Valvula
CSA Certified
• ANSI Z21.21 / CSA 6.5
• Marked C/I
• File # 157406
FM Approved
• Class 7411
• File # 3047863
Commonwealth of Massachusetts
Approved Product
• Approval code G1-1107-35
• Gas Safety Shutoff Valve
is fast opening, while V2 of the DMV-DLE gas, propane, butane, air and other
is slow-opening for smoother light-off. inert gases. Suitable for up to 0.1% by
Max. flow adjustment on V2 provides volume, dry H2S.
variable main flow on both models.
A “dry” gas has a dew point lower than
Internal profiles and compact design +15 °F and its relative humidity is less
optimize flow and provide a low pres- than 60 %.
sure drop.
Directly mounting the following DUNGS Viton versions available and suitable for
accessories creates a compact valve up to 1 % H2S and 100 % Humidity.
1…8 train without additional piping:
Specification
DMV Two normally closed safety shutoff valves in one housing. V1 and V2 are fast opening, fast closing.
DMV-D Two normally closed safety shutoff valves in one housing. V1 and V2 are fast opening, fast closing.
Adjustable max. flow on V2.
DMV-DLE Two normally closed safety shutoff valves in one housing. V1 fast opening, fast closing. V2 slow
opening, fast closing valve. Adjustable max. flow V2 and adjustable initial lift with V2.
Specifications
Flange sizes 65 (2 1/2") 80 (3") 100 (4") 125 (5")
Connection flange as per DIN 2501 Part 1, to fit pre-weld flanges as per DIN 2633
(PN 16) DN 125, ISO 7005 - 1 (PN 16), or ISO 7005 - 2 (PN 16).
Max. operating pressure 7 PSI (500 mbar)
Max. body pressure 15 PSI (1000 mbar)
Max. close off pressure 7 PSI (500 mbar)
Electrical ratings (+10 % / -15 %) 110 - 120 VAC @ 50 - 60 Hz and 24 VDC. Part numbers listed on page 3.
220 - 240 VAC @ 50 - 60 Hz (P/N on request)
Enclosure rating NEMA Type 12 (NEMA Type 4 optional)
Electrical connection DIN-connector with 1/2” NPT conduit adapter (order separately)
Operating time 100 % duty cycle
Closing time <1s
Opening time (to max. flow) DMV-... V1 & V2 < 1 s
DMV-D… V1 & V2 < 1 s
DMV-DLE… V1 < 1 s; V2 Adjustable to approx. 10 to 20 s at 70 °F
Initial lift adjustment Adjustable on V2 DLE only; 0 to 70 % of total flow; 0 to 25% of stroke
Not available on 24 VDC Versions.
Max. flow adjustment Adjustable on V2 <10 to 100 % of total flow; <10 to 100% of stroke
Not available on 24 VDC Versions.
Materials in contact with gas Housing: Aluminium, Steel; free of non-ferrous metals
Sealings on valve seats: NBR-based rubber. Versions with FKM/Viton available
for corrosive gases.
Ambient temperature rating +5 °F to +140 °F (-15 °C to +60 °C) NBR Versions
+32 °F to +140 °F (0 °C to +60 °C) Viton Versions
Installation position Safety shut off valve from vertically upright to horizontal
Gas strainer (standard) Installed in the housing upstream V1 (23 mesh)
Proof of Closure option CPI 400 valve switch with indication lamps and SPDT interlock switch
Test ports / G 1/8 ISO 228 ports available on both sides. Each side has two ports upstream
Pressure switch mounting ports V1, one between V1 and V2, one downstream V2.
G 1/4 ISO 228 on both flanges, upstream of V1, downstream of V2
G 3/4" Port upstream V1 each side of the valve
Position indication option Visual Indicator (VI) to show valve position
Valve proving system VPS 504; mounts directly to either side of DMV
Vent line adapter 1" NPT Field mountable
Power Consumption with all coils energized (24 VDC/120 VAC & 230 VAC)
Inrush (VA) Operation (VA)
DMV-D(LE) 5065/11 eco 6xx 130 VA 32 VA
DMV-D(LE) 5080/11 eco 6xx 190 VA 40 VA
DMV-D(LE) 5100/11 eco 6xx 250 VA 50 VA
DMV-D(LE) 5125/11 eco 6xx 250 VA 50 VA 2…8
Dimensions inch (mm)
4…8
Valve Type Pipe Size Coil No. Valve Voltage NEMA Proof of Order No.
