Brosur Katalog Fire Alarm HOOSEKI
Brosur Katalog Fire Alarm HOOSEKI
Brosur Katalog Fire Alarm HOOSEKI
Semi Addressable
Full Addressable
ADDRESSABLE FIRE ALARM CONTROL PANEL CONVENTIONAL FIRE ALARM CONTROL PANEL
FEATURES
FEATURES Two-Stage alarm delay function :
At the first stage, when the detector sends the signal for the first time, the control
English LCD Screen (240 x 128 or 240 character).
LCD backlight energy-saving protection function. panel will automatically reset the signal and enter the second stage for standby
Two-wire circuits for supper long transmission distance after 8 seconds.
(up to 1,5 km between the control panel and modules). At the second stage, if there is another signal sent by the detectors within 9-40
The data memory device can store up to 2000 historical records permanently seconds, the control panel will triggered the fire alarm, else reset the alarm signal.
(the device in graphic system can be expandable up to 20 million records). This will prevent the control panel from sending false alarms.
Composed voice alarm function (broadcost)in human voice to operators). Standby battery protection :
Voice guidance function (while operating) During power-cut, when the standby battery is under DC 18V it will automatically
Abnormal temperature protection function (I/O modules over loading).
stop discharging to extend battery life.
5LCs, IDCs are equipped with insulation for false inspection function.
Protection against lighting surge :
Protection against lightning surge. HOOSEKI Fire Alarm
I/O modules miswiring protection to accessories are available. Power supply module with protection against lightning surge to avoid device
Control Panel
I/O modules are equipped with segment isolation function. damage caused by high voltage or power surge.
A table to review all I/O modules statuses is available for casier operation. Quality control :
Addresses and interlocks can be display on the LCD screen. All interior components of the display module and base boards in the unit are
Weekly automatic check function. approved by CE and CNS. All products have to pass strict inspection before
Repeat alarm function. delivery to ensure durability.
Two stage alarm delay function
Abnormal voltage inspection :
Standby battery with power saving function HOOSEKI Fire Alarm
With abnormal voltage display function, the system can indicate high and low voltage.
Build in-printer Control Panel
Modular design :
The system has modular design with inputs/ outputs independet terminal module. If there is a problem on site, users do not have
to remove external wires and can easly replace defective boards improving the efficiency of maintenance and inspection.
HOOSEKI Fire Alarm Annunciator Exterior design :
Equipped with zone display panel board. The panel (made of flame retardant plastic) adopt a streamline design for clear
DIMENSIONS (STEEL) *Size mark in red represent with printer aption. indication of zone’s name, floor, building, properties, etc.
Cabinet Wall-mount Other Functions:
Can be integrated with the TYY Voice Evacuation System and the Emergency Telephone System in one cabinet for more
Addressas appealing look and less space consuming.
/Loops 255/1L
255/1L
510/2L 765/3L 1020/4L 1275/5L 1530/6L 1785/7L 2040/8L
DIMENSIONS (STEEL)
H(mm) 450 500 840 1020 Cabinet Wall-mount
Number
of Loops 5~10L 15L 20L 25~30L 35~40L 45~50L 55~60L 65~70L 75~80L 85~90L 95~100L 105~110L 115~120L
W(mm) 480 480 480 480 H(mm) 400 495 580 520 580 700 760 840 930 1020 1110 1195 1350
W(mm) 300 300 300 480 480 480 480 480 480 580 580 580 580
D(mm) 130 (*160) 160 180 180
