Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
179 views57 pages

Instruction Manual: Magnetic Flowmeters 10DS3111 Design Level E Sizes 1 Through 12 Inches

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 57

INSTRUCTION MANUAL

MAGNETIC FLOWMETERS
10DS3111 Design Level E
Sizes 1 through 12 inches

SERIES 3000 AC MAGNETIC FLOWMETER

PN25011
The following is a registered trademark of E. I. du Pont de Nemours and Company:

TEFLON ®
TEFZEL®

The following is a trademark of Haynes International Incorporated:


HASTELLOY

The following is a trademark of Linatex Corporation of America:


LINATEX

The following are trademarks of ABB Inc. :


MAG-X®

WARNING notices as used in this manual apply to hazards or unsafe practices which could result in personal
injury or death.

CAUTION notices apply to hazards or unsafe practices which could result in property damage.

NOTES highlight procedures and contain information which assist the operator in understanding the information
contained in this manual.

All software, including design, appearance, algorithms and source codes, is copyrighted by ABB Inc. and is
owned by ABB Inc. or its suppliers.

WARNING
POSSIBLE PROCESS UPSETS
Maintenance must be performed only by qualified personnel and only after securing equipment controlled
by this product. Adjusting or removing this product while it is in the system may upset the process being
controlled. Some process upsets may cause injury or damage.

NOTICE
The information contained in this document is subject to change without notice.

ABB Inc., its affiliates, employees, and agents, and the authors of and contributors to this publication
specifically disclaim all liabilities and warranties, express and implied (including warranties of
merchantability and fitness for a particular purpose), for the accuracy, currency, completeness, and/or
reliability of the information contained herein and/or for the fitness for any particular use and/or for the
performance of any material and/or equipment selected in whole or part with the user of/or in reliance upon
information contained herein. Selection of materials and/or equipment is at the sole risk of the user of this
publication.

This document contains proprietary information of ABB Inc., and is issued in strict confidence. Its use, or
reproduction for use, for the reverse engineering, development or manufacture of hardware or software
described herein is prohibited. No part of this document may be photocopied or reproduced without the
prior written consent of ABB Inc..

Copyright 2003 ABB Inc. [May 2003]


10DS3111E INSTRUCTION MANUAL

Table of Contents
READ FIRST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I

1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1


1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1.2 Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 Model Number Breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4

2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1


2.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2 Meter Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.3 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2.4.1 Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2.4.2 Pipe Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2.5 Grounding Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
2.5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
2.5.2 Conductive Pipeline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
2.5.3 Non-Conductive or Electrically Insulated Pipeline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
2.6 Electrical Interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
2.7 Conduit Seal and Pressure Relief. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18

3.0 START-UP and OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1


3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2 Dual Frequency Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

4.0 FUNCTIONAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1


4.1 Basic Operating Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1.1 Signal Voltage Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1.2 Volumetric Flow Rate Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.2 Operating Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2.1 Liquid Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2.1.1 Liquid Conductivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2.1.2 Liquid Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.2.1.3 Other Liquid Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.2.2 Metering Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5

5.0 CIRCUIT DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1


5.1 Meter Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2 Constant Meter Capacity (CMC) PC Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1

6.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1


6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.2 System Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.3 Static Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.3.1 Magnet Coil Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.3.1.1 Signal Converter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.3.2 Electrode Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5

7.0 PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1

i
10DS3111E INSTRUCTION MANUAL

Figure List
FIGURE 1-1. EXPLOSION-PROOF/ CONTINUOUS SUBMERGENCE METER . . . . . . . . . . . . . . . . . . 1-2

FIGURE 2-1. PROTECTOR PLATES FOR TEFLON LINERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3


FIGURE 2-2. PROPER HOISTING METHOD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
FIGURE 2-3. OUTLINE DIMENSIONS, 1 - 4 INCH FLOWMETER WITH ANSI FLANGES . . . . . . . . . . 2-6
FIGURE 2-4. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH ANSI FLANGES . . . . . . . . . 2-7
FIGURE 2-5. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH ANSI FLANGES, HI-TEMP 2-8
FIGURE 2-6. OUTLINE DIMENSIONS, 1 - 4 INCH FLOWMETER WITH DIN FLANGES . . . . . . . . . . . 2-9
FIGURE 2-7. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH DIN FLANGES . . . . . . . . . 2-10
FIGURE 2-8. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH DIN FLANGES, HI-TEMP . 2-11
FIGURE 2-9. OUTLINE DIMENSIONS, 1 - 4 INCH FLOWMETER WITH ANSI FLANGES,
CONTINUOUS SUBMERGENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
FIGURE 2-10. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH ANSI FLANGES,
CONTINUOUS SUBMERGENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
FIGURE 2-11. OUTLINE DIMENSIONS, 1 - 4 INCH FLOWMETER WITH DIN FLANGES,
CONTINUOUS SUBMERGENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
FIGURE 2-12. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH DIN FLANGES,
CONTINUOUS SUBMERGENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
FIGURE 2-13. BOLT TIGHTENING SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
FIGURE 2-14. GASKET LOCATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
FIGURE 2-15. RECOMMENDED PIPING ARRANGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
FIGURE 2-16. GROUNDING PROCEDURE, CONDUCTIVE PIPELINE . . . . . . . . . . . . . . . . . . . . . . . 2-21
FIGURE 2-17. GROUNDING PROCEDURE, NON-CONDUCTIVE PIPELINE . . . . . . . . . . . . . . . . . . 2-22
FIGURE 2-18. 10DS3111E PRIMARY CONNECTIONS FOR REMOTE SIGNAL CONVERTER . . . . 2-23
FIGURE 2-19. CONDUIT ENTRY SEAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-24

FIGURE 3-1. TYPICAL INSTRUMENT TAG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1


FIGURE 3-2. FLOWMETER INTERCONNECTIONS FOR REMOTE SIGNAL CONVERTER. . . . . . . . 3-2
FIGURE 3-3. CONTINUOUS SUBMERGENCE PRIMARY CONNECTIONS
FOR REMOTE SIGNAL CONVERTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3

FIGURE 4-1. BASIC OPERATING PRINCIPLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1

ii
10DS3111E INSTRUCTION MANUAL

Table List
TABLE 1-1. LIQUID TEMPERATURE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
TABLE 1-2. PRESSURE RATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
TABLE 1-3. VACUUM LIMIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
TABLE 1-4. METER CAPACITY VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8

TABLE 2-1. METER WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2


TABLE 2-2. CONTINUOUS SUBMERGENCE WEIGHT FACTORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
TABLE 2-3. TORQUE RECOMMENDATIONS (ANSI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
TABLE 2-4. TORQUE RECOMMENDATIONS (DIN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17

TABLE 4-1. ELECTRODE DIAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4

TABLE 6-1. METER COIL RESISTANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3

TABLE 7-1. FLANGE GASKETS FOR METER BODY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1


TABLE 7-2. PROTECTOR PLATES FOR TEFLON LINED METERS . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
TABLE 7-3. LINER PROTECTOR/GROUNDING RINGS FOR TEFLON LINED METERS . . . . . . . . . . . 7-2
TABLE 7-4. GROUNDING RINGS - SIZES 1 THROUGH 4 INCHES . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
TABLE 7-5. GROUNDING RINGS - SIZES 6 THROUGH 12 INCHES . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
TABLE 7-6. METER BASE AND JUNCTION BOX GASKETS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
TABLE 7-7. HARDWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3

iii
10DS3111E INSTRUCTION MANUAL

READ FIRST

WARNING

INSTRUCTION MANUALS
Do not install, maintain, or operate this equipment without reading,
understanding and following the proper factory-supplied instructions
and manuals, otherwise injury or damage may result.

RETURN OF EQUIPMENT
All Flowmeters and/or Signal Converters being returned to the factory
for repair must be free of any hazardous materials (acids, alkalis,
solvents, etc). A Material Safety Data Sheet (MSDS) for all process
liquids must accompany returned equipment. Contact the factory for
authorization prior to returning equipment.

Read these instructions before starting installation;


save these instructions for future reference.

Contacting the Factory . . .


