MC200 Technical Manual: File Name: EAAM058702EN - Docx Rev. 02 Date: 20/04/2018 ID Document: EAAM0578EN Product: MC200

Download as pdf or txt
Download as pdf or txt
You are on page 1of 215

MC200 Technical

Manual

File name: EAAM058702EN.docx


Rev. 02 Date: 20/04/2018
ID Document: EAAM0578EN
Product: MC200
Revision Date Pages Notes

00 05/06/2017 214 First version of the manual for the version 01.00 of
the controller.
01 06/11/2017 214 Update paragraph: 6.5.5.1, 6.5.5.2, 7, 7.9.3.1, 7.11,
7.12, 7.15, 8.8
02 20/04/2018 214 Update paragraph: 5.6.2, 5.11.2

ii MC200 Technical Manual EAAM0578EN


1 Introduction................................................................................................................. 13
1.1 References ......................................................................................................... 13
1.2 Introduction and prerequisites ............................................................................ 13
1.3 Notes on the parameters configuration of the device ......................................... 13
1.4 Definitions ........................................................................................................... 14
1.4.1 Acronyms ..................................................................................................... 14
1.5 Conventions........................................................................................................ 15
1.6 Revisions of the software.................................................................................... 15
2 Views of the device .................................................................................................... 16
3 Technical features ...................................................................................................... 18
3.1 Measurement resolution ..................................................................................... 24
4 Installation .................................................................................................................. 25
4.1 Mounting ............................................................................................................. 25
4.2 Wiring ................................................................................................................. 25
5 IN/OUT connections and configuration .................................................................... 27
5.1 Basic diagram ..................................................................................................... 28
5.2 Functional earth (JB) .......................................................................................... 28
5.3 Device supply (JC).............................................................................................. 29
5.4 Digital inputs 1-18 (JL, JO, JP) ........................................................................... 29
5.4.1 JL - Digital inputs 1-8 .................................................................................... 30
5.4.2 JP - Digital inputs 9-13 ................................................................................. 31
5.4.3 JO - Digital inputs 14-18 ............................................................................... 31
5.4.4 Virtual digital inputs ...................................................................................... 32
5.4.5 Digital inputs configuration ........................................................................... 32
5.5 Digital outputs 1-18 (JJ, JH, JD, JQ, JR) ............................................................ 37
5.5.1 JJ - Digital outputs 15-16 .............................................................................. 37
5.5.2 JH - Digital outputs 17-18: outputs for the command on the loads switching 38
5.5.3 JD - Digital inputs 1-4 ................................................................................... 39
5.5.4 JO - Digital inputs 5-9 ................................................................................... 39
5.5.5 JQ - Digital inputs 10-14 ............................................................................... 40
5.5.6 Digital outputs configuration ......................................................................... 40
5.5.7 AND/OR logics ............................................................................................. 43
5.6 Analogue inputs 1-7 (JU, JK, JJ) ........................................................................ 47
5.6.1 JU - Analogue inputs 1-2 .............................................................................. 48
5.6.2 JK - Analogue inputs 3-6 .............................................................................. 48
5.6.3 JJ-4 Analogue input 07 ................................................................................. 49
5.6.4 Configuration of digital inputs (AI_CONTROLLER) ...................................... 49
5.6.5 Virtual digital inputs (AI_VIRTUAL) .............................................................. 51
5.6.6 Conversion curves ........................................................................................ 53
5.7 Analogue outputs (JT, JS) .................................................................................. 54
5.7.1 Configuration of the analogue outputs .......................................................... 54
5.8 Optional additional modules ............................................................................... 55
5.9 JG/JF – Mains/ generators bus voltage measure inputs ..................................... 57
5.9.1 Star or Wye (three phases, four wires) ......................................................... 57
5.9.2 Delta (three phases, three wires) ................................................................. 59

MC200 Technical Manual EAAM0578EN iii


5.9.3 Single phase (one phase, two wires) ............................................................ 61
5.9.4 Aron insertion of voltmetric transformers ...................................................... 62
5.10 JE-JI Current measurement inputs. .............................................................. 63
5.10.1 JE - Currents measurement inputs 1-3 ................................................... 63
5.10.2 JI - Currents measurement input 4 .......................................................... 64
5.11 Communication ports ................................................................................... 66
5.11.1 JA - Serial port 1 RS232 ......................................................................... 66
5.11.2 JW - Serial port 2 RS485 ........................................................................ 68
5.11.3 JNA - USB Serial port: function mode ..................................................... 68
5.11.4 JY - Ethernet port 10 100Mbps ............................................................... 69
5.12 CAN bus Communication ports .................................................................... 71
5.12.1 JM - CAN bus port 0................................................................................ 71
5.12.2 JX - CAN bus port 1 ................................................................................ 72
6 Main functions ............................................................................................................ 73
6.1 Front panel ......................................................................................................... 73
6.2 Buttons ............................................................................................................... 74
6.3 Indicators (ref. to fig. 1 and 2) ............................................................................. 76
6.4 Multifunctional display......................................................................................... 78
6.4.1 LCD lighting .................................................................................................. 78
6.4.2 Contrast adjustment ..................................................................................... 78
6.4.3 Colours scheme ........................................................................................... 78
6.4.4 Mode navigation ........................................................................................... 78
6.4.5 Display area layout (ref. to fig. 4) .................................................................. 79
6.4.6 Top status bar (ref. to fig. 5) ......................................................................... 79
6.5 Display mode ...................................................................................................... 81
6.5.1 Programming (P.XX) .................................................................................... 81
6.5.2 PLC (L.XX) ................................................................................................... 88
6.5.3 Status information (S.XX) ............................................................................. 91
6.5.4 Electrical measurements (M.XX) .................................................................. 97
6.5.5 Measurement from CAN bus PMCB (B.XX) ............................................... 102
6.5.6 History logs (H.xx) ...................................................................................... 105
6.6 Language selection........................................................................................... 113
7 Operation sequence ................................................................................................. 114
7.1 Operation mode ................................................................................................ 115
7.1.1 Events and signalling ................................................................................. 118
7.2 Generators bus voltage detection ..................................................................... 120
7.2.1 External sensor .......................................................................................... 120
7.2.2 Internal sensor............................................................................................ 120
7.2.3 Events and signalling ................................................................................. 120
7.3 Load bus voltage detection ............................................................................... 121
7.3.1 Signalling .................................................................................................... 121
7.4 Mains ................................................................................................................ 122
7.4.1 Automatic Mains Failure ............................................................................. 122
7.4.2 “Loss of mains” protection .......................................................................... 125
7.5 Synchronization ................................................................................................ 126
7.5.1 Synchro-check............................................................................................ 126
7.5.2 Voltages, frequency and phase regulations................................................ 128
7.5.3 Digital inputs for synchronization ................................................................ 132
7.5.4 Digital outputs for synchronization .............................................................. 132

