Wago-I/O-System 750: Manual
Wago-I/O-System 750: Manual
Wago-I/O-System 750: Manual
WAGO-I/O-SYSTEM 750
750-450
4 AI RTD
4-Channel Analog Input Module for Resistance
Sensors
Version 1.2.0
2 WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Hansastraße 27
D-32423 Minden
E-Mail: info@wago.com
Web: www.wago.com
Technical Support
E-Mail: support@wago.com
Every conceivable measure has been taken to ensure the accuracy and
completeness of this documentation. However, as errors can never be fully
excluded, we always appreciate any information or suggestions for improving the
documentation.
E-Mail: documentation@wago.com
We wish to point out that the software and hardware terms as well as the
trademarks of companies used and/or mentioned in the present manual are
generally protected by trademark or patent.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Table of Contents 3
750-450 4 AI RTD
Table of Contents
1 Notes about this Documentation .............................................................6
1.1 Validity of this Documentation.................................................................6
1.2 Revision History......................................................................................6
1.3 Copyright ................................................................................................6
1.4 Symbols .................................................................................................7
1.5 Number Notation ....................................................................................8
1.6 Font Conventions ...................................................................................8
2 Important Notes ........................................................................................9
2.1 Legal Bases............................................................................................9
2.1.1 Subject to Changes ............................................................................9
2.1.2 Personnel Qualifications ....................................................................9
2.1.3 Use of the 750 Series in Compliance with Underlying Provisions ....... 9
2.1.4 Technical Condition of Specified Devices......................................... 10
2.1.4.1 Disposal ......................................................................................10
2.1.4.1.1 Electrical and Electronic Equipment ........................................ 10
2.1.4.1.2 Packaging ...............................................................................11
2.2 Safety Advice (Precautions) ................................................................. 12
3 Device Description ..................................................................................14
3.1 View .....................................................................................................16
3.2 Connectors ...........................................................................................17
3.2.1 Data Contacts/Local Bus.................................................................. 17
3.2.2 Power Jumper Contacts/Field Supply .............................................. 18
3.2.3 Push-in CAGE CLAMP® Connectors ................................................ 19
3.3 Display Elements ..................................................................................21
3.4 Operating Elements ..............................................................................22
3.5 Schematic Diagram ..............................................................................22
3.6 Technical Data .....................................................................................23
3.6.1 Device Data .....................................................................................23
3.6.2 Power Supply ...................................................................................23
3.6.3 Communication ................................................................................23
3.6.4 Inputs ...............................................................................................24
3.6.5 Measuring Accuracy at 25°C ............................................................ 24
3.6.6 Connection Type .............................................................................. 26
3.6.7 Climatic Environmental Conditions ................................................... 26
3.7 Approvals .............................................................................................27
3.8 Standards and Guidelines .................................................................... 28
4 Process Image.........................................................................................29
4.1 Overview ..............................................................................................29
4.2 Control and Status Bytes ...................................................................... 30
4.3 Process Data ........................................................................................32
4.3.1 Overview of Sensor Types ............................................................... 32
4.3.2 Pt100 (IEC 751), ID 0 ....................................................................... 33
4.3.2.1 Standard Format ......................................................................... 33
4.3.2.2 S5-FB250 Format ........................................................................ 34
4.3.3 Ni100 (DIN 43760), ID 1 ................................................................... 35
Manual
Version 1.2.0
4 Table of Contents WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
4.3.3.1 Standard Format ......................................................................... 35
4.3.3.2 S5-FB250 Format ........................................................................ 36
4.3.4 Pt1000 (IEC 751), ID 2 ..................................................................... 37
4.3.4.1 Standard Format ......................................................................... 37
4.3.4.2 S5-FB250 Format ........................................................................ 38
4.3.5 Pt500 (IEC 751), ID 3 ....................................................................... 39
4.3.5.1 Standard Format ......................................................................... 39
4.3.5.2 S5-FB250 Format ........................................................................ 40
4.3.6 Pt200 (IEC 751), ID 4 ....................................................................... 41
4.3.6.1 Standard Format ......................................................................... 41
4.3.6.2 S5-FB250 Format ........................................................................ 42
4.3.7 Ni1000 (TK6180, DIN 43760), ID 5 .................................................. 43
4.3.7.1 Standard Format ......................................................................... 43
4.3.7.2 S5-FB250 Format ........................................................................ 44
4.3.8 Ni120 (Minco), ID 6 .......................................................................... 45
4.3.8.1 Standard Format ......................................................................... 45
4.3.8.2 S5-FB250 Format ........................................................................ 46
4.3.9 Ni1000 (TK5000), ID 7 ..................................................................... 47
4.3.9.1 Standard Format ......................................................................... 47
4.3.9.2 S5-FB250 Format ........................................................................ 48
4.3.10 Ni1000 (TK6180, DIN 43760), High-Resolution, ID 8 ....................... 49
4.3.10.1 Standard Format ......................................................................... 49
4.3.10.2 S5-FB250 Format ........................................................................ 50
4.3.11 Ni1000 (TK5000), High-Resolution, ID 9 .......................................... 51
4.3.11.1 Standard Format ......................................................................... 51
4.3.11.2 S5-FB250 Format ........................................................................ 52
4.3.12 Pt1000 (IEC 751), High-Resolution, ID 10 ........................................ 53
4.3.12.1 Standard Format ......................................................................... 53
4.3.12.2 S5-FB250 Format ........................................................................ 54
4.3.13 Pt100 (IEC 751), High-Resolution, ID 11 .......................................... 55
4.3.13.1 Standard Format ......................................................................... 55
4.3.13.2 S5-FB250 Format ........................................................................ 56
4.3.14 Potentiometer, ID 13 ........................................................................ 57
4.3.14.1 Standard Format ......................................................................... 57
4.3.14.2 S5-FB250 Format ........................................................................ 58
4.3.15 Resistance Measurement 1, 0 Ohm … 5.0 kOhm, ID 14 .................. 59
4.3.15.1 Standard Format ......................................................................... 59
4.3.15.2 S5-FB250 Format ........................................................................ 60
4.3.16 Resistance Measurement 2, 0 Ohm … 1.2 kOhm, ID 15 .................. 61
4.3.16.1 Standard Format ......................................................................... 61
4.3.16.2 S5-FB250 Format ........................................................................ 62
5 Mounting.................................................................................................. 63
5.1 Mounting Sequence..............................................................................63
5.2 Inserting and Removing Devices .......................................................... 64
5.2.1 Inserting the I/O Module ................................................................... 64
5.2.2 Removing the I/O Module ................................................................ 65
6 Connect Devices .....................................................................................66
6.1 Connecting a Conductor to the Push-in CAGE CLAMP® ...................... 66
6.2 Connection Examples ........................................................................... 67
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Table of Contents 5
750-450 4 AI RTD
6.2.1 4 × 2 Wires.......................................................................................67
6.2.2 4 × 3 Wires.......................................................................................68
6.2.3 4 × 4 Wires.......................................................................................69
6.2.4 4 × 3 Wires, Potentiometer............................................................... 70
7 Commissioning .......................................................................................71
7.1 Parameterization with WAGO-I/O-CHECK............................................ 71
7.1.1 Parameterization Dialog ................................................................... 73
7.1.1.1 Toolbar ........................................................................................73
7.1.1.1.1 Main Menu .............................................................................. 74
7.1.1.1.2 Application Menu .................................................................... 75
7.1.1.2 Navigation Area ........................................................................... 76
7.1.1.3 Application Area .......................................................................... 77
7.1.1.3.1 Importing/Exporting Parameter File ......................................... 78
7.1.1.3.2 Menu Item "Settings" .............................................................. 79
7.1.1.3.3 Menu Item "Scaling" ................................................................ 84
7.1.1.3.4 Application Example of Scaling ............................................... 86
7.1.1.3.5 Menu Item "Calibration" .......................................................... 88
7.1.1.3.5.1 Application example for calibration ..................................... 90
7.1.1.4 Status Bar ...................................................................................92
7.2 Configuration and Parameterization using a GSD File with
PROFIBUS DP and PROFINET IO ....................................................... 93
8 Diagnostics..............................................................................................94
8.1 Error Response ....................................................................................94
9 Appendix ................................................................................................. 97
9.1 Configuration and Parameterization using a GSD File with
PROFIBUS DP and PROFINET IO ....................................................... 97
9.1.1 Configuration 4 AI RTD .................................................................... 97
9.1.1.1 PROFIBUS DP (750-333, 750-833) Fieldbus Coupler
PROFINET IO (750-370) Fieldbus Coupler ................................. 97
9.1.1.2 PROFINET IO (750-375, 750-377) Fieldbus Coupler................... 97
9.1.2 Parameterization 4 AI RTD .............................................................. 98
9.1.2.1 All PROFIBUS DP and PROFINET IO Fieldbus Couplers ......... 101
9.1.2.2 PROFIBUS DP (750-333, 750-833) Fieldbus Coupler ............... 102
9.1.2.3 PROFINET IO (750-370, 750-375, 750-377) Fieldbus Coupler .. 102
10 Use in Hazardous Environments ......................................................... 104
10.1 Marking Configuration Examples ........................................................ 105
10.1.1 Marking for Europe According to ATEX and IECEx ........................ 105
10.1.2 Marking for the United States of America (NEC) and
Canada (CEC) ............................................................................... 109
10.2 Installation Regulations....................................................................... 112
10.2.1 Special Notes Regarding Explosion Protection .............................. 112
10.2.2 Special Notes Regarding ANSI/ISA Ex .......................................... 114
List of Figures ................................................................................................ 115
List of Tables .................................................................................................. 116
Manual
Version 1.2.0
6 Notes about this Documentation WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
The I/O module 750-450 shall only be installed and operated according to the
instructions in this manual and in the manual for the used fieldbus coupler or
controller.
