Toll Plaza
Toll Plaza
Toll Plaza
C D
V1 W2 V1 W1
STRONG
PANTRY
ROOM 2400 X 2140 PUBLIC COMMUNICATION
ACCOUNT 1200 X 2370
AND MONTHLY PASS
3500
MANAGER'S CABIN 3770 X 3270
W1 2500 X 3270 W1
D2
D2 D1 D2
D1 D1
D2
B SERVER ROOM ENTRANCE B
1730
W5 3770 X 1500 4000 X 1500 D3
5190 X 3760
D1 D1
3500
REST ROOM D3
STORE
3770 X 3270 3770 X 3270
A A
CONTROL ROOM
5190 X 3370
W1 W1
1230
W3 W3
W4
C D
4000 5420 4000
B B
OPEN TERRACE
GENERAL NOTES :-
1. ALL STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE RELEVANT
STRUCTURAL DRAWINGS.
2. DISCREPANCY AND/OR AMBIGUITY, IF ANY, SHALL BE GOT RECTIFIED WELL BEFORE
EXECUTION.
3. THE BUILDING IS DESIGNED AS PER FOLLOWING I.S. CODES.
· IS : 1905 - 1987 : CODE OF PRACTICE FOR STRUCTURAL USE OF
UNREINFORCED MASONRY.
BRICK PARAPET WALL · IS 4326 : 1993 : EARTHQUAKE RESISTANT DESIGN AND CONSTRUCTION OF
A A BUILDINGS - CODE OF PRACTICE.
· IS 456 : 2000 " PLAIN & REINFORCED CONCRETE - CODE OF PRACTICE "
· IS 875 (PART-2) : 1987 " CODE OF PRACTICE FOR DESIGN LOAD (OTHER THAN
EARTHQUAKE) FOR BUILDINGS AND STRUCTURES "
· IS 1893 (PART-1) : 2002 " CRITERIA FOR EARTHQUAKE RESISTANT DESIGN OF
STRUCTURES "
· IS 13920 : 1993 " DUCTILE DETAILING OF REINFORCED CONCRETE
STRUCTURES SUBJECTED TO SEISMIC FORCES - CODE OF PRACTICE "
4. ALL BRICKS SHALL CONFIRM TO IS : 1077-1986 AND SHALL HAVE MINIMUM CRUSHING
STRENGTH OF 3.5 MPA.
5. ALL BRICKS MASONARY SHALL BE IN CEMENT:SAND MORTAR IN PROPORTION OF 1:6.
6. IN MORTAR MIX, FAT LIME SHOULD BE ADDED TO THE EXTENT OF 1/4 PART OF
CEMENT (BY VOLUME) FOR IMPROVING WORKABILITY.
7. THIS BUILDING IS DESIGNED FOR GROUND STOREY ONLY.
8. THE DENSITY OF FILLING MATERIAL FOR SUNK SLABS SHALL NOT EXCEED 18 KN/M,
UNLESS OTHERWISE SPECIFIED.
9. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED.
10. THIS DRAWING IS NOT TO SCALE, ONLY WRITTEN DIMENSIONS SHALL BE FOLLOWED.
11. GRADE OF MATERIALS
C D · CONCRETE GRADE : M-25
· STEEL GRADE : FE-500
EPC CONTRACTOR:- PROOF CONSULTANT PROJECT TITLES:- REV DATE REFERENCE DRAWING TITLE
CLIENT:- KHANNA DESIGNERS & RFP FOR BALANCE WORKS FOR REHABILITATION AND UP-GRADATION GROUND FLOOR AND TERRACE (ROOF) FLOOR PLAN
SHREEJI INFRASTRUCTURE INDIA R0 FOR OFFICE BUILDING AT TOLL PLAZA
CONSULTANTS PVT.LTD. OF BAMEETHA-SATNA SECTION OF NH-75 FROM KM 57+160 TO KM
PVT. LTD. PUBLIC WORKS DEPARTMENT (MPPWD NH) Office No 416, ILD Trade Centre 155+000 [DESIGN LENGTH 97.840 KM] IN THE STATE OF MADHYA
R1
LINTEL LEVEL
GROUND LEVEL
FRONT SIDE ELEVATION RIGHT SIDE ELEVATION
LINTEL LEVEL
GROUND LEVEL
BACK SIDE ELEVATION LEFT SIDE ELEVATION
1000
PARAPET WALL
1000
SINTEX
PARAPET WALL SINTEX
SLAB TOP
LVL.
