XPXMP-18 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 45

XINJE

XP/XMP-18 series
Integral industrial controller
Operating manual

Xinje Electronic Co.,Ltd


Data No. PHC01 20080730 3.0
Xinje
Catalog
Preface
XP/XMP-18 Safety Notes
Ser
ies ————————————————————

Summarization 1
————————————————————
Op
erat
ingma
nual
Input/output specification and 2

exterior layout
————————————————————
3
PLC Function and Application
————————————————————
4
HMI Function and Application
5

Extension Ability

V1.0
This manual includes some basic precautions which you should follow to keep you safe and protect the
products. These precautions are underlined with warning triangles in the manual. About other manuals that
we do not mention, please follow basic electric operating rules.

Precautions Please follow the precautions. If not, it may lead the controlsystem
incorrect or abnormal, even cause fortune lose.

The models could only be used according to the manual, and an only be
Correct
used along with the peripheral equipments recognized or recommended
Application
by Xinje Electronic. They could only work normally in the condition of
be transported, kept and installed correctly, also please operate and
maintain them according to the recommendation.

Xinje Electronic Co., Ltd. Copyright reserved


Without exact paper file allowance, copy, translate or using the manual is not allowed. Disobey this,
people should take the responsibility of loss. We reserve all the right of expansions and their design
patent.

Duty Declare
We have checked the manual, its content fits the hardware and software of the products.As mistakes are
unavoidable, we couldn’t promise all correct. However, we would check the data in the manual frequently,
and in the next edition, we will correct the necessary information. Your recommendation would be highly
appreciated
Catalog

SAFETY NOTICE ............................................................................................................................8

1. SUMMARIZATION .....................................................................................................................9

1-1. Product summarization ......................................................................................................9


1-2. Specs ................................................................................................................................11
1-3. Parts explanation..............................................................................................................13
1-4. Outline dimension............................................................................................................15

2. IN-OUT SPECS AND EXTERIOR LAYOUT ...........................................................................17

2-1. Input specs .......................................................................................................................17


2-2. Relay output specs and circuit .........................................................................................19
2-3. Transistor output specs and circuit...................................................................................21

3. PLC FUNCTION AND APPLICATION ....................................................................................23

3-1. PLC instruction................................................................................................................23


3-2. soft component range.......................................................................................................24
3-3. Set up a project ................................................................................................................28
3-4. communication function ..................................................................................................31

4. HMI FUNCTION AND APPLICATION ....................................................................................35

4-1. HMI function introduction...............................................................................................35


4-2. Build a project..................................................................................................................36

5. THE EXTENSION ABILITY OF XP/XMP ...........................................................................39

5-1. extend BD board ..............................................................................................................39


5-2. extend MA model ............................................................................................................42
5-3. Other extension................................................................................................................45

5
6
Preface

Thank you for purchasing Xinje XP/XMP series integral industrial controller, please read the
manual before operating.

n This manual provides user with the guide of using and operating our product, it
Manual purpose
includes the product characteristics, spec explanation, using method, etc.

n This manual contains product summarization, exterior layout, PLC program,

and exterior extension.

Ø Summarization: introduce the product characteristics, specs, dimension,


installation.
Ø Exterior layout: introduce the product power spec, in-out layout.
Ø PLC program: introduce how to program in PLC.
Ø HMI picture: introduce how to edit picture in OP.
Ø Exterior extension: introduce extension ability of the product.

Suitable people This manual aims to below users:

n Terminal user
n Debugging person
n Technology support person

Make sure you have read the safety notice before operating.

Scope This manual applies to the XP/XMP series integral industrial controller.

Tele-document Xinje provides user with press document and tele-document:


n User CD
Contained software, manual and application examples
n Xinje website
Welcome to www.xinje.com download center to find electronic
document.

Contact us If you have any questions, please contact us.


Tel: 86-0510-85134136
Fax: 86-0510-85111290
Addr: 4th Floor, Building 7, Originality Industrial Park, Liyuan
Development Zone, Wuxi City, Jiangsu province, China

7
Safety notice

Read the manual carefully before operating. Be aware of the safety and correct operation. The
content below is focus on XP/XMP series products only.

Please safekeeping the manual, put in somewhere easy to get and read and give the manual to final
user.

◎ Notice items ◎

ATTENTION

● Do not put the wire close to cable, keep 10cm distance at least.
● Do not change the inside module of product or it may cause fault, error action, loss,
fire.
● When it smelly or noisy, cut the power immediately ( short tweet after power on is
normal ).
● Do not press the screen with pen, screwdriver or other sharp tools, it may cause
screen break or error.
● For installing the product, tighten the screws to avoid loosing.
● Transport, install, store, assemble and maintain the product accurately to avoid
breaking.

DANGEROUSNESS

● Confirm the power voltage and wire connection before turn on the power in order to
avoid breaking
● Do not touch the connection point to avoid getting an electric shock
● Do not open the back cover board
● Cut all the power before installation and take-down to avoid error and fault
● Please use in the surrounding the manual stated to avoid accident
● Do not use the product under the condition of high frequency radiation, strong
magnetic field to avoid interference

8
1. Summarization

1-1. Product summarization

XP/XMP-18 series integral industrial controller integrated human machine interface (HMI) and
PLC (XC1, XC2, XC3 series). It can instead of HMI and PLC to fulfill the control function. It can
save space with slim outline and improve the convenience of maintenance.