D(mm) 120 120 120 180 180 180 180 200 200 200 200 200 200
Interlock
SPECIFICATIONS Cabinet Floor-standing 2-in-1 3-in-1 4-in-1 Control Panel
Number 125~130L 135~150L 155~170L 135~260L 265~300L 305~340L 345~450L 455~600L 1L 1L
of Loops
ITEM Specifications H(mm) 1600 1800 2000 1600 1800 2000 1800 1800 180 250
W(mm) 580 580 580 1160 1160 1160 1740 2320 180 210
Model HS-ADD-1P/8L(1Loop/8Loop), HS-ADD-AN1/8 (1 Loop/8 Loop)
Power Source 110V AC 50/60 Hz or 220V AC 50/60 Hz D(mm) 260/360 260/360 260/360 260/360 260/360 260/360 260/360 260/360 75 90
Addresses / Loops 128/1L 256/1L 512/2L 768/3L 1024/4L 1280/5L 1536/6L 1792/7L 2048/8L
Standby Battery 24V DC SPECIFICATIONS
Transmission Distance Two-wires (able for branch wiring 1,5km
ITEM Specifications
Annunciator Use RS-485 for 800m, Network Signal Transceiver for 3km and Optical Fiber
Connection for up to 40km Model HS-5L, 10L, 15L, 20L, HS-25L, 30L, 40L, 50L (5 Zone - 40 Zone)
AN-5L, 10L, 15L, 20L, 25L, 30L, 40L, 50L (5 Zone - 50 Zone)
Loop Voltage Load Power / Indicating Lamp / Zone Telephone : 24V DC Power Source 110V AC 50/60 Hz or 220V AC 50/60 Hz
SLC power source: 32V AC Standby Battery 24V DC
Power Consumption Main control panel (monitoring) : 500mA Charging Voltage Below 26V DC 450mA, trickle charging
Circuit Voltage 24V DC operation voltage, under 10~11V DC 32mA
Communication module for each system (monitoring): 280 mA Rated Impedance Under 50 , Ground Resistance above 2M
Transmission Method Selective and sequential (I/O modules) Detector Connection No limiitation for Conventional Rate of Rise Heat / Fixed Temperature Heat
Detectors : Up to 30 Photoelectric Smoke Detectors (24V DC 40 A) per zone
Broadcast Output Relay output : interlock relay board x 13 sets for a max of 2,000 contacts E.O.L Resistor 10K
Method (relay board = 40 contacts [standard], 160 contacts [expansion]) No. of Indicators 1.2 times of the number of zone (LED indicating lamp)
Main Audio Voice notifications, human voice or voice alarm (over 90 dB) No. of Bells 1.2 times of the number of zone
o Color Green/ Red / Black
Ambient Temperature 0~40 C Buttons Rocker Switch / Push-button / Capacitive Touch Switch
Cabinet Material Powder coating steel (optional Flame retardant ABS enclosure available Cabinet Material Powder coating steel (optional Flame retardant ABS enclosure available
up to 256/1L only) up to 20L only HOOSEKI Fire Alarm
Main Audio Mono tone sounder (above 85dB for 1m distance) Annunciator
Alarm Relay Contact 2 sets of No-Voltage NO contact, capacity AC 250V / 7A
FIRE ALARM SYSTEM FIRE ALARM SYSTEM
&ŝƌĞůĂƌŵW͘͘>ŽŵďŝŶĂƟŽŶ^ĞƌŝĞƐ Fire Alarm Accesories
Base Manual
Call Point (HS-Base) FRONT VIEW HS-PBL
DESCRIPTION SIDE VIEW Fire Alarm Combination
This Fire Manual Station can quickly transmit a signal to the fire
receiver terminals or the repeaters while the button under a
TOP VIEW DESCRIPTION
transparent protective cover has been pushed at the first finding
Material Plate MS tebal 1.2 mm
of a fire accident. (This signal is beyond the accumulated time
Engsel SH-006
limitation).
There is a light over the button. The light will light up as a signal has been exactly Mata ayam
received by the receiver terminal. There is also a telephone jack for telephone Knob pintu
Color Red
FIRE ALARM SYSTEM FIRE ALARM SYSTEM
I/O Modules I/O Modules
Control Modules
Isolation Module 1 In 1 Out
Control Modules 1 In 1 Out (with isolation function)
FUNCTIONS Coomunication isolation function, when short circuit occurred in the module, the
Isolation module for addressable 2 wire communication module will be automatically isolated from the main communication line.