1.3 Copyright
This Manual, including all figures and illustrations, is copyright-protected. Any
further use of this Manual by third parties that violate pertinent copyright
provisions is prohibited. Reproduction, translation, electronic and phototechnical
filing/archiving (e.g., photocopying) as well as any amendments require the
written consent of WAGO Kontakttechnik GmbH & Co. KG, Minden, Germany.
Non-observance will involve the right to assert damage claims.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Notes about this Documentation 7
750-450 4 AI RTD
1.4 Symbols
Personal Injury!
Indicates a high-risk, imminently hazardous situation which, if not avoided, will
result in death or serious injury.
Personal Injury!
Indicates a moderate-risk, potentially hazardous situation which, if not avoided,
could result in death or serious injury.
Personal Injury!
Indicates a low-risk, potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
Damage to Property!
Indicates a potentially hazardous situation which, if not avoided, may result in
damage to property.
Important Note!
Indicates a potential malfunction which, if not avoided, however, will not result in
damage to property.
Manual
Version 1.2.0
8 Notes about this Documentation WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Additional Information:
Refers to additional information which is not an integral part of this
documentation (e.g., the Internet).
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Important Notes 9
750-450 4 AI RTD
2 Important Notes
This section includes an overall summary of the most important safety
requirements and notes that are mentioned in each individual section. To protect
your health and prevent damage to devices as well, it is imperative to read and
carefully follow the safety guidelines.
All changes to the coupler or controller should always be carried out by qualified
personnel with sufficient skills in PLC programming.
The devices have been developed for use in an environment that meets the IP20
protection class criteria. Protection against finger injury and solid impurities up to
12.5 mm diameter is assured; protection against water damage is not ensured.
Unless otherwise specified, operation of the devices in wet and dusty
environments is prohibited.
Manual
Version 1.2.0
10 Important Notes WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
prototype test certificate must be obtained that confirms the correct installation of
the system in a housing or switch cabinet.
• Repairs,
• Changes to the hardware or software that are not described in the
operating instructions,
• Improper use of the components.
Further details are given in the contractual agreements. Please send your
request for modified and new hardware or software configurations directly to
WAGO Kontakttechnik GmbH & Co. KG.
2.1.4.1 Disposal
Electrical and electronic equipment contain materials and substances that can be
harmful to the environment and health. Electrical and electronic equipment must
be disposed of properly after use.
WEEE 2012/19/EU applies throughout Europe. Directives and laws may vary
nationally.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Important Notes 11
750-450 4 AI RTD
Environmentally friendly disposal benefits health and protects
the environment from harmful substances in electrical and
electronic equipment.
• Observe national and local regulations for the disposal of electrical and
electronic equipment.
2.1.4.1.2 Packaging
Manual
Version 1.2.0
12 Important Notes WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Important Notes 13
750-450 4 AI RTD
Manual
Version 1.2.0
14 Device Description WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
3 Device Description
The I/O module 750-450 (4 AI RTD) measures resistance at field level or
evaluates platinum or nickel resistance sensors.
The resistance values are converted into temperature values. A microprocessor
in the I/O module linearizes the measured resistance values and converts them
into a numeric value proportional to the temperature of the selected resistance
sensor.
The WAGO-I/O-CHECK commissioning tool can be used to set the required
operating mode.
The I/O module has four input channels, providing a direct connection to 2-/ 3-or
4-wire resistance sensors.
The sensors are connected to the Push-in CAGE CLAMP® terminals
+R1/−R1 … +R4L/−R4L.
The assignment of the connections is described in the “Connectors” section.
Connection examples are shown in section “Connect Devices” > … >
“Connection Example(s)”.
The operating status of the channels is indicated by a green status LED per
channel.
A red error LED per channel indicates a wire break, a short circuit or that the
signal is outside the measuring range.
The meaning of the LEDs is described in the “Display Elements” section.
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node.
An arrangement in groups within the group of potentials is not necessary.
The 750-450 module can be used with the fieldbus couplers and controllers of
the WAGO-I/O-SYSTEM 750 of the specified version or higher listed in the
“Compatibility list” table.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Device Description 15
750-450 4 AI RTD
Table 4: Compatibility List 750-450
Bus System Fieldbus Coupler/Controller Item No.. Firmware Version
750-375 03
PROFINET Fieldbus coupler
750-377 03
Fieldbus coupler 750-333 17
PROFIBUS
Programmable fieldbus controller 750-833 16
750-342 18
Fieldbus coupler 750-352 04
750-362 02
750-841 20
750-842 19
750-843 03
750-852 01
750-862 02
750-871 08
ETHERNET 750-872 04
Programmable fieldbus controller
750-873 04
750-880 04
750-881 04
750-882 04
750-885 04
750-890 02
750-891 02
Fieldbus controller PFC100 750-810x 04
Fieldbus controller PFC200 750-82xx 01
Fieldbus coupler 750-306 4L
DeviceNet ECO Fieldbus coupler 750-346 11
Programmable fieldbus controller 750-806 11
750-337 20
Fieldbus coupler
750-338 20
750-347 10
CANopen ECO Fieldbus coupler
750-348 10
750-837 15
Programmable fieldbus controller
750-838 15
750-315/300-000 01
Fieldbus coupler
® 750-316/300-000 01
Modbus
750-815/300-000 01
Programmable Fieldbus controller
750-816/300-000 01
EtherCat Fieldbus coupler 750-354 03
SERCOS III Fieldbus coupler 750-351 04
CC-Link Fieldbus coupler 750-310 03
BACnet Programmable Fieldbus controller 750-831 03
KNX Programmable Fieldbus controller 750-889 07
The field voltage and the system voltage are electrically isolated from each other.
Manual
Version 1.2.0
16 Device Description WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
3.1 View
Figure 1: View
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Device Description 17
750-450 4 AI RTD
3.2 Connectors
Manual
Version 1.2.0
18 Device Description WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
The I/O module 750-450 has 2 self-cleaning power jumper contacts that supply
and transmit power for the field side. The contacts on the left side of the I/O
module are designed as blade contacts and those on the right side as spring
contacts.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Device Description 19
750-450 4 AI RTD
®
Figure 4: Push-in CAGE CLAMP Connectors
®
Table 7: Legend for Figure "Push-in CAGE CLAMP Connectors" – 4-Channel, 2-Wires
Channel Designation Connector Function
+R1 1 Sensor 1: +R
−R1 9 Sensor 1: −R
1
+R1L 2 Not used*
−R1L 10 Not used*
+R2 3 Sensor 2: +R
−R2 11 Sensor 2: −R
2
+R2L 4 Not used*
−R2L 12 Not used*
+R3 5 Sensor 3: +R
−R3 13 Sensor 3: −R
3
+R3L 6 Not used*
−R3L 14 Not used*
+R4 7 Sensor 4: +R
−R4 15 Sensor 4: −R
4
+R4L 8 Not used*
−R4L 16 Not used*
* contacting from outside prohibited
Manual
Version 1.2.0
20 Device Description WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
®
Table 8: Legend for Figure "Push-in CAGE CLAMP Connectors" – 4-Channel, 3-Wires
Channel Designation Connector Function
+R1 1 Sensor 1: +R
−R1 9 Sensor 1: −R
1
+R1L 2 Sensor 1: +RL
−R1L 10 Not used*
+R2 3 Sensor 2: +R
−R2 11 Sensor 2: −R
2
+R2L 4 Sensor 2: +RL
−R2L 12 Not used*
+R3 5 Sensor 3: +R
−R3 13 Sensor 3: −R
3
+R3L 6 Sensor 3: +RL
−R3L 14 Not used*
+R4 7 Sensor 4: +R
−R4 15 Sensor 4: −R
4
+R4L 8 Sensor 4: +RL
−R4L 16 Not used*
* contacting from outside prohibited
®
Table 9: Legend for Figure "Push-in CAGE CLAMP Connectors" – 4-Channel, 4-Wires
Channel Designation Connector Function
+R1 1 Sensor 1: +R
−R1 9 Sensor 1: −R
1
+R1L 2 Sensor 1: +RL
−R1L 10 Sensor 1: −RL
+R2 3 Sensor 2: +R
−R2 11 Sensor 2: −R
2
+R2L 4 Sensor 2: +RL
−R2L 12 Sensor 2: −RL
+R3 5 Sensor 3: +R
−R3 13 Sensor 3: −R
3
+R3L 6 Sensor 3: +RL
−R3L 14 Sensor 3: −RL
+R4 7 Sensor 4: +R
−R4 15 Sensor 4: −R
4
+R4L 8 Sensor 4: +RL
−R4L 16 Sensor 4: −RL
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Device Description 21
750-450 4 AI RTD
Manual
Version 1.2.0