Product characteristics

u Integrate logical control, analog quantity in-out and HMI into the product
On-off quantity input: 10 points, optical coupling insulation
On-off quantity output: 8 points, relay output/transistor output/R&T mixture output
Analog quantity: XP/XMP can extend BD board to realize analog quantity in-out control
Easy edit of the HMI picture, rich function
u LCD display: 192×64 pixel ( 3.7 inch ), LCD useful life can reach 0.5 million hours
u 26 function keys can be redefined by user
u Sensitive and accurate key-press
u Multifunctional download port: HMI and PLC use one download cable
u Waterproof level is IP20
u Small structure, space saving
u Simple and modern outline

Type List

XMP series
Relay output Transistor Relay&Transistor
output output
XMP1-18R XMP1-18T XMP1-18RT
XMP2-18R XMP2-18T XMP2-18RT
XMP3-18R XMP3-18T XMP3-18RT

XP series
Relay Transistor Relay&Transistor
output output output
XP1-18R XP1-18T XP1-18RT
XP2-18R XP2-18T XP2-18RT
XP3-18R XP3-18T XP3-18RT

9
Type Name

1 2 3 4

1: Name XP, XMP series


2: PLC Type 1: XC1 series
2: XC2 series
3: XC3 series
3: In-out points 18: Input 10 points, output 8 points
4: Output Type R: Relay output
T: Transistor output
RT: Relay&Transistor output

Notice: XMP series exclude XMP2-32 series products in this manual. About these products,
please refer to Integral Controller Manual XMP2-32.

10
1-2. Specs

General Specs

Item Specs
Power supply
DC12V~DC24V
voltage
Power Less than 10W(TYP2.0W)
Power cut
Electric Less than 20ms
moment permit
Endurable AC1000V/10MA for 1minute ( between signal
voltage and ground )
Insulated About 10MΩ,DC500V ( between signal and
impedance ground )
Operating
0~50℃
temperature
Storage
–10~60℃
temperature
Environment
20~85% ( No dew )
Surrounding temperature
Endurable
10~25Hz ( X, Y, Z direction for 30 minutes )
quiver
Anti-jamming Voltage Noise: 1000Vp-p
Air No causticity gas
Protection According to IP20
Cooling mode Natural wind
Dimension 172.0*121.0*56.5
Configuration Panel open
aperture 164.0*113.0
dimension
Download port RS-232
Port
Com port RS-485

11
HMI Specs

Item Specs
XP series XMP series
Type Kelly/Blue LCD
Screen
3.7 inch
dimension
Useful life Over 20000 hours, 25℃, 24hours operating
Display area 192*64
Contrast Regulation resistance available
Characteristic
Character
Chinese, English
setting
Character size Lattice font, vector font
Matrix or resistance
Touch mode Touch unable
touch mode
Picture 64KB Flash ROM
Register
Data 4KB SRAM

PLC Specs

Specs
Item
XP1/XMP1 XP2/XMP2 XP3/XMP3
Program executing format Loop scan format, time scan format
Program format Instruction, C language and ladder chart
Processing speed 0.5us
Power cut retaining Use Flash ROM and Li battery
User program’s capacity 32KB 128KB 128KB
I/O points Input 10 points, output 8 points
Interior coil’s points (M) 448 8768 8768
Points 80 640 640
Timer 100mS timer:Set time 0.1~3276.7 seconds
(T) Specs 10mS timer:Set time 0.01~327.67 seconds
1mS timer:Set time 0.001~32.767 seconds
Points 48 640 640
Counter 16 bits counter:set value K0~32767
Specs
(C) 32 bits counter:set value -2147483648~2147483647
Data Register(D) 288 words 2612 words 9024 words

12
Flash ROM Register(FD) 510 words 512 words 2048 words
Extension D register (ED) - - 16383
High speed processing - High speed count, pulse output,
function external interrupt
Setting of time scan space 0~99mS
Password protection 6 bits ASCII
Self diagnose function Power on self-diagnose, Monitor timer, grammar check

Note: The user program capacity is referred to the capacity under “secret downloading mode”.

1-3. Parts explanation

Configuration

Screen area

Function
key 6 7 8 9 Number
1 2 3 4
2 3 4 5 key

5 6 7 8 1 0

13
MODE: XP3-18R
Program SN:
DATE:
2
2
006
006
050
051
21
0
18

port 无锡市信捷科技电子有限公司
Points connect
with BD board

Power
supply

RS-485 Com port Output points Input points

In-out points arrangement

24V, 0V: power supply input


A, B: RS-485 com port
COM: common ground
X: Input
Y: Output

Program port

Program port is a RS-232 com port which has double functions of downloading PLC program and
HMI pictures. The pins function of the port is as below:

Pin Function
Pin2 RXD
Pin3 TXD
Pin5 GND
Pin7 RTS

Xinje provides special program cable to download the PLC program or HMI program. You also
can make the cable by yourself. Please see the pin connection between PC and the port.

