
ASHRAE American Society of Heating, Refrigerating and Air Conditioning Engineers;
ASME American Society of Mechanical Engineers;
HVAC Heating, Ventilation and Air Conditioning
NEMA National Electric Manufacturers Association
NFRC National Fenestration Rating Council, Inc.
ISO International Organization for Standardization
QCVN National Technical Regulation;
TCVN National Standard
6
Unofficial Translation by the Vietnam Green Building Council
2. TECHNICAL REQUIREMENTS
2.1. Building envelope
2.1.1 Technical requirements for building envelope shall only apply to air-conditioned spaces.
2.1.2 Requirements for building exterior walls and roofs
1) Thermal Resistance R0 of the opaque parts:
- Exterior walls above the ground surface (opaque parts of the walls) of the air-conditioned spaces
shall maintain a minimum overall thermal resistance value R0.min no smaller than 0.56 m2.K/W;
- Flat roofs and roofs with gradient of less than 15 degrees placed directly above the air-
conditioned spaces shall maintain a minimum overall thermal resistance value R0.min no smaller
than 1.00 m2.K/W.
NOTES:
- Flat roofs with reflective materials: Thermal resistance value R0.min may be multiplied by a coefficient of
0.80 for roofs designed with reflective materials that have a solar reflectivity within a range of 0.700.75(1)
to increase heat reflectivity for the exterior roof surface (Annex 5);
- Roofs with gradient of 15 degrees or above: The minimum total thermal resistance value for roofs may
be identified by multiplying R0.min with a coefficient of 0.85;
- Roofs which are not obliged to follow Item 2.1.2: More than 90% of the roof is covered with a permanent
sunshade with ventilation. The sunshade must be installed at a minimum clearance of 0.3 m from the roof
surface to be recognized as having ventilation between the roof and sunshade (double-layer roof with an
air cushion in between).
SHGC
WWR (%)
North South Other orientations
20 0.90 0.90 0.80
30 0.64 0.70 0.58
40 0.50 0.56 0.46
50 0.40 0.45 0.38
60 0.33 0.39 0.32
70 0.27 0.33 0.27
80 0.23 0.28 0.23
90 0.20 0.25 0.20
100 0.17 0.22 0.17
NOTES:
- WWR shall be calculated for each of the façades then averaged for the entire building(2);
- If WWR does not match with the values in the table, SHGC values shall be determined through linear
interpolation using the nearest higher and lower WWR values;
1 VGBC’s comment: It should be materials that have a solar reflectivity higher than 0.70.
2
VGBC’s comment: Actually there is no need to calculate the average WWR of the building as SHGC requirements are given for
different orientations.
7
Unofficial Translation by the Vietnam Green Building Council
- SHGC of each façade or the entire building can be determined through the area-weighted average value
of the transparent parts on building façades:
𝐧
∑𝐢=𝟏(𝐒𝐇𝐆𝐂𝐢 × 𝐀𝐢 )
SHGC =
𝐀𝟏 + 𝐀𝟐 + …+ 𝐀𝐧
SHGCi, Ai – respectively, SHGC value and area of the transparent part i (i=1, n).
- Maximum SHGC value of glazed roofs is set at 0.3. For attic spaces designed with daylighting,
maximum SHGC value of skylight is 0.6.
- In case of building facades being installed with permanent vertical or horizontal sunshades,
SHGC values in Table 2.1 may be adjusted by multiplying them with the A coefficients in Table
2.2a and Table 2.2b.
Table 2.2a - Coefficient A for permanent horizontal sunshades
8
Unofficial Translation by the Vietnam Green Building Council
- For buildings adjacent to the street, ground floor spaces, if designed for product and service
promotion purposes, shall not have to comply with the SHGC requirements when meeting all
of the following requirements: (a) Ground floor height is no greater than 6m; (b) Continuous
sunshades with b/H > 0.5; (c) The area of glazing is smaller than 75% of the gross wall area of
the ground floor at the side adjacent to street.