3000
1200
2100
D3
2100
D2 D1 D2 D1
FLOOR
COPING
PLINTH FINISH
900
LVL. FLOOR
COPING
FINISH
450
PLINTH
F.G.L. LVL.
450
GRADE SLAB
F.G.L. F.G.L.
FOUNDATION
LEVEL
PCC LEVELING GRADE SLAB
COURSE
FOUNDATION
LEVEL
SECTION A-A PCC LEVELING
COURSE
SECTION C-C
PARAPET TOP
LVL.
1000
1000
PARAPET WALL SINTEX
PARAPET WALL SINTEX PARAPET WALL
SLAB TOP
LVL.
LINTEL WITH
WEATHER SHED
LINTEL
LVL.
600 600 600
900
900
3000
3000
1200
2100
D2 D1 D2
2100
D1 D3 D1
1200
1200
FLOOR
900
FLOOR
FINISH COPING COPING
PLINTH FINISH PLINTH
LVL. BRICK STEPS LVL.
450
450
F.G.L. F.G.L.
FOUNDATION FOUNDATION
LEVEL LEVEL
PCC LEVELING PCC LEVELING
COURSE COURSE
SECTION B-B
SECTION D-D
EXTRA AT EXTRA AT
0.0 TOP STEEL 0.0 TOP STEEL
THICKNESS
0.0
SLAB
45°
L1 L2 L3
COVER TO LINK
C
L OF END SUPPORT CL OF MID SUPPORT
NOMINAL
MINIMUM 2-10T EXTRA A = L1/4 (OR) L2/4
STIRRUPS SPACING SUPPORTED STIRRUPS ON EITHER SIDE WHICHEVER IS GREATER
< 150MM AT SPLICE OF SUPPORTED BEAM (TYP.)
TOP BARS BEAM
A A
L1/4
IR db
Ld+10Ø
Ld+10Ø
d
S
R IS M BAR (db),
WHIC OF HOO 10 TIME
L1/10 L1/7 L2/7
ORE
M OR
P
LAP 2d 2d LAP
2d LAP
DIAM m MINIMU
BOTTOM BARS
HEVE
S=d/4 OR 8Ø REST S < d/2 S=d/4 OR 8Ø S=d/4 OR 8Ø REST S < d/2
ETER
FOR 2d DISTANCE FOR 2d DISTANCE FOR 2d DISTANCE
(SMALLER OF THE TWO) (SMALLER OF THE TWO)
50 MM MAX.
75 m
50 MM MAX. 50 MM MAX.
END SPAN (L1) MID SPAN (L2)
GENERAL NOTES :-
LD = TENSION SPLICE/LAP LENGTH 1. ALL STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE RELEVANT
ACCOUNTING CONCRETE GRADE TYPICAL TRANSVERSE REINFORCEMENT ARCHITECTURAL DRAWINGS.
TYPICAL DETAILS OF BEAM REINFORCEMENT Ø = DIAMETER OF LONGITUDINAL BAR (HOOP) DETAILS FOR COLUMNS 2. DISCREPANCY AND/OR AMBIGUITY, IF ANY, SHALL BE GOT RECTIFIED WELL BEFORE
(SCALE: N.T.S) EXECUTION.
(SCALE: N.T.S) 3. THE BUILDING IS DESIGNED AS PER FOLLOWING I.S. CODES.
· IS : 1905 - 1987 : CODE OF PRACTICE FOR STRUCTURAL USE OF UNREINFORCED
MASONRY.
· IS 4326 : 1993 : EARTHQUAKE RESISTANT DESIGN AND CONSTRUCTION OF
BUILDINGS - CODE OF PRACTICE.