iv MC200 Technical Manual EAAM0578EN


7.5.5 Automatic synchronization.......................................................................... 133
7.5.6 Manual synchronisation .............................................................................. 133
7.5.7 MCB synchronization failure ....................................................................... 134
7.6 Inhibition to genset automatic intervention ........................................................ 136
7.6.1 Inhibition from contact ................................................................................ 136
7.6.2 Inhibition from clock .................................................................................... 136
7.6.3 Inhibition to load management ................................................................... 137
7.6.4 Inhibition due to mains failure ..................................................................... 137
7.6.5 Inhibition due to “GCB circuit breaker not open”......................................... 137
7.6.6 Signalling .................................................................................................... 137
7.7 Inhibition to supply the loads ............................................................................ 137
7.7.1 Inhibition from contact ................................................................................ 138
7.7.2 Modbus commands .................................................................................... 138
7.7.3 Due to mains failure ................................................................................... 138
7.7.4 Inhibition due to “GCB circuit breaker not open” ......................................... 138
7.7.5 Inhibition for “synchronization on MCB in progress” ................................... 138
7.7.6 Inhibition for MCB synchronization failure .................................................. 139
7.7.7 Inhibition for “no supplying generators” ...................................................... 139
7.7.8 Inhibition for “TEST without load” ............................................................... 139
7.7.9 Signalling .................................................................................................... 139
7.8 Power measurements ....................................................................................... 140
7.8.1 Power measurements on the generators.................................................... 140
7.8.2 Power measurements on the mains ........................................................... 140
7.8.3 Power measurements on MGCB ................................................................ 140
7.8.4 Power measurements on the loads ............................................................ 141
7.8.5 Calculated powers ...................................................................................... 141
7.9 Circuit breakers management ........................................................................... 142
7.9.1 Digital outputs............................................................................................. 142
7.9.2 Digital inputs ............................................................................................... 145
7.9.3 Management logic ...................................................................................... 147
7.9.4 Events and signalling ................................................................................. 155
7.10 Gensets supplying ...................................................................................... 156
7.11 Active power management ......................................................................... 156
7.11.1 BASE LOAD.......................................................................................... 156
7.11.2 IMPORT/EXPORT ................................................................................ 157
7.11.3 Transfer to generators........................................................................... 158
7.11.4 Load and unload ramps ........................................................................ 159
7.12 Reactive power management ..................................................................... 160
7.13 Commands for gensets .............................................................................. 162
7.14 Plant types.................................................................................................. 164
7.14.1 MPM (Multiple Prime Mover) ................................................................. 165
7.14.2 MSB (Multiple Stand By) ....................................................................... 167
7.14.3 MSB+MSTP (Multiple Stand By + Multiple Short Time Parallel) ........... 170
7.14.4 MPTM (Multiple Parallel to Mains) ........................................................ 174
7.14.5 MPTM+MSB (Multiple Parallel to Mains + Multiple Stand By) ............... 176
7.15 Load function .............................................................................................. 178
7.15.1 Starting/stopping generators to meet power requests ........................... 178
7.15.2 Selecting generators ............................................................................. 180
7.16 Load shedding ............................................................................................ 182
7.16.1 All loads management........................................................................... 182

MC200 Technical Manual EAAM0578EN v


7.16.2 Single load management ...................................................................... 183
7.16.3 Manual commands ................................................................................ 183
7.16.4 Notes about “load shedding” ................................................................. 184
7.16.5 Events ................................................................................................... 184
7.17 “Peak shaving/lopping” ............................................................................... 185
7.17.1 Power management .............................................................................. 185
7.17.2 Events ................................................................................................... 185
8 Anomalies ................................................................................................................. 186
8.1 Silence the horn ................................................................................................ 187
8.2 Acknowledge the anomaly ................................................................................ 187
8.3 Cancel the anomaly .......................................................................................... 188
8.4 Events and signalling ........................................................................................ 188
8.5 OVERRIDE of protections ................................................................................ 189
8.6 Anomalies connected to digital inputs............................................................... 190
8.7 Anomalies connected to analogue inputs ......................................................... 190
8.8 Faults list .......................................................................................................... 191
005 - At least one GCB is not opened ........................................................................ 191
007 – Manual STOP pressed in automatic mode ....................................................... 191
008 - Power required for supply not reached .............................................................. 192
013 - MCB not closed ................................................................................................. 192
014 - MGCB not closed .............................................................................................. 192
016 – Maximum current (#1) ...................................................................................... 192
017 – Maximum current (#2) ...................................................................................... 194
021 – Time-out for stopping generators...................................................................... 194
022 – Time-out for starting generators ....................................................................... 195
023 – MCB opening failure ......................................................................................... 195
024 – MGCB opening failure ...................................................................................... 195
037 – Low power supply voltage ................................................................................ 195
038 – High power supply voltage................................................................................ 196
045 – Maximum auxiliary current ................................................................................ 196
048 – Emergency stop................................................................................................ 196
051 – High internal board temperature ....................................................................... 196
057 – Clock not valid .................................................................................................. 197
062 – Faulty CAN bus 0 link ....................................................................................... 197
200 – CAN bus PMCB faulty connection .................................................................... 197
201 – Duplicated address over the PMCB .................................................................. 197
202 – Wrong number of generators over the PMCB................................................... 197
207 – Maximum time in parallel to the grid. ................................................................ 198
252 – CAN bus (EXBUS) expansion modules missing ............................................... 198
253 – CAN bus (EXBUS) missing measure ................................................................ 198
254 – CAN bus (EXBUS) duplicate address ............................................................... 199
255 – Disconnected CAN bus sensor (EXBUS) ......................................................... 199
271 – MGCB synchronization failure .......................................................................... 199
272 – MCB synchronization failure ............................................................................. 199
273 – Incoherent parameters ..................................................................................... 199
274 – Production line open ......................................................................................... 200
275 – Interface device not opened ............................................................................. 200
279 – Inconsistent bar voltage .................................................................................... 200
281 – Maximum power exported to the mains. ........................................................... 201
301...554 - Generic anomalies linked to digital inputs ................................................ 201