22 Device Description WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Device Description 23
750-450 4 AI RTD
3.6.3 Communication
Table 13: Technical Data – Communication
Data width, internal (local bus)
4-channel operation 4 x 16 bits data,
4 x 8 bits control/status (optional)
Manual
Version 1.2.0
24 Device Description WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
3.6.4 Inputs
Table 14: Technical Data – Inputs
Number of inputs 4 (parameterizable)
Sensor types Pt100 (IEC 751)*,
Ni100 (DIN 43760),
Pt1000 (IEC 751),
Pt500 (IEC 751),
Pt200 (IEC 751),
Ni120 (Minco),
Ni1000 (TK6180, DIN 43760),
Ni1000 (TK5000),
Potentiometer (Rmax = 5000 Ω),
Resistance measurement 1 (0 Ω … 5000 Ω),
Resistance measurement 2 (0 Ω … 1200 Ω)
Connection types 2/3/4 wires
Measuring current ≤ 350 μA per measuring circuit
Conversion time
2-/4-wire ≤ 100 ms per channel
3-wire ≤ 200 ms per channel
Resolution 16 bits
Temperature coefficient ≤ ±5 ppm/K
* Default
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Device Description 25
750-450 4 AI RTD
Table 16: Technical Data – Measuring Accuracy at 25°C Ambient Air Temperature, 3 Wires
Pt100 (IEC 751)* −200 °C… 850 °C ≤ ±0.6 K
−50 °C … 150 °C ≤ ±0,6 K
Pt200 (IEC 751) −200 °C … 850 °C ≤ ±0.5 K
Pt500 (IEC 751) −200 °C … 850 °C ≤ ±0.5 K
Pt1000 (IEC 751) −200 °C … 850 °C ≤ ±0.2 K
−50 °C … 150 °C ≤ ±0.2 K
Ni100 (DIN 43760) −60 °C … 250 °C ≤ ±0.4 K
Ni120 (Minco) −80 °C … 260 °C ≤ ±0.3 K
Ni1000 (TK5000 (Landis & Staefa)) −60 °C … 250 °C ≤ ±0.2 K
−50 °C … 150 °C ≤ ±0.2 K
Ni1000 (TK6180, DIN 43760), −60 °C … 250 °C ≤ ±0.2 K
−50 °C … 150 °C ≤ ±0.2 K
Potentiometer 0 % … 100 % ≤ ±0.1 %
Resistance measurement 1 0 Ω … 5000 Ω ≤ ±0.7 Ω
Resistance measurement 2 0 Ω … 1200 Ω ≤ ±0.7 Ω
* Default
Table 17: Technical Data – Measuring Accuracy at 25°C Ambient Air Temperature, 4 Wires
Pt100 (IEC 751)* −200 °C… 850 °C ≤ ±0.6 K
−50 °C … 150 °C ≤ ±0,6 K
Pt200 (IEC 751) −200 °C … 850 °C ≤ ±0.5 K
Pt500 (IEC 751) −200 °C … 850 °C ≤ ±0.3 K
Pt1000 (IEC 751) −200 °C … 850 °C ≤ ±0.2 K
−50 °C … 150 °C ≤ ±0.2 K
Ni100 (DIN 43760) −60 °C … 250 °C ≤ ±0.3 K
Ni120 (Minco) −80 °C … 260 °C ≤ ±0.3 K
Ni1000 (TK5000 (Landis & Staefa)) −60 °C … 250 °C ≤ ±0.2 K
−50 °C … 150 °C ≤ ±0.2 K
Ni1000 (TK6180, DIN 43760), −60 °C … 250 °C ≤ ±0.2 K
−50 °C … 150 °C ≤ ±0.2 K
Resistance measurement 1 0 Ω … 5000 Ω ≤ ±0.3 Ω
Resistance measurement 2 0 Ω … 1200 Ω ≤ ±0.3 Ω
* Default
Manual
Version 1.2.0
26 Device Description WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Device Description 27
750-450 4 AI RTD
3.7 Approvals
The following approvals have been granted to 750-450 I/O modules:
Conformity Marking
UL508
The following Ex approvals have been granted to the basic version of 750-450
I/O modules:
The following ship approvals have been granted to the basic version of 750-450
I/O modules:
DNV GL
[Temperature: B, Humidity: A, Vibration: B, EMC: B,
Enclosure: A]
Manual
Version 1.2.0
28 Device Description WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
and to EN 61131-2
and to EN 61131-2
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 29
750-450 4 AI RTD
4 Process Image
4.1 Overview
Manual
Version 1.2.0
30 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 31
750-450 4 AI RTD
Manual
Version 1.2.0
32 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Table 25: Process Data – Overview of Standard Format and S5-FB250 Format
View
Two's complement/
Sensor Standar S5-FB250 Format
ID Measuring range Amount sign
type d
Resolu- Raw value Resolu- Raw value
tion range tion range
0 Pt100 IEC 751 −200 °C … 850 °C 0.1 °C −2000 … 8500 0.5 °C −400 … 1700
DIN
1 Ni100 −60 °C … 250 °C 0.1 °C −600 … 2500 0.5 °C −120 … 500
43760
2 Pt1000 IEC 751 −200 °C … 850 °C 0.1 °C −2000 … 8500 0.5 °C −400 … 1700
3 Pt500 IEC 751 −200 °C … 850 °C 0.1 °C −2000 … 8500 0.5 °C −400 … 1700
4 Pt200 IEC 751 −200 °C … 850 °C 0.1 °C −2000 … 8500 0.5 °C −400 … 1700
TK6180
5 Ni1000 DIN −60 °C … 250 °C 0.1 °C −600 … 2500 0.5 °C −120 … 500
43760
6 Ni120 Minco −80 °C … 260 °C 0.1 °C −800 … 2600 0.5 °C −160 … 520
TK5000
7 Ni1000 (Landis + −60 °C … 250 °C 0.1 °C −600 … 2500 0.5 °C −120 … 500
Staefa)
TK6180
8 Ni1000 DIN −50 °C … 150 °C 0.01 °C −5000 … 15000 0.05 °C −1000 … 3000
43760
TK5000
9 Ni1000 (Landis + −50 °C … 150 °C 0.01 °C −5000 … 15000 0.05 °C −1000 … 3000
Staefa)
10 Pt1000 IEC 751 −50 °C … 150 °C 0.01 °C −5000 … 15000 0.05 °C −1000 … 3000
11 Pt100 * IEC 751 −50 °C … 150 °C 0.01 °C −5000 … 15000 0.05 °C −1000 … 3000
12 Reserved for expansions
13 Potentiometer – 0 % … 100 % 0.005 % 0 … 20000 0.05 % 0 … 2000
Resistance
14 measurement – 0 Ohm … 5 kOhm 0.2 Ohm 0 … 25000 4 Ohm 0 … 1250
range 1
Resistance
15 measurement – 0 Ohm … 1.2 kOhm 0.05 Ohm 0 … 24000 0.5 Ohm 0 … 2400
range 2
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 33
750-450 4 AI RTD
The "Pt100 (IEC 751)" setting is used by the I/O module to convert the resistance
measured values from Pt100 sensors (IEC 751) to temperature values and
outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.1 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x03E8 (dec. 1000).
The maximum numeric range in the two's complement representation that can be
displayed with one word ranges from −32768 to +32767. The numeric range that
is used depends on the set sensor type and on the resolution for the process
value. With the "Pt100 (IEC 751)" setting, the possible numeric range
corresponds to the temperature range of −200 °C to +850 °C, meaning it covers
a range of −2000 to +8500.
Manual
Version 1.2.0
34 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Pt100 (IEC 751)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Pt100 sensors (IEC 751) and
outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 35
750-450 4 AI RTD
The "Ni100 (DIN 43760)" setting is used by the I/O module to convert the
resistance measured values from Ni100 sensors (DIN 43760) to temperature
values and outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.1 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x03E8 (dec. 1000). The maximum range in the two's complement
representation that can be displayed with one word ranges from -32768 to
+32767. The numeric range that is used depends on the set sensor type and on
the resolution for the process value. With the "Ni100 (DIN 43760)" setting, the
possible numeric range corresponds to the temperature range of −60 °C to +250
°C, meaning it covers a range of −600 to +2500.
Manual
Version 1.2.0
36 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Ni100 (DIN 43760)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Ni100 sensors (DIN 43760)
and outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 37
750-450 4 AI RTD
The "Pt1000 (IEC 751)" setting is used by the I/O module to convert the
resistance measured values from Pt1000 sensors (IEC 751) to temperature
values and outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.1 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x03E8 (dec. 1000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value. With the "Pt1000 (IEC 751)"
setting, the possible numeric range corresponds to the temperature range of
−200 °C to +850 °C, meaning it covers a range of −2000 to +8500.
Manual
Version 1.2.0
38 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Pt1000 (IEC 751)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Pt1000 sensors (IEC 751)
and outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 39
750-450 4 AI RTD
The "Pt500 (IEC 751)" setting is used by the I/O module to convert the resistance
measured values from Pt500 sensors (IEC 751) to temperature values and
outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.1 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x03E8 (dec. 1000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value. With the "Pt500 (IEC 751)"
setting, the possible numeric range corresponds to the temperature range of
−200 °C to +850 °C, meaning it covers a range of −2000 to +8500.
Manual
Version 1.2.0
40 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Pt500 (IEC 751)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Pt500 sensors (IEC 751) and
outputs them as temperature values. The temperature values are displayed at a
resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 41
750-450 4 AI RTD
The "Pt200 (IEC 751)" setting is used by the I/O module to convert the resistance
measured values from Pt200 sensors (IEC 751) to temperature values and
outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.1 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x03E8 (dec. 1000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value. With the "Pt200 (IEC 751)"
setting, the possible numeric range corresponds to the temperature range of
−200 °C to +850 °C, meaning it covers a range of −2000 to +8500.