· IS 456 : 2000 " PLAIN & REINFORCED CONCRETE - CODE OF PRACTICE "
· IS 875 (PART-2) : 1987 " CODE OF PRACTICE FOR DESIGN LOAD (OTHER THAN
EARTHQUAKE) FOR BUILDINGS AND STRUCTURES "
· IS 1893 (PART-1) : 2002 " CRITERIA FOR EARTHQUAKE RESISTANT DESIGN OF
STRUCTURES "
10*db · IS 13920 : 1993 " DUCTILE DETAILING OF REINFORCED CONCRETE STRUCTURES
(>= 75 mm)
SUBJECTED TO SEISMIC FORCES - CODE OF PRACTICE "
300 4. IN REINFORCEMENT DETAILS,
TOP BARS SECONDARY BEAM · T INDICATES HYSD / TMT STEEL BARS Fe415 / Fe500 GRADE CONFORMING TO IS:
TYP.
1786 - 2008.
5. NOT MORE THAN 50% OF THE BARS SHALL BE SPLICED AT ONE SECTION.
6. LAP LENGTH SHALL BE 50 TIMES THE DIAMETER OF BAR.
7. ALL BRICKS SHALL CONFIRM TO IS : 1077-1986 AND SHALL HAVE MINIMUM CRUSHING
>= Ld+2*db
>= Ld+2*db
9. IN MORTAR MIX, FAT LIME SHOULD BE ADDED TO THE EXTENT OF 1/4 PART OF CEMENT
(BY VOLUME) FOR IMPROVING WORKABILITY.
10. THIS BUILDING IS DESIGNED FOR GROUND STOREY ONLY.
11. FOR FOOTING DESIGN, SBC CONSIDERED AS 100 kN/m2 AT 2000MM DEPTH FROM NGL.
°
60
12. IN FOOTINGS & SLABS, REINFORCEMENT PARALLEL TO SHORTER SIDE SHOULD BE
50 MM Ld PLACED IN BOTTOM LAYER.
MAXIMUM BOTTOM BARS 13. THE DENSITY OF FILLING MATERIAL FOR SUNK SLABS SHALL NOT EXCEED 18 KN/M,
UNLESS OTHERWISE SPECIFIED.
WHERE B 2-12T MAIN BEAM 14. USE COVER BLOCKS OF APPROPRIATE SIZE. THE COVER-BLOCKS MAY BE OF RICH
· Ld = DEVELOPMENT LENGTH OF BAR
AS PER SHAPE MORTAR OR APPROVED QUALITY P.V.C. COVER-BLOCKS SHOULD BE SECURELY TIED TO
· db = DIAMETER OF BAR
THE REINFORCEMENT.
WHERE
TYPICAL DETAILS AT END JUNCTION & LAP SPLICES IN BEAMS · db = DIAMETER OF BAR
TYPICAL SECTION OF BENT UP 15. SUITABLE CHAIRS SHALL BE PROVIDED TO SUPPORT AND MAINTAIN CORRECT POSITION
OF REINFORCEMENT. (12MM DIA AS PER IS:2502)
(SCALE: N.T.S) HANGER TYPE BARS AT THE JUNCTION OF SECONDARY
16. BENDING OF BARS SHALL BE CARRIED OUT AS PER IS:2502.
BEAMS WITH MAIN BEAMS
(SCALE: N.T.S) 17. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED.
TYPICAL DETAILS OF BEAM 18. THIS DRAWING IS NOT TO SCALE, ONLY WRITTEN DIMENSIONS SHALL BE FOLLOWED.
WEB REINFORCEMENT 19. GRADE OF MATERIALS
(SCALE: N.T.S) · CONCRETE GRADE : M-25
· STEEL GRADE : FE-500
20. COVER :
· FOOTING : 50MM
· COLUMNS : 40MM
· BEAMS : 25MM
SLAB 20MM
230
100
Booth protection
750
1700
750
230 600
A A
300
Door PP‘ 3075 8200 3075
8mm@100mmcc 5500
PP‘
1650 1650 A 230 4000
230 3500 300 1200
B SECTIONALDETAILOFBEAM 3000
Traffic flow direction Glass window
6300(min.)