Should assistance be required with any of the company’s products, contact the following:

Telephone:

24-Hour Call Center


1-800-HELP-365

E-Mail:

ins.techsupport@us.abb.com

I
10DS3111E INSTRUCTION MANUAL

The NEMA 4X rating applies to the meter body and electronics enclosure only. The following
accessories (if supplied) may not meet NEMA 4X unless specifically ordered as NEMA 4X:
• meter flanges
• meter installation hardware: studs, nuts, bolts
• enclosure mounting hardware for pipe or wall mounting
• conduit hardware
This product is painted with a high performance epoxy paint. The corrosion protection provided by
this finish is only effective if the finish is unbroken. It is the users’ responsibility to "touch-up" any
damage that has occurred to the finish during shipping or installation of the product. Special attention
must be given to: meter flange bolting, pipe mounting of electronics, conduit entries and covers that
are removed to facilitate installation or repair. For continued corrosion protection throughout the
product life, it is the users’ responsibility to maintain the product finish. Incidental scratches and other
finish damage must be repaired and promptly re-painted with approved touch-up paint. Provide the
model number and size of your product to the nearest factory representative to obtain the correct
touch-up paint.

II
10DS3111E INSTRUCTION MANUAL

1.0 INTRODUCTION

1.1 General
1.1.1 Description
The Series 3000 Magnetic Flowmeter is a compact, volumetric, liquid flow rate detector that uses as
the process transducing method the characteristic of a conductive liquid to generate an induced
voltage when flowing through a magnetic field. The amplitude of the voltage produced is directly
proportional to the flow rate of the metered liquid.

Being a completely obstructionless metering instrument, the meter may be used with many non-ho-
mogeneous liquids and is as independent of the tendency to plug or foul as the pipeline in which it is
mounted. An inherent advantage of obstructionless construction is that pressure losses are reduced
to levels occurring in equivalent lengths of equal diameter pipeline. This reduces or conserves
pressure source requirements in new or existing hydraulic lines as compared to other metering
methods. The compact size of the meter results in a light-weight unit which requires no additional
support other than that used normally on pipe runs. Short laying lengths minimize the need for
altering existing pipe runs to accommodate metering. A basic construction of corrosion resistant
wetted parts and a variety of meter lining materials permit metering of most corrosive and reactant
liquids.

Factors such as liquid viscosity and density require no compensation and have no effect on the
measurement accuracy of the meter. Metering limitations are confined to a minimum threshold of
electrical conductivity inherent to the liquid being metered. The degree of liquid conductivity has no
effect upon metering accuracy as long as it is greater than this minimum level. Liquid temperature is
limited only to the extent that it may affect liquid conductivity, and liquid pressure to the extent that it
can not exceed the meter material specification limits.

For information applicable to the signal converter, refer to the signal converter instruction bulletin.

1.1.2 Construction
The meter consists of a flanged, stainless steel pipe spool which serves as a meter body. A pair of
flat magnet coils are installed on opposite sides of the meter housing inner surface. Permeable iron
straps and pole pieces focus the magnetic field generated by the coils and provide a flux return path.

An interior liner of Hard Rubber, Soft Rubber, TEFLON ® (PTFE), TEFZEL ® (ETFE), neoprene,
polyurethane, or LINATEX is assembled into the spool and formed against the flange faces. Two
cylindrical electrodes are mounted diametrically opposed within the central portion of the meter body
and are completely insulated from the metal pipe. The end surfaces of the electrodes are virtually
flush with the inner surface of the insulating liner and come into contact with the liquid to be metered.

1-1
10DS3111E INSTRUCTION MANUAL

The Primary housing for the continuous


submergence and explosion-proof design
is different from the other configurations in
that it is sealed with a round screw-on ac-
cess cover. The interior of this housing is
filled with a gelatin-like silicone rubber
compound which helps give the meter its
waterproof rating. The construction of this
meter is shown in Figure 1-1.

The NEMA 4X rating applies to the meter


body and electronics enclosure only. The
following accessories (if supplied) may not
meet NEMA 4X unless specifically ordered
as NEMA 4X:
• meter flanges
• meter installation hardware:
studs, nuts, bolts
• enclosure mounting hardware
for pipe or wall mounting
• conduit hardware

FIGURE 1-1. EXPLOSION-PROOF/ CON-


TINUOUS SUBMERGENCE METER

NEMA 4X, Corrosion Resistant Finish

This product is painted with a high performance epoxy paint. The corrosion protec-
tion provided by this finish is only effective if the finish is unbroken. It is the users’
responsibility to "touch-up" any damage that has occurred to the finish during ship-
ping or installation of the product. Special attention must be given to: meter flange
bolting, pipe mounting of electronics, conduit entries and covers that are removed
to facilitate installation or repair. For continued corrosion protection throughout the
product life, it is the users’ responsibility to maintain the product finish. Incidental
scratches and other finish damage must be repaired and promptly re-painted with
approved touch-up paint. Provide the model number and size of your product to the
nearest factory representative to obtain the correct touch-up paint.

1-2
10DS3111E INSTRUCTION MANUAL

1.2 Model Number Breakdown


Refer to the data sheet or data tag on the equipment for the model number of the instrument
furnished. The details of a specific model number are shown on the following pages.

1-3
10DS3111E INSTRUCTION MANUAL

Model Number Breakdown

10DS3111 E _ _ _ _ _ _ _ _ _ _ _ _ _ _

Engineering Reference

Design Level E

Meter Lay Length


Short Form (WMAG) D
Replacement for 10D1419 & 10D1465 E
Replacement for 10D1435 F
Other Z

Liner Material
Hard Rubber A
Soft Natural Rubber B
Polyurethane D
PTFE TEFLON E
Neoprene L
Rotomolded TEFZEL N
Linatex P

Size
inches mm
1 25 09
1-1/2 40 11
2 50 12
3 80 14
4 100 15
6 150 17
8 200 18
10 250 19
12 300 20

Flange Standard/Pressure Rating


DIN PN 10 w/Cable Seal Connections C
DIN PN 16 w/Cable Seal Connections D
DIN PN 25 w/Cable Seal Connections E
DIN PN 40 w/Cable Seal Connections F
ANSI Class 150 w/ 1/2in. NPT Conduit Conn. P
ANSI Class 300 w/ 1/2in. NPT Conduit Conn. Q

Flange Material
Carbon Steel 1
304 Stainless Steel 2

Protector Plate (TEFLON Liner only)


None Required A
316 Stn. Steel B
HASTELLOY C E

Electrode Type
Flush 2
Bullet Nose 3

1-4
10DS3111E INSTRUCTION MANUAL

Model Number Breakdown (continued)

10DS3111 E _ _ _ _ _ _ _ _ _ _ _ _ _ _

Electrode Material
316 Stn. Steel B
HASTELLOY® B C
HASTELLOY® C D
Titanium E
Tantalum F
Platinum / Iridium H
Zirconium L

Certification
Standard (None) A

FM Approved-Nonincendive for CL I, Div 2, Gp A,B,C & D; Electrodes Intrinsically Safe K


forCL I, Div 1, Gp A,B,C & D; Outdoor Hazardous Locations, NEMA 4X. Dust-Ignitionproof
CL II, Div 1, Gp E,F & G: Suitable for CL III, Div 1.

FM Approved - Explosionproof for CL I, Div 1, GP B,C & D; Dust-Ignitionproof CL II, L


Div 1, GP E,F & G; Suitable for CL III, Div 1, Electrodes Intrinsically Safe for CL I, Div 1,
GP A, B, C & D - Outdoor Hazardous Location, NEMA 4X.

Enclosure Classification
General Purpose: IEC 529, IP 65, NEMA 4X 1

Accidental Submergence: IEC 529, IP 67, NEMA 4X, 33ft H2O/48h (10m H20/48h) 2

Continuous Submergence: IEC 529, IP 68, NEMA 4X, 33ft H2 O (10m H20) Continuous Duty, 5
Signal Cable permanently installed

Accidental Submergence: IEC 529, IP 67, NEMA 4X, 33ft H2O/48h (10m H20/48h), Tropical - 9
Improved Moisture Protection, Signal Cable permanently installed

Fluid Temperature Range


Teflon, Rotomolded Tefzel, < 266o F (130o C) 1
Teflon, Extended Temperature, < 356o F (180o C) 2
Hard Rubber / Soft Rubber / Linatex, < 176o F (80o C) 3
Neoprene / Polyurethane < 190o F (88o C) 4

Line Excitation Frequency


50 Hz 1
60 Hz 3

Customer Information Language


English w/ Riveted SST Tag 2
English w/ Self-adhesive Tag 8

Converter Type
50SM1000 1
Other 9
None X

1-5
10DS3111E INSTRUCTION MANUAL

1.3 Specifications
Power Requirements Refer to Section 1.2 Model Number Breakdown.

Power Consumption Refer to the signal converter instruction bulletin.