vi MC200 Technical Manual EAAM0578EN


701...774 - Generic anomalies linked to analogue inputs ........................................... 201
900 – Incoherent PLC Parameters ............................................................................. 201
901...964 - Anomalies connected to the PLC ............................................................. 202
9 Other functions ......................................................................................................... 203
9.1 PLC logic .......................................................................................................... 203
9.2 Loads protection from mains breaker damages ................................................ 203
9.3 Clock................................................................................................................. 203
9.3.1 Clock automatic update .............................................................................. 204
9.3.2 Weekly planning for TEST. ......................................................................... 204
9.3.3 Weekly planning for working days. ............................................................. 205
9.3.4 Weekly planning of intervention forcing. ..................................................... 205
9.3.5 Configurable calendars............................................................................... 206
9.4 11.3 Thermometer ............................................................................................ 210
9.5 Counters ........................................................................................................... 210
9.5.1 Counters reset ............................................................................................ 211
9.6 Alternative parameters configurations. ............................................................. 212
9.7 Non-volatile memory ......................................................................................... 213

MC200 Technical Manual EAAM0578EN vii


INDEX

DIF.2063 35; 189


A
DIF.2093 35; 157
AIF.0000 48; 49; 50; 51 DIF.2096 35; 158
AIF.0100 47; 50 DIF.2151 35; 212
AIF.2001 49; 50; 51; 54; 101 DIF.2152 35; 212
AIF.2003 49; 50; 51; 54; 101 DIF.2153 35; 213
AIF.2005 49; 50; 51; 54; 101 DIF.2154 35; 213
AIF.2051 49; 50; 51 DIF.2181 35; 154
AIF.2101 50; 51; 134 DIF.2251 35; 183; 184
AIF.2103 50; 51; 129 DIF.2252 35; 183; 184
AIF.2105 50; 51; 129 DIF.2271 35; 116
AIF.2107 50; 51; 129 DIF.2272 35; 116
AIF.2201 50; 51; 133; 134 DIF.2273 35; 116
AIF.2303 50; 51; 140 DIF.2501 35; 136
AIF.2307 50; 51; 156; 157; 185 DIF.2502 35; 138
AIF.2309 50; 51; 157; 158; 185 DIF.2701 35; 117; 118
AIF.2405 50; 51; 160; 161 DIF.2702 30; 35; 178
AIF.4001 51; 52 DIF.2704 35; 65; 196
AOF.0000 55 DIF.2705 35; 50
AOF.0101 55; 202 DIF.2706 35; 116; 117; 118; 138; 150; 151; 187; 188
AOF.0102 55 DIF.2708 35
AOF.1000 54; 55; 162 DIF.2712 36
AOF.1001 55; 162 DIF.2713 36
AOF.1002 55; 163 DIF.2721 36; 182
AOF.1003 55; 163 DIF.2722 36; 185
AOF.3101 53; 55 DIF.3002 30; 36; 145; 192; 195; 200
AOF.3111 55 DIF.3003 30; 36; 145; 192; 195; 200
AOF.3121 55 DIF.3004 36; 156
AOF.3201 55 DIF.3101 36; 123
AOF.3211 55 DIF.3102 36; 120
AOF.3221 55 DIF.3103 36
DIF.3104 36; 121
D
DIF.3201 36; 93
DIF.0000 30; 31; 32; 33 DIF.3202 36; 93
DIF.0101 33 DIF.3203 36; 93
DIF.1001 33; 146; 151 DIF.3204 36; 93
DIF.1002 33; 34; 146; 151 DIF.3205 36; 93
DIF.1003 33; 146 DIF.3206 36; 93
DIF.1004 34; 132; 146; 149; 200 DIF.4001 32; 36; 190
DIF.1005 34; 43; 145; 147; 153; 154 DIF.4002 36; 190
DIF.1006 34; 43; 145; 147; 153 DIF.4004 36; 190
DIF.1031 34; 146; 150 DIF.4005 36; 190
DIF.1032 34; 146; 150 DIF.4008 36; 190
DIF.1033 34; 146 DIF.4021 36; 190; 203
DIF.1034 34; 132; 146; 148; 200 DIF.4022 36; 190; 203
DIF.1035 34; 43; 145; 147; 152; 153 DIF.4024 37; 190; 203
DIF.1036 34; 43; 145; 147; 152 DIF.4062 37; 189; 190
DIF.2001 34; 188 DIF.4064 37; 189; 190
DIF.2002 34; 187 DIF.4261 37; 190; 200
DIF.2029 34; 116 DOF.0000 37; 39; 40; 42
DIF.2030 34; 117 DOF.0101 42; 202
DIF.2031 35; 116 DOF.0102 42
DIF.2032 35; 117 DOF.0103 42; 43; 132