PLAN VIEW OF BOOTH
Receiver Trafficsignal Traffic signal
Recever
3500
1500
Glasswindow
Barrier
2400
Barrier
Safetyblock Safetyblock
Top and bottom
8Ø @ 200mm c/c 1620 1880
900
1700
200
800
800
Slab120mmthk. Traffic flow direction Traffic flow direction
3500 1200
300
ROOF PLAN OF CABIN
RCCslab RCCbeam
120mmthick 180mmthick
Safetyblock
2400
25000
1620 1880
LAYOUT FOR TRAFFIC ISLAND WITH TOLL BOOTH(DOUBLE)
900
500
300 1200
GSB150mmthk.
2300
PCCM15100mmthk.
IPS40mmthk. 150
150
SECTIONA-A
150
PCC
400
400
16mm@150mmcc
150 250
150 250
100 PCC
230 3400
GL GL 12mm@200mmcc
GL GL 2300 SECTIONB-B
ELEVATION OF SAFETY BLOCK
Brick work
Brick work 200 CM1:6
SAFETY BLOCK
750
CM1:6 B B
330 300 1700
430 400
500
SAME AS PARAPET
WALL HEIGHT
4000 1395 2630 1395 4000 115 35
THICKNESS
R.C.C. WALL
900
1310 (STRONG ROOM)
SLAB
390 510
390 510
390 510
TYPE-A TYPE-A TYPE-A C
L OF PLINTH BEAM/ R.C.C. WALL
150 8T@175 C/C
900
900
900
A FIRST FLOOR
LEVEL PLINTH BEAM-PB3 BOTH WAYS
TYPE-E 150
(350X450) PLINTH
PB3 RL:
350
350
390 510
150mm THICK
TYPE-B
TYPE-B
TYPE-B
TYPE-D
825 (FB1)
TYPE-A
900
PB2
2370
RCC GRADE SLAB (M25)
450
PB1
100mm THICK
TYPE-D
50 12T@100 C/C
TYPE-A
P.C.C (M15)
3500
450 450
TYPE-D 12T@100 C/C COMPACTED EARTH
900
REST
OR UP TO GOOD SOIL
TYPE-B 230
1130
PB4
2-12T THRU PLINTH BRICK WALL FOOTING
TYPE-B TYPE-B
450 450
450 450
4-12T RL:
TYPE-B
900
900
C
150mm THICK
CLEAR HEIGHT
3000
RCC GRADE SLAB
450
TYPE-A
TYPE-B
TYPE-B
450
TYPE-C
(M25) 450
1730
1730
450 450
900 100mm THICK
H
P.C.C (M15)
150
2175
RCC COLUMN
900
D 750
450 450 COMPACTED EARTH
1130
450 450
900
E 390 510
DETAIL OF R.C.C. WALL & PLINTH BEAM (230X450)
( SCALE - 1 : 20 ) 900
TYPE-B
3500
TYPE-B
TYPE-A
TYPE-A
TYPE-B
TYPE-B
GRADE (OUTER SIDE-STRONG ROOM)
2370
SLAB PLINTH
RL: ( SCALE - 1 :30)
450
C
L OF PLINTH BEAM/ R.C.C. WALL
390 510
390 510
LEVELING COURSE
900
900
REINF.PARALLEL
F FGL: TO `L' &`B'
TYPE-A TYPE-A R.C.C. WALL
(STRONG ROOM)
F1 F1
G BOTH WAYS
OR UP TO GOOD SOIL
TYPE-A PLINTH
RL:
Pb
REINF.PARALLEL
150mm THICK
1200 4-12T RCC GRADE SLAB (M25)
450
RCC COLUMN
TO `B'
4000 5420 4000 100mm THICK P.C.C (M15)
FGL:
Pl
L
50
(TYP.) COMPACTED EARTH
FOUNDATION / CENTER LINE PLAN RCC FOOTING FILLING
(SCALE - 1 : 75) 230
PCC LEVELING
300
TYP. REINF.PARALLEL TO `L' COURSE TYPE - D
D
4-12T (PLINTH BEAM)
230
t
SCHEDULE OF FOOTING 8T @150 C/C FOUNDATION RL.: ( SCALE - 1 :30)
TYP.
1786 - 2008.
