Defination of Fire
Defination of Fire
Defination of Fire
Defination of fire
As a process, fire can take many form, all of which involve chemical reaction between
combustible specties and oxygen from the air and heat to meet our industrial and domestic needs
but unchecked, can cause untold material damage and human suffering. Such an approach
require a detailed understanding of fire behaviour from an engineering standpoint. The study of
fire chemistry is as essential to the fire protection Engineer as study of chemistry is to the
Chemical Engineer.
Note:- The flamming mode can be conceived of as a tetrahedrol , in which each of the four sides
is contiguous with the other sides and each sides represent one of the four basic requirements of
combustion: fuel, temperature, oxygen and uninhibited combustion chain reactions. As Shown
on the Right side of the figure, the Surface combustion mode can be symbolized correctly in the
form of traditional triangle; in which each of the three sides in contiguous with other two sides
and each sides representing one of the three basic requirements - fuel, temperature, oxygen.
Fire Prevention & Protection
Defination of fire
Sr.
Types of Fire Extinguishers Class of Fire
No.
A B C D
1 Water (Gas Cartridge) S NS NS NS
2 Water (stored pressure) S NS NS NS
3 Mechanical Foam U S NS NS
4 Dry chemical powder Gas cartridge) U S S NS*
5 Dry chemical powder (metal type) S S S NS
6 Carbon di-oxide U S S NS
7 Halon U S S NS
S: Suitable
NS: Not suitable
U : Can be used in case of emergency but not much effective.
* : Special dry powder can be used.
Taking into consideration the views of technical authority, the number and size of first
aid fire appliances that are installed in any particular premises for protecting building
structure and occupancy hazard are according the following factors,
Fire Prevention & Protection
Defination of fire
Defination of fire
In case of fire
Defination of fire
In case of fire
Do's / Dont's
Do's
Acquaint yourself with the layout of the escape routes, staircases, refuge areas and the
location of fire alarms.
Train yourself and the security personnel in the proper operation and use of first-aid hose
reel provided at each floor level and fire extinguishers. Also train them in switching on
the fire pump, at ground/basement level and also the booster pump at terrace level, and
the method of summoning the Fire Brigade Department in the event of a fire.
Keep always closed the fire doors of staircases, main entrance to the factory building/
company
All the fire protection installations such as fire pumps, wet riser-cum-downcomer,
sprinkler installation, fire extinguishers etc should be kept in a good state. Timely use of
these will help in controlling/extinguishing the fires in the early stages, thereby
minimising life losses and property losses.
Always maintain good house keeping.
Ground all the lifts, including FIRE LIFT, in case of a fire.
Practice evacuation drills periodically.
Irrespective of the magnitude of fire, summon the Fire Brigade at the earliest.
Seek the advice and guidance of Fire Brigade Department in the matter of fire safety.
In case of fire, guide the Fire Brigade Department personnel about the location and extent
of fire, information about trapped persons, if any, and provide any other information they
may request. Help them to help you.
Remember, FIREMAN IS YOUR FRIEND .
Dont's
Do not allow encroachments or storages in the courtyards of the building. Open
courtyards are required for placing and operating the fire and rescue appliances in case of
emergency.
Do not allow storages or obstructions in the common corridors and staircases. These exit
routes, if maintained clear, will help easy escape in case of fire.
Do not allow the Fire doors of the staircases to be kept open. In case of fire, heat and
smoke enters the staircases and prevent the escape of people.
In case of fire, do not use LIFTS for escape. They may fail midway trapping people
inside. Use only staircases.
Do not allow Electric Meter Rooms to be used as storages, dumping places or as living
quarters for servants. They are potential fire hazards.
During Diwali Season, do not keep any combustibles in the balconies. Do not dry clothes
in the balconies or outside the building line. Flying crackers have caused serious fires.
Do not use the basement for any purpose other than permitted purpose. Because of ill-
ventilation, habitation or working in the basement will make a death trap for people.