3) If the aforementioned requirements for R0 and SHGC are not applicable, the overall thermal transfer
value (OTTV) of the opaque and transparent parts of building envelope shall be applied; and
required as follow:
- OTTVT for walls is no greater than 60 W/m2;
- OTTVM for roofs is no greater than 25 W/m2.
NOTE: OTTVT for walls and OTTVM for roofs are determined using prevailing standards and technical
guidelines.
2.1.3 Requirements for building components and elements of the walls and roofs
1) Thermal conductivity coefficient λ of materials and Overall thermal resistance value R0 of walls
and roofs are determined in accordance with ISO 6946:2017, or following the instructions in Annex
1, 2, 3, 4 and 6 of this Regulation;
NOTES: Thermal conductivity coefficient λ of a material can be determined based on manufacturer’s
published data, or according to TCVN 4605:1988, TCVN 9258:2012.
2) SHGC Certification of glazing must be provided by manufacturers. SHGC values of glazing shall
be determined in accordance with NFRC 200-2017 standards and conducted by an independent
laboratory.
9
Unofficial Translation by the Vietnam Green Building Council
Table 2.3. Coefficient of performance (COP) for direct electric air conditioners
COPMin,
Type of equipment Cooling output, kW Test procedures
kW/kW
10
Unofficial Translation by the Vietnam Green Building Council
2) Each of chillers, hot air systems, cooling tower fans and pumps with capacity equal to or greater
than 5 HPs (3.7 kW) must be equipped with an automatic control device to adjust capacity and flow
rate according to cooling or heating load and water level.
3) For ventilation and air conditioning system with capacity equal to or greater than 5 HPs (3.7 kW),
fan motors must have a Fan Efficiency Grade (FEG) higher than 67 as rated under AMCA Standard
205.
NOTE: ISO 12759:2010 can also be applied.
4) Buildings with central air conditioning system must be equipped with enthalpy recovery system.
Energy recovery efficiency of the equipment shall be no smaller than 50%.
5) Insulation material and thickness of refrigerant conduits, cooled water conduits, air supply and air
recovery ducts must be designed, installed and commissioned in accordance with a technical
standard, which is selected for the entire building.
NOTE: The technical standard shall be selected by project owner. Applicable standards may include: TCVN
5687:2010, ASHRAE 90.1 and other equivalent standards.
6) Coefficient of Performance – COP (or Cooling Seasonal Performance Factor – CSPF) specified in
Table 2.3 and Table 2.4, and Fan Efficiency Grade - FEG must be reviewed by an independent
laboratory. Prior to the acquisition and installation of air-conditioning equipment, testing
certificates of each technical criteria must be provided by manufactures.
3 VGBC’s comment: Air-cooled chillers with separated condenser should be rated with matching condensers.
4 VGBC’s comment: It should be single-effect chiller according to ASHRAE 90.1-2013.
11
Unofficial Translation by the Vietnam Green Building Council
2.3. Lighting
2.3.1 Natural lighting
Workrooms, study rooms and reading rooms with daylit zones must be equipped with artificial
lighting control systems.
NOTE: Lighting control requirements for daylit zones shall not be applied to hospitals and medical centers,
apartments and other building types that have specialized lighting needs.
3) Lighting control
a) Lighting control
- Design and install lighting shut-off controls to turn lighting devices off when not needed,
independent controls should be provided for areas of no more than 2,500 m2 but not more than
one floor(5);
5 VGBC’s comment: Based on ASHRAE Standard 90.1-2007, the following details can be added:
Design and install automatic lighting shut-off controls which can function on either:
1. a scheduled basis using time-of-day operated control device that turns lighting off at specific programmed times.
An independent program schedule shall not cover an area of more than 2,500 m2 and shall not cover more than one floor;
2. an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space;
3. a signal from another control or alarm system that indicates the area is unoccupied.