150
RL: RL: TYP. RL:
150mm THICK 150mm THICK 150mm THICK 5. NOT MORE THAN 50% OF THE BARS SHALL BE SPLICED AT ONE SECTION.
RCC GRADE SLAB (M25) RCC GRADE SLAB (M25) RCC GRADE SLAB (M25) 6. LAP LENGTH SHALL BE 50 TIMES THE DIAMETER OF BAR.
450
450
450
7. ALL BRICKS SHALL CONFIRM TO IS : 1077-1986 AND SHALL HAVE MINIMUM CRUSHING
100mm THICK P.C.C (M15) 100mm THICK P.C.C (M15) 100mm THICK P.C.C (M15)
STRENGTH OF 3.5 MPA.
FGL: FGL: GL: FGL:
8. ALL BRICKS MASONARY SHALL BE IN CEMENT:SAND MORTAR IN PROPORTION OF 1:6.
COMPACTED EARTH COMPACTED EARTH COMPACTED EARTH 9. IN MORTAR MIX, FAT LIME SHOULD BE ADDED TO THE EXTENT OF 1/4 PART OF CEMENT
(BY VOLUME) FOR IMPROVING WORKABILITY.
MIN. 2000 BELOW GR.LVL.
REST
OR UP TO GOOD SOIL
OR UP TO GOOD SOIL
OR UP TO GOOD SOIL
450
450
450 450 450 350 14. USE COVER BLOCKS OF APPROPRIATE SIZE. THE COVER-BLOCKS MAY BE OF RICH
MORTAR OR APPROVED QUALITY P.V.C. COVER-BLOCKS SHOULD BE SECURELY TIED TO
2-10T THE REINFORCEMENT.
150 175 175
600 600 600 15. SUITABLE CHAIRS SHALL BE PROVIDED TO SUPPORT AND MAINTAIN CORRECT POSITION
OF REINFORCEMENT. (12MM DIA AS PER IS:2502)
750 750 750 16. BENDING OF BARS SHALL BE CARRIED OUT AS PER IS:2502.
100
8T @150 C/C 17. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED.
PCC LEVELING PCC LEVELING PCC LEVELING
18. THIS DRAWING IS NOT TO SCALE, ONLY WRITTEN DIMENSIONS SHALL BE FOLLOWED.
COURSE COURSE COURSE
390 510 450 450 390 510 19. GRADE OF MATERIALS
3-10T · CONCRETE GRADE : M-25
900 900 900 · STEEL GRADE : FE-500
TYPICAL DETAILS OF COPING 20. COVER :
TYPE - A TYPE - B TYPE - C ( SCALE - 1 :10) · FOOTING : 50MM
(OUTER SIDE) (INNER SIDE) (FOR STEP / OTTA) · COLUMNS : 40MM
· BEAMS : 25MM
( SCALE - 1 :30) ( SCALE - 1 :30) ( SCALE - 1 :30) · SLAB : 20MM
L2
230
LW1 LW1 LW1 LW1
FB6c
L1 L1 2-12T
FB5
(01) (01) (01) (01) (01) (01)
L2 L2 (01) FB3b
L2 FB3a
LW1 LW1
350
L3 S4 (02) 8T @ 200 C/C
L1 (02) (03) (02) (01)
L1 L1 L1
(01) S6
FB6b
FB7b
L1
(FOR BEAM FB2 TO FB7)
LW1 LW1
L1 S1 (01) S1
L2 (02) (02)
L2
(02)
L1 L1 FB2
S2
L1 (02) (02)
L2 L2
SCHEDULE OF SLAB REINFORCEMENT
(01) (01) (01)
FB6a
FB7a
L2 L2
L2 (01) (01) BAR DIA OF BAR NUMBERS/
L2 SHAPE OF BAR ( mm ) REMARKS
MARK SPACING
01 8T @ 200 C/C ALT BENT UP
02 8T @ 400 C/C EXTRA AT TOP
L1 LW1 L1 L1 LW1 L1 (01) @ 200 C/C DISTRIBUTION STEEL
03 8T
FB1
L1 L1
FB1 (230X825) (REFER SEPARATE DETAIL)
SLAB TH.