Meter Characteristics

Meter Size/Flow Ca- Refer to Table 1-4.


pacity

Span Factory set at specified range between extremes listed in


Table 1-4; can be field adjusted.

Rangeability 20:1

Minimum Liquid 20 µS/cm


Conductivity

System Accuracy Refer to the signal converter instruction bulletin.

Meter Capacity Specified on meter data tag (equal to maximum flow capacity in
engineering units). Refer to Table 1-4.

Environmental Limits

Ambient Temperature –13 o to 140 o F (–25 o to 60o C)

Relative Humidity 10 to 90% Non-condensing

Process Limits

TABLE 1-1. LIQUID TEMPERATURE

Maximum Minimum
Liner Material
Temperature Temperature
TEFLON 356 o F (180 o C)
TEFZEL 266 o F (130 o C) -13 o F (-25o C)
Neoprene/Polyurethane 190 o F (88o C)
Hard Rubber, Soft Rubber, LINATEX 175 o F (80o C)

1-6
10DS3111E INSTRUCTION MANUAL

TABLE 1-2. PRESSURE RATING, PSIG (MPa)

Maximum Temperature
Flange Flange 100o F 175o F 190o F 266o F 356o F
Class Material (38o C) (80o C) (88o C) (130o C) (180o C)
Pressure PSIG (MPa)
ANSI Carbon Steel 285 (1.96) 260 (1.79) 255 (1.76) 235 (1.62) 215 (1.48)
150 304 SST 275 (1.90) 245 (1.69) 240 (1.76) 215 (1.48) 190 (1.31)
ANSI Carbon Steel 740 (5.10) 690 (4.76) 680 (4.69) 660 (4.55) 640 (4.41)
300 304 SST 720 (4.96) 630 (4.34) 615 (4.24) 555 (3.83) 495 (3.41)
DIN Carbon Steel 145 (1.00) 145 (1.00) 145 (1.00) 145 (1.00) 145 (1.00)
PN10 304 SST 140 (0.97) 137 (0.94) 137 (0.94) 133 (0.92) 128 (0.88)
DIN Carbon Steel 232 (1.60) 232 (1.60) 232 (1.60) 232 (1.60) 232 (1.60)
PN16 304 SST 224 (1.54) 219 (1.51) 218 (1.50) 212 (1.46) 205 (1.41)
DIN Carbon Steel 362 (2.50) 362 (2.50) 362 (2.50) 362 (2.50) 362 (2.50)
PN25 304 SST 352 (2.43) 331 (2.28) 327 (2.25) 304 (2.10) 280 (1.93)
DIN Carbon Steel 580 (4.00) 580 (4.00) 580 (4.00) 580 (4.00) 580 (4.00)
PN40 304 SST 564 (3.89) 530 (3.65) 525 (3.62) 488 (3.36) 449 (3.10)

TABLE 1-3. VACUUM LIMIT

Temperature
Liner
Meter Size
Material 68o F 212 o F 266 o F 356 o F
(20 o C) (100 o C) (130 o C) (180 o C)
1- 4 in TEFLON/
Full Vacuum To 266o F (130o C) 6.7 psia
(15-100 mm) TEFZEL
6 - 12 in TEFLON/
3.9 psia 5.8 psia 6.7 psia 8.7 psia
(150-300 mm) TEFZEL
Neoprene/
All Full Vacuum To 190 o F (88o C)
Polyurethane
Hard Rubber/
All Full Vacuum To 175 o F (80o C)
Soft Rubber
1- 4 in
LINATEX Full Vacuum To 175 o F (80o C)
(15-100 mm)
6 - 12 in
LINATEX 3.9 psia 5.8 psia To 175 o F (80o C)
(150-300 mm)

1-7
TABLE 1-4. METER CAPACITY VALUES

Flow Ranges Capacity Setting


Meter Meter 0 to Value Tabulated ( If not specified by
Size Capacity* Minimum Maximum customer)
inch mm gpm gpm L/min gpm L/min gpm L/min
1 25 52.83 2.65 10.0 52.8 200.0 16.00 60.0
1 ⁄2
1 40 158.5 7.93 30.0 158.0 600.0 50.0 200
m 3/h m 3/h m 3/h
2 50 264.1 13.3 3.0 264.0 60.0 80.0 20.0
3 80 792.5 39.7 9.0 792.0 180.0 250 60.0
4 100 1056 52.9 12.0 1056.0 240.0 320 80.0
6 150 2641 133 30.0 2641.0 600.0 800 200
8 200 4755 238 54.0 4755.0 1080.0 1500 300
10 250 7925 397 90.0 7925.0 1800.0 2500 550
12 300 10567 528 120.0 10567 2400 3500 800

* Each meter is calibrated to determine its flow capacity at a given velocity, which has been
established as 32.808 ft/s (10 m/s) for the meter capacity (Range DN). The meter capacity expressed
in gpm is recorded on the meter nameplate.

The meter capacity is the base upon which maximum and minimum limits for range settings and
outputs are established.

Flow velocity can be determined as follows:

Meter Capacity:

Flow Velocity (ft/s) = (Operating gpm x 32.808)/Meter Capacity

NOTE
The maximum meter flow range is a function of the signal converter used. The maxi-
mum flow range can not exceed the meter capacity.
10DS3111E INSTRUCTION MANUAL

Physical Characteristics

Outline Dimensions See Figures 2-3 through 2-6

Vibration Limits 1.5 g for 10 - 150 Hz

Signal Cable Non-Permanently Installed Cable:


(supplied with the 100 ft. (33 m) Max.
signal converter)

Permanently Installed Cable:


Standard Length - 50 feet (16 m)

Optional Length - Up to 100 feet (33 m) in 10 foot


increments, as specified

Materials of
Construction

Meter Liner see Section 1.2 Model Number Breakdown

Electrodes see Section 1.2 Model Number Breakdown

Meter Body 304 SST, epoxy finish

Flanges carbon steel or 304 SST, as specified

Meter Housing cast aluminum, epoxy finish

Electronics Housing cast aluminum, epoxy finish, 316 SST attachment screws,
gasketed cover

Meter Enclosure Ratings

NOTE
Enclosures are suitable for indoor or outdoor installation.
Enclosure ratings apply to the meter.

Watertight Housing NEMA 4X, IEC 529 IP65


(standard)

Accidental NEMA 4X, IEC 529 IP67, 30 feet H 2O/48 h (9 m H 2O/48 h)


Submergence

Continuous NEMA 4X, IEC 529 IP68, 30 feet H 2O (9 m H2 O)


Submergence

Conduit Connections two 1/2 inch NPT internally threaded entrances

Certifications refer to Section 1.2 Model Number Breakdown

1-9
10DS3111E INSTRUCTION MANUAL

2.0 INSTALLATION

2.1 Inspection
All meters are shipped in heavy duty containers which are specially designed to provide adequate
protection during transit. Since the meter will be operated in conjunction with an electronic signal
converter, both instruments may be in the same shipping container. An itemized list of all items
included in the shipment is attached to the shipping container. Refer to the instruction bulletin
supplied with the signal converter for operation and maintenance procedures for the converter.

The system is normally supplied with a signal converter. Interconnection cable and conduit seals are
supplied with the signal converter.

Inspect all items included in the shipment for indications of damage which may have occurred during
shipment. All damage claims should be reported to the shipping agent involved before attempting to
install or operate this equipment. If the damage is such that faulty operation is likely to result, the
damage should be brought to the attention of the factory Service Department.