14
DB9 pins DB9 pins

XP/XMP PC

2 RXD 2 RXD
3 TXD 3 TXD
5 GND 5 GND
7 RTS 7 CTS

Communication port

Communication port ( A and B ) is a RS-485 com port. This port is used to connect other devices.
Please refer to paragraph 3-4 for details.

1-4. Outline dimension

Outline dimension

Unit: mm
56.5 1
72
11

21
1

6 7 8 9
1 2 3 4
2 3 4 5

5 6 7 8 1 0

1
62

15
Installation dimension

Unit: mm

1
64

13
1

16
2. In-out specs and exterior layout

2-1. Input specs

Basic unit

Input signal’s DC24V±10%


voltage
D
Cp owe
r
Input signal’s 7mA/DC24V sup
ply
current
Input ON current Above 4.5mA CO
M
R2
Input OFF current Below 1.5mA R1
X*
0
Input response time About 10ms
Input signal’s Contact input or
format NPN open collector
transistor R4
Circuit insulation Photo-electricity R3
X*
7
coupling insulation
Input action’s LED light when
display input ON

Input connection

Because there is no 24V power supply inside XP/XMP, it needs an outside supplier to drive the
photo-electricity switch sensor. The supplier should be DC 24V±4V. The output transistor of
sensor should be NPN open collector.

DCpower
supply
+5
V
CO
M
R2
R1
X*
0
R
6 R5

L
ED
I=7
mA

R4
R3 powersu
pply
X*
7 DC24
V
s
ens
or

17
l Input points
Connect input point and com point with non-voltage point or NPN open collector transistor to
turn on the input.
l Input loop
The first loop and the second loop are insulated by optical coupler, the second loop has C-R
filter which can prevent wrong action caused by industry noise or input points oscillation. As
the result, there will be a response delay for 10ms to the input points. There is digital filter in
the input points.
l Input sensitivity
Input current is DC 24V 7mA. To make the input reliable, the ON current should be above
3.5mA, the OFF current should be below 1.5mA.

Typical connection

18
2-2. Relay output specs and circuit

Relay output specs

Type R /RT output T output


Relay output R:Y0~Y7
RT:Y4~Y7
Power supply Below AC250V、DC30V
Circuit insulation Machinery insulation
Action indication Produce close sound
Resistor 3A NO
load
Maximum
Inductance 80VA
load
load
LED load 100W
Minimum load DC5V 2mA
Response OFF→ON 10ms
time ON→OFF 10ms

Relay output circuit

l Output points
Relay output has two common points. Different units can drive the loader of different
power-voltage systems.
l Loop insulation
It is electric insulated between relay output point and outside load circuit.
l Action indication
Relay output coil produces close sound when it is on.
l Response time
The response time is about 10ms transferring the ON or OFF signal from relay output coil to
the output connection.
l Output current
Output current is 3A per point to drive resistor load for voltage below AC250V.
Inductor load is below 80VA ( AC100V or AC200V ) and light load is below 100W
( AC100V or AC200V ).
l Open leakage current
There is no leakage current when output point is OFF, it can drive neon light.
l Use life of relay output point
The standard life of inductor load such as contactor, solenoid valve: according to our
experiment results, 20VA load is about 3 million times, 35VA load is about 1 million times,
80VA load is about 0.2 million times. However, the life will extend if parallel connect surge

19
absorber with the load.

Output connection example

Toavo
idb ur
ningPLCbasi
cc i
rc u
it
setafusee v
ery4points
5A~10A
+
24V ACpowe
r
Load ~ supply
Y
*0 <AC25
0V
re
lay dr

Y
*1
iveci

Y
*2 M
rcu

Y
*3
it

R
ela
you
tpu
t

Note: T type has no relay output, do not connect AC220V, or the product will be broken.

Constitution of output circuit

l For DC inductor load, please parallel connect with commutate diode. If not connect with the
commutate diode, the point’s life will be decreased greatly. Please choose the commutate
diode which allow inverse voltage endurance up to 5~10 times of the load’s voltage, ordinal
current exceeds load current.
l Parallel connect AC inductor load with surge absorber can reduce noise and extend useful life
of the points.

DC load

AC load

20
2-3. Transistor output specs and circuit

Transistor output can divide into two types: high speed pulse output and normal transistor output.

