TECHNICAL SPECIFICATION
500mm Long 1) DESIGN CONDITIONS :
Aviation Light 1.1 BASIC WIND SPEED : 41 m/s (AS 1170.2-2011 Region A)
(By Others) Galvanised Steel
Lightning Rod 1.2 TERRAIN CATEGORY : 1 (OPEN SEA, UNOBSTRUCTED)
1.3 BASE ELEVATION : 4m above Ground Level
1.4 LANTERN QTY : Max. 6 Nos. Floodlights
1.5 LANTERN WEIGHT : 180 kg total (incl. Ballast)
1.6 LANTERN DIRECTION : UNI-DIRECTIONAL
1.7 DEFLECTION LIMIT : max. 2.5% of mast height
at Serviceability Wind
2) STANDARDS :
Raising and lowering
(Self-Locking) Headframe 2.1 MAST DESIGN : AS 1170.2 , AS 4100
c/w winch wire ropes, lantern 2.2 STEEL MATERIAL : BS EN 10025 S355JR
mounting brackets & 2.3 WELDING : AS 1554
electrical cable 2.4 GALVANISING : HOT-DIP TO AS 4680
2.5 QUALITY ASSURANCE : ISO 9001:2015
16 ~F 36 Holes for
FLOODLIGHT ARRANGEMENT
175
M30 Anchor Bolts Gr8.8
200
C.L.
on 710 PCD Hot-Dip Galvanised
(175mm Thread Protrusion
from Concrete Level)
600
900
700
M30
20-SIDED POLYGONAL
100
Lantern Mounting Height
B 11JUL12 AMENDED BASE DIMENSION AND ADDED MAST DIAMETERS. ALBERT TS LIM
A 30APR12 ADDED AVIATION LIGHT AND LIGHTNING ROD. ALBERT TS LIM
A 30APR12 ADDED BASE FLANGE AND ANCHOR BOLT DETAIL DIMENSIONS. ALBERT TS LIM