BEAM-FB1
( SHOWING G.F. SLAB & BEAMS LAYOUT ) X
4 -12T SIDE FACE
2000 2-16T THRU REINFORCEMENT 2000
STRUCTURAL LAYOUT AT GROUND FLOOR LINTEL LEVEL (NOTE : ALL SLABS ARE 125 MM THICK.)
2-16T 2-16T
825
8T@100C/C
ALT.CHIPPIYA RCC COL. RCC COL.
2-16T THRU
SLAB SLAB
X
LVL: LVL: BRICK WALL BEAM-FB1 (230x825)
300 300 STIRRUPS 8T 8T 8T
FLOOR FINISH 230 DETAILS OF ALTERNATE BENT BARS SPACING c/c 100 150 100
LVL:
** PROPS OF SHUTTERING UNDER LINTEL NOS. 17 REST 17
BRICK WALL BRICK WALL LEVEL, CHAJJA, SILL, BRACKETS SHALL BE
125
230
900
EXECUTION.
2-12T AT TOP 3. THE BUILDING IS DESIGNED AS PER FOLLOWING I.S. CODES.
8T@150C/C · IS : 1905 - 1987 : CODE OF PRACTICE FOR STRUCTURAL USE OF UNREINFORCED
8T@100C/C MASONRY.
825
115 4 -12T SIDE FACE · IS 4326 : 1993 : EARTHQUAKE RESISTANT DESIGN AND CONSTRUCTION OF
300
· IS 456 : 2000 " PLAIN & REINFORCED CONCRETE - CODE OF PRACTICE "
CHHAJJA LEVEL IS 875 (PART-2) : 1987 " CODE OF PRACTICE FOR DESIGN LOAD (OTHER THAN
100 100 ·
EARTHQUAKE) FOR BUILDINGS AND STRUCTURES "
2-12T AT BOTTOM MAX. 600
8T @ 200 C/C 2 -16T IS 1893 (PART-1) : 2002 " CRITERIA FOR EARTHQUAKE RESISTANT DESIGN OF
150
·
230 STRUCTURES "
RCC CHHAJJA
100 X 100 R.C.C. POCKET 100 X 100 R.C.C. POCKET D/W OPENING · IS 13920 : 1993 " DUCTILE DETAILING OF REINFORCED CONCRETE STRUCTURES
1-12T VERTICAL BAR 1-12T VERTICAL BAR 230
SECTION X-X SUBJECTED TO SEISMIC FORCES - CODE OF PRACTICE "
2 -12T 4. IN REINFORCEMENT DETAILS,
BRICK WALL BRICK WALL · T INDICATES HYSD / TMT STEEL BARS Fe415 / Fe500 GRADE CONFORMING TO IS:
L3 (115X150) 1786 - 2008.
5. NOT MORE THAN 50% OF THE BARS SHALL BE SPLICED AT ONE SECTION.
RCC COPING (AT PARTITION WALL / OPENINGS) 6. LAP LENGTH SHALL BE 50 TIMES THE DIAMETER OF BAR.
TYPICAL WEATHER SHED (LW1) DETAIL 7. ALL BRICKS SHALL CONFIRM TO IS : 1077-1986 AND SHALL HAVE MINIMUM CRUSHING
PLINTH RCC COPING PLINTH
RL: RL: STRENGTH OF 3.5 MPA.
8. ALL BRICKS MASONARY SHALL BE IN CEMENT:SAND MORTAR IN PROPORTION OF 1:6.
230 9. IN MORTAR MIX, FAT LIME SHOULD BE ADDED TO THE EXTENT OF 1/4 PART OF CEMENT
COPING COPING (BY VOLUME) FOR IMPROVING WORKABILITY.
REINFORCEMENT REINFORCEMENT 2-12T 10. THIS BUILDING IS DESIGNED FOR GROUND STOREY ONLY.
TYPICAL SECTIONAL DETAILS OF RCC POCKET & VERTICAL BAR 11. FOR FOOTING DESIGN, SBC CONSIDERED AS 100 kN/m2 AT 2000MM DEPTH FROM NGL.