Continuous electrical ducts through the height of the building enable the fire to spread
from one floor to another. Seal them at each floor slab level.
Do not allow Air-Condition ducting to pass through one floor to another, because fire,
heat and smoke travel through these ducts and spread to the other part of the building.
Sectionalise them, as far as practical even on a particular floor, so as to limit the spread of
fire, heat and smoke, and minimise the damages.
Never paint or coat fire detectors or sprinkler heads. If done, they will become
ineffective.
Do not re-enter the ire affected building to collect the valuables or for any other purpose.
It may cost your life.
Do not decorate walls and ceilings of common corridors with combustible material such
as wooden paneling etc. They create unwarranted fire risk in the escape route in case of
fire.
Do not allow Fire fighting tanks to be misused or remain empty. Do not block access to
the tank. You/Fire Service may need them for use at any moment.
Avoid damage to wet riser system. It has been provided for your use to extinguish/check
spread of fire before arrival of Fire Brigade. It's good maintenance ensures your safety.
Do not 'switch off' Fire/Smoke Detection System. This may lead to fire remaining
unnoticed till it assumed large magnitude
Do not 'switch off' electricity of the entire building in the event of a fire. This will cause
stoppage of all the fire protection and fire fighting system installed in the building.
Do not carry out additions and alteration in the building. Consult Fire Brigade before
undertaking such works.
Defination of fire
In case of fire
Do's / Dont's
Defination of fire
In case of fire
Do's / Dont's
Evacuation drill
Guidelines for Fire Drill and Evacuation Procedures For High Rise Buildings
(Above 15 m in height)
E-1 INTRODUCTION
In case of fire in a high rise building, safe evacuation of its occupants may present serious
problems unless a plan for orderly and systematic evacuation is prepared in advance and all
occupants are well drilled in the operation of such plan. These guidelines are intended to assist
them in this task.
E-2 ALARMS
Any person discovering fire, heat or smoke shall immediately report such condition to the fire
brigade, unless he has personal knowledge that such a report has been made. No person shall
make, issue, post or maintain any regulation or order, written or verbal, that would require any
person to take any unnecessary delaying action prior to reporting such condition to the fire
brigade.
E-3 DRILLS
E-3.1 – Fire drills shall be conducted, in accordance with the Fire Safety Plan, at least
once every three months for existing buildings during the first two years. Thereafter, fire
drills shall be conducted at least once every six months.
E-3.2 – All occupants of the building shall participate in the fire drill. However,
occupants of the building, other than building service employees, are not required to
leave the floor or use the exits during the drill.
E-3.3 – A written record of such drills shall be kept on the premises for a three years
period and shall be readily available for fire brigade inspection.
E-4.5 – Fire command station shall be provided with floor pan of the building and other
pertinent information relative to the service equipment of the building.
E-5.1 – A format for the Fire Safety Plan shall be as given in E-8
E-5.2 – The applicable parts of the approved Fire Safety Plan shall be distributed to all
tenants of the building by the building management when the Fire Safety Plan has been
approved by the Fire Authority.
E-5.3 – The applicable parts of the approved Fire Safety Plan shall then be distributed by
the tenants to all their employees and by the building management to all their building
employees.
E-5.4 – Where the owner of the building is also an occupant of the building, he shall be
responsible for the observance of rules and the Fire Safety Plan in the same manner as a
tenant.
E-5.5 – In the event there are changes from conditions existing at the time the Fire Safety
Plan for the building was approved, and the changes are such so as to require amending
the Fire Safety Plan, within 30 days after such changes, an amended Fire Safety Plan
shall be submitted to the fire brigade for approval.
E-9 DUTIES
FIRE WARDEN INSTRUCTIONS FOR YOUR OWN SAFETY YOU SHOULD KNOW
Two push button fire alarm boxes are provided per floor. You should read the operating
instructions.
You should read the operating instructions on the body of the fire extinguishers provided
on you floor.
The nearest exit from your table.