viii MC200 Technical Manual EAAM0578EN


DOF.1005 42; 162 EVT.1014 106; 136
DOF.2001 42; 142; 143 EVT.1020 106; 120
DOF.2002 42; 143 EVT.1021 106
DOF.2003 42; 143 EVT.1022 106; 120
DOF.2004 38; 42; 143 EVT.1030 106; 155
DOF.2031 42; 143 EVT.1031 106; 155
DOF.2032 42; 143 EVT.1032 106; 155
DOF.2033 42; 143 EVT.1033 106; 155
DOF.2034 38; 42; 143 EVT.1035 106; 155
DOF.2251 42; 182 EVT.1036 106; 155
DOF.2252 42; 182 EVT.1037 106; 155
DOF.2253 42; 182 EVT.1038 106; 155
DOF.2254 43; 182 EVT.1050 106
DOF.3001 43; 118 EVT.1051 106
DOF.3002 43; 118 EVT.1052 106
DOF.3003 43; 118 EVT.1053 106
DOF.3004 43; 118 EVT.1054 106
DOF.3005 43; 118 EVT.1055 106
DOF.3011 43; 118 EVT.1056 106
DOF.3012 43; 118 EVT.1057 106
DOF.3030 43; 121 EVT.1058 106
DOF.3031 43; 121 EVT.1059 106
DOF.3033 43; 125 EVT.1060 106
DOF.3034 43 EVT.1061 106
DOF.3035 43 EVT.1062 106
DOF.3036 43 EVT.1074 106
DOF.3037 43 EVT.1075 106
DOF.3062 43; 162 EVT.1076 106; 204
DOF.3081 34; 43; 145; 153 EVT.1077 106
DOF.3082 34; 43; 145; 152 EVT.1078 106
DOF.3083 34; 43; 145; 153 EVT.1080 106; 138
DOF.3084 34; 43; 145; 153 EVT.1081 107; 138
DOF.3091 43; 132; 145 EVT.1082 107; 189
DOF.3092 43; 132; 145 EVT.1083 107; 189
DOF.3093 43; 132; 145 EVT.1086 107
DOF.3094 43; 128; 132; 145 EVT.1087 107
DOF.3096 43 EVT.1091 107
DOF.3151 43; 188 EVT.1092 107
DOF.3152 43; 186; 188 EVT.1093 107
DOF.3153 43 EVT.1094 107
DOF.3154 43; 188 EVT.1095 107
DOF.4001 43; 188 EVT.1096 107
DOF.4002 43; 188 EVT.1098 107
DOF.4004 43; 188 EVT.1099 107
DOF.4005 43; 188 EVT.1100 107
DOF.4035 43; 188 EVT.1101 107
EVT.1102 107
E
EVT.1103 107
EVT.1001 106; 118 EVT.1104 107
EVT.1002 106; 118 EVT.1105 107
EVT.1003 106; 118 EVT.1151 107
EVT.1004 106; 118 EVT.1152 107
EVT.1005 106; 118 EVT.1153 107
EVT.1010 106; 125 EVT.1154 107
EVT.1011 106; 125 EVT.1155 107
EVT.1012 106; 125 EVT.1156 107
EVT.1013 106; 136 EVT.1160 107

MC200 Technical Manual EAAM0578EN ix


EVT.1161 107 P.0144 56; 197; 198; 199
EVT.1162 107 P.0151 57
EVT.1163 107 P.0152 57; 122
EVT.1164 107 P.0201 123
EVT.1165 107 P.0203 123
EVT.1201 107; 138 P.0204 123
EVT.1202 107; 138 P.0207 136
EVT.1203 107; 138 P.0208 136
EVT.1204 107; 139 P.0219 144; 168; 171
EVT.1221 107; 136 P.0220 144
EVT.1222 107; 136 P.0222 34; 35; 115; 116; 117
EVT.1223 107; 137 P.0236 81; 85; 123
EVT.1224 107; 137 P.0237 123
EVT.1225 107; 137 P.0238 124
EVT.1226 107; 137 P.0239 124
EVT.1291 107; 181 P.0244 124
EVT.1301 184 P.0246 142
EVT.1302 184 P.0247 143
EVT.1303 184 P.0248 147; 169; 174
EVT.1304 184 P.0301 126
EVT.1305 184 P.0303 126
EVT.1306 184 P.0305 127
EVT.1307 184 P.0307 127
EVT.1308 184 P.0328 120
EVT.1321 107; 108 P.0361 196
EVT.1331 108; 185 P.0362 49; 195; 196
EVT.1332 108; 185 P.0363 49; 195; 196
P.0364 49; 196
P
P.0365 49; 196
P.0000 82; 83 P.0366 196; 197; 210
P.0001 82; 83 P.0367 65; 196
P.0002 82; 83 P.0368 65; 196
P.0003 82; 83 P.0384 201
P.0004 116; 117; 118; 138; 150; 151; 187; 188 P.0385 201
P.0101 58; 59; 60; 61; 62; 98; 120; 212 P.0386 201
P.0102 58; 59; 60; 61; 62; 120; 126; 212 P.0408 204
P.0103 57; 120; 212 P.0409 204; 206
P.0104 57; 212 P.0410 204
P.0105 122; 123; 127; 212 P.0418 117; 197; 204
P.0107 64; 212 P.0419 117; 204
P.0108 65; 196; 212 P.0420 34; 116; 117; 204
P.0109 64; 65; 212 P.0421 136; 197; 205
P.0116 58; 59; 60; 61; 62; 85; 122; 123; 124; 126; 212 P.0422 136; 197; 205
P.0117 57; 122; 212 P.0423 136; 197; 205
P.0118 57; 122; 212 P.0426 118; 197; 205
P.0119 58; 59; 60; 61; 62; 97; 122; 123; 212 P.0427 118; 206
P.0124 63; 140; 141; 212 P.0428 118; 206
P.0128 57; 58; 59; 60; 61; 62; 98; 120; 212 P.0441 105; 118; 120; 125; 136; 155; 181; 184; 185
P.0129 57; 58; 59; 60; 61; 62; 97; 122; 212 P.0442 109
P.0130 65; 140; 141; 212 P.0443 109
P.0131 65; 98; 196; 212 P.0451 67; 68
P.0132 65; 140 P.0452 67
P.0135 65; 196; 212 P.0453 67
P.0139 64; 212 P.0454 67
P.0141 55; 197; 198; 199 P.0456 70
P.0142 55; 197; 198; 199 P.0469 83
P.0143 56; 197; 198; 199 P.0470 67