2-1
10DS3111E INSTRUCTION MANUAL

2.2 Meter Handling


When a TEFLON lined meter is specified, two optional liner protector plates (one on each flange
face) are factory installed (when specified at time of order). These plates serve to contain the flared
ends of the liner, and to prevent damage to the liner during installation and handling. These protector
plates are attached to the meter with flat head screws that securely hold the liner in place. If the
pressure on the liner is relieved, the TEFLON will tend to curl away from the flange. These protector
plates must remain in place when the meter is installed. Refer to Figure 2-1.

During shipment, the liner is protected by wood or composition protectors as shown in Figure 2-2;
these are removed before the meter is installed; leave them in position while moving the meter to the
installation site.

To place the meter in the pipeline a sling and hoist may be necessary. Do not pass a rope or wire
sling through the meter; the liner will be damaged if the meter is supported by the liner. Lift the meter
as shown in Figure 2-2.

Table 2-1 lists the weights of the meters by size and flange classification. Weights shown are
approximate and should be used only as a guide when installing the meter.

TABLE 2-1. METER WEIGHTS

Meter ANSI Class 150 ANSI Class 300


Size DIN PN10-16 DIN PN25-40
Inches mm lbs kg lbs kg
1 25 8 3.5 19 8.4
1 ⁄2
1 40 12 5.3 23 10.1
2 50 16 7.1 27 11.9
3 80 26 11.5 36 15.9
4 100 37 16.3 51 22.5
6 150 70 32 140 64
8 200 155 70 210 95
10 250 220 100 295 134
12 300 275 125 365 166

If the continuous submergence option is chosen for Model 10DS3111, the meter weights shown
above must be modified by adding the weights shown in the following table:

TABLE 2-2. CONTINUOUS SUBMERGENCE WEIGHT FACTORS

Meter Size Add to Meter Weight from Table Above


Inches mm lbs kg
1 25 1.01 .46
1 1⁄2 40 0.96 .44
2 50 1.04 .47
3 80 1.08 .49
4 100 1.92 .87
6 150 11.23 5.1
8 200 15.57 7.1
10 250 23.27 10.6
12 300 50.47 22.9

2-2
10DS3111E INSTRUCTION MANUAL

LINER PROTECTOR PLATES, SIZES 1 THROUGH 4 INCHES

LINER PROTECTOR/GROUNDING RINGS, SIZES 6 THROUGH 12 INCHES

FIGURE 2-1. PROTECTOR PLATES FOR TEFLON LINERS

2-3
10DS3111E INSTRUCTION MANUAL

FIGURE 2-2. PROPER HOISTING METHOD


Figure is for reference only, the flowmeter shown in this illustration is not the meter
described in this instruction bulletin.

2-4
10DS3111E INSTRUCTION MANUAL

2.3 Location
The Flowmeter is suitable for either indoor or outdoor installation. When selecting the location of the
installation, consideration should be given to the ambient and process temperature limits, as stated
in the Specifications Sub-Section 1.3.

Several variations of resistance to water-entry are available:

• The Standard meter is rated NEMA 4X (IEC 529 IP65), watertight, and will
withstand periods of rain and hose down.
• If periodic flooding may occur, an optional NEMA 4X (IEC 529 IP67) accidental
submergence Flowmeter is available to withstand submergence up to 48 hours.
These ratings apply to TEFLON-lined meters only after the meter is properly
installed in the pipeline.
• If periodic flooding is expected to keep the meter submerged for periods longer
than 48 hours, an optional continuous submergence NEMA 4X (IEC 529 IP68)
configuration is available.

It is recommended that the meter not be installed in the immediate vicinity of heavy induction
equipment.

Access for wiring interconnections and servicing of the integrally mounted Signal Converter should
be considered when installing the meter. A minimum of five inches of overhead clearance is required
for cover removal.

Outline dimensions of the Flowmeter are given in Figures 2-3 through 2-8.

Outline dimensions of the optional remotely mounted Signal Converter are given in the instruction
manual supplied with the Signal Converter.

The installation site must be provided with a convenient source of power as specified for the Signal
Converter. The power line should have a disconnect switch and a suitable fuse or circuit breaker as
shown on the applicable interconnection diagram provided in the instruction manual supplied with the
Signal Converter.

2-5
10DS3111E INSTRUCTION MANUAL

Ref. 10D4287

FIGURE 2-3. OUTLINE DIMENSIONS, 1 - 4 INCH FLOWMETER WITH


ANSI FLANGES

2-6
10DS3111E INSTRUCTION MANUAL

Ref. OD-10D-4123 r4

FIGURE 2-4. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH


ANSI FLANGES

2-7
10DS3111E INSTRUCTION MANUAL

FIGURE 2-5. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH


ANSI FLANGES, HI-TEMP

2-8
10DS3111E INSTRUCTION MANUAL

Ref. 10D4288

FIGURE 2-6. OUTLINE DIMENSIONS, 1 - 4 INCH FLOWMETER WITH DIN


FLANGES

2-9
10DS3111E INSTRUCTION MANUAL

FIGURE 2-7. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH


DIN FLANGES

2-10
10DS3111E INSTRUCTION MANUAL

FIGURE 2-8. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH


DIN FLANGES, HI-TEMP

2-11
10DS3111E INSTRUCTION MANUAL

FIGURE 2-9. OUTLINE DIMENSIONS, 1 - 4 INCH FLOWMETER WITH


ANSI FLANGES, CONTINUOUS SUBMERGENCE

2-12
10DS3111E INSTRUCTION MANUAL

FIGURE 2-10. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH


ANSI FLANGES, CONTINUOUS SUBMERGENCE

2-13
10DS3111E INSTRUCTION MANUAL

FIGURE 2-11. OUTLINE DIMENSIONS, 1 - 4 INCH FLOWMETER WITH


DIN FLANGES, CONTINUOUS SUBMERGENCE

2-14
10DS3111E INSTRUCTION MANUAL

FIGURE 2-12. OUTLINE DIMENSIONS, 6 - 12 INCH FLOWMETER WITH


DIN FLANGES, CONTINUOUS SUBMERGENCE

2-15
10DS3111E INSTRUCTION MANUAL

2.4 Mounting
2.4.1 Orientation
The meter may be installed in horizontal, vertical or sloping pipe runs. However, precautions must be
taken to assure that the metering tube is filled at all times during measurement. A vertical installation,
with the pipe line carrying liquid upwards assures a filled line under low flow rate conditions and also
minimizes wear on the meter lining by abrasive grit. Horizontal installations should be made with the
meter in the lower section of a pipeline to assure a filled meter condition.

For horizontal or sloping installations the meter should be placed so that the electronic housing of the
meter is on top. This will align the meter electrodes in a lateral plane. Positioning the meter in this
way eliminates the possibility of entrained air acting as an electrode insulator.

The meter must be oriented in accordance with the direction of process flow, as indicated by the
FLOW arrow on the meter body. For accurate metering, a straight pipe run equivalent to a minimum
of three straight pipe diameters are required upstream of the meter for elbows and tees, measured
from the center of the meter (refer to Figure 2-15).

If a control valve is required, it is recommended that it be placed downstream of the meter. Upstream
valves can create turbulence that result in air pockets and may affect the meter’s accuracy or cause
its output to be noisy. A minimum of ten pipe diameters of straight pipe are required upstream
between the meter and a control valve or pump.

2.4.2 Pipe Connections


The TEFLON and polyurethane lined meters
have raised faced flanges rated as specified. The
neoprene and hard-rubber lined meters have full
faced flanges rated as specified. Two flange gas-
kets are supplied per meter; the mounting studs
and nuts are furnished by the user.

For 4-bolt and 8-bolt flanges, tighten the flange


bolts in a "star" pattern as shown in FIGURE 2-13
to avoid localized stresses on the gaskets. Use a
similar method for 8-bolt flanges.

Refer to Figure 2-14 for proper gasket locations


and Figure 2-15 for recommended piping ar-
rangement.

The meter should be oriented such that the pres-


sure relief valve points in a safe direction should
a situation occur where the device could be acti-
vated. For further discussion of the pressure re-
lief mechanism and orientation, refer to Section
2.7 of this instruction manual.