230
12. IN FOOTINGS & SLABS, REINFORCEMENT PARALLEL TO SHORTER SIDE SHOULD BE
AT CORNER L-JUNCTIONS AND T-JUNCTIONS OF 230 BRICK WALL 2-10T PLACED IN BOTTOM LAYER.
13. THE DENSITY OF FILLING MATERIAL FOR SUNK SLABS SHALL NOT EXCEED 18 KN/M,
8T @ 200 C/C
25 300 UNLESS OTHERWISE SPECIFIED.
DOWEL BAR IN THE FORM 14. USE COVER BLOCKS OF APPROPRIATE SIZE. THE COVER-BLOCKS MAY BE OF RICH
150
8T @ 200 C/C
OF U STIRRUPS OF DIA 8 MM MORTAR OR APPROVED QUALITY P.V.C. COVER-BLOCKS SHOULD BE SECURELY TIED TO
900
900
100
STRONG
ROOM WC
W.B.
FD
CONTROL ROOM
147+685
147+485
147+535
147+585
147+635
147+735
147+785
147+835
147+885
PROOF CONSULTANT PROJECT TITLES:- REV DATE REFERENCE
EPC CONTRACTOR:- DRAWING TITLE
CLIENT:- KHANNA DESIGNERS & RFP FOR BALANCE WORKS FOR REHABILITATION AND UP-GRADATION TYPICAL LAYOUT OF TOLL PLAZA
SHREEJI INFRASTRUCTURE INDIA R0
CONSULTANTS PVT.LTD. OF BAMEETHA-SATNA SECTION OF NH-75 FROM KM 57+160 TO KM
PVT. LTD. PUBLIC WORKS DEPARTMENT (MPPWD NH) Office No 416, ILD Trade Centre 155+000 [DESIGN LENGTH 97.840 KM] IN THE STATE OF MADHYA
R1
230
100
Booth protection
1200
750
A A
600
Door
300
750 3075 8200 3075
PP‘
8mm@100mmcc
230
5500
PP‘
870 1630 A 230 4000
230 300 1200
B SECTIONAL DETAIL OF BEAM 3000
Traffic flow direction Glass window
6300(min.)
PLAN VIEW OF BOOTH
Receiver Traffic signal
2500
1500
Glass window
Barrier
2400
Safety block
Top and bottom
8mmØ @200mm c/c
870 1630
900
1200
200
800
Slab120mmthk. Traffic flow direction
2500 1200
300
ROOF PLAN OF CABIN
1800
1200
Glasswindow Booth protection
Chevron marking
Barrier Receiver Traffic signal Traffic flow direction
1500
Safety block
2400
25000
Brick column
Brick wall 870 1630
LAYOUT FOR TRAFFIC ISLAND WITH TOLL BOOTH (SINGLE)
900
2500
500
300 1200
GSB150mmthk.
1800
PCC M15 100mmthk.
IPS 40mmthk. 150
150
SECTION A-A
150
PCC
400
400
16mm@150mmcc
150 250
PCC
150 250
100
230 3400
12mm@200mmcc
GL GL
GL GL SECTION B-B 1800
CM1:6 B B
330 300 1100
430 400
500
PCC100mmthk PCC100mmthk
700
730
DETAIL-B
DETAIL-A TOP VIEW OF SAFETY BLOCK
2.0m
50.0m
um) 1 in 10 Ta
er (Minim per (Minim
1in10 Tap EXTRA WIDE 4.10
um)
500 100 TOLL LANE-2
1.80
3.20
1.80
TOLL LANE-1 3.20
2.30
3.20 TOLL LANE-1
1.80
3.20
2.0m
TOLL LANE-2
1in10 Tap 1.80
um) 100 500
e r (Minimu per (Minim
1 in 10 Ta
4.10 EXTRA WIDE
m) 2.00
500.0
Taper length125.0m 1000.0
As required
Bar Marking
LM-300mmthick
Edge of Carriageway line(150mm)
32 32 30 28 Detail1
26 23 20 17 13 9 5
Detail2
Carriageway
Paved Shoulder LM-100mmthick
Granular Shoulder
PAVEMENT MARKING FOR TOLL PLAZA Granular Shoulder
100mm
100mm
SOAK PIT