High speed pulse output

Type RT output T output


High speed pulse Y0~Y1 Y0~Y1
output point
Power supply Below DC5~30V
Maximum current 50mA
Maximum pulse 200KHZ
frequency

Normal transistor output

Type RT output T output


Transistor output point Y2~Y3 Y2~Y7
Power supply Below DC5~30V
Circuit insulation Optical coupling insulation
Resistor 0.4A
load
Maximum
Inductor 12W/DC24V
load
load
Light load 1.5W/DC24V
Minimum load DC5V 2mA
Repose OFF→ON Below 0.2ms
time ON→OFF Below 0.2ms

Normal transistor output circuit

l Output point

21
There is one common point for basic unit transistor output
l Power supply
The load circuit power supply should be steady voltage of DC5~30V.
l Circuit insulation
The inside circuit of XP/XMP is insulated with output transistor by optical coupler.
l Action indication
When driving optical coupling,LED lights,output transistor is ON.
l Response time
From optical coupler driving (or cut) to transistor ON (or OFF), the time is below 0.2ms.
l Output current
The current is 0.4A per point. But due to restriction of temperature going up, the total current
is 0.8A every four points.
l Open current
Less than 0.1mA.

ToavoidburningPLCbasiccircuit
usesuitablefusefortheload
1A
DCpower
Load supply
Y*4 DC5~30V
p
d

Load
h
r
o
i
t

Y*5
v
o
e c
-e
l

Load
ec
i

Y*6
t
r
r
c
i
u
c
i

Load
i
t
t

Y*7
y

22
3. PLC function and application

3-1. PLC instruction


The XP/XMP integrated with XC series PLC. The function of PLC is the same as XC series.

XP/XMP Type Integrated PLC type


XP1/XMP1 series XC1 series
XP2/XMP2 series XC2 series
XP3/XMP3 series XC3 series

Instruction

1. XP1/XMP1 series include SFC instructions and applied instructions, exclude special function
instructions.
2. XP2/XMP2 series and XP3/XMP3 series have the same instructions. They include SFC
instructions, applied instructions and special function instructions.
Please refer to XC Series PLC Manual: paragraph 4, 5, 6.

Special function instructions

XP2/XMP2 and XP3/XMP3 have special function instructions, please refer to XC Series PLC
Operating Manual: paragraph 6. Here we only give the port definition and distribution.
1. High speed count
XP2/XMP2/XP3/XMP3 series
Increase mode Pulse+direction mode AB phase mode
C600C602 C604 C606 C608 C610 C612 C614 C616 C618 C620 C622 C624 C626 C628 C630 C632 C634
Highest
80K 80K 10K 10K 10K 80K 10K 10K 80K 5K 5K
frequency
4 times
√ √
frequency
Count
√ √ √ √ √ √ √
interruption
X000 U U A
X001 U Dir B
X002
X003 U U A
X004 Dir B
X005
X006 U U A
X007 Dir B

23
X010
X011 U
X012

2. High speed pulse output


u T type: Y0, Y1 available, the highest frequency is 200KHz
u RT type: Y0, Y1 available, the highest frequency is 200KHz
u R type: unavailable

3. Interrupt function

Channel Input Pointer tag Disable interruption


Rising interruption Falling interruption instruction
CHL1 X2 I0000 I0001 M8050
CHL2 X5 I0100 I0101 M8051
CHL3 X10 I0200 I0201 M8052

4. Frequency measurement
The point is X1, X11, X12.

5. Pulse width modulation


The point is Y0, Y1.
u T type: Y0, Y1 available
u RT type: Y0, Y1 available
u R type: unavailable

6. Precise timer
32 bit precise timer, the timer range is T600 to T618, match with 10 interruption tag.

3-2. soft component range

XP/XMP series soft component ID distribution list is as below:


If extending BD board, the in-out point definition, please refer to XP Series Extended BD Board
Manual.

24
XP1/XMP1 series:
Soft
Name Range Points
component
X Input points X000~X011(octal) 10
Y Output points Y000~Y007(octal) 8
M0~ M199
320
【M200~M319 】
For special using M8000~M8079
M Auxiliary relay For special using M8120~M8139
For special using M8170~M8172 128
For special using M8238~M8242
For special using M8350~ M8370
S Process S0~S31 32
T0~T23:100ms not accumulation
T100~T115:100ms accumulation
T200~T223:10ms not accumulation
T Timer 80
T300~T307:10ms accumulation
T400~T403:1ms not accumulation
T500~T503:1ms accumulation
C0~C23:16 bits plus counter
C300~C315:32bits plus/minus counter
C Counter 【C600~C603】: vacant 48
【C620~C621】: vacant
【C630~C631】: vacant
D0 ~D99
150
【D100~D149】
For special using D8000~D8029
For special using D8060~D8079
D Data register
For special using D8120~D8179
138
For special using D8240~D8249
For special using D8306~D8313
For special using D8460~D8469
FD0~FD411 412
For special using FD8000~FD8011
Flash ROM For special using FD8202~FD8229
FD
register For special using FD8306~FD8315 98
For special using FD8323~FD8335
For special using FD8350~ FD 8384

25
XP2/XMP2 and XP3/XMP3 series:
Soft Range Point
Name
component XP2/XMP2 XP3/XMP3 XP2/XMP2 XP3/XMP3
X Input point X000~X011(octal) 10
Output
Y Y000~Y007(octal) 8
point
M0~ M2999
Auxiliary 8000
M 【M3000~M7999 】
relay
M8000~M8767 768