FIGURE 2-13. BOLT TIGHTENING


SEQUENCE

2-16
10DS3111E INSTRUCTION MANUAL

2.4.3 Torque Specifications


It is recommended that the bolts and nuts be lubricated and tightened using a torque wrench. The
bolts and nuts should be tightened to approximately 50% of the torque value during the first pass, to
approximately 80% during the second pass and to the full torque during the third pass. The maximum
torque rate values shown in TABLES 2-3 and 2-4 must not be exceeded.

For liner materials other than those shown in the tables, the flange bolts should be tightened
sufficiently to stop any leaks but should not exceed the values shown in the tables.

TABLE 2-3. TORQUE RECOMMENDATIONS (ANSI)

ANSI Class 150 ANSI Class 300


Max. Max.
Bolt No. Bolt No. &
Liner Size Torque Torque
& Size Size
Material in. mm Rate Rate
(in.) (in.)
(ft-lb) (ft-lb)
1 25 " 10 " 15
1-1/2 40 " 15 4 x 3/4 25
2 50 4 x 5/8 25 8 x 5/8 15
PTFE / 3 80 " 40 " 25
TEFZEL / 4 100 8 x 5/8 35 " 40
Rubber 6 150 8 x 3/4 60 12 x 3/4 65
8 200 " 75 12 x 7/8 120
10 250 12 x 7/8 70 16 x 1 150
12 300 " 95 16 x 1-1/8 230

TABLE 2-4. TORQUE RECOMMENDATIONS (DIN)

Liner Size Bolt No. & Max.Torque Rate PN


Material in. mm Size ft-lb Nm bar
1 25 4 x M12 15.1 20.5 40
1-1/2 40 4 x M16 31.3 42.5 40
2 50 4 x M16 41.0 55.5 40
3 80 8 x M16 35.8 48.5 40
PTFE/
4 100 8 x M16 34.3 46.5 16
Rubber
6 150 8 x M20 60.8 82.5 16
8 200 12 x M20 59.7 81.0 16
10 250 12 x M24 88.5 120.0 16
12 300 12 x M24 118.0 160.0 16

NOTE:
• Torques listed are for bolts with threads lubricated
• All meters with PTFE liners need to be re-torqued after 48 hours of operation

2-17
10DS3111E INSTRUCTION MANUAL

CBI-3007

FIGURE 2-14 . GASKET LOCATIONS

2-18
10DS3111E INSTRUCTION MANUAL
FIGURE 2-15. RECOMMENDED PIPING ARRANGEMENT
Figure is for reference only, the flowmeter shown in this illustration is not the meter
2-19

described in this instruction bulletin.


10DS3111E INSTRUCTION MANUAL

2.5 Grounding Procedure


2.5.1 General
Satisfactory operation of metering system requires that careful attention be paid to proper grounding
techniques. A good ground is one that is in contact with the earth over a large conductive area. An
excellent example of this is a metallic cold water pipe which is underground. A great number of pipe
branches form a large conductive area of contact which provides a low resistance connection to
earth. A hot water or steam pipe must first return to a boiler before it becomes a cold water pipe, and
therefore, its greater length of ungrounded path offers a less desirable ground bus. A metallic
structural member of a building, such as a supporting "I " beam, may be a good earth ground, but it
is a second choice to a metallic cold water pipe.

Flowmeter grounding requirements are a combination of standard grounding methods and a bonding
of the meter body to the process liquid. The most important of these is the process bonding, which is
ensuring that the meter body is in contact with the process liquid at both ends of the meter body. The
bonding procedure places an electrical short circuit across the meter, thereby routing any stray
current around the liquid in the meter (rather than through it).

From the point of view of grounding there are two basic types of piping systems:
• electrically conductive pipeline: the process liquid comes in contact with conductive
pipe. This piping requires that each meter flange be connected with a bonding wire
to the adjacent pipeline flange. The grounding procedure to use with conductive
pipeline is described in 2.5.2.
• non-conductive or electrically insulated pipeline: the pipeline may be made of an
electrically non-conductive material (plastic, concrete, etc.) or lined with a
non-conductive material (rubber, TEFLON, etc). These non-conductive pipelines
require the use of metal grounding rings to bond the process liquid to ground. The
grounding procedure to use with nonconductive pipeline is described in 2.5.3.
Proper grounding of the meter is required for optimum system performance.

2-20
10DS3111E INSTRUCTION MANUAL

2.5.2 Conductive Pipeline


If the meter is included as part of a conductive pipeline that is not electrically insulated from the liquid
to be metered, the following grounding procedure should be followed. Refer to Figure 2-16 to
supplement the following text.

1) Drill and tap both pipeline flanges adjacent to the bonding connections on the meter.
The lugs on the bonding cables are sized for a 1/4 inch bolt (metric M6 fasteners).

2) Obtain a bright metal surface around the edges of the tapped hole with a file or emery
cloth.

3) Attach the bonding wire and another length of ground wire to the flanges as shown. Use
internal tooth lockwashers as shown in the detail. The wire to the good external ground
should be #12 AWG or heavier copper wire.

FIGURE 2-16. GROUNDING PROCEDURE; CONDUCTIVE PIPELINE


Figure is for reference only, the flowmeter shown in this illustration is not the meter
described in this instruction bulletin.

2-21
10DS3111E INSTRUCTION MANUAL

2.5.3 Non-Conductive or Electrically Insulated Pipeline


If the meter is included as part of a non-conductive or liquid insulated pipeline (such as totally plastic
pipe, ceramic lined iron pipe, or cast pipe with internal bitumastic coating), the following grounding
procedures apply. Refer to Figure 2-17 to supplement the following text.

1) For this service, the meter requires the use of grounding rings. The grounding rings
should be installed between the meter flanges and the mating flanges of the pipeline as
shown in Figure 2-14. A gasket is required on both sides of the grounding ring. If the meter
is supplied with a grounding ring/protector plate fastened to the meter flange,only one gas-
ket is required between the grounding ring/protector plate and the pipeline flange. Proper
gasket locations are shown in Figure 2-14.

2) Attach the bonding wire and ground wire to the tab of the grounding ring. Use internal
tooth lockwashers and hex head nut and bolts as shown in Figure 2-15. The ground wire
should be #12 AWG, or heavier, copper wire.

FIGURE 2-17. GROUNDING PROCEDURE; NON-CONDUCTIVE PIPELINE


Figure is for reference only, the flowmeter shown in this illustration is not the meter
described in this instruction bulletin.

2-22
10DS3111E INSTRUCTION MANUAL

2.6 Electrical Interconnection


The Series 3000 Magnetic Flowmeter is furnished with a remotely mounted Signal Converter.
Interconnection details are provided in the Instruction Bulletin provided with the Signal Converter.

WARNING
ELECTRICAL SHOCK HAZARD. Equipment powered by ac line voltage
constitutes a potential electric shock hazard to the user. Make certain
that the system power input leads are disconnected from the operating
branch circuit before attempting electrical interconnections.

The cable from the remote converter is connected to the Primary using the customer connection box
mounted on the meter body. FIGURE 3-2 shows the customer connection circuit board located inside
the customer connection box. The signal cable from the remote converter is connected to the meter
using the terminal blocks labeled "CUSTOMER CONNECTIONS" shown in FIGURE 3-2.

When incorporating the interconnection procedures, the grounding procedures given in Section 2.5
must be followed.

For explosion proof meter installation, all interconnection wiring must be installed according to
National Electrical Code (NEC) ANSI/NFPA 70 Section 500.

NOTE
For meters capable of continuous submergence, the signal ca-
ble has been permanently installed by the factory. Do not
loosen the cable seal fitting or remove the connection box lid
since this will break the seal and void the warranty.

2.7 Conduit Seal and Pressure Relief


In accordance with the National Electrical Code (NEC) ANSI/NFPA 70, Article 501-5(f)(3), the
flowmeter includes a conduit entry seal and pressure relief to prevent the process liquid from entering
the electrical conduit system. This safety feature considers the remote possibility of a primary seal
failure, in which case, the secondary seal will prevent the process from entering the electrical conduit
system.

It is the user’s responsibility to properly install the conduit entry cable seal fitting supplied with the
signal cable provided with the remotely mounted signal converter. This will ensure proper perform-
ance of this safety feature. Refer to Figure 2-18.