Your assembly point on ground floor (check with your Fire/Deputy Fire Warden)
FOR YOUR OWN PROTECTION YOU SHOULD REPORT TO YOUR FIRE
DEPUTY FIRE WARDEN.
o If any exit door/route is obstructed by loose materials, foods, boxes, etc.
o If any staircase door, lift lobby door does not close automatically, or does not
close completely.
o If any push button fire alarm point, or fire extinguishers is obstructed, damaged or
apparently out of order.
Break the glass of the nearest push button fore alarm and push the button.
Attack the fire with extinguishers provided on your floor. Take guidance from your
Wardens.
Evacuate if your Warden asks you to do so.
Defination of fire
In case of fire
Do's / Dont's
Classification of fires as per ISI 2190/1979
Evacuation drill
To prevent fire
Do not overload electrical circuit; it may cause short circuit and a fire.
Use one socket for electrical appliances
Do not leave electrical appliances unattended.
Switch off electric appliances after use and remove the socket. It is fire safe practice.
Switch off the "Main switch" before the house for long time duration.
Do not keep electric wiring hanging, batten properly.
Do not use candle the in case of power failure. User battery operated tourches.
Smoke only in the Smoking Zone, use non- combustible ashtrays for depositing lighted
smoking material
Use ashtray while Smoking
Keep matches, crackers, lighters away from the children.
Keep L.P.G. Stove/Segree/Burner on raised non-combustible platform.
Turn off both the L.P.G. gas cylinder valve and burner knob of the gas segree/cooking
range etc. when not in use after cooking.
Ventilate the entire room if L.P.G. cylinder is leaking and do not switch on/off any of the
electric switches the room in . Replace L.P.G. supply tube periodically or as and when
advised by Mechanic.
If L.P.G. cylinder is leaking-
o Close the main cylinder valve.
o Ventilate the entire room.
o Do not operate electric switch.
Do not allow children to play with fire crackers.
Do not light fire works very close to the buildings .
Close the windows and openings properly to prevent ingress of lighted flying crackers.
Do not leave lighted oil lamps, agarbattis or candles on the floor or near combustible
material. Put them off before retiring to bed.
Do not store scrap/combustible material in and around the building; dispose it regularly.
Fire Prevention & Protection
Defination of fire
Utility of fire extinguishers
Fixed fire fighting equipments
In case of fire
Do's / Dont's
Classification of fires as per ISI 2190/1979
Evacuation drill
To prevent fire
Fire drill
CONTROL ROOM will coordinate the conduct of fire drills every six months in each of
the Company's offices to familiarise all members of the staff and security personnel with
the procedures to be followed in the event of fire. CONTROL ROOM will decide the
date and timing of the fire drills in consultation with the various Business Functions in
the region and arrange to intimate all concerned atleast 10 days in advance.
A CONTROL ROOM representative will record the events of each fire drill and circulate
this to all Managers in the concerned region. The Regional Office, CONTROL ROOM
will maintain the original fire drill report.
CONTROL ROOM will conduct these fire drills on its own or through a professional
organisation. In the event a professional organisation's help is sought, the cost will be
borne by all functions in that particular location/region.
You Can Stop Fires
Do's
Acquaint yourself with the layout of the escape routes, staircases, refuge areas and the
location of fire alarms.
Train yourself and the security personnel in the proper operation and use of first-aid hose
reel provided at each floor level and fire extinguishers. Also train them in switching on
the fire pump, at ground/basement level and also the booster pump at terrace level, and
the method of summoning the Fire Brigade Department in the event of a fire.
Keep always closed the fire doors of staircases, main entrance to the factory building/
company
All the fire protection installations such as fire pumps, wet riser-cum-downcomer,
sprinkler installation, fire extinguishers etc should be kept in a good state. Timely use of
these will help in controlling/extinguishing the fires in the early stages, thereby
minimising life losses and property losses.
Always maintain good house keeping.