S0~ S511
S Status 1024
【S512~M1023 】
T0~T99:100ms not accumulation
T100~T199:100ms accumulation
T200~T299:10ms not accumulation
T300~T399:10ms accumulation
T Timer 640
T400~T499:1ms not accumulation
T500~T599:1ms accumulation
T600~T618:1ms with interruption precise time
T620~T639:vacant
C0~C299:16 bits forth counter
C300~C318:32 bits forth/back counter
【C320~C598】:32 bits forth/back counter
C Counter 【C600~C619】:one phase high speed counter 640
【C620~C629】:Pulse + direction high speed
counter
【C630~C639】:AB phase high speed counter
D0~D999 D0~ D3999
2000 8000
【D4000~D4999】 【D4000~D7999】
Data
D For special using
register For special using
D8000~D8511 612 1024
D8000~D9023
D8630~D8729
FD0~FD127 FD0~FD1535 128 1536
FlashROM
FD For special using For special using
register 384 512
FD8000~FD8383 FD8000~FD8511
Extend data
ED - 【ED0~ED16383】 - 16384
register

NOTE:
※1. The memorizer area in 【 】 is the defaulted power failure retentive area, the power
failure retentive area of soft components D, M, S, T, C can be set via FD register. For
the details, please see the following table.
※2. Flash ROM register needn’t set power failure retentive area, its data won’t lose when

26
power is cut (No battery).
※3. The serial number of input coil and output relay are octal data, other memorizers’
number are all decimal data.
※4. There is no I/O point connected with exterior device can be used as interior relay.

Soft component power failure area setting:


XP1/XMP1:
Soft Power failure
Area Function Default value
component memory area
First address of the power
D FD8202 100 D100~D149
failure memory area of D
First address of the power
M FD8203 200 M200~M319
failure memory area of M
First address of the power
T FD8204 640 No set
failure memory area of T
First address of the power
C FD8205 320 C320~C631
failure memory area of C
First address of the power
S FD8206 512 S0~S31
failure memory area of S

XP2/XMP2:
Soft Power failure
Area Function Default value
component memory area
First address of the power
D FD8202 4000 D4000~D4999
failure memory area of D
First address of the power
M FD8203 3000 M3000~M7999
failure memory area of M
First address of the power
T FD8204 640 No set
failure memory area of T
First address of the power
C FD8205 320 C320~C639
failure memory area of C
First address of the power
S FD8206 512 S512~S1023
failure memory area of S

XP3/XMP3:
Soft Power failure
Area Function Default value
component memory area
First address of the power
D FD8202 4000 D4000~D7999
failure memory area of D
First address of the power
M FD8203 3000 M3000~M7999
failure memory area of M
First address of the power
T FD8204 640 No set
failure memory area of T

27
First address of the power
C FD8205 320 C320~C639
failure memory area of C
First address of the power
S FD8206 512 S512~S1023
failure memory area of S
First address of the power
ED FD8207 0 ED0~ED16383
failure memory area of ED

NOTE:
Users can set the power failure memory area, but the area can not over the soft component area.

3-3. Set up a project

About the software

The PLC program editing software is the same as Xinje XC series. Software name is XCPPro.
The interface of software is as below:

Set up a project

We take XP3-18R as a example to explain how to set up a project.


1. Modify the type
Open the software, click file---change PLC model:

28
Choose “ XP3-18/XMP3-18”:

XP1/XMP1series choose
XP1-18/XMP1-18;

XP2/XMP2 series choose


XP2-18/XMP2-18;

XP3/XMP3 series choose


XP3-18/XMP3-18

2. Compile the program


For program compiling and software operating please refer to XC Series Edit Tool XCP Pro User
Manual.

29
Download the program

1. Connection
Before downloading the program, please ensure the XP/XMP has connected with PC successfully.
( The cable connection please refer to paragraph 1-3 ).
Click to open software serial port configuration:

Choose the correct serial port, baudrate and parity or click “check” to choose these parameters
automatically.
When below window shows “ connect to PLC succeeded ”, it means the connecting is successful.
Click OK to continue.

If the connecting is not successful, the window will show “ communication error ”. Please check
the serial port and the cable.

2 Download the program


After connecting successfully, click to download the PLC program. If the PLC is running, it
will pop up the stop running window, click OK to continue downloading.

30
After downloading, click to run the PLC program.

3 Upload the program


If you want to check the PLC program in XP/XMP, click to upload the program to the PC.
Then click to save the program.

3-4. communication function

XP/XMP series support Modbus and free format communication protocol. The instructions please
refer to XC Series PLC Operating Manual paragraph 6-4-1 and 6-4-2.

Communication port

XP/XMP series product have program port ( DB9 pins port ) and RS-485 com port ( A, B point ).
Program port can only be used to download PLC program and HMI pictures. However, RS-485
port can be used to communicate with other devices.
RS-485 port can be connected with varied devices, the communication parameters ( baud rate,
data bit, etc ) can be set via software.

31
MODE: XP3-18R
SN: 200605021
18
DATE: 20060510

无锡市信捷科技电子有限公司

RS-485
com port

RS-485 com port: Point A means “ + ” signal, point B means “ – ” signal.