A pressure relief is provided in the electronics housing in the customer connection box on the meter.
The pressure relief is located in the center of the housing joint on the side opposite from the conduit
connection. If the primary seal should fail, the pressure relief will vent the process preventing an over
pressurization and potentially dangerous failure of the electronics housing.

It is the user’s responsibility to be aware of this safety feature and to consider the unlikely event of its
functioning. Based on knowledge of the process and meter application, the user should consider the
installation orientation of the meter and possible use of deflectors to safely direct the vented process.

2-23
FIGURE 2-19. CONDUIT ENTRY SEAL INSTALLATION
10DS3111E INSTRUCTION MANUAL

3.0 START-UP and OPERATION

3.1 General
The meter is calibrated at the factory. Each meter is calibrated to determine its meter capacity at a
given velocity. Refer to Table 1-4.

Prior to initial system start up, verify that the meter is properly installed; check flow direction, wiring
interconnection and grounding as discussed in Section 2.0 Installation. Particular attention should be
given to the meter grounding procedures; improper grounding may result in unsatisfactory perform-
ance. Refer to the signal converter instruction bulletin for interconnection wiring.

Except for system zero adjustment, there are no operating controls that require field adjustment
unless the full scale range setting was not specified at time of purchase. If the full scale range setting
must be set or changed, refer to the instruction bulletin supplied with the signal converter.

The flowmeter does not require zeroing, however, system zero adjustment must be performed prior
to start-up. The procedure for system zero adjustment is discussed in the signal converter instruction
bulletin.

Start flow through the process piping system that includes the meter. Allow a nominal flow through
the pipeline for several minutes to purge entrapped air. The pipeline must be full for accurate flow
measurement.

Apply the appropriate power for the meter by closing the external switch or circuit breaker; there are
no switches inside of the equipment. Also, energize any auxiliary equipment associated with the flow
metering system, such as remote analog recorders, controllers or rate indicators.

Initiate process flow through the pipeline. Flow measurement and concurrent output signal transmis-
sion will commence with flow through the meter.

FIGURE 3-1. TYPICAL INSTRUMENT TAG

3-1
10DS3111E INSTRUCTION MANUAL

CUSTOMER
CONNECTIONS

JUMPER TO BE IN
"16A" POSITION

GROUND
TERMINAL

FIGURE 3-2. 10DS3111E PRIMARY CONNECTIONS FOR REMOTE


MOUNTED SIGNAL CONVERTER

Note: The assembly shown is a "typical" assembly and may not


represent the configuration of your specific model. Newer models may
be different from the configuration shown.

3-2
10DS3111E INSTRUCTION MANUAL

CUSTOMER
CONNECTIONS

FIGURE 3-3. CONTINUOUS SUBMERGENCE PRIMARY CONNECTIONS


FOR REMOTE MOUNTED SIGNAL CONVERTER

Note: Figure shows electronics without encapsulation material. Normally


the converter housing is filled with a silicone rubber encapsulant.

3-3
10DS3111E INSTRUCTION MANUAL

4.0 FUNCTIONAL DESCRIPTION

The meter body houses two signal electrodes and two flux producing magnet coils, as shown
schematically in Figure 4-1. All flowmeter intraconnection wiring is terminated at a printed circuit
assembly located in the base mounted on the meter housing.

The meter provides two output signals to the signal converter:


• an electrode signal that contains the flow rate information
• the reference signal which is proportional to the magnet excitation current
(theoretically, this reference signal is proportional to the flux density in the metering
section).
The reference voltage is derived across a precision constant meter capacity (CMC) resistance
network that is connected in series with the magnet coils. Changes in magnet drive voltage, which
cause a variation of flow signal, will simultaneously cause a proportional variation of the reference
voltage. The circuitry will provide an exact ratio and thereby provide immunity to power supply
variation. The magnet coil drive circuitry is contained in the signal converter.

4.1 Basic Operating Principle


4.1.1 Signal Voltage Generation
The operating principle of the Series 3000 meter is based upon Faraday’s Law of Induction which
states that the voltage induced across any conductor as it moves at right angles through a magnetic
field will be proportional to the velocity of that conductor. This principle finds common application in
direct and alternating current generators. Essentially, the meter constitutes a modified form of a
generator.

Figure 4-1 graphically illustrates the basic op-


erating principle. A magnetic field, "B", being
generated in planes which are perpendicular
to the axis of the meter pipe. A disk of the
metered liquid can be considered as a con-
ductor. The transverse length "D" is equal to
the meter pipe diameter. Since the velocity "V"
of the liquid disk is directed along the axis of
the meter pipe, a voltage, signal "Es", will be
induced within this liquid which is mutually
perpendicular to the direction of the liquid ve-
locity and the flux linkages of the magnetic
field; i.e., in the axial direction of the meter
electrodes. This electrode voltage is the sum-
mation of all incremental voltages developed
within each liquid particle that passes under
the influence of the magnetic field.

FIGURE 4-1. BASIC OPERATING PRINCIPLE

4-1
10DS3111E INSTRUCTION MANUAL

This may be expressed mathematically as:

(Equation #1)

1
Es = BDV
α

where:

E s = induced electrode voltage


B = magnetic field strength
D = meter pipe diameter
α = dimensionless constant
V = liquid velocity

The metered liquid constitutes a continuous series of conductive liquid disks moving through a
magnetic field. The more rapid the rate of liquid flow, the greater the instantaneous value of signal
voltage as monitored at the meter electrodes.

4.1.2 Volumetric Flow Rate Measurement


The meter is a volumetric flow rate measuring instrument. This can be shown by substituting the
physical equivalent of liquid velocity into equation #1 as follows:

(Equation #2)

V = Q = 4Q
A πD 2

Substituting for V in equation #1

4
E s = 1 BD Q2
α πD

and solving for Q:

∴ Q = παD • Es
4 B

Since B = β E r

and since α, D and β are constant:

4-2
10DS3111E INSTRUCTION MANUAL

(Equation #3)

Q = γ Es
Er

where:

Q = volumetric flow rate


A = cross-sectional area
D = pipe section diameter
E s = induced signal voltage
E r = reference voltage
B = magnetic flux density
α = dimensionless constant
β & γ = dimensional constant
V = liquid velocity

Therefore, volumetric flow rate is directly proportional to the ratio of the induced signal voltage to the
reference voltage as measured by the meter.

4.2 Operating Characteristics


4.2.1 Liquid Variables
4.2.1.1 Liquid Conductivity
The meter requires a liquid conductivity of 20 microsiemens per centimeter or higher for operation.
This minimum liquid conductivity requirement is not affected by the length of the signal interconnec-
tion cable as long as the factory-supplied or factory-approved interconnection cable (with driven
shields) is used. The nominal maximum transmission distance is limited to 100 feet (30 m) which is
the standard length of cable supplied unless specified otherwise.

The conductivity of a given liquid, σ, may be determined experimentally under a filled meter
condition, as follows:

1) Turn off power to the signal converter. Remove the converter housing cover. Disconnect
and identify the electrode signal interconnection leads from terminals "1" and "2" of the sig-
nal converter.

2) Measure the resistance between signal leads "1" and "2" with an ac ohmmeter.

CAUTION
Do not use a dc ohmmeter for this measurement as polarization
effects will produce completely erroneous data.

4-3
10DS3111E INSTRUCTION MANUAL

The conductivity of the process liquid (in microsiemens/cm) may be determined from the electrode ac
resistance measurement (in megohms) by substitution of values in the following equation.

σ= 1
(R ac - 0.072) x Electrode Diameter, in cm

where,

0.072 is the electrode barrier resistance in megohms; i.e., 36 kΩ x 2/10 6

and,

typical electrode diameter is 0.77 cm

For example, assuming the measured ac electrode resistance (full pipe) is 192,000 ohms and
electrode diameter is 0.76 cm, then

σ= 1 = 10.82 µS/cm
(0.192 - 0.072) x 0.77

This is above the threshold for specified measurement accuracy for the particular liquid, meter size
and signal converter combination. Liquid conductivities at the operating temperature may also be
determined from standard references for many pure liquids. Factory Field Engineers are equipped to
determine the conductivities of special liquids at the user’s site.

Electrode diameters vary with meter size and type of liner, the values given in Table 4-1 are typical
electrode diameters.