Seat Type Closure
Material
DMV 5065/624 eco DN 65 (2 1/2") 1411/2P-4 NBR 110 VAC 4 V2 269397
DMV-DLE 5065/624 eco DN 65 (2 1/2") 1411/2PL-4 NBR 110 VAC 4 V2 269400
DMV 5065/634 eco DN 65 (2 1/2") 1411/2P-4 NBR 110 VAC 4 V1 & V2 269398
DMV-DLE 5065/634 eco DN 65 (2 1/2") 1411/2PL-4 NBR 110 VAC 4 V1 & V2 269401
DMV 5080/624 eco DN 80 (3") 1511/2P-4 NBR 110 VAC 4 V2 269387
DMV-DLE 5080/624 eco DN 80 (3") 1511/2PL-4 NBR 110 VAC 4 V2 268488
DMV 5080/634 eco DN 80 (3") 1511/2P-4 NBR 110 VAC 4 V1 & V2 269388
DMV-DLE 5080/634 eco DN 80 (3") 1511/2PL-4 NBR 110 VAC 4 V1 & V2 269403
DMV-5100/624 eco DN 100 (4") 1611/2P-4 NBR 110 VAC 4 V2 269394
DMV-DLE 5100/624 eco DN 100 (4") 1611/2PL-4 NBR 110 VAC 4 V2 269408
DMV 5100/634 eco DN 100 (4") 1611/2P-4 NBR 110 VAC 4 V1 & V2 269395
DMV-DLE 5100/634 eco DN 100 (4") 1611/2PL-4 NBR 110 VAC 4 V1 & V2 269409
DMV 5125/624 eco DN 125 (5") 1711/2P-4 NBR 110 VAC 4 V2 269390
DMV-DLE 5125/624 eco DN 125 (5") 1711/2PL-4 NBR 110 VAC 4 V2 269414
DMV 5125/634 eco DN 125 (5") 1711/2P-4 NBR 110 VAC 4 V1 &V2 269391
DMV-DLE 5125/634 eco DN 125 (5") 1711/2PL-4 NBR 110 VAC 4 V1 & V2 269415
Note: Viton versions available upon request
5…8
Valve Type Pipe Size Coil No. Valve Seat Voltage NEMA Type Proof of Order No.
Material Closure
DMV 5080/602 eco DN 80 (3") 1511/2P Viton 24 VDC 12 no 267171
DMV-5080/622 eco DN 80 (3") 1511/2P Viton 24 VDC 12 V2 269352
DMV-5080/632 eco DN 80 (3") 1511/2P Viton 24 VDC 12 V1 & V2 269353
DMV-5100/602 eco DN 100 (4") 1611/2P Viton 24 VDC 12 no 267172
DMV-5100/622 eco DN 100 (4") 1611/2P Viton 24 VDC 12 V2 269354
DMV-5100/632 eco DN 100 (4") 1611/2P Viton 24 VDC 12 V1 & V2 269355
DMV-5125/602 eco DN 125 (5") 1711/2P Viton 24 VDC 12 no 267173
DMV-5125/622 eco DN 125 (5") 1711/2P Viton 24 VDC 12 V2 269356
DMV-5125/632 eco DN 125 (5") 1711/2P Viton 24 VDC 12 V1 & V2 269357
6…8
Dual Modular Valve (DMV) system
Port 1
Port 2
Port 3
Port 4
Port 5
Port 9
V1 V2
Port 6 Port 7
DMV
Port 9 Port 5
Port 1
Port 2
Port 4
Port 3
Valve Valve
switch switch
Min. gas pressure switch Max. gas pressure switch
Pressure drop for other gases the “corrected” flow rate in CFH through f (f = 0.66 for propane). Use this “cor-
To determine the pressure drop when the valve for the other gas used. For ex- rected” flow rate and the flow curve on
using a gas other than natural gas, ample, when using propane, divide the the next page to determine pressure
use the flow formula below and f value volume (CFH) of propane required for drop for propane.
located in the table below to determine the application by the calculated value
7…8
Dual Modular Safety
Shutoff Valves with
Proof of Closure Option
Flow curve
Pressure drop (in. W.C.)
Based on 60 °F
14.65 psia, dry
40,000 60,000