12
Unofficial Translation by the Vietnam Green Building Council
- Each control device shall be designed and installed to cover a maximum occupied area of 250
m2 for a space area equal to or less than 1,000 m2; or to cover a maximum occupied area of
1,000 m2 for a space area greater than 1,000 m2.
- For areas within a distance of 6 meters to an exterior wall, which is designed with glazing with
WWR ≥ 40%, lighting control devices must be installed to enable reducing lighting power.
NOTE: This requirement is not applicable to spaces with around-the-clock lighting requirement; as well
as spaces with special requirement for safety and security.
c) Upon installing, testing and commissioning of electric motors as per prevailing regulations,
manufacturers’ published information of the minimum motor efficiency affixed on housing must
be tested.
13
Unofficial Translation by the Vietnam Green Building Council
14
Unofficial Translation by the Vietnam Green Building Council
b) Prior to the installation of water heaters, equipment efficiency data provided by manufacturers must
be reviewed.
c) Thermal insulation of hot water pipes shall be designed, installed and commissioned in accordance
with a design standard, which is selected for the entire building.
d) Control of water heating systems
Temperature control systems shall be installed to maintain water temperature at a maximum of
49°C when in use;
Temperature control systems shall be installed to maintain tap water temperature at washbasins
and bathtubs in public restrooms at a maximum of 43°C.
Recirculating pumps used to maintain storage tank water temperature shall be controlled to
operate correspondingly with the operation mode of hot water supply system.
e) For apartment buildings designed with centralized water heating systems, a renewable energy
source (solar, wind, heat recovery, etc.) shall be used as a supplement to the main energy source
for water heating systems.
3. REGULATION ON MANAGEMENT
3.1. Design documentation of new construction or retrofit of buildings within the scope of this
Regulation shall include a narrative report demonstrating the compliance with the requirements of
this Regulation.
3.2. The review and assessment process of building design, construction and commissioning shall be
conducted in accordance with the prevailing regulations, including QCVN 09:2017/BXD.
4. IMPLEMENTATION
4.1. The Science - Technology and Environment Department (Ministry of Construction) is responsible
for providing implementation guidelines of QCVN 09:2017/BXD to concerned parties.
4.2. Governmental authorities for construction are responsible for monitoring the compliance with
QCVN 09:2017/BXD of construction investment activities within their management duties
according to the prevailing regulations.
4.3. For any problems that may arise during the adoption of this Regulation, the concerned parties shall
contact the Science - Technology and Environment Department (Ministry of Construction) for
guidance and support.
15
Unofficial Translation by the Vietnam Green Building Council
Thermal
Unit weight,
Name of Material conductivity ,
kg/m3
W/(m.K)
1. Concrete
Cement wire mesh roof tile 2500 2.04
Reinforced concrete 2400 1.55
Heavy-weight concrete 2200 1.20
1500 0.70
Light-weight concrete
1200 0.52
(cinder concrete)
1000 0.41
1000 0.40
800 0.29
Autoclaved foam concrete
600 0.21
400 0.15
800 0.29
Autoclaved foam silicate concrete 600 0.21
400 0.15
2. Gypsum
Gypsum drywall board 1000 0.23
Gypsum-slag concrete 1000 0.37
3. Baked materials and mortars
Baked clay brick 2000 0.93
Baked clay brick 1600 0.70
Baked clay brick, bonded with heavy-weight mortar 1800 0.81
Baked clay brick, bonded with light-weight mortar 1700 0.76
16
Unofficial Translation by the Vietnam Green Building Council
Thermal
Unit weight,
Name of Material conductivity ,
kg/m3
W/(m.K)
Hollow brick (1300 kg/m3), bonded with light-weight 1350 0.58
mortar (1400 kg/m3)
Multi-hole brick, bonded with heavy-weight mortar 1300 0.52
Cement mortar 1800 0.93
Three-component mortar 1700 0.87
Lime mortar 1600 0.81
4. Non-fired bricks and Autoclaved Aerated Concrete (AAC) blocks
Cinder block 1400 0.58
Silicate bricks, bonded with heavy-weight mortar 1900 0.87
Autoclaved aerated non-fired brick 400 – 900 0.12 – 0.13
Autoclaved Aerated Concrete (AAC) 400 – 800 0.153
5. Glass materials
Glass (wall, window) 2500 0.78
Fiberglass 200 0.06
6. Wood materials
Pine and cedar (across the grain) 550 0.15
Pine and cedar (along the grain) 550 0.17
Plywood board 600 0.17
600 0.16
Fiberboard 250 0.08
150 0.06
Corkwood 250 0.07
7. Metals
Steel, sheet metal 7850 58
Aluminum 2600 220
NOTES:
- Thermal conductivity: 1 W/(m.K) = 0.86 kcal/m.h.0C;
- Thermal conductivity value of material can be taken from experimental results or ISO 10456:2007
technical standards.
