PARTIAL DISCHARGE ANALYZER

DAC-PD-9
Electrical equipment such as power transmission and distribution equipment critical for social
infrastructures and factories that operate 24 hours a day is demanded of high reliability even when
used under severe conditions. Recent years have seen attempts to diagnose the accurate
remaining lifespan during periodic inspections, and realize use of such equipment beyond the
design life-cycle through implementation of appropriate maintenance. In addition, equipment
diagnostic techniques as means of preventive maintenance have also become essential to prevent
the sudden breakdown of electrical equipment. To meet the expectations for these electrical
equipment diagnoses, Soken Electric Co., Ltd. has developed Digital Partial Discharge Analyzer
DAC-PD-9 that incorporates the very latest digital technology.

Partial Discharge Analyzer


Model DAC-PD-9

PD Analyzing Software

Covering widely required tests by IEC standards, DAC-PD-9 is an analyzer with a wide-band
amplifier. The set incorporates the same conventional testing functions as low-frequency
(narrowband), wide-band and tuned measuring instruments do. Moreover, it is also capable of
ultra wide-band measurements (up to 40 MHz). DAC-PD-9 allows a selection of optimum
frequency bands suitable for any type of test specimens to enable quantitative and
reproducible partial discharge measurements. In addition, the set can sample in time-series
all data to enable statistical and quantitative measurements.

Test Specimen

●HV Transformer ●Power Cable ●Generator, Motor, Coil ●Capacitor, Bushing ●Circuit Breaker, Switch

TRANSFORME CABLE GENERATOR MOTOR CONDENSER GIS

G M

SOKEN ELECTRIC CO., LTD.


DAC-PD-9
PARTIAL DISCHARGE ANALYZER

Features
 Digital technology enables determination of the true polarity of partial discharges.
 All parameters such as cumulative frequency and net peak are displayed in real time.
 Discharge pulses of positive and negative electrodes can be counted simultaneously.
 Center frequencies and frequency bandwidths can be freely selected for measurement.
 The large-capacity memory enables long-term data storage.

Variable Measuring Frequency 周波数帯域:HIGH


Fre qu e n cy Ba n d: HIGH
VH F Ba n d
ゲイン 4M VHF帯域 40M
The evaluation of partial discharge largely depends on Ga in

selection of frequency bands. Taking into account the


propagation characteristics and electrical structure of test BW 周波数
⊿f=3M
specimen, and paying attention to the noise environment 周波数帯域:MID
Fre qu e n cy Ba n d: MID 任意の中心周波数
Fre qu e n cy

and data reproducibility, the optimal frequency band ゲイン 400k


Wid e Ba nd
広帯域
Opti ona l Ce ntr e Fr equ en c y

4M
should be selected Ga in

●Frequency Band: Low Band :20kHz - 400kHz


: MID Band :400kHz - 4MHz Fre qu e n cy Ba n d: L o w
周波数
Fre qu e n cy

: HIGH Band :4MHz - 40MHz 周波数帯域:LOW

●Center Frequency
10 k Na rr o w Ba n d 400k
:40kHz - 40MHz ゲイン 10k 狭帯域
Ga in 400k

●Frequency Band Range


LOW Band :30kHz,50kHz,100kHz,300kHz 周波数
MID Band :300kHz,500kHz,1MHz,3MHz Fre qu e n cy

HIGH Band :300kHz,500kHz,1MHz,3MHz

Partial Discharge Analyzing Software Polarity Judgment


Data such as Q, Phase and Time obtained Auto-Judging in polarity of partial discharge
by DAC-PD-9 can be saved in PC with USB waves in a wide band.
interface to analyze and evaluate.

Numerical Evaluation of Partial Discharges by a digital sampling


●Average discharge current I
The average discharge current is expressed in coulombs per second(C/s) or in amperes(A).
1
I= (| q1 | + |q 2 | +  + | q i |)
Tref
●Discharge power P
Where an ui is instantaneous value of the test voltage at the instant occurrence of the
individual apparent charges magnitude as qi.
The discharge power is expressed in watts (W) and becomes the cause of the electric
power loss of the sample.
1
P= (q1・u1 + q 2 ・u 2 +  + q i・u i )
Tref
●Quadratic rate D
The quadratic rate is expressed in (coulombs)2 per second (C2/s), and the partial
discharge magnitudes will be accentuated and displayed.
1
D= (q12 + q 22 +  + q i2 )
Tref
■ Digital PD Analyzer DAC-PD-9
- TFT liquid crystal and touch keys enable simple, visual operation.
- Compact (W320 x D350 x H150mm) and lightweight (10 kg).
- Interface with USB and LAN.
- The analyzer can be used by itself for measurement independent of a PC.
- Measured data is stored in USB memory.