x MC200 Technical Manual EAAM0578EN


P.0472 68 P.0857 162
P.0473 68 P.0858 100; 156; 157; 158; 185
P.0474 68 P.0859 100; 157; 158; 185
P.0475 68 P.0860 100; 160; 161
P.0478 69 P.0861 163
P.0479 69 P.0862 163
P.0491 187 P.0863 163
P.0492 78 P.0867 100; 133; 134
P.0493 78 P.0868 130; 134
P.0494 97 P.0869 130
P.0495 75; 80; 151; 152; 192 P.0878 159; 172; 175
P.0496 76 P.0879 158; 160; 172; 175
P.0499 78 P.0880 35; 156; 157; 158; 170; 171; 174; 176; 185
P.0500 69; 70 P.0890 159; 170; 198
P.0501 69; 70 P.0897 198
P.0502 69; 70 P.0899 137; 174; 175
P.0503 69; 70 P.0900 174; 176; 200
P.0504 70 P.0903 147
P.0505 70 P.0904 158
P.0508 70; 71 P.0922 35
P.0509 70; 71 P.0924 35
P.0510 70; 71 P.1171 185
P.0511 70; 71 P.1172 185
P.0513 70 P.1173 185
P.0514 70 P.1174 185
P.0802 147; 149; 164; 200 P.1175 185
P.0803 197; 198 P.1181 183
P.0804 198 P.1182 183
P.0805 137; 138; 191 P.1183 183
P.0806 154; 165; 166; 168; 169; 170; 171; 173; 192 P.1184 183
P.0820 179; 180 P.1185 183
P.0822 180; 181 P.1186 183; 184
P.0823 180; 181 P.1900 207; 209
P.0824 180 P.1901 207
P.0825 181 P.1902 207; 208
P.0826 178; 179 P.1903 209
P.0827 179 P.1904 209
P.0828 178; 179 P.1957 209
P.0829 179 P.1958 209
P.0830 179 P.1959 209
P.0831 162 P.1960 209
P.0840 100; 133; 134 P.1961 210
P.0841 127 P.1962 210
P.0842 128; 130 P.1963 210
P.0843 127 P.1964 210
P.0844 128 P.2000 32
P.0845 128 P.2001 33; 152; 153; 154; 190; 192; 195; 200
P.0846 126 P.2002 33; 146; 190
P.0847 146; 147; 203 P.2003 33; 190
P.0848 133 P.2050 32
P.0849 130 P.2100 32
P.0850 130 P.2151 32
P.0852 133; 172; 173; 175; 199 P.2152 32
P.0853 133; 171; 173; 199 P.2153 32
P.0854 142; 146; 148; 149; 200 P.2200 32
P.0855 142; 146; 147; 148; 149; 200 P.2250 32
P.0856 162 P.3000 41; 42

MC200 Technical Manual EAAM0578EN xi


P.3015 38 P.9526 194
P.3016 38 P.9527 194
P.3020 41 P.9528 194
P.3200 41
S
P.3250 41; 42
P.4001 47; 129; 133; 134; 156; 157; 160; 198 ST.000 119
P.4002 101; 191 ST.001 119
P.4003 191 ST.002 119
P.4004 191 ST.003 119
P.4005 189; 191 ST.004 119
P.4006 191 ST.006 189
P.4007 191 ST.007 189
P.4008 191 ST.008 189
P.4017 49 ST.009 189
P.4018 49 ST.011 189
P.4019 49 ST.012 189
P.4020 49 ST.013 189
P.4051 51; 52 ST.015 189
P.4052 52 ST.017 32
P.4053 52 ST.065 155
P.4054 52 ST.066 32; 155
P.4055 52 ST.068 155
P.4056 52 ST.069 155
P.4057 52 ST.070 155
P.4058 52 ST.071 155
P.6001 54 ST.072 155
P.9501 197 ST.073 155
P.9502 192; 193; 194 ST.074 155
P.9503 139; 146; 148; 154 ST.075 155
P.9504 122 ST.080 137
P.9505 123 ST.081 137
P.9506 114; 148; 156; 161; 178; 200 ST.083 137
P.9511 166; 168; 169; 171; 172; 175; 195 ST.084 137
P.9512 166; 167; 168; 169; 172; 174; 176; 195 ST.088 139
P.9513 154; 175 ST.089 139
P.9514 167; 170; 203 ST.090 139
P.9515 133; 134; 139 ST.091 139
P.9517 158; 159 ST.092 139
P.9521 192; 193; 194 ST.093 139
P.9522 192; 193; 194 ST.094 139
P.9523 192; 193 ST.097 132
P.9524 192; 193 ST.098 132
P.9525 194 ST.099 132

xii MC200 Technical Manual EAAM0578EN


1
1.1
[1] SICES EAAM0588xx MC200 Parameters Chart.