TABLE 4-1. ELECTRODE DIAMETERS

Meter Size Electrode Diameters


inches (mm) TEFLON Lined Meter Neo/Poly Lined Meter
1 - 1 1⁄2 (25-40) .770 cm (.303 inch) ------------
2 - 4 (50-100) .820 cm (.323 inch) .635 cm (.250 inch)
6 - 12 (150-300) 1.200 cm (.472 inch) .635 cm (.250 inch)

4-4
10DS3111E INSTRUCTION MANUAL

4.2.1.2 Liquid Temperature


Having established the minimum liquid conductivity requirements for a given application, any liquid
which exhibits equal or higher conductivity may be metered without concern for any system compen-
sating adjustments. However, the effect of the liquid conductivity versus temperature should be
considered.

Most liquids exhibit a positive temperature coefficient of conductivity. It is possible for certain
marginal liquids to become sufficiently non-conductive at lower temperatures so as to hamper
accurate metering; whereas, the same liquid at higher or normal environmental temperatures may be
metered with optimum results. The possibility of an adverse temperature conductivity characteristic
should be investigated before attempting to meter such a liquid. Process or ambient temperatures
are limited by the meter materials specification.

Other normal effects of temperature, such as influence upon liquid viscosity and density, the size of
the metering area, and the flux density of the magnetic field, have negligible or no effect upon
metering accuracy.

4.2.1.3 Other Liquid Variables


Other liquid variables such as viscosity, density and liquid pressure have no direct influence on
metering accuracy. Liquid density has no effect on volumetric flow rate since only the area of the
meter pipe and liquid velocity are required to determine the rate of flow. Viscosity and metering
pressure are restricted to physical limitations alone, such as the pressure limits of the meter pipe
flange connections.

4.2.2 Metering Characteristics


The metering pipe must be completely filled at all times for accurate measurement. Where there is a
possibility of operation with a partially filled horizontal pipeline, it is recommended that the meter be
installed in a vertical position so that the process flows upward. A vertical installation offers the
advantage of an even distribution of wear on the meter liner in the event that abrasives are present
in the process stream.

The meter will measure the total amount of material passing in the process stream. The meter will not
differentiate between the amount of liquid and the amount of entrained gases. Also, in the case of a
slurry, the meter will not differentiate between the amount of liquid and solids. If the liquid to mixant
ratio is important for process control, then separate measurements of the concentration of the
medium must be made and appropriate correction factors applied to the meter output.

In applications involving variable quantities of uniformly dispersed, non-conductive mixing agents, it


must be determined that the higher concentrations of mixant will not drive the average conductivity of
the liquid mixture below the minimum conductivity level for the given installation.

4-5
10DS3111E INSTRUCTION MANUAL

5.0 CIRCUIT DESCRIPTION

5.1 Meter Signals


The meter body houses two signal electrodes and two flux producing magnet coils. All meter
intraconnection wiring is terminated at the CMC/ZERO pc board located in the base of the meter
housing.

The meter provides two output signals to the associated signal converter; one, an electrode signal
that contains the flow rate information, and two, the reference signal which is proportional to the
magnet excitation current (theoretically, this reference signal is proportional to the flux density in the
metering section). The reference voltage is derived across a precision "constant meter factor"
resistance network that is connected in series with the magnet coils. Changes in magnet drive
voltage, which cause a variation of flow signal, will simultaneously cause a proportional variation of
the reference voltage. The circuitry will provide an exact ratio and thereby provide immunity to power
supply variation. The magnet coil drive circuitry is contained in the signal converter.

5.2 Constant Meter Capacity (CMC) PC Assembly


The CMC pc assembly provides the following functions:

1. Establishes interconnections between the meter internal wiring and the signal
converter.

2. Permits factory adjustment of meter capacity values to a fixed value for each nominal size
meter.

3. Permits factory adjustment of meter zero.

4. Aligns the phase of the electrode and reference signals.

5-1
10DS3111E INSTRUCTION MANUAL

6.0 MAINTENANCE

6.1 General
Except for an occasional performance verification check, there is no routine maintenance required for
the meter. It is suggested that the meter body not be disassembled. If disassembled, complete
waterproof sealing is required for satisfactory operation and is best done at the factory. Replacement
of faulty magnet drive coils and electrode replacement is a factory operation. Factory calibration after
this type of repair is the only way to guarantee meter accuracy.

The manufacturer offers a Repair/Exchange Program to facilitate replacement of a defective meter or


converter. If the equipment is beyond the warranty limit, under this program a fixed price will be
charged for replacement of defective equipment, with appropriate credit issued when the repairable
unit is received by the manufacturer (charges prepaid). The equipment available under this program
is as follows:
• the meter with the interconnection junction box without the signal converter
• the signal converter

WARNING
All flowmeters and/or signal converters being returned to the
manufacturer for repair must be free of any hazardous materials (acids,
alkalis, solvents, etc.). A Material Safety Data Sheet (MSDS) for all
process liquids must accompany returned equipment. Contact the
manufacturer for authorization prior to returning equipment.

NOTE
Operation and maintenance procedures for the signal converter are pro-
vided in the instruction bulletin supplied with the signal converter.

When communicating with the manufacturer in regard to replacement of a complete meter or the
signal converter, it is important to refer to the complete instrument serial number to assure that the
correct replacement will be supplied. This information is provided on the manufacturing specification
sheet supplied with the meter, and on the instrument data tag.

6.2 System Troubleshooting


In the event that faulty operation of the meter is evident, the following procedure can be used as a
guide to isolate the malfunctioning device as either the meter or the signal converter. A standard
multimeter is suitable for making most of the test measurements.

To supplement the following discussion refer to:


• Section 5.0 Circuit Description
• Signal converter instruction manual

6-1
10DS3111E INSTRUCTION MANUAL

NOTE
The meter housing is supplied as a sealed unit. Therefore, customer field
repairs to these meters are not recommended. In the event of a malfunc-
tion, repairs should only be performed by a factory field service engineer,
or the complete meter returned to the manufacturer for service (shipping
charges prepaid).

WARNING
Equipment powered by an ac line voltage presents a potential electric
shock hazard. Servicing of the flowmeter or signal converter should
only be attempted by a qualified electronics technician.

1. If improper meter operation is suspected, proceed as follows:

a) Remove the access cover from the meter junction box.


b) Inspect for evidence of water entry in the junction box.

If water is present, de-energize system at power source. Inspect conduit seals and cover gaskets for
possible source of water entry. Replace the seals and/or gasket as required. Allow interior of junction
box and converter housing to dry completely before restoring system power.

2. Since signal wiring and operating procedures are dependent upon the type of converter and the
mounting option selected, the user should refer to the instruction bulletin supplied with the signal
converter for system troubleshooting procedures. A static performance test for the meter mounted
components is discussed in Section 6.3.

3. Possible causes of erroneous flow rate indication are:


• incorrect grounding
• excessive noise due to a heavy slurry process
or a non-homogeneous process
• loose or intermittent wiring
• non-full or empty meter pipe
• excess air entrained in process liquid
• fluid conductivity below minimum specifications

4. The customer connection box mounted on the meter Primary contains an assembly of two printed
circuit boards. The upper board contains the terminal blocks for the customer connections as well as
a terminal strip with a jumper block labeled J1 (shown in FIGURE 3-2). The proper position for this
jumper in the 10DS3111E is between the center terminal and the lower terminal marked 16A as
shown in the figure below.

16P PROPER
JUMPER
POSITION
16A
J1

6-2
10DS3111E INSTRUCTION MANUAL

6.3 Static Test


If improper operation of the meter is suspected, the following resistance measurements can be made
to establish whether an electrical malfunction has occurred. An analog multimeter is required for
checking the electrodes. Either an analog or digital multimeter can be used for checking the coils.
These measurements can be made at the flowmeter pc board.

WARNING
Equipment that operates from ac line voltage constitutes a potential
electric shock hazard to the user. Make certain that the system power is
disconnected before making the following ohmmeter checks.

