Isolated Footing
Isolated Footing
Isolated Footing
Isolated Footing 1
0.3 m
Elevation
X 0.75 m
0.25 m
1.5 m
0.2 m
0.75 m
1.5 m
Plan
Input Values
Footing Geomtery
Column Dimensions
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 2 of 15
Pedestal
Include Pedestal : No
Pedestal Shape : N/A
Pedestal Height (Ph) : N/A
Pedestal Length - X (Pl) : N/A
Pedestal Width - Z (Pw) : : N/A
Design Parameters
Soil Properties
Cohesion : 0.00kN/m2
Global Settings
Top Reinforcement Option : Calculate only when foundation is subjected to uplift forces
Concrete Design Option : Net Pressure(Gross Pressure - Self Weight Pressure)
Top Reinforcement Factor : 1.00
------------------------------------------------------
Design Calculations
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 3 of 15
Footing Size
Load Combinations
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 4 of 15
Moments are about the center of footing / pile cap (does not include moments caused by lateral loads)
For the loads shown in this table, the sign convention is the same as that for JOINT LOADS in STAAD.Pro when global Y is the vertical axis.
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 5 of 15
2
Area from initial length and width, Ao = Lo X W o = 2.25 m
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 6 of 15
2
Min. area required from bearing pressure, Amin = 0.96 m
Note: Amin is an initial estimation considering self-weight, axial load and moment against factored bearing capacity.
Pressures at 4 Corners
Please note that pressures values displayed in tables below are calculated after dividing by soil bearing factor
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of negative pressure will be set to zero and the pressure
will be redistributed to remaining corners.
Pressure at
Pressure at top Pressure at top bottom right Pressure at
Load Case / left corner right corner corner bottom left corner
Combination (kN/m2) (kN/m2) (kN/m2) (kN/m2)
Stability Check
OTM
Sliding Force
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 7 of 15
Load
Along X- Along Z- Required About X- About Z- Required
Case Resultant
Direction Direction FOS Direction Direction FOS
No.
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 8 of 15
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - X Direction
Critical Load Case And The Governing Factor Of Safety For Overturning And Sliding - Z Direction
Ultimate Pressures
The base pressures reported in this table do not include the effect of buoyancy. However, the area of footing in contact includes the effect of
buoyancy (if any).
Area of
Load Case / Pressure at Pressure at Pressure at Pressure at
footing in
Load top left top right bottom right bottom left
Contact with
Combination corner corner corner corner
soil (Au)
ID (kN/m2) (kN/m2) (kN/m2) (kN/m2) 2
(m )
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 9 of 15
Actual Area in Contact for all ultimate load cases exceeds the minimum required. Hence Safe
Maximum Corner Pressure from all ultimate load cases is less than the allowable. Hence Safe
Shear Calculation
X 0.75 m
Z
0.115 m
0.75 m
Plan
Total Footing Depth, D = 0.30m
Calculated Effective Depth, d = D - Ccover - 1 * db = 0.23 m
For rectangular column, = Bcol / Dcol = 1.24
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 10 of 15
X 0.75 m
Z 0.42 m
0.75 m
0.42 m
Plan
Check that 0.75 X Vc > Vux where Vux is the shear force for the critical load cases at a distance d from the face of the column caused by bending about the X axis.
X 0.75 m
0.395 m 0.395 m
0.75 m
Plan
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 11 of 15
Check that 0.75 X Vc > Vuz where Vuz is the shear force for the critical load cases at a distance d from the face of the column caused by bending about the Z axis.
8 - ϕ16
Calculate the flexural reinforcement along the X direction of the footing. Find the area of steel required, A, as per Section 3.8 of Reinforced Concrete Design (5th ed.) by
Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in Mpa
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 12 of 15
Because the number of bars is rounded up, make sure new reinforcement ratio < ρmax
Total reinforcement area, As_total = Nbar X (Area of one bar) = 1608.51 mm2
d= D - Ccover - 0.5 X (dia. of = 0.23 m
one bar)
8 - ϕ16
Calculate the flexural reinforcement along the Z direction of the footing. Find the area of steel required, A, as per Section 3.8 of Reinforced Concrete Design (5th ed.) by
Salmon and Wang (Ref. 1)
The strength values of steel and concrete used in the formulae are in Mpa
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 13 of 15
Because the number of bars is rounded up, make sure new reinforcement ratio < ρmax
Total reinforcement area, As_total = Nbar X (Area of one bar) = 1608.51 mm2
d= D - Ccover - 1.5 X (dia. of 0.23 m
=
one bar)
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 14 of 15
Footing Reinforcement
Along Z on Bottom
ϕ16 8 11.20 17.68
Face
Along X on Bottom
ϕ16 8 11.20 17.68
Face
Along Z on Top
N/A N/A N/A N/A
Face
Along X on Top
N/A N/A N/A N/A
Face
Concrete
Soil Excavation
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO... 12/03/2020
Page 15 of 15
12/03/2020
1m
X 0.75 m
file:///E:/Files/Structural%20Projects/Mar/2-Storey%20Commercial/2-STOREY%20CO...
Z
0.25 m
1.5 m
0.2 m
0.75 m
1.5 m
0.3 m
Plan
TOP N/A
L B D AstX(T) AstZ(T) AstX(B) AstZ(B)
Foundation
0.75 m