Manual
Version 1.2.0
42 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Pt200 (IEC 751)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Pt200 sensors (IEC 751) and
outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 43
750-450 4 AI RTD
The "Ni1000 (TK6180, DIN 43760)" setting is used by the I/O module to convert
the resistance measured values from Ni1000 sensors (TK6180, DIN 43760) to
temperature values and outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.1 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x03E8 (dec. 1000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value. With the "Ni1000 (TK 6180, DIN
43760)" setting, the possible numeric range corresponds to the temperature
range of −60 °C to +250 °C, meaning it covers a range of −600 to +2500.
.
Manual
Version 1.2.0
44 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Ni1000 (TK6180, DIN 43760)" and activated S5-FB250 format,
the I/O module converts the resistance measured values of Ni1000 sensors
(TK6180, DIN 43760) and outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 45
750-450 4 AI RTD
The "Ni120 (Minco)" setting is used by the I/O module to convert the resistance
measured values from Ni120 sensors (Minco) to temperature values and outputs
the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.1 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x03E8 (dec. 1000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value. With the "Ni120 (Minco)" setting,
the possible numeric range corresponds to the temperature range of −80 °C to
+260 °C, meaning it covers a range of −800 to +2600.
Manual
Version 1.2.0
46 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Ni120 (Minco)" and activated S5-FB250 format, the I/O module
converts the resistance measured values of Ni120 sensors (Minco) and outputs
them as temperature values. The temperature values are displayed at a
resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 47
750-450 4 AI RTD
The "Ni1000 (TK5000)" setting is used by the I/O module to convert the
resistance measured values from Ni1000 sensors (TK5000) to temperature
values and outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.1 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x03E8 (dec. 1000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value. With the "Ni1000 (TK 5000)"
setting, the possible numeric range corresponds to the temperature range of −60
°C to +250 °C, meaning it covers a range of −600 to +2500.
Manual
Version 1.2.0
48 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Ni1000 (TK5000)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Ni1000 sensors (TK5000)
and outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 49
750-450 4 AI RTD
The "Ni1000 (TK 6180, DIN 43760)" setting is used by the I/O module to convert
the resistance measured values from Ni1000 sensors (TK 6180, DIN 43760) to
temperature values and outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.01 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x2710 (dec. 1000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value.With the "Ni1000 (TK6180, DIN
43760)" setting, the possible numeric range corresponds to the temperature
range of −50 °C to +150 °C, meaning it covers a range of −5000 to +15000.
Manual
Version 1.2.0
50 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Ni1000 (TK6180, DIN 43760)" and activated S5-FB250 format,
the I/O module converts the resistance measured values of Ni1000 sensors (DIN
43760) and outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.05 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 51
750-450 4 AI RTD
The "Ni1000 (TK 5000)" setting is used by the I/O module to convert the
resistance measured values from Ni1000 sensors (TK 5000) to temperature
values and outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.01 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x2710 (dec. 1000). The maximum range in the two's complement
representation that can be displayed with one word ranges from -32768 to
+32767. The numeric range that is used depends on the set sensor type and on
the resolution for the process value. With the "Ni1000 (TK 5000)" setting, the
possible numeric range corresponds to the temperature range of −50 °C to +150
°C, meaning it covers a range of −5000 to +15000.
Manual
Version 1.2.0
52 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Ni1000 (TK5000)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Ni1000 sensors (TK5000)
and outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.05 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 53
750-450 4 AI RTD
The "Pt1000 (IEC 751)" setting is used by the I/O module to convert the
resistance measured values from Pt1000 sensors (IEC 751) to temperature
values and outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.01 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x2710 (dec. 1000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value. With the "Pt1000 (IEC 751)"
setting, the possible numeric range corresponds to the temperature range of −50
°C to +150 °C, meaning it covers a range of −5000 to +15000.
Manual
Version 1.2.0
54 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Pt1000 (IEC 751)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Pt1000 sensors (IEC 751)
and outputs them as temperature values.
The temperature values are displayed at a resolution of 1 digit per 0.05 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 55
750-450 4 AI RTD
The "Pt100 (IEC 751)" setting is used by the I/O module to convert the resistance
measured values from Pt100 sensors (IEC 751) to temperature values and
outputs the results in degrees Celsius.
The temperature values are displayed with a resolution of 1 digit per 0.01 °C in
one word (16 bits). Temperature values below 0 °C are represented in two's
complement binary. As a result, 0°C corresponds to the numeric value 0x0000
and 100°C to 0x2710 (dec. 10000). The maximum numeric range in the two's
complement representation that can be displayed with one word ranges from -
32768 to +32767. The numeric range that is used depends on the set sensor
type and on the resolution for the process value. With the "Pt100 (IEC 751)"
setting, the possible numeric range corresponds to the temperature range of −50
°C to +150 °C, meaning it covers a range of −5000 to +15000.
Manual
Version 1.2.0
56 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Pt100 (IEC 751)" and activated S5-FB250 format, the I/O
module converts the resistance measured values of Pt100 sensors (IEC 751) and
outputs them as temperature values. The temperature values are displayed at a
resolution of 1 digit per 0.05 °C. The status information is depicted in bit 0 to bit 2
and the digitalized measured value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 57
750-450 4 AI RTD
4.3.14 Potentiometer, ID 13
Potentiometer!
The "Potentiometer" sensor type and the corresponding measuring range may
only be used with 3-wire connecting technology.
At the "Potentiometer" setting the I/O module outputs the resistance ratio
between the slider resistance (connections +Rx/+RxL) and the overall resistance
(connections +Rx/−Rx) of the potentiometer connected to the system. The set
values are displayed at a resolution of 1 digit per 0.005 % in one word (16 bits).
The maximum numeric range in the two's complement representation that can be
displayed with one word ranges from −32768 to +32767. The numeric range that
is used depends on the set sensor type and on the resolution for the process
value. With the "Potentiometer" setting, the possible numeric range corresponds
to the defined measuring range of 0 % to 100 %, meaning it covers a range of 0
to +20000.
Manual
Version 1.2.0
58 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
At the "Potentiometer" setting the I/O module outputs the resistance ratio
between the slider resistance (connections +Rx/+RxL) and the overall resistance
(connections +Rx/−Rx) of the potentiometer connected to the system. The
resistance ratio is displayed at a resolution of 1 digit per 0.05 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 59
750-450 4 AI RTD
With the setting "Resistance measurement 1" (0 Ohm ... 5.0 kOhm), the I/O
module outputs the resistance measured values of the sensors directly.
The resistance values are displayed at a resolution of 1 digit per 0.2 Ω in one
word (16-bit). The maximum numeric range in the two's complement
representation that can be displayed with one word ranges from -32768 to
+32767. The numeric range that is used depends on the set sensor type and on
the resolution for the process value. With the "Resistance measurement 1"
setting, the possible numeric range corresponds to the defined measuring range
of 0 Ohm to 5.0 kOhm, meaning it covers a range of 0 to +25000.
Manual
Version 1.2.0
60 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Resistance measurement 1" (0 Ohm ... 5.0 kOhm) and activated
S5-FB250 format, the I/O module outputs the resistance measured values of the
sensors directly.
The resistance values are displayed at a resolution of 1 digit per 4 Ω. The status
information is depicted in bit 0 to bit 2 and the digitalized measured value in bit 3
to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Process Image 61
750-450 4 AI RTD
With the setting "Resistance measurement 2" (0 Ohm to 1.2 kOhm), the I/O
module outputs the resistance measured values of the sensors directly.
The resistance values are displayed at a resolution of 1 digit per 0.05 Ω in one
word (16-bit). The maximum numeric range in the two's complement
representation that can be displayed with one word ranges from -32768 to
+32767. The numeric range that is used depends on the set sensor type and on
the resolution for the process value. With the "Resistance measurement 2"
setting, the possible numeric range corresponds to the defined measuring range
of 0 Ohm to 1.2 kOhm, meaning it covers a range of 0 to 24000.
Manual
Version 1.2.0
62 Process Image WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
With the setting "Resistance measurement 2" (0 Ohm ... 1.2 kOhm) and activated
S5-FB250 format, the I/O module outputs the resistance measured values of the
sensors directly.
The resistance values are displayed at a resolution of 1 digit per 0.5 Ω. The
status information is depicted in bit 0 to bit 2 and the digitalized measured value
in bit 3 to bit 15.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Mounting 63
750-450 4 AI RTD
5 Mounting
5.1 Mounting Sequence
Fieldbus couplers, controllers and I/O modules of the WAGO-I/O-SYSTEM 750
are snapped directly on a carrier rail in accordance with the European standard
EN 60175 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler or controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Manual
Version 1.2.0
64 Mounting WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
2. Press the I/O module into the assembly until the I/O module snaps into the
carrier rail.
With the I/O module snapped in place, the electrical connections for the data
contacts and power jumper contacts (if any) to the fieldbus coupler or controller
or to the previous or possibly subsequent I/O module are established.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Mounting 65
750-450 4 AI RTD
Electrical connections for data or power jumper contacts are disconnected when
removing the I/O module.