Ground all the lifts, including FIRE LIFT, in case of a fire.
Practice evacuation drills periodically.
Irrespective of the magnitude of fire, summon the Fire Brigade at the earliest.
Seek the advice and guidance of Fire Brigade Department in the matter of fire safety.
In case of fire, guide the Fire Brigade Department personnel about the location and extent
of fire, information about trapped persons, if any, and provide any other information they
may request. Help them to help you.
Remember, FIREMAN IS YOUR FRIEND .
Dont's
Training
LOCATION:
The State Fire Training Centre is established in Santacruz (East) approximately 05 kms.
away from the Santacruz Railway Station and in the close proximity of the Complex of
Mumbai University. It is 3 kms. away from the National & International Airports.
Though it is within Mumbai, it enjoys a very silent and peaceful location.
INFRASTRUCTURE:
The Training Centre has one Classroom having capacity to accommodate 75 students
with all the Audio & Visuals required for the Training such as OHP, TV, D.V.D. There
are 3 Dormitories having capacity to accommodate 50 Trainees.
APPLIANCES & EQUIPMENTS:
The Training Centre maintains a well-equipped Fire Engine, 1 Troop Carriers, 2
conventional vehicles & Trailer Pump and other all the basic requirements for the Fire
Fighting Training.
STAFF:
The Training Centre is headed by the Fire Advisor to Govt. of Maharashtra and is having
following staff. In addition to this paid staff, Mumbai has a great advantage of Faculties
from the multi-discipline areas from the various Fire Services such as for Civic Fire
Services, we have the M.C.G.M. Fire Department, for Nuclear Hazards, we have
B.A.R.C. Fire Services Experts, for Industrial Fire Hazards, we have experts from MIDC,
MSEB, R.C.F. and such other Industries, for Oil & highly inflammable Chemicals, we
have experts from the Bombay Harbor, For Air Port & Sea Ports, also experts from the
Air-Port Authorities and Sea-Port Authorities extend valuable combination due to which
the Training Centre has been able to deliver quality products and has been able to
maintain the quality of Training on sustain basis. So far the Training Centre has
conducted about 110 number of courses of different types and has been able to produce
so many Fire Fighters not only for the State of Maharashtra but even for the other States.
ACHIEVEMENT:
This Training Centre has achieved an excellent rating by the Fire Advisor to Govt. of
India, Director General Civil Defence and the Director, National Fire Service College,
who has personally visited the Training Centre. The major achievement of this Training
Centre is - in the year June, 2003 we have been able to commence the Sub-Officers'
course from the National Fire Service College, Ministry of Home Affairs, Govt. of India
and Govt. of India had declared the Centre as "Regional Training Centre" to cater the
need of neighbouring States.
FUTURE PLAN:
A proposal is approved by Govt. of India for according the permission for re-
appropriation of grants received under the 11th & 12th Finance Commission for the
utilization of the physical infrastructure of the State Fire Service Academy by raising
atleast a 7 storied buildings accommodating 50 hostel rooms, 4 class-rooms, 3
Conference Rooms, good Canteen & Cafeteria, which can house the Modern Fire
appliances. The work of this project on deposit contribution basis has been given to
MMRDA and Govt. of Maharashtra has already paid about Rs.10.82 crore to MMRDA
for this project. The University of Mumbai has already agreed in principle to commence a
full-fledge degree course of B.Sc. (Fire Technology) at par with the National Fire Service
College.
LONG-TERM PLAN:
With a clear vision and mission and with a intention to address the need of State to
produce the required skill set and knowledge set, manpower to cope up with likely
natural and man-made disasters, the State may have to cope up with.
SHORT-TERM PLAN:
As a possible action plan is to create atleast 8 to 10 Specialized Search & Rescue Teams
to cope up with Natural Disasters such as earthquake, landslides, building collapse etc.
The Training Center is striving to create the Teams for the spills Disasters such as Oil
spills and hazardous industrial accidents & Road, Rail accidents.