Attention:
XP1/XMP1 series product can only be used as slaver station while using their RS-485 port to
communicate with other devices.

Communication parameter

Station No. Modbus station No. : 1-254, 255(FF) is for free format communication
Baud rate 300bps~115.2Kbps
Data bit 8 or 7 bits
Stop bit 2 or 1 bits
Check Even, odd, no check

The defaulted parameters of the port:


Station number is 1, baud rate is 19200bps, 8 data bit, 1 stop bit, even check

Parameter setting

User can set com port parameters. Please see below list for details.
Attention:
After changing the parameters in Flash register, it is need to reboot the XP/XMP to make the
setting become effective.

32
Number Function Description
FD8220 Communication mode 255 is free format,
( station number ) 1~254 is modbus station number
FD8221 Communication format Baud rate, data bit, stop bit, check
AB FD8222 ASC timeout judgment time Unit: ms, 0 means no timeout waiting
com FD8223 Reply timeout judgment time Unit: ms, 0 means no timeout waiting
port FD8224 Start symbol High 8 bits invalid
FD8225 End symbol High 8 bits invalid
8/16 bits cushion,
FD8226 Free format setting with/without start bit,
with/without stop bit

The way of setting communication parameters:

FD8221:

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0:300bps
0:No check
1:600bps
1:Odd check
2:1200 bps
2:Even check
3:2400 bps
0:2 stop bits 4:4800 bps
2:1stop bit 5:9600 bps
6:19.2K bps
0:8bits data 7:38.4K bps
1:7bits data 8:57.6K bps
9:115.2K bps

FD8226:

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0:8 bits communication


Reserved
1:16 bits communication

0: without start symbol


1: with start symbol

0:without end symbol


1:with end symbol

33
Modbus communication

XMP series product support master and slave mode of Modbus communication protocol.
Master format: When PLC is set to be master station, PLC sends request to other slave station
devices via Modbus instructions, other devices respond to the master station.
Slave format: When PLC is set to be slave station, it can only respond to other master devices.
The defaulted status of XMP is Modbus slave mode.

Communication address

The internal soft unit’s numbers of XMP are corresponded with Modbus station address numbers,
please see the following table:
Coil space: ( Modbus address prefix is “ 0x ” )
Bit component address Modbus address Modbus address
( decimal K ) ( hex H )
M0~M7999 0~7999 0~1F3F
X0~X1037(octal) 16384~16927 4000~421F
Y0~Y1037(octal) 18432~18975 4800~4A1F
S0~S1023 20480~21503 5000~53FF
M8000~M8511 24576~25087 6000~61FF
T0~T618 25600~26218 6400~666A
C0~C634 27648~28282 6C00~6E7A

Register space: ( Modbus address prefix is “ 4x ” )


Word component Modbus address Modbus address
address ( decimal K ) ( hex H )
D0~D7999 0~7999 0~1F3F
TD0~TD618 12288~12906 3000~326A
CD0~CD634 14336~14970 3800~3A7A
D8000~D8511 16384~16895 4000~41FF
FD0~FD5000 18432~23432 4800~5B88
FD8000~FD8511 26624~27135 6800~69FF

Free format communication

Free format communication transfer data in the format of data block, each block can transfer 128
bytes at most. Meanwhile each block can set a start symbol and a end symbol, or not set.
When communicating in free format mode, FD8220 should be 255.

Start Symbol (1 byte) Data Block (max bytes 128 ) End Symbol (1 byte)

34
4. HMI function and application

4-1. HMI function introduction

The HMI part of XP/XMP used OP330/MP330 series display. The faceplate key-press function is
as below:

Key-press Function
Whatever the mode of the display is in, it will return to original system
screen once you press the key ( the defaulted screen is No.1 ). Generally, set
the original system screen to be main menu or most used screen.

Turn the screen to the last page

Turn the screen to the next page

Press the key to modify the register value. The register which is being
modified will display in reverse colour and the bit will twinkle. If there is no
register component in the screen it will do vacancy operation once. Before
pressing [ENT] key, press [SET] key again to cancel the setting and
continue modifying the next data register.
To write the modified value in the register and continue modifying next
register. After the last register in the screen has been modified, it will quit
the setting.
Alarming list key. After setting the function of alarming list, press this key
to jump to the alarming list screen.

Clear the selected area when modifying the register data.

Set the positive or negative of the data when modifying the register data.

Number key 0-9, press the key to set the number you want

Function key F1-F8

NOTE:
Besides the function listed in the up table, all the keys can be defined as the function of “force
ON”, “force OFF”, “reverse” or “momentary ON”.
Please see below picture. Open OP software, put a button in the screen. All the faceplate
key-presses are displayed in the key menu, user can set the function as they need.

35
4-2. Build a project

About the software

XP/XMP series product integrated the function of HMI and PLC, when editing the HMI screen,
use HMI software OP20.

The interface of OP20 is shown as below:

36
Build a project

We take XMP3-18R as an example to explain how to build a project.


1. build a new project
Open the OP software, click “file”-“new project” or click “ ” to build a new project.
2. choose the display type
In the “select model” window, choose the correct type of XP/XMP. For this example we select
“MP330(XMP)”.