17
Unofficial Translation by the Vietnam Green Building Council
Annex 4(6): Thermal resistance of unventilated air layer Ra (m2.K/W) (for reference)
A. Wall surface
1 Polished white limestone 0.35
2 Polished dark limestone 0.50
3 Polished white marble 0.30
4 Polished dark marble 0.65
5 Polished light grey granite 0.55
6 polished grey granite 0.60
7 White glazed-brick 0.26
8 bright brown glazed-brick 0.55
9 Dusted common brick 0.77
10 New-red common brick 0.7 – 0.74
11 Bright surface tile 0.45
12 Smooth, even concrete surface 0.54 – 0.65
13 Yellow-white painted mortar surface 0.42
14 Dark painted mortar surface 0.73
15 White painted mortar surface 0.40
16 Light blue painted mortar surface 0.59
17 Grey cement painted mortar surface 0.47
18 White cement painted mortar surface 0.32
19 Plain wood 0.59
20 Dark painted wood 0.77
21 Light yellow painted wood 0.60
6 VGBC’s comment:
The values in this table apply when the emissivities of the surfaces bounding the air layer are higher than 0.8.
In other configurations, thermal resistance of unventilated air layer should be calculated following ISO 6946.
18
Unofficial Translation by the Vietnam Green Building Council
B. Roof surface
22 New white fibro-cement board 0.42
23 white fibro-cement board, 6-month used 0.61
24 white fibro-cement board, 12-month used 0.71
25 White corrugated sheet 0.26
26 Black corrugated sheet 0.86
27 Red or brown roof tile 0.65 – 0.72
28 Grey cement roof tile 0.65
29 New galvanized steel sheet 0.30
30 Dusted galvanized steel sheet 0.90
31 Unpolished aluminum 0.52
32 Unpolished aluminum 0.26
C. Painted surface
33 Pink paint 0.52
34 Blue paint 0.64
35 Bright-blue cobalt paint 0.58
36 Purple cobalt paint 0.83
37 Yellow paint 0.44
38 Red paint 0.63
D. Transparent materials
39 7 mm-thick glass 0.076
40 4.5 mm-thick glass 0.04
41 6 mm-thick glass with heat absorbing surface 0.306
42 0.1 mm-thick polyclovinil screen 0.096
43 0.08 mm-thick AFF polyamide screen 0.164
44 0.085 mm-thick AFF polyethylene screen 0.109
Annex 6: Total thermal resistance R0 of common walls and roofs (for reference)
19
Unofficial Translation by the Vietnam Green Building Council
E. Non-autoclaved aerated foam concrete brick wall (standard thickness: 110/220 mm)
NOTES:
1
TCVN 1451:1998 Solid clay bricks
2
TCVN 1450:2009 Hollow clay bricks
3
TCVN 7959:2011 Lightweight concrete - Autoclaved aerated concrete bricks (AAC)
4
TCVN 6477:2011 Concrete brick
5
TCVN 9029:2011 Lightweight concrete - Non-autoclaved aerated, foam concrete bricks - Specifications
6
TCVN 7575:2007 3D construction panels
20