■Analysis
Partial Discharges can be displayed visibly in
2D or 3D graphics for analysis.

Σn-Q(Cumulative Number-Quantity)
■Calibrator DAC-CP-2
●Output Voltage :5V、50V
●Lamp Time :<20nS
●Generating Pulses :0~10000pC
●Repetition Frequency:50Hz
●Power Source :Battery 7.2V
0Q-φ-t(Quantity-Phase-Time) ●Size :W170×H60×D110(mm)
●Weight :800g, approx.

Q-φ-V(Quantity-Phase-Voltage) ■Detector DAC-PDE-2


●Applicable Frequency Band
:10kHz - 4MHz
●Max. Applicable Current
:Balance Circuit 5A
:Un-balance Circuit 1A
●Size :W170×H70×D110(mm)
●Weight :1kg, approx.
理由
■Detector and Divider DAC-PDE-6
●Applicable Frequency Band
:10kHz – 4MHz
●Max. Applicable Current
:Balance Circuit 5A
:Un-balance Circuit 50mA
●Test Frequency :50/60Hz
●Test Voltage Dividing Capacitor:2μF
●Size :W180×H100×D120(mm)
●Weight :2.3kg, approx.

■Coupling Capacitor
DAC-LCC-15 DAC-LCC-30 DAC-LCC-50
Rated Voltage(kV) 15 30 50
Rated Current(A) 3 3 3
Capacitance(pF) 1000 1000 600
■Clamp-type High Frequency CT Hight(mm) 512 702 912
●Measuring Frequency Band: Weight(kg) 8 13 15
10kHz - 100MHz
●Max. Current:39.3A
●Aperture:31Φ
DAC-PD-9
PARTIAL DISCHARGE ANALYZER
Specifications

Partial Discharge Measuring Unit


Maximum Partial Discharge Measuring Range 1-100000pC
Phase Resolution 1 deg.
Evaluted Inception Frequency 10 - 400pps
Allowable Repetition Frequency Rate Measuring Range 0 - 9999pps
Polarity Auto Judgement
Frequency Range Center Frequency 40kHz - 40MHz
Frequency Range Width LOW 30kHz,50kHz,100kHz,300kHz
Low Band:20kHz-400kHz MID 300kHz,500kHz,1MHz,3MHz
MID Band :400kHz-4MHz HIGH 300kHz,500kHz,1MHz,3MHz
HIGH Band:4MHz-40MHz Gain LOW -40dB to 74dB
MID -40dB to 74dB
HIGH -40dB to 104dB
Input Characteristic Input Impedance 50Ω
Input Voltage Range 0 - 2 Vp-p
Memory Max.3000 Cycles
(Number of sycles Power Source
Frequency)
Voltage Detection(Torigger source)
Input Characteristic Input Impedance 1MΩ
Input Voltage Range 0 - 20Vrms
Input Frequency Range 50/60Hz
Interface/Power Source
Interface USB 2.0/1.1 or equivalent B type、LAN
External Memory Function USB
Size and Weight W320×D350×H150(mm) Approx. 10kg
Power Source AC100V-240V ±10% 50/60Hz
Ambient Temperature/Humidity 0 - 40℃ / 20 - 85%(No Dew)
Partial Discharge Analysing Software
System Requirements OS Windows XP, 7

Connection Diagram

●GST(Grounded Specimen Test) ●UST(Un-grounded Specimen Test)

Blocking Coil
ブロッキング
ブロッキング コイル
コイル
Blocking Coil
Test Source Test
試験電源
Source
試験電源
Coupling
Coupling Capacitor カップリング Specimen
Specime
カップリング Capacitor
コンデンサ 供試品 DAC-PD-9
供試品 コンデンサ DAC-PD-9
測定器本体 測定器本体

PA RTIAL DISC HARGE DETE CTOR

PA RTIAL DISC HARGE DETE CTOR

D1 D2 D3

D1 D2 D3 V OL T.
TRG.IN
USB GND 1A AC 100V
SIGNAL
V OL T.
TRG.IN
USB GND 1A AC 100V
SIGNAL G ND
USE
O UT F
G ND
USE
F
O UT
B A L AN C E U N BA L A N CE

B A L AN C E U N BA L A N CE

接地 Grounding
接地
Grounding

2018/06/07

1-34-22, TOBITAKYU TEL: 81 42 490 6929 (Export Dept)


CHOFU, TOKYO 182-0036 FAX: 81 42 490 6807
JAPAN www.soken-jp.com

You might also like