Manual
Version 1.2.0
66 Connect Devices WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
6 Connect Devices
6.1 Connecting a Conductor to the Push-in CAGE
CLAMP®
The Push-in CAGE CLAMP® connection is appropriate for solid, stranded and
finely stranded conductors.
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
Terminate both solid and stranded or ferruled conductors by simply pushing them
in - no tool required. For all other types of conductors, Push-in CAGE CLAMP®
must be opened for connection with an operating tool with a 2.5 mm blade (order
no. 210-719).
1. To open the Push-in CAGE CLAMP® insert the actuating tool into the
opening above the connection.
3. To close the Push-in CAGE CLAMP® simply remove the tool - the
conductor is then clamped firmly in place.
®
Figure 10: Connecting a Conductor to a Push-in CAGE CLAMP
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Connect Devices 67
750-450 4 AI RTD
6.2.1 4 × 2 Wires
Table 56: Connection Terminals, Functions and Measuring Circuits, 4-Channel, 2 Wires
Termination Chann Function Description Measuring
el circuit
Measuring current output and
1 +R1
measuring voltage input (+)
2 +R1L Not used
1 1
Measuring current return line and
9 −R1
measuring voltage input (−)
10 −R1L Not used
Measuring current output and
3 +R2
measuring voltage input (+)
4 +R2L Not used
2 2
Measuring current return line and
11 −R2
measuring voltage input (−)
12 −R2L Not used
Measuring current output and
5 +R3
measuring voltage input (+)
6 +R3L Not used
3 3
Measuring current return line and
13 −R3
measuring voltage input (−)
14 −R3L Not used
Measuring current output and
7 +R4
measuring voltage input (+)
8 +R4L Not used
4 4
Measuring current return line and
15 −R4
measuring voltage input (−)
16 −R4L Not used
Manual
Version 1.2.0
68 Connect Devices WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
6.2.2 4 × 3 Wires
Table 57: Connection Terminals, Functions and Measuring Circuits, 4-Channel, 3 Wires
Termination Chann Function Description Measuring
el circuit
Measuring current output and
1 +R1
measuring voltage input (+)
Measuring voltage input for line
2 +R1L
1 resistance (−) 1
Measuring current return line and
9 −R1
measuring voltage input (−)
10 −R1L Not used
Measuring current output and
3 +R2
measuring voltage input (+)
Measuring voltage input for line
4 +R2L
2 resistance (−) 2
Measuring current return line and
11 −R2
measuring voltage input (−)
12 −R2L Not used
Measuring current output and
5 +R3
measuring voltage input (+)
Measuring voltage input for line
6 +R3L
3 resistance (−) 3
Measuring current return line and
13 −R3
measuring voltage input (−)
14 −R3L Not used
Measuring current output and
7 +R4
measuring voltage input (+)
Measuring voltage input for line
8 +R4L
4 resistance (−) 4
Measuring current return line and
15 −R4
measuring voltage input (−)
16 −R4L Not used
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Connect Devices 69
750-450 4 AI RTD
6.2.3 4 × 4 Wires
Table 58: Connection Terminals, Functions and Measuring Circuits, 4-Channel, 4 Wires
Termination Channe Function Description Measuring
l circuit
1 +R1 Measuring current output (+)
2 +R1L Measuring voltage input (+)
1 1
9 −R1 Measuring current return line (−)
10 −R1L Measuring voltage input (−)
3 +R2 Measuring current output (+)
4 +R2L Measuring voltage input (+)
2 2
11 −R2 Measuring current return line (−)
12 −R2L Measuring voltage input (−)
5 +R3 Measuring current output (+)
6 +R3L Measuring voltage input (+)
3 3
13 −R3 Measuring current return line (−)
14 −R3L Measuring voltage input (−)
7 +R4 Measuring current output (+)
8 +R4L Measuring voltage input (+)
4 4
15 −R4 Measuring current return line (−)
16 −R4L Measuring voltage input (−)
Manual
Version 1.2.0
70 Connect Devices WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 71
750-450 4 AI RTD
7 Commissioning
7.1 Parameterization with WAGO-I/O-CHECK
The WAGO-I/O-CHECK software from WAGO Kontakttechnik GmbH & Co. KG
can be used to conveniently and completely configure and parameterize the
I/O module, including:
• Monitoring
WAGO-I/O-CHECK
You can obtain the WAGO-I/O-CHECK software on a CD under Item No. 759-
302. This CD contains all the application program files and an explanation. You
can find a description at the internet page at http://www.wago.com
Manual
Version 1.2.0
72 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
In order to open specific parameterization dialogs for the I/O module, proceed as
follows:
The configuration dialog appears, which forms the basis for the following
description. This forms the basis for the subsequent explanation.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 73
750-450 4 AI RTD
1 Toolbar
2 Navigation bar
3 Application area
4 Status bar
7.1.1.1 Toolbar
The toolbar is divided into the following areas in the parameterization dialog for
the I/O module:
• Main menu
• Application menu
Manual
Version 1.2.0
74 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 75
750-450 4 AI RTD
The application menu is called up via the blue button to the left in the toolbar, and
contains the following buttons:
Manual
Version 1.2.0
76 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
When you click on one of the buttons in the main menu a new window opens,
which also has a navigation section on the left side.
The navigation section for menu item "Settings" contains five buttons.
The navigation sections for menu items "Scaling" and "Calibration" each has four
buttons.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 77
750-450 4 AI RTD
Here, an overview of all of the I/O module channels are displayed individually.
This overview provides information about the number of channels for the I/O
module being used. You can view the measured value, the raw value and the
error status for each channel in this overview.
Manual
Version 1.2.0
78 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Two specific buttons are available to you in the “Settings” and “Scaling” menu
items described below:
Once you have changed the settings and you want to close a dialog, the
following warning message appears:
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 79
750-450 4 AI RTD
In this menu item you can configure the parameters for the module settings under
"Module" in the navigation area at the left.
Manual
Version 1.2.0
80 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Table 64: Menu Item "Settings" > "Module"
Option Description
Process value format
Number format Two's complement representation
Amount/Sign representation
Use the SIEMENS-S5 The SIEMENS-S5 format is enabled. Display of status indicators
format in the bottom three bits:
Bit 0: Overflow. Is Bit 1: Error. Bit 2: Always 0.
set when over- Set for wire
range/under-range break/short circuit (if
(when violation of "Indicate wire
range upper/lower break/short circuit" is
limit is active) active).
The SIEMENS-S5 format is deactivated. Status indicators not
displayed.
Watchdog Timer
Deactivate watchdog The option "Deactivate watchdog timer" is active. The green
timer LEDs remain permanently lit.
The option "Deactivate watchdog time" is deactivated. If no
process data is exchanged with the bus coupler for 100 ms, the
green LEDs go out.
Filter selection
disabled Notch filter deactivated.
50 Hz Notch filter active (50 Hz)
60 Hz Notch filter is active (60 Hz)
50/60 Hz Notch filter is active (50/60 Hz)
You can specify the channel settings for each individual channel under menu
item "Channel 1" to "Channel 4" in the navigation section. The possible settings
are identical for each channel. Therefore, the description of menu item "Channel
1" also applies to the other channels.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 81
750-450 4 AI RTD
Manual
Version 1.2.0
82 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Table 65: Menu Item "Settings"
Option Description
Sensor type selection
Sensor type Ni100 [DIN 43760]
Ni120 [Minco]
−50 °C … 150 °C
Ni1000 [TK 5000
(Landis+Staefa)]
−60 °C … 250 °C You can select these
sensor type for each
−200 C … 850 °C channel.
Pt100 [IEC 751]
−50 °C … 150 °C
Pt200 [IEC 751]
Pt500 [IEC 751]
−200 C … 850 °C
Pt1000 [IEC 751]
−50 C … 150 °C
Potentiometer
Resistance measurement 1
Resistance measurement 2
Selection of connection type
Connection type Disabled Channel is deactivated.
2-wire This channel operates using 2-
wire connection technology.
3-wire This channel operates using 3-
wire connection technology.
4-wire This channel operates using 4-
wire connection technology.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 83
750-450 4 AI RTD
Display of status information (diagnostics functions)
Globally activate Diagnostics functions have been globally activated and are
diagnostics functions displayed in the status byte. For this, at least one of the
following diagnostics function must be activated individually
again.
Diagnostics functions have been globally deactivated.
Display wire break The "Wire break" diagnostics function is active and is displayed
in the status byte.
"Wire break" diagnostics function not displayed.
Display short circuit The "Short circuit" diagnostics function is active and is displayed
in the status byte.
"Short circuit" diagnostics function not displayed.
Display group error The "Group error" (general error) diagnostics function is active
and is displayed in the status byte.
"Group error" diagnostics function not displayed.
Display violation of The "Violation of measuring range upper limit" diagnostics
measuring range upper function is active and is displayed in the status byte.
limit "Violation of measuring range upper limit" diagnostics function
not displayed.
Display violation of The "Violation of measuring range lower limit" diagnostics
measuring range lower function is active and is displayed in the status byte.
limit "Violation of measuring range lower limit" diagnostics function
not displayed.
Specifying User-Defined Limits
Upper limit Here, you can define your own upper limit. This limit is specified on the
basis of the set sensor type in degrees Celsius, as a percentage, or in
Ohms.
Display violation of the The "Violation of upper limit" diagnostics function is active and is
defined upper limit displayed in the status byte. Violation of the limit value that you
have specified is indicated under "Upper Limit".