This window shows all the display type


supported by OP software.
We can select the correct type according to the
content in the bracket.
XP series should select OP330
XMP series should select MP330

3. select PLC type


As the XP/XMP is a integrated product of OP and XC, the OP will communicate with XC inside
the product, the communication parameters are defaulted.

4. edit the screen


After these three steps, we can enter screen editing mode. For the editing details, please refer to
OP Series Display User Manual chapter 2.

37
Screen download

1. Select com port


Before downloading the screen, select the correct com port. The port is DB9 pins serial port of PC.
The computer will select the port automatically, user only need to know the port number. If user
can not confirm which port to use, try each port in file. If the com port is wrong, it will prompt
you with the note “can not open”:

Click “file”-“comm port…” to select the correct com port:

2. download
Connect the XP/XMP DB9 pins com port and PC serial port using download cable. Power on the
XP/XMP, click to start downloading:

If the downloading is completed, it will pop up below window:

Attention:
(1) Do not cut the power when downloading, or you have to download again
(2) The downloading cable of downloading OP screen is the same as downloading PLC program
(3) Do not download when XCPPro and OP software are both opened

38
5. The extension ability of XP/XMP

5-1. Extend BD board

XP3/XMP3 series product (exclude XMP2-32R/T-E ) can extend XP3 series BD board via the
insertion groove at the back in order to control and measure the analog quantity.
The specs and type of BD board is as below table:

BD board type

Type Function
XP3-2AD2PT-BD 2 channels analog input
2 channels PT100 temperature measurement
XP3-2TC-P-BD 2 channels K thermocouple temperature measurement
PID adjustment inside
XP3-2PT2AD1DA-BD 2 channels PT100 temperature measurement
2 channels analog input
1 channel analog output

BD board specs

XP3-2AD2PT-BD:
Item Voltage input Temperature input
Analog input DC0~5V、0~10V(Input resistor 300k Platinum resistor Pt100(2-line
signal Ω) format)
Temperature
measurement - -100~350℃
range
Distinguish ratio 0.15mV(10/16383) 0.1℃
Digital output
0~16383 -1000~3500
range
Integrated
±0.8% of the full-scale
precision
Convert time 15ms×4 channels
PID output value 0~K4095
Empty loader
0 3500
defaulted value

39
Input
characteristic

Insulation No insulation among each channel of PLC


0 point (As it is operated via data register, it is not restricted by master
I/O point
PLC’s standard max control points)

XP3-2TC-P-BD:
Items Content
Analog input signal K type thermocouple
Input points 2 points
Temperature 0℃~970℃
measurement range
Digital output range 0~9700, 16 bits binary
Output points 2 points
Output format NPN collector open transistor output
Control precision 0.4℃
Distinguish ratio 0.1℃
Integrated precision ±0.8% ( relative max value)
Convert speed 45ms×2 channels
Analog using power DC24V±10%,50mA

XP3-2PT2AD1DA-BD:
Item Voltage input Temperature input D/A output
Analog input DC0~5V, 0~10V(input Platinum resistor Pt100 (2

signal resistor 300kΩ) lines format)
Digital input
- - 10 bits binary (0-1023)
range
Analog output
- - 0~20mA, 4~20mA
range
Temperature
measurement - -100~350℃ -
range
Distinguish
0.15mV(10/16383) 0.1℃ 1/1023
rate
Digital output 0~16383 -1000~3500 -

40
range
Integrated
±0.8% of the full-scale
precision
Convert time 15ms×4 channels
PID output 0~K4095
Empty loader
0 3500 -
defaulted value

In-out
characteristics

insulation There is no insulation among each channel of PLC


0 point (As it is operated via data register, it is not restricted by master PLC’s standard
I/O point
max control points)

Installation position of BD board

The installation position of BD board on XP3/XMP3 is as below:

MODE: XP3-18R
SN: 200
6 05021
18
DATE : 20060510
Install here
无锡市信捷科技电子有限公司

The configuration method and using details please refer to BD Board Manual.

41
5-2. Extend MA model

XP/XMP can extend MA model via RS-485 com port (A and B point) in order to control and
measure analog quantity.
The type and specs of MA model are as below:

MA model type

Type Function
MA-8X8YR 8 channels digital input, 8 channels digital output
MA-16X 16 channels digital input
MA-16YR/T 16 channels digital output
MA-4DA 4 channels analog output
MA-4AD 4 channels analog input
MA-8AD-A/V 8 channels analog input
MA-4AD2DA 4 channels analog input, 2 channels analog output
MA-6TC-P 6 channels type K thermocouple temperature control
MA-6PT-P 6 channels PT100 temperature control

MA model specs

Type Description
MA-8X8YR 8 channels digital input,8 channels
digital relay output
MA-16X 16 channels digital input