[2] SICES EAAM0458xx - BoardPRG3.xx Manual.

[3] SICES S.r.l EAAS0341xx Serial communication and SMS protocol.

[4] SICES EAAS0589xx MC200 Modbus Registers.

[5] CANopen – Cabling and Connector Pin Assignment – CiA Draft Recommendation DR-
303-1

[6] BOSCH CAN Specification – Version 2.0 – 1991, Robert Bosch Gmbh.

[7] SICES EAAP0457xx USB driver Installation Guide

[8] SICES EAAM0199xx - DST4602/GC500/GC400/GC600 Parallel functions manual.

[9] SICES EAAM0432xx – PLC Editor Manual

[10] SICES EAAM0412xx – PLC Description for SICES devices

1.2
For the appropriate use of this manual, it is required knowledge of the use and of the
installation of generator groups.

WARNING!!!

Every intervention must be carried out by skilled personnel. There are dangerous voltages on
the terminals of the device; before carrying out any operation on them, make sure to open the
MCB and MGCB circuit breakers or to open the related fuses.

Do not remove or change any connection while the gensets are running (or more generally,
while the plant is operating).

Do not disconnect for any reason the terminals of the current transformers (CT)

Wrong operations on the connections can cause the disconnection of the loads from the mains
or the gensets.

Please read this manual carefully before using the device.

The device uses many configurable parameters and it is therefore impossible to


describe all their possible combinations and effects.

In this document, there is not a detailed description of all the programming parameters: to this
purpose, see documents [1]. Consider that document as part of this manual.

SICES S.r.l provides the devices with a generic “default” configuration; is at the
installer’s care to adjust the operating parameters to the specific application.

SICES S.r.l carries out a great effort to improve and update its products; therefore, they are
subject to both hardware and software modifications without notice. Some of the features
described in this manual may therefore differ from those present in your device.

1.3
Although most of the parameters and features can be accessed and configured by directly
operating on the device, some features or configurations, due to their nature, can only
be set or changed through the PC program SICES Board Programmer3 (hereinafter called

MC200 Technical Manual EAAM0578EN 13


“BoardPrg3”), which can be downloaded for free after registration on the SICES S.r.l website
www.sices.eu.

It simplifies a lot the configuration of the device and we strongly suggest its use. It also allows
you to save the current configuration of the device on a file and to reuse it on other identical
devices.

The program also allows the configuration, saving or loading of the characteristic curves of
non-standard analogue sensors with resistive or voltage output.

BoardPrg3 supports all SICES devices; the connection to the PC can be direct via serial
RS232 or USB, or by remote via modem, serial RS845 or Ethernet. For the use of the program,
refer to the document [2].

1.4
This document uses the words “ALARM” and “UNLOAD” to indicate a fault that makes the
genset operation impossible; the MGCB circuit breaker or the GCBs circuit breakers are
immediately opened (without any power unload). The genset controllers will turn off the
engines with standard procedure (with cooling cycle).

This document uses the word “WARNING” to indicate a fault that requires an operator action
but does not require the opening of MGCB (or GCBs) circuit breakers, and that does not
require the shutdown of the gensets.
1.4.1 Acronyms
AIF It identifies a function for the configuration of the analogue inputs (“Analogue
Input Function”). The number that follows the caption “AIF.” is the code to set in
the parameter that configures the function of the desired analogue input.

AOF It identifies a function for the configuration of the analogue outputs (“Analogue
Output Function”). The number that follows the wording “AOF.” is the code to
be set in the parameter that configures the function of the desired analogue
output.

DIF It identifies a function for the configuration of the digital inputs (“Digital Input
Function”). The number that follows the caption “DIF.” is the code to set in the
parameter that configures the function of the desired digital input.

DOF It identifies a function for the configuration of the digital outputs (“Digital Output
Function”). The number that follows the caption “DOF.” is the code to set in the
parameter that configures the function of the desired digital output.

DTC It indicates a diagnostic code received from the engine control unit (ECU) via
CAN bus (“Diagnostic Trouble Code”).

ECU It indicates the engine electronic control unit (“Engine Control Unit”).

EVT It identifies an event stored within the historical records. The number that follows
the caption “EVT.” is the numeric code of the event.

GCB This term identifies the circuit breaker that connects the genset to the load (or
to the parallel bars in case of plants with more gensets) (“Genset Circuit
Breaker”).

MCB This term identifies the circuit breaker that connects the mains to the load
(“Mains Circuit Breaker”).

MGCB It indicates the circuit breaker that connects the parallel bars of the gensets to
the load (“Master Genset Circuit Breaker”).

MPM See the description of the type of plant in [8].

MPtM See the description of the type of plant in [8].

14 MC200 Technical Manual EAAM0578EN


MPtM + MSB See the description of the type of plant in [8].

MSB See the description of the type of plant in [8].

MSB + MSTP See the description of the type of plant in [8].

PMCB It identifies the communication bus (by SICES) that allows all devices exchange
information to manage the parallel functions described in the document [8]
(“Power Management Communication Bus”).

SPM See the description of the type of plant in [8].

SPtM See the description of the type of plant in [8].

SPtM + SSB See the description of the type of plant in [8].

SSB See the description of the type of plant in [8].

SSB + SSTP See the description of the types of plant in [8].

1.5
In this manual, a vertical bar on the right of the paragraphs signals the modifications, with
respect to the previous version. The modifications on the fields of a table are highlighted with
a grey background.

1.6
Several parts of this manual refer to the controller's software revisions. These revisions are
marked with the assigned SICES code (shown on the rear panel of the controller). The format
of the code is EB0250270XXYY, where “XX” is the main version and “YY” is the minor version.
Thus, the code EB02502700100 refers to the controller software release "1.00". The page
“S.03” of the TFT display also shows the software revision.