"Violation of upper limit" diagnostics function not displayed.
Lower limit Here, you can define your own lower limit. This limit is specified on the
basis of the set sensor type in degrees Celsius, as a percentage, or in
Ohms.
Display violation of the The "Violation of lower limit" diagnostics function is active and is
defined lower limit displayed in the status byte. Violation of the limit value that you
have specified is indicated under "Lower Limit".
"Violation of lower limit" diagnostics function not displayed.
Manual
Version 1.2.0
84 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
In this menu item you can assign parameters for the scaling settings.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 85
750-450 4 AI RTD
Table 66: Menu Item "Scaling" > "Channel 1 …4"
Option Description
Line resistance
Line resistance offset Here, specify the line resistance that is to be applied when calculating the
measured values.
Scaling settings
Activate manufacturer Manufacturer scaling is active. Manufacturer scaling is being
scaling applied. This means that you cannot input the individual gain
multiplier, gain divisor or offset.
Manufacturer scaling deactivated.
Activate user scaling User-defined scaling is active. By activating this setting you can
also specify the individual gain multiplier and offset.
User-defined scaling deactivated.
Offset The offset value shifts the zero point of the non-scaled process value
(shift along the Y axis).
Gain multiplier The gain multiplier changes the slope factor for the non-scaled process
value.
Gain divisor The gain divisor determines the resolution for the gain multiplier. The
factory default setting for the gain divisor is 256.
Process value The process value is the resistance/temperature value that is yielded from
the temperature or resistance measurement. Depending on the set sensor
type, the process value is given in °C or Ohm.
The measured values calculated by the I/O module can also be scaled by the
user as an option. A linear equation is applied to the sensor-specific variable for
this:
With:
The values gain multiplier and scaling offset are required to perform user-defined
scaling. When these two factors are input, a scaled process value is yielded as
the result. The gain divisor determines the resolution for the gain multiplier. The
factory default setting for the gain devisor is 256.
Manual
Version 1.2.0
86 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
A description of how you can calculate the scaled process value is given
below. The equation for calculating the scaled process value using the
"Sensor type Pt100 (IEC 751) " setting in the standard format, with the
corresponding variables is:
Example:
((20 °C × 512) / 256) + 20 = 60 °C
Refer to the table below for more sample calculations for the sensor type Pt100
(IEC 751) in the standard format.
Table 67: Examples of Scaled Process Value, Standard Format, Pt100 (IEC 751)
Gain multiplier Scaling offset Scaled process value
in °C at 20 °C* at 30 °C* at 40.2 °C*
256 (1**) 0 20 °C 30 °C 40.2 °C
256 (1**) 10 30 °C 40 °C 50.2 °C
384 (1.5**) 15 45 °C 60 °C 75.3 °C
512 (2**) 20 60 °C 80 °C 100.4 °C
640 (2.5**) 20 70 °C 95 °C 120.5 °C
*) unscaled process value
**) Multiplier (= gain multiplier/gain divisor)
Refer to the table below for more sample calculations for the sensor type Pt100
(IEC 751) in the
S5-FB250 format.
Table 68: Examples of Scaled Process Value, S5-FB250 Format, Pt100 (IEC 751)
Gain multiplier Scaling offset Scaled process value in Ohm
in °C at 20 °C* at 30 °C* at 40.2 °C*
256 (1**) 0 20 °C 30 °C 40 °C
256 (1**) 10 30 °C 40 °C 50 °C
384 (1.5**) 15 45 °C 60 °C 75.5 °C
512 (2**) 20 60 °C 80 °C 100.5 °C
640 (2.5**) 20 70 °C 95 °C 120.5 °C
*) unscaled process value
**) Multiplier (= gain multiplier/gain divisor)
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 87
750-450 4 AI RTD
• Example using Resistance measurement 2 setting
The equation for calculating the scaled process value using the "Sensor type
Resistance measurement 2" setting in the standard format, with the
corresponding variables is:
Example:
((100°Ohm × 384) / 256) + 15 = 165 Ohm
Refer to the table below for more sample calculations for the sensor type
Resistance measurement 2 in the standard format.
Table 69: Examples of Scaled Process Value, Standard Format, Resistance Measurement 2
Gain multiplier Scaling offset Scaled process value in Ohm
in Ohm at 100 Ohm* at 155 Ohm* at 300.2 Ohm*
256 (1**) 0 100 Ohm 155 Ohm 300.2 Ohm
256 (1**) 10 110 Ohm 165 Ohm 310.2 Ohm
384 (1.5**) 15 165 Ohm 247.5 Ohm 465.3 Ohm
512 (2**) 20 220 Ohm 330 Ohm 620.4 Ohm
640 (2.5**) 20 270 Ohm 407.5 Ohm 770.5 Ohm
*) unscaled process value
**) Multiplier (= gain multiplier/gain divisor)
Refer to the table below for more sample calculations for the sensor type
Resistance measurement 2 in the S5-FB250 format.
Table 70: Examples of Scaled Process Value, S5-FB250 Format, Resistance Measurement 2
Gain multiplier Scaling offset Scaled process value in Ohm
in Ohm at 100 Ohm* at 155 Ohm* at 300.2 Ohm*
256 (1**) 0 100 Ohm 155 Ohm 300.0 Ohm
256 (1**) 10 110 Ohm 165 Ohm 310.0 Ohm
384 (1.5**) 15 165 Ohm 247.5 Ohm 465.5 Ohm
512 (2**) 20 220 Ohm 330 Ohm 620.5 Ohm
640 (2.5**) 20 270 Ohm 407.5 Ohm 770.5 Ohm
*) unscaled process value
**) Multiplier (= gain multiplier/gain divisor)
Manual
Version 1.2.0
88 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
In this menu item you can calibrate the channels of the I/O module.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 89
750-450 4 AI RTD
Table 71: Menu Item "Calibration"
Option Description
Calibration settings
Manufacturer Manufacturer configuration is active. Manufacturer calibration is
configuration applied. This means that you cannot input the individual gain and
offset values.
Manufacturer configuration is deactivated.
Gain Gain changes the slope factor for the
A/D raw value.
Offset Offset shifts the zero point
of the A/D raw value (shift along the Y axis).
User calibration User calibration is active. By activating this setting you can also
specify the individual gain and offest values.
User calibration is deactivated.
A/D raw value Analog/Digital converter raw value. This is a 24-bit value.
Resistance value This is the value that is output after calculation of the gain and offset value
[Ohm] and conversion from an A/D raw value. The value is output in Ohms.
User-defined calibration enables you to calibrate the I/O module for your
individual needs. The following equations apply to calculation of the two requisite
factors:
With:
• m= calibration gain
• b= calibration offset
• x1= actual value 1 (A/D raw value)
• x2= actual value 2 (A/D raw value)
• y1= setpoint 1
• y2= setpoint 2
Manual
Version 1.2.0
90 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Example:
The two values for the measured resistance must first be converted to the
corresponding A/D raw values. The following equation is used for this conversion:
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 91
750-450 4 AI RTD
Example:
You should acquire as many A/D raw values as possible (at least 10) for each
calibration point.
Example:
In the next step, determine the mean value for each of the two reference
resistance values from all of the acquired A/D raw values. The values x1 and x2
are obtained when you calculate the mean value.
Example:
You can then insert all of the calculated values into the equations to obtain the
calibration gain and calibration offset.
The calibration gain is the slop factor and the calibration offset the factor for
shifting along the Y axis.
Manual
Version 1.2.0
92 Commissioning WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Example:
Calibration gain:
(13288883 − 332222)) / (13287103 − 333892) = 1.000266343
Calibration offset:
332222 − 1.000266343 × 333892 = −1759
• Status indicator
• Online status
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Commissioning 93
750-450 4 AI RTD
Manual
Version 1.2.0
94 Diagnostics WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
8 Diagnostics
8.1 Error Response
The response of the I/O module in the event of an error depends on the
configuration for wire break / short circuit monitoring, under-range / over-range
monitoring and limit upper/lower limit violation monitoring. You can
activate/deactivate these diagnostics functions in Register 35.
The I/O module only allows one error to be indicated. A dedicated bit in the status
byte is assigned to each error. The associated status byte is set if an error status
is detected. This is why error statuses are given priority levels. In the event of
several errors being present, the error with the highest priority will always be
displayed.
The following priority levels apply for this:
Potentiometer!
The "Potentiometer" sensor type and the corresponding measuring range may
only be used with 3-wire connecting technology.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Diagnostics 95
750-450 4 AI RTD
Manual
Version 1.2.0
96 Diagnostics WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
The limits for detecting an under-range / over-range, a short circuit / wire break or
a lower/upper limit violation and the output process values are specified in the
process image tables.
A general error signals that an error is present without any detailed information.
This includes all error statuses from Register 6 (see Section "Startup" > "Register
Assignment"). A general error is also indicated when several of the error statuses
given in Register 6 occur simulatneously. The prerequisite for displaying a
general error status is that at least one of the bits 0 … 5 of the status byte is set.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Appendix 97
750-450 4 AI RTD
9 Appendix
9.1 Configuration and Parameterization using a GSD
File with PROFIBUS DP and PROFINET IO
Manual
Version 1.2.0
98 Appendix WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Appendix 99
750-450 4 AI RTD
Manual
Version 1.2.0
100 Appendix WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Figure 27: Example of the 750-375 and 750-377 Fieldbus Coupler Parameterization Dialog
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Appendix 101
750-450 4 AI RTD
The following assignment applies to the parameters of the I/O module when
using PROFIBUS-DP and PROFINET-IO fieldbus couplers.