MA-16YR 16 channels digital relay output

MA-16YT 16 channels digital transistor output

MA-4DA
Item Voltage output Current output
DC0~5V、0~10V DC0~20mA、4~20mA
Analog output range ( exterior load resistor (exterior load resistor less than
2KΩ~1MΩ) 500Ω)
Digital input range 10 bits binary numbers
Resolution ratio 1/1023(10Bit)
Integrated precision 0.8%
Conversion speed 3ms/1 channel
Power of analog quantity DC24V±10%,100mA
Installation Use M3 screw or fix on DIN46277 rail ( width 35mm )

42
Profile dimension 63mm×102mm×73.3mm

MA-8AD-A/V
Item Voltage Current
DC0~5V、0~10V DC0~20mA、4~20mA
Analog input range ( exterior load resistor ( exterior load resistor less than
2KΩ~1MΩ) 500Ω)
Maximum input range ±18V 0~40mA
Digital output range 12 bits binary numbers

Resolution 1/4095(12Bit)

Integrated precision 0.8%


Conversion speed 20ms per channel
Power supply for analog DC24V±10%,100mA
Installation Use M3 screw or fix on DIN46277 rail ( width 35mm )
Profile dimension 63mm×102mm×73.3mm

MA-4AD
Item Analog input (4AD)
Analog input type Voltage input Current input

Analog input range 0~5V,0~10V 0~20mA,4~20mA


Maximum input range DC±18V 0~40mA

Digital output range 12 bits binary value (0~4095)

Resolution 1/4095(12Bit)
PID output range 0~K4095

Integrated precision 0.8%


Converting speed 20ms per channel

Power for analog DC24V±10%,100mA

Installation Fix up the module with M3 screw or put on DIN46277 rail (width 35mm)
Profile dimension 63mm×102mm×73.3mm

MA-4AD2DA
Item Analog input ( 4AD ) Analog output ( 2DA )

Voltage input Current input Voltage output Current output

Analog input range 0~5V,0~10V 0~20mA,4~20mA -

Max input range DC±18V 0~40mA -

0~5V、0~10V, 0~20mA、4~20mA
Analog output range - ( exterior load (exterior load resistor
resistor 2KΩ~1MΩ) less than 500Ω)

43
Digital input range - 10 bits binary number (0~1023)

Digital output range 12 bits binary number (0~4095) -

Resolution 1/4095(12Bit) 1/1023(10Bit)

PID output value 0~K4095

Integrated precision 0.8%

Conversion speed 20ms/1 channel 3ms/1 channel

Power supply for


DC24V±10%,100mA
analog quantity
Installation Use M3 screw or fix on the DIN46277 ( width 35mm ) rail

Profile dimension 63mm×102mm×73.3mm

MA-6TC-P

Item Specs
Using environment 0℃~60℃

Measure temperature range 0℃~1000℃


Digital output range 0~4095, 12 bits with sign, binary

Precision 1℃
Integrated precision 1℃

Conversion speed 20ms/1 channel


Power supply for analog DC24V±10%, 50mA
Installation Use M3 screw or fix on DIN46277 ( width 35mm ) rail

Profile dimension 63mm×102mm×73.3mm

MA-6PT-P
Item Description
Analog input signal Pt100 Pt hot resistance

Measure temperature range -100℃~350℃


Digital output range Full-scale 4095, 12 bits with sign, binary

Control precision ±0.1℃


Resolution 0.1℃
Integrated precision 0.8% ( related maximum )

Conversion speed 20ms/1 channel


Power supply for analog DC24V±10%,50mA
Installation Use M3 screw or fix on DIN46277 rail ( width 35mm )
Profile dimension 63mm×102mm×73.3mm

44
MA model connection

XP/XMP can connect with MA model via RS-485 com port (A and B point). It can extend 16 MA
models via setting DIP switch of MA model.
Please see the connection figure:

0
V B V
O1 VO2 GN
D 0V B VO1 V O
2 GN
D
2
4V A IO
1 GN
D I
O2 2
4V A I
O1 G
ND I
O2

MA-4AD2DA MA-4AD2DA
AO A
O
PW
R P
WR

RU
N R
UN
ER
R E
RR

6 7 8 9 AI A
I

1 2 3 4
2 3 4 5
A
I1 VI
2 G
ND A
I3 V
I4 G N
D AI
1 V
I2 GN
D A
I3 V
I4 G ND

5 6 7 8 1 0 V
I1 GN
D AI
2 VI
3 GN
D A
I4 V
I1 GN
D AI
2 VI
3 GN
D A
I4

XP/XMP MA station No.1…………….MA station No.16


The details and using method please refer to MA Model Manual.

5-3. Other extension

Besides BD board and MA model, XP/XMP series product can extend other devices which
support RS-485 and Modbus protocol.
XP/XMP can extend 32 devices via RS-485 com port such as PLC, meter, printer, inverter, HMI
etc.
The connection figure is as below:

6 7 8 9
1 2 3 4
2 3 4 5

5 6 7 8 1 0

RS485 Modbus protocol

MA
Meter HMI Inverter
module

Attention:
The connection method is Bus mode, transmission line should start from station 1 to station 2,
then from station 2 to station 3…….., connect as this sequence until the last station. Star mode or
ring mode connections are not permitted.

45