MC200 is a “dual processor” device and uses two different firmwares:

• EB0250270XXYY: for the main processor that deals with the operation management
and the user interface (System controller).
• EB0250252XXYY: for the minor processor that deals with the electrical measurements
and the related protections (Measure Engine).

MC200 Technical Manual EAAM0578EN 15


2
MC200 Front view

MC200 Rear view

16 MC200 Technical Manual EAAM0578EN


MC200 Upper view

MC200 Lower view

MC200 Technical Manual EAAM0578EN 17


3
INFORMATION! GND refers to the potential of the terminal JC-1

Supply power voltage +VBATT.


Operation. From 7 to 32Vdc with continuous operation.
The device identifies the plant operation at 12 or 24V to manage its alarms when
powered up and whenever OFF/RESET mode is selected.
Protection against polarity reversal with built-in self-resetting fuse.
Resolution of the measurement of the battery voltage to 12 bits.
Starting minimum voltage. The operation is guaranteed during the engines start up to Vbatt=5VDC for an
undefined time.
Power consumption in stand- Display minimum brightness:
by. 350mA @ 13.5 Vdc
200mA @ 27 Vdc

Display maximum brightness:


420mA @ 13.5 Vdc
225mA @ 27 Vdc
Maximum power consumption Display minimum brightness:
during operation (relays, horn, Max. 670mA @ 7 Vdc
digital inputs activated; static 375mA @ 13.5 Vdc
outputs not activated). 235mA @ 27 Vdc

Display maximum brightness:


Max. 810mA @ 7 Vdc
440mA @ 13.5 Vdc
260mA @ 27 Vdc
Mains and generators’ bars voltage inputs.
Measurement of the L-N and L-L phases voltages.
Measurements of the neutral voltages referred to the device supply negative.
Sampling frequency. 10Khz.
Scale. Adjustable through the device parameters between LV (100V) and HV (400V).
Type of measurement. True RMS measurements (TRMS).
Input impedance. > 0,8 MΩ L-N
> 1,3 MΩ L-N
> 0.8 MΩ L-GND
> 0.5 MΩ N-GND
Maximum voltages applicable. MAX 300Vac in CAT.IV for measurements L-N.
MAX 520Vac in CAT.IV for measurements L-L.
MAX 600Vac in CAT.III for measurements L-L.
Maximum voltages measurable Max 448 Vac for measures L-N (with voltage N-GND = 0 Vrms).
with scale HV.
Maximum voltages measurable Max 147 Vac for measures L-N (with voltage N-GND = 0 Vrms).
with scale HV.
Max tension in Common-Mode Max 100 Vrms.
from GND with HV scale.
Max tension in Common-Mode Max 80 Vrms.
from GND with HV scale.

18 MC200 Technical Manual EAAM0578EN


Connection modes. 3 phases 4 wires.
3 phases 3 wires.
Single-phase 2 wires.
Aron insertion with 2 voltage transformers.
Measurement resolution. 12 bit.
Measurement accuracy. <0,5% F.S.
Current measurement inputs.
3 inputs with internal CT and common CTs ratio.
1 independent input with internal CT and specific ratio that can be used to
measure current / power for mains / loads / gensets or for any other auxiliary
source.
Internal amplifier with automatic change of scale for currents lower than 1,2Aac
and higher than 1,5Aac.
It is required the use of current transformers with a secondary current from 1A to
5A.
Scale. 1Aac or 5Aac (automatically selected from the device).
Measurement range. Up to 7Aac.
Type of measurement. True RMS measurements (TRMS).
Auto-consumption. < 1VA.
Maximum currents allowed. + 40% of the rated current.
Possible sinusoidal transient voltage surges up to 20 Aac with progressive loss
of the measurement accuracy depending on the amplitude of the surge.
Measurement resolution. 12 bit.
Measurement accuracy. <0,2% F.S.
Frequency measurements.
50 or 60Hz nominal frequencies measured by L1-L2 phase voltages, for both the
mains and the generators’ bars inputs.
In case of single-phase systems, the controller measures the frequency on the
L1 voltage with respect to N (connected in place of L2).
Frequency minimum sensitivity
on mains voltage inputs.
Rated voltage 100Vac Rated voltage 400Vac
8 Vrms L1-N @ 50Hz 24 Vrms L1-N @ 50Hz
14 Vrms L1-L2 @ 50Hz 41 Vrms L1-L2 @ 50Hz

8 Vrms L1-N @ 60Hz 8 Vrms L1-N @ 60Hz


16 Vrms L1-L2 @ 60Hz 43 Vrms L1-L2 @ 60Hz

MC200 Technical Manual EAAM0578EN 19


Frequency minimum sensitivity
on the generators’ bars voltage
inputs. Rated voltage 100Vac Rated voltage 400Vac
1 Vrms L1-N @ 10Hz 1,2Vrms L1-N @ 10Hz
1.7 Vrms L1-L2 @ 10Hz 2 Vrms L1-L2 @ 10Hz

5 Vrms L1-N @ 50Hz 13 Vrms L1-N @ 50Hz


9 Vrms L1-L2 @ 50Hz 22 Vrms L1-L2 @ 50Hz

6 Vrms L1-L2 @ 50Hz 18 Vrms L1-N @ 60Hz


10 Vrms L1-L2 @ 60Hz 31 Vrms L1-L2 @ 60Hz

Measurement resolution. 0.1Hz ± 50ppm, 35ppm/C typical.