6.3.1 Magnet Coil Check


6.3.1.1 Signal Converter
Verify that the system power service has been de-energized. Turn off the power to the signal
converter to de-energize the meter. Remove cable leads M1 and M2/M3 from the customer terminal
block. Measure magnet coil series resistance by connecting the ohmmeter between M1 and M2/M3.
The value displayed should correspond to that indicated in Table 6-1. A reading of infinity or a short
circuit between leads indicates defective coil(s). If proper coil resistance is verified, reconnect cable
leads to terminals M1 and M2/M3. If coil(s) is defective, meter must be returned to the factory for
service.

TABLE 6 -1. METER COIL RESISTANCE

Coil Resistance
Meter Size Nominal, ohms ±20%
Each Series
inches mm Coil Resistance *
1 25 156 312
1 1⁄2 40 240 480
2 50 190 380
3 80 110 220
4 100 74 148
6 150 11 22
8 200 10.7 21.4
10 250 10.7 21.4
12 300 10.7 21.4

* M1 to M3
Reference temperature = 60o C

6-3
10DS3111E INSTRUCTION MANUAL

6.3.2 Electrode Check


The electrode check is essentially a resistance measurement that can be made to establish that a
short (or high resistance leakage path) does not exist between one, or both, electrodes and the meter
body. Verify that the system power service has been de-energized.

To perform this test, the meter must be removed from the pipeline and the meter liner thoroughly
dried. When the meter liner has been dried, proceed as follows:

1) Disconnect and identify(tag) the electrode signal leads, 1 and 2, from the terminal
board in the signal converter (or from the terminal board in the base of the meter
housing).

2) Place ohmmeter on highest available range (for example: R x 100,000).

3) Connect the ohmmeter "minus" lead to the meter ground stud and the "plus" lead
to electrode line 1. This reading should be infinite. If any resistance can be measured,
the meter is defective and must be replaced.

4) Check the other electrode by connecting the ohmmeter "plus" lead to line 2. This
reading must also be infinite. If any resistance can be measured, the meter is
defective and must be replaced.

5) If measurement of both electrodes indicate an infinite resistance reading, the meter


may then be returned to on-stream operation. LINES 1 AND 2 FROM THE RESPEC-
TIVE ELECTRODES MUST BE RECONNECTED TO TERMINALS 1 AND 2 OF THE
TERMINAL BOARD. DO NOT INTERCHANGE THESE PROCESS SIGNAL CON-
NECTIONS.

6-4
10DS3111E INSTRUCTION BULLETIN

7.0 PARTS LIST

TABLE 7-1. FLANGE GASKETS FOR METER BODY

NOTE
Polyurethane and neoprene lined meters use neoprene gaskets.
TEFLON lined meters use TEFLON gaskets.

Two gaskets are required for each meter. If the meter has grounding rings, two additional gaskets are
required for each meter.

Meter Size Liner Material


ANSI
Flange Neoprene
Class Teflon/ Polyurethane
Inches mm
Tefzel Hard/Soft Rubber
150 333N239P30 ----------
1 25
300 333N205P30 ----------
150 333C526U20 ----------
1 1⁄2 40
300 333N314P30 ----------
150 333N415P30 333N415Q10
2 50
300 333N416P30 333N416Q10
150 333N509P30 333N509Q10
3 80
300 333N510P30 333N510Q10
150 333N604P30 333N604Q10
4 100
300 333N702P30 333N702Q10
150 333N811P30 333N811Q10
6 150
300 333N801P30 333N801Q10
150 333N812P30 333N812Q10
8 200
300 333N802P30 333N802Q10
150 333N807P30 333N807Q10
10 250
300 333N821P30 333N821Q10
150 333N806P30 333N806Q10
12 300
300 333N803P30 333N803Q10

1 25 DIN PN 10-40 333C609U02 -


1-1⁄2 40 DIN PN 10-40 333C609U03 -
2 50 DIN PN 10-40 333C608U05 333C609U01
3 80 DIN PN 10-40 333C608U06 333C609U02
DIN PN 10/16 333C608U07 333C609U03
4 100
DIN PN 25/40 333C608U08 333C609U04

7-1
10DS3111E INSTRUCTION BULLETIN

TABLE 7-2. PROTECTOR PLATES FOR TEFLON LINED METERS

Order number consists of two protector plates and mounting screws. Grounding rings are not
available for this application. When ordering, specify 614B452U__ and suffix from the table below.

Meter Size Flange Rating ANSI Class 150


Protector Inches = 1⁄2 1 1 1⁄2 2 3 4
Plate Material (mm) = (15) (25) (40) (50) (80) (100)
316 sst Suffix = 02 03 04 05 06 07
HAST "C" Suffix = 16 17 18 19 20 21

Flange Rating
Meter Size ANSI Class 300
Protector Inch = 4
Plate Material (mm) = (100)
316 sst Suffix = 40
HAST "C" Suffix = 47

TABLE 7-3. LINER PROTECTOR/GROUNDING RINGS FOR TEFLON LINED METERS

Order number consists of two protector plates which serve as grounding rings, and mounting screws.
Separate grounding rings are not available for this application. When ordering, specify 614B384U__
and suffix from the table below.

Flange Rating Flange Rating


Meter Size ANSI Class 150 ANSI Class 300
Protector Inches = 6 8 10 12 6 8 10 12
Plate Material (mm) = (150) (200) (250) (300) (150) (200) (250) (300)
316 sst Suffix = 01 07 13 19 04 10 16 22
HAST "C" Suffix = 02 08 14 20 05 11 17 23

TABLE 7-4. GROUNDING RINGS - SIZES 1 THROUGH 4 INCHES

Order number consists of two grounding rings and mounting screws.When ordering, add suffix to the
BM number.

Flange Rating Flange Rating


ANSI Class 150 ANSI Class 300
Meter Size Material = 316 SST HAST "C" 316 SST
Inches mm BM No. Suffix BM No. Suffix
1 25 800D508 U02 U10 800D708 U03
1 1⁄2 40 800D508 U03 U11 ---------- ---
2 50 800D508 U04 U12 800D708 U04
3 80 800D508 U05 U13 800D708 U05
4 100 800D508 U06 U14 800D708 U06

7-2
10DS3111E INSTRUCTION BULLETIN

TABLE 7-5. GROUNDING RINGS - SIZES 6 THROUGH 12 INCHES

NOTE
Polyurethane and neoprene lined meters use neoprene gaskets.
TEFLON lined meters use TEFLON gaskets.

Order number consists of one grounding ring and mounting screws. Order a quantity of two for each
meter. Order by the referenced part number.

Flange Rating Flange Rating


ANSI Class 150 ANSI Class 300
304 SST with 304 SST with 304 SST with 304 SST with
Meter size Neoprene gasket TEFLON gasket Neoprene gasket TEFLON gasket
Inches mm Part Number Part Number Part Number Part Number
6 150 644B009U01 644B009U02 644B009U23 644B009U24
8 200 644B009U03 644B009U04 644B009U25 644B009U26
10 250 644B009U69 644B021U24 644B009U71 644B021U26
12 300 644B009U70 644B021U25 644B009U72 644B021U27

TABLE 7-6. METER BASE AND JUNCTION BOX GASKETS

Standard Meter
Junction Box Base Gasket D333F021U01
Base to Spacer Gasket D333F009U01
Spacer to Cover Gasket D333F008U01

Continuous Submergence Meter


Cover O-Ring 101A820U01

TABLE 7-7. HARDWARE

Description Remote Converter


Cover Mounting Screws 09G114AU20 - Qty. 4

7-3
PN25011

The Company’s policy is one of continuous product improvement and the


right is reserved to modify the information contained herein without notice.
© 2003 ABB Inc. Printed in USA

ABB Inc. ABB Instrumentation Ltd ABB Instrumentation S.p.A ABB Automation Products GmbH
125 East County Line Road Howard Road, St. Neots Via Sempione 243 Industriestr. 28
Warminster, PA 18974 USA Cambs. England, PE19 3EU 20016 Pero (Milano) Italy D-65760 Eschborn Germany
Tel. 215-674-6000 Tel. +44 (0) 1480-475-321 Tel: +39 (02) 33928 1 Tel: +49 (0) 6196 800 0
FAX: 215-674-7183 FAX: +44 (0) 1480-217-948 Fax: +39 (02) 33928 240 Fax: +49 (0) 6196 800 1849

You might also like