Module Base
(IN) (OUT) system
S+ S- S+ S- Recoomend to use for each 25 addressable equipments FEATURES
Isolation short circuit indicating lamp
Bult-in tri-state LED indicator to indicate different
Not occupy address
statuses, “Monitoring”, “Disconnection”, and
INPUT OUTPUT Deploy at main line for branching purpose
“Fire State”. HS-ADD-I/O-1
HS-ADD-IM SLC Contact SLC Contact Isolation module deploys between main line and branch
SPECIFICATIONS
Binary coded address dip switch
line, when short circuit happens, isolation module will
Two-wire multi-transmission
auto-isolate the error part with the main line so can avoid EOL : Below 10K capacitor / address.
Stable communication with resistance to noise
the whole zone break-down Operating Environment : 0 C- 50 C relative
and disturbances
Alumina rail lock strukture, easy to install humidity below 85%
Self-test function for circuit disconnection and
Monitoring Current : 420 A
activation
Activating Current : 16mA
SPESIFICATIONS Expandable to connect with photoelectric
Load Voltage Input : 24V DC (YRR-02)
smoke, rate of rise heat and fixed temperature
Function Communication short circuit isolation Rated Voltage : 33V AC
Operating Voltage DC16~36V heat detectors
Output Contact Capacity : 30V DC / 2A (max)
Current Consumption DC32V normal 400 A LED indication pattern, as follows :
Material : Flame retardant plastic
Reaction time Below 0.3 sec monitoring (flash at intervals of 2.5s),
Ambient Temperature 0 C~50 C Relative Humidity below 95%
Dimensions : 80 (H) x 60 (W) x 30 (D) mm
disconnection (flash at intervals 0.5s) and fire
Dimension 67 x 100 x 26 mm Note : EOL capacitor
state (on)
Material Fire~proof plastic
Can be fixed on alumunium railings for easy
installment
Wiring Notes :
Addressable Detector Base’s L+ LC connect
to Convensional Detectors’ L+ LC, polarized
Provided current is not over 1.3mA/DC24V
A Profesional terminal device is needed,
cannot use a normal 10K
FIRE ALARM SYSTEM FIRE ALARM SYSTEM
Rate of Rise Heat Detector Fixed Temperature Heat Detector
Contacting Point
- OPERATION
Insulator Leak Hole MOUNTING STATUS PRINCIPLES
Thermostat Terminal
Diaphragm
Heat-Detecting Chamber
MOUNTING STATUS
DIMENSIONS
Base
Unit: mm 42 83 Heat-Detecting Plate
Body Pitch
Contacting Point Circular Disk Bi-Metal
90 Cap 83
Insulated Pin
Pitch
102 Base
WIRING AND CONNECTION
46
46
O 90
O 103
O 103
FIRE ALARM SYSTEM
Photoelectric Type Smoke Detector HS-WT30L
ISO 9001, Approved
DESCRIPTION
The photoelectric type smoke detector is based on the
photoelectric sensing principle to make up.
When fire break out and smoke enters the light- tight
box, the particles of smoke scatter the infrared light,
and this scattered light goes into the receiving element,
thereby emitting an electric current, and while the
electric current is up to the fixed extend, the fire alarm
will be activated. This is an advance scientific device. It
is very quick and accurate to activate the early fire
HS-WT30L warning system. Because of the pretty and compact
styling, it is most suitable for the interior decoration of the
modern buildings.
MOUNTING STATUS
SPECIFICATION
Unit: mm
Main Model: HS-WT30L
Series Model: HS-WT30L1. HS-WT30L3
83
Rated Voltage: 24V DC
Pitch
Working Voltage: 12V to 30V DC
Standby current: 60 micro amps.(max)
Base
Alarm Current:1OOmilli amps.(max)
Initial Stabilizing Time: 15sec Body
46
Identification Light: Red color(LED).
Ambient Temperature: -10 C~+50 C
Ambient Humidity: 0-95%
O 103
Body Case: Fire-Proof Plastic
Weight: Approx.140g.
Color: Creamy-white. WIRING AND CONNECTION
Used Conventional
HS-R1L
60 mm
SPECIFICATIONS
Technical Specifications Smoke Detectors
Normal Rated Voltage 1,5 - 5 VDC
Operating Voltage 1.5 VDC
Alarm Current 20mA
Weight 30g