SD-651 v3 PDF
SD-651 v3 PDF
SD-651 v3 PDF
SD-651 Low-Profile
Plug-In Smoke Detectors
Operating Voltage/Alarm Current: See Adapter Base F110: Retrofit replacement flange for B400 Series flanged
Selection Guide following bases.
Standby Current: 85μA Standby RA400Z: Remote annunciator for 2 or 4 wire systems, 3-32V.
Fits standard single gang electrical box.
Sensitivity: 1 - 3.18%/ft.
B401BH-2: Sounder base. Requires an external 24 VDC
Height: 2.0” in B401 power supply. Mounts to 4” square electrical box (112” mini-
Diameter: 4.1” installed in B401; 6.1” installed in B110LP mum depth, 218” recommended).
Shipping Weight: 5.2 oz SMK400: Surface mounting kit provides for entry of surface
wiring conduit. For use with B401 or B401R mounting bases
Construction: Flame retardant thermoplastic only.
Temperature: Photo: 32°F to 120°F (0°C to 49°C) EOLR-1: End of line relay for power supervision, 12/24 VDC
UL Listed Velocity Range: Photo: 0–3000 fpm (0–15.2 m/s) systems.
Smoke Detector Spacing: On smooth ceilings (as defined in M02-09-00: Test magnet with 32° telescoping handle.
NFPA 72), spacing of 30 feet (900 sq. ft.) may be used as a XR-2B: Detector removal tool. Allows installation and/or
guide. Other spacing may be used depending on ceiling removal of SD-651 detector heads from base in high ceiling
height, high air movements, and other conditions or response installations when used with XP-4.
requirements.
XP-4: Extension pole for XR-2B. Comes in three 5 ft.
sections.
C58-227-01: Replacement dust cover for SD-651 smoke
detectors.
RMK400: Recessed mounting kit (B401 sold separately).