Manual
Version 1.2.0
102 Appendix WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Appendix 103
750-450 4 AI RTD
Table 78: General Module / Channel Parameters
Parameter Value Explanation
Diagnosis: Short circuit 0 (false) A short circuit on the respective signal channel
Channel x (x = 0…3) does not lead to transmission of a diagnostic
alarm nor to entry in the diagnostics database of
the station proxy.
*)
1 (true) Provided that the channel diagnostics of the
respective signal channel has been activated, a
short circuit leads to transmission of a
diagnostic alarm and entry in the diagnostics
database of the station proxy.
Diagnosis: Measuring 0 (false) An overrange on the respective signal channel
range overflow does not lead to transmission of a diagnostic
Channel x (x = 0…3) alarm nor entry in the diagnostics database of
the station proxy.
*)
1 (true) Provided that the channel diagnostics of the
respective signal channel has been activated,
an
overrange leads to transmission of a diagnostic
alarm and entry in the diagnostics database of
the station proxy.
Diagnosis: Wire break 0 (false) A wire break on the respective signal channel
Channel x (x = 0…3) does not lead to transmission of a diagnostic
alarm nor to entry in the diagnostics database of
the station proxy.
*)
1 (true) Provided that the channel diagnostics of the
respective signal channel has been activated, a
wire break leads to transmission of a diagnostic
alarm and entry in the diagnostics database of
the station proxy.
Process alarm: 0 (false) Falling below the lower user limit on the
Lower user limit value respective signal channel does not lead to
undershot transmission of a process alarm. The lower user
Channel x (x = 0…3) limit is set in another attribute.
*)
1 (true) Provided that the channel diagnostics of the
respective signal channel has been activated,
falling below the lower user limit leads to
transmission of a process alarm. No entry in the
diagnostics database of the station proxy is
made. The lower user limit is set in another
attribute.
Process alarm: 0 (false) Exceeding the upper use limit on the respective
Upper user limit value signal channel does not lead to transmission of
exceeded a process alarm. The upper user limit is set in
Channel x (x = 0…3) another attribute.
*)
1 (true) Provided that the channel diagnostics of the
respective signal channel has been activated,
exceeding the upper user limit leads to
transmission of a process alarm. No entry in the
diagnostics database of the station proxy is
made. The upper user limit is set in another
attribute.
*)
Default settings
Manual
Version 1.2.0
104 Use in Hazardous Environments WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 105
750-450 4 AI RTD
Figure 29: Text Detail – Marking Example According to ATEX and IECEx
Manual
Version 1.2.0
106 Use in Hazardous Environments WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Table 79: Description of Marking Example According to ATEX and IECEx
Marking Description
TUEV 07 ATEX 554086 X Approving authority resp. certificate numbers
IECEx TUN 09.0001 X
Dust
II Equipment group: All except mining
3D Category 3 (Zone 22)
Ex Explosion protection mark
tc Type of protection: Protection by enclosure
IIIC Explosion group of dust
T135°C Max. surface temperature of the enclosure
(without a dust layer)
Dc Equipment protection level (EPL)
Mining
I Equipment group: Mining
M2 Category: High level of protection
Ex Explosion protection mark
d Type of protection: Flameproof enclosure
I Explosion group for electrical equipment for
mines susceptible to firedamp
Mb Equipment protection level (EPL)
Gases
II Equipment group: All except mining
3G Category 3 (Zone 2)
Ex Explosion protection mark
nA Type of protection: Non-sparking equipment
IIC Explosion group of gas and vapours
T4 Temperature class: Max. surface temperature
135 °C
Gc Equipment protection level (EPL)
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 107
750-450 4 AI RTD
Figure 30: Marking Example for Approved Ex i I/O Module According to ATEX and IECEx
Figure 31: Text Detail – Marking Example for Approved Ex i I/O Module According to ATEX and
IECEx
Manual
Version 1.2.0
108 Use in Hazardous Environments WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Table 80: Description of Marking Example for Approved Ex i I/O Module According to ATEX and
IECEx
Marking Description
TUEV 12 ATEX 106032 X Approving authority resp. certificate numbers
IECEx TUN 12 0039 X
Dust
II Equipment group: All except mining
3 (1) D Category 3 (Zone 22) equipment containing a safety
device for a category 1 (Zone 20) equipment
Ex Explosion protection mark
tc Type of protection: Protection by enclosure
[ia Da] Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 20
IIIC Explosion group of dust
T135°C Max. surface temperature of the enclosure
(without a dust layer)
Dc Equipment protection level (EPL)
Mining
I Equipment Group: Mining
M2 (M1) Category: High level of protection with electrical
circuits which present a very high level of protection
Ex Explosion protection mark
d Type of protection: Flameproof enclosure
[ia Ma] Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
electrical circuits
I Explosion group for electrical equipment for mines
susceptible to firedamp
Mb Equipment protection level (EPL)
Gases
II Equipment group: All except mining
3 (1) G Category 3 (Zone 2) equipment containing a safety
device for a category 1 (Zone 0) equipment
Ex Explosion protection mark
ec Equipment protection by increased safety “e”
[ia Ga] Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 0
IIC Explosion group of gas and vapours
T4 Temperature class: Max. surface temperature
135 °C
Gc Equipment protection level (EPL)
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 109
750-450 4 AI RTD
10.1.2 Marking for the United States of America (NEC) and Canada
(CEC)
Manual
Version 1.2.0
110 Use in Hazardous Environments WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Figure 34: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 505
Table 82: Description of Marking Example for Approved Ex i I/O Module According to NEC 505
Marking Description
CI I, Explosion protection group
Zn 2 Area of application
AEx Explosion protection mark
nA Type of protection
[ia Ga] Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC Group
T4 Temperature class
Gc Equipment protection level (EPL)
Figure 35: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 506
Table 83: Description of Marking Example for Approved Ex i I/O Modules According to NEC 506
Marking Description
CI I, Explosion protection group
Zn 2 Area of application
AEx Explosion protection mark
nA Type of protection
[ia IIIC] Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC Group
T4 Temperature class
Gc Equipment protection level (EPL)
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 111
750-450 4 AI RTD
Figure 36: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 84: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking Description
Dust
Ex Explosion protection mark
nA Type of protection
[ia IIIC] Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC Group
T4 Temperature class
Gc Equipment protection level (EPL)
X Symbol used to denote specific conditions of use
Gases
Ex Explosion protection mark
nA Type of protection
[ia Ga] Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
IIC Group
T4 Temperature class
Gc Equipment protection level (EPL)
X Symbol used to denote specific conditions of use
Manual
Version 1.2.0
112 Use in Hazardous Environments WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
The product is an open system. As such, the product must only be installed in
appropriate enclosures or electrical operation rooms to which the following
applies:
• For use in Zone 2 (Gc), compliance with the applicable requirements of the
standards EN/IEC/ABNT NBR IEC 60079-0, -7, -11, -15
• For use in mining (Mb), minimum degree of protection IP64 (acc. EN/IEC
60529) and adequate protection acc. EN/IEC/ABNT NBR IEC 60079-0 and
-1
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 Use in Hazardous Environments 113
750-450 4 AI RTD
Explosive atmosphere occurring simultaneously with assembly, installation or
repair work must be ruled out. Among other things, these include the following
activities
• Replacing fuses
Outside the device, suitable measures must be taken so that the rated voltage is
not exceeded by more than 40 % due to transient faults (e.g., when powering the
field supply).
Manual
Version 1.2.0
114 Use in Hazardous Environments WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
• WARNING – Product components with fuses must not be fitted into circuits
subject to overloads!
These include, e.g., motor circuits.
Additional Information
Proof of certification is available on request.
Also take note of the information given on the operating and assembly
instructions.
The manual, containing these special conditions for safe use, must be readily
available to the user.
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 List of Figures 115
750-450 4 AI RTD
List of Figures
Figure 1: View ....................................................................................................16
Figure 2: Data Contacts .....................................................................................17
Figure 3: Power Jumper Contacts ......................................................................18
Figure 4: Push-in CAGE CLAMP® Connectors ...................................................19
Figure 5: Display Elements.................................................................................21
Figure 6: Schematic Switching Diagram .............................................................22
Figure 7: Insert I/O Module (Example) ................................................................64
Figure 8: Snap the I/O Module into Place (Example) ..........................................64
Figure 9: Removing the I/O Module (Example) ...................................................65
Figure 10: Connecting a Conductor to a Push-in CAGE CLAMP® ......................66
Figure 11: Connection Example 750-450, 4-Channel, 4 x 2 Wires .....................67
Figure 12: Connection Example 750-450, 4-Channel, 4 x 3 Wires .....................68
Figure 13: Connection Example 750-450, 4-Channel, 4 x 4 Wires .....................69
Figure 14: Connection Example 750-450, 4-Channel, 4 x 3 Wires,
Potentiometer............................................................................................70
Figure 15: WAGO-I/O-CHECK User Interface ....................................................72
Figure 16: Parameterization Dialog for the I/O Module .......................................73
Figure 17: Buttons in the Main Menu ..................................................................74
Figure 18: Buttons in the Application Menu ........................................................75
Figure 19: Display of Measured Values in the Application Area..........................77
Figure 20: “Settings” Menu Item Warning Message ............................................78
Figure 21: Menu item "Settings" > "Module" .......................................................79
Abbildung 22: Menu item "Settings" > "Channel" ................................................81
Abbildung 23: Menu Item "Scaling" ....................................................................84
Figure 24: Menu Item "Calibration" .....................................................................88
Figure 25: Example of the PROFIBUS DP Fieldbus Coupler Parameterization
Dialog........................................................................................................98
Figure 26: Example of the 750-370 Fieldbus Coupler Parameterization
Dialog........................................................................................................99
Figure 27: Example of the 750-375 and 750-377 Fieldbus Coupler
Parameterization Dialog ..........................................................................100
Figure 28: Marking Example According to ATEX and IECEx ............................105
Figure 29: Text Detail – Marking Example According to ATEX and IECEx .......105
Figure 30: Marking Example for Approved Ex i I/O Module According to
ATEX and IECEx ....................................................................................107
Figure 31: Text Detail – Marking Example for Approved Ex i I/O Module
According to ATEX and IECEx ................................................................107
Figure 32: Marking Example According to NEC................................................109
Figure 33: Text Detail – Marking Example According to NEC 500 ....................109
Figure 34: Text Detail – Marking Example for Approved Ex i I/O Module
According to NEC 505.............................................................................110
Figure 35: Text Detail – Marking Example for Approved Ex i I/O Module
According to NEC 506.............................................................................110
Figure 36: Text Detail – Marking Example for Approved Ex i I/O Modules
According to CEC 18 attachment J .........................................................111
Manual
Version 1.2.0
116 List of Tables WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
List of Tables
Table 1: Revision History .................................................................................... 6
Table 2: Number Notation ................................................................................... 8
Table 3: Font Conventions .................................................................................. 8
Table 4: Compatibility List 750-450 ....................................................................15
Table 5: Legend for Figure “View” ......................................................................16
Table 6: Legend for Figure “Power Jumper Contacts” ........................................18
Table 7: Legend for Figure "Push-in CAGE CLAMP® Connectors" –
4-Channel, 2-Wires ...................................................................................19
Table 8: Legend for Figure "Push-in CAGE CLAMP® Connectors" –
4-Channel, 3-Wires ...................................................................................20
Table 9: Legend for Figure "Push-in CAGE CLAMP® Connectors" –
4-Channel, 4-Wires ...................................................................................20
Table 10: Legend for Figure “Display Elements”.................................................21
Table 11: Technical Data – Device Data ............................................................23
Table 12: Technical Data – Power Supply ..........................................................23
Table 13: Technical Data – Communication .......................................................23
Table 14: Technical Data – Inputs ......................................................................24
Table 15: Technical Data – Measuring Accuracy at 25°C Ambient Air
Temperature, 2 Wires ...............................................................................24
Table 16: Technical Data – Measuring Accuracy at 25°C Ambient Air
Temperature, 3 Wires ...............................................................................25
Table 17: Technical Data – Measuring Accuracy at 25°C Ambient Air
Temperature, 4 Wires ...............................................................................25
Table 18: Technical Data ‒ Field Wiring .............................................................26
Table 19: Technical Data – Power Jumper Contacts ..........................................26
Table 20: Technical Data – Data Contacts .........................................................26
Table 21: Technical Data – Climatic Environmental Conditions ..........................26
Table 22: Process Image ...................................................................................29
Table 23: Control Byte........................................................................................30
Table 24: Status byte .........................................................................................30
Table 25: Process Data – Overview of Standard Format and S5-FB250
Format ......................................................................................................32
Table 26: ID 0, Pt100 Setting (IEC 751), Standard Format .................................33
Table 27: ID 0, Pt100 (IEC 751) Setting, S5-FB250 Format ...............................34
Table 28: ID 1, Ni100 (DIN 43760) Setting, Standard Format .............................35
Table 29: ID 1, Ni100 (DIN 43760) Setting, S5-FB250 Format ...........................36
Table 30: ID 2, Pt1000 Setting (IEC 751), Standard Format ...............................37
Table 31: ID 2, Pt1000 (IEC 751) Setting, S5-FB250 Format .............................38
Table 32: ID 3, Pt500 (IEC 751) Setting, Standard Format .................................39
Table 33: ID 3, Pt500 (IEC 751) Setting, S5-FB250 Format ...............................40
Table 34: ID 4, Pt200 Setting (IEC 751), Standard Format .................................41
Table 35: ID 4, Pt200 (IEC 751) Setting, S5-FB250 Format ...............................42
Table 36: ID 5, Ni1000 (TK6180, DIN 43760) Setting, Standard Format ............43
Table 37: ID 5, Ni1000 (TK6180, DIN 43760) Setting, S5-FB250 Format ...........44
Table 38: ID 6, Ni120 (Minco) Setting, Standard Format ....................................45
Table 39: ID 6, Ni120 (Minco) Setting, S5-FB250 Format ...................................46
Table 40: ID 7, Ni1000 (TK5000) Setting, Standard Format ...............................47
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 List of Tables 117
750-450 4 AI RTD
Table 41: ID 7, Ni1000 (TK5000) Setting, S5-FB250 Format ..............................48
Table 42: ID 8, Ni1000 (TK6180, DIN 43760) Setting, Standard Format ............49
Table 43: ID 8, Ni1000 (DIN 43760) Setting, S5-FB250 Format .........................50
Table 44: ID 9, Ni1000 (TK5000) Setting, Standard Format ...............................51
Table 45: ID 9, Ni1000 (TK5000) Setting, S5-FB250 Format ..............................52
Table 46: ID 10, Pt1000 Setting (IEC 751), Standard Format .............................53
Table 47: ID 10, Pt1000 (IEC 751) Setting, S5-FB250 Format ...........................54
Table 48: ID 11, Pt100 Setting (IEC 751), Standard Format ...............................55
Table 49: ID 11, Pt100 (IEC 751) Setting, S5-FB250 Format .............................56
Table 50: ID 13, Potentiometer, Standard Format ..............................................57
Table 51: ID 13, Potentiometer Setting, S5-FB250 Format .................................58
Table 52: ID 14, "Resistance Measurement 1" Setting, Standard Format ...........59
Table 53: ID 14, "Resistance Measurement 1" Setting, S5-FB250 Format .........60
Table 54: ID 15, "Resistance Measurement 2" Setting, Standard Format ...........61
Table 55: ID 15, "Resistance Measurement 2" Setting, S5-FB250 Format .........62
Table 56: Connection Terminals, Functions and Measuring Circuits,
4-Channel, 2 Wires ...................................................................................67
Table 57: Connection Terminals, Functions and Measuring Circuits,
4-Channel, 3 Wires ...................................................................................68
Table 58: Connection Terminals, Functions and Measuring Circuits,
4-Channel, 4 Wires ...................................................................................69
Table 59: Connection Terminals, Functions and Measuring Circuits,
Potentiometer............................................................................................70
Table 60: Buttons on the Main Menu ..................................................................74
Table 61: Buttons in the Application Menu .........................................................75
Table 62: Buttons in the “Settings” and “Scaling” Menus ....................................78
Table 63: Buttons in the “Settings” Menu............................................................78
Table 64: Menu Item "Settings" > "Module" ........................................................80
Table 65: Menu Item "Settings" ..........................................................................82
Table 66: Menu Item "Scaling" > "Channel 1 …4" ..............................................85
Table 67: Examples of Scaled Process Value, Standard Format,
Pt100 (IEC 751) ........................................................................................86
Table 68: Examples of Scaled Process Value, S5-FB250 Format,
Pt100 (IEC 751) ........................................................................................86
Table 69: Examples of Scaled Process Value, Standard Format, Resistance
Measurement 2 .........................................................................................87
Table 70: Examples of Scaled Process Value, S5-FB250 Format, Resistance
Measurement 2 .........................................................................................87
Table 71: Menu Item "Calibration" ......................................................................89
Table 72: Priority Levels for Diagnostics Functions ............................................94
Table 73: Behavior in the Event of an Error Dependent on the Configuration .....95
Table 74: Configuration ......................................................................................97
Table 75: Configuration ......................................................................................97
Table 76: Specific Module / Channel Parameters for 75x-450 ..........................101
Table 77: General Module / Channel Parameters.............................................102
Table 78: General Module / Channel Parameters.............................................102
Table 79: Description of Marking Example According to ATEX and IECEx.......106
Table 80: Description of Marking Example for Approved Ex i I/O Module
According to ATEX and IECEx ................................................................108
Table 81: Description of Marking Example According to NEC 500 ...................109
Manual
Version 1.2.0
118 List of Tables WAGO-I/O-SYSTEM 750
750-450 4 AI RTD
Table 82: Description of Marking Example for Approved Ex i I/O Module
According to NEC 505.............................................................................110
Table 83: Description of Marking Example for Approved Ex i I/O Modules
According to NEC 506.............................................................................110
Table 84: Description of Marking Example for Approved Ex i I/O Modules
According to CEC 18 attachment J .........................................................111
Manual
Version 1.2.0
WAGO-I/O-SYSTEM 750 119
750-450 4 AI RTD
Manual
Version 1.2.0
WAGO Kontakttechnik GmbH & Co. KG
Postfach 2880 • D - 32385 Minden
Hansastraße 27 • D - 32423 Minden
Phone: +49 571 887 – 0
Fax: +49 571 887 – 844169
E-Mail: info@wago.com
Internet: www.wago.com