Digital inputs 01-08.
8 opto-insulated digital inputs with same supply, internal supply terminal
connected to the device positive JC (2) +Vbatt.
They are active when the input is connected to the supply negative GND. When
they are open, the inputs terminals voltage is like Vbatt.
Activation/deactivation 2,5VDC.
threshold.
Typical current with closed 5,3mA @ +Vbatt= 13.5Vdc
contact. 11,5mA @ +Vbatt= 27Vdc
Input signal delay. Adjustable by the related parameter for each input.
Digital inputs 09-18.
Two groups of 5 opto-insulated inputs with two separated common supplies,
which can be connected to GND (active inputs to +Vbatt) or to +Vbatt (active
inputs to GND).
Two selectors (S2 and S3) must be set to configure two groups of inputs as
Common Plus or as Common Negative.
Activation/deactivation 2,5VDC.
threshold.
Typical current with closed 5,3mA @ Vbatt= 13.5Vdc
contact. 11,5mA @ Vbatt= 27Vdc
Input signal delay. Adjustable by the related parameter for each input.
Digital outputs 01-04.
Type of output. 4 independent static outputs to battery positive.
The positive supply terminal of the device (JC-2 +Vbatt) supplies the output
current.
All relay outputs are adjustable by parameter.
Rated supply. Maximum 500mAdc @ 32Vdc for each output

Output resistor (status ON). Max 350mΩ.


Leakage current (status OFF). Max 5uA@32Vdc.
Protections. Internal current limited to about 4A maximum on transients >150us.
Thermal protection, short circuit, overvoltage and inverted polarity.
Digital outputs 05-13.

20 MC200 Technical Manual EAAM0578EN


Type of output. 9 independent static outputs to battery negative.
The negative supply terminal of the device (JC-1 GND) supplies the output
current.
All relay outputs are adjustable by parameter.
Rated supply Max. 280mAdc @ 32Vdc for each output.
Total maximum current for all activated outputs 2A @ 50°C.
Output resistor (status ON). Max 500mΩ.
Leakage current (status OFF). Max 1uA@32Vdc.
Protections. Internal current limited to 2,2A typical.
Thermal protection, short circuit, overvoltage with Auto Restart.
Inverted protection polarity.
Digital outputs 14 - Output Hardware Watch-Dog.
Type of output. 1 static outputs to battery negative.
The negative supply terminal of the device (JC-1 GND) supplies the output
current.
If enabled through the selector S4, the output works as a watchdog system
hardware-independent.
If the watchdog is enabled (S4=ON) and the device works correctly, the output is
activated.
If the device is blocked and/or does not refresh the watchdog circuit for a time
higher than 5 seconds, the output fails.
If the device is turned off, the output immediately fails.
If the watchdog is disabled (S4=OFF) the status of the output depends on its
configuration.
Rated supply. Max. 280mAdc @ 32Vdc.
Total maximum current for all activated outputs 2A @ 50°C.
Output resistor (status ON). Max 500mΩ.
Leakage current (status OFF). Max 1uA@32Vdc.
Protections. Internal current limited to 2,2A typical.
Thermal protection, short circuit, overvoltage with Auto Restart.
Inverted protection polarity.
Digital outputs 15 and 16.
Type of output. 2 relays with NO contacts and one positive common terminal.
The positive common terminal has also the function of input for the emergency
stop. The page S.15 of the display shows the measurement of the voltage on the
common input (EM-S).
All outputs are adjustable by parameter.
Rated supply. Max. 3A @ 30Vdc for each output.

Protections. Self-restoring fuse and integrated opening power-surge protection diodes.

Digital outputs 17 and 18.


Type of output. 2 relays with dry contacts for the contactors command.
All relay outputs are adjustable by parameter.
Rated supply. Max. 10A @250Vac.

Analogue inputs 01-02.


Type of input. 2 differential analogue inputs 0...10Vdc.
Both inputs offer the possibility of differential measurement to compensate the
differences of negative measurement with respect to GND.
There’s a 5Vdc (JU-1) regulated and protected output and an internal GND
terminal (JU-2) that can be used as reference for external potentiometers on the
two analogue inputs.

MC200 Technical Manual EAAM0578EN 21


Measurement range. 0 - 10Vdc.
Compensation range. From -10Vdc to +6Vdc.
Input impedance. > 470kΩ.
Frequency. 10kHz.
Resolution. 12 bit.
Measurement accuracy. <0,4% F.S.
Analogue inputs 03-07.
Type of input. 4 adjustable analogue inputs.
Adjustable as voltage, current (with external resistor) and digital inputs.

Voltage inputs. Measurement range 0 – 10Vdc with error < 0,2%.


Input impedance: >470kΩ.
Current inputs. Measurement range 0 - 20mA with 500Ω external resistor.
Frequency. 10kHz.
Resolution. 12 bit.
Digital outputs 01-02.
Type of output. 2 galvanically insulated ±10Vdc voltage outputs.
Each output has an integrated trimmer to reduce the maximum output voltage,
preserving in this way signal resolution.
Regulation range. From -1Vdc to +10Vdc.
Resolution. 16 bit.
Minimum load impedance. >10 kΩ.
Insulation rated voltage. Max operating 560Vdc.
3KVdc on transient < 60s.
Insulation resistor. >1000MΩ @ 500Vdc.
RS232 Communication interface.
Type of interface. 1 RS232 serial port standard TIA/EIA, not insulated on DB connector 9 poles
male CANON.
Electrical signals. TX. RX, DTR, DSR, RTS, GND.
Settings. Baud rate selectable by parameter: 300, 600, 1200, 2400, 4800, 9600*, 19200,
38400, 57600, 115200 bps.
Parity: None*, Even, Odd.
Stop bit: 1*,2.
* Default Setting.
Type of transmission. Modbus RTU Slave*, Modem AT
* Default Setting.
RS485 Communication interface.
Type of interface. 1 RS485 serial port standard TIA/EIA, with galvanic insulation.
Terminal resistor connectible with S5 switch.
Electrical signals. DATA+ (A), DATA– (B).
Settings. Baud rate selectable by parameter: 300, 600, 1200, 2400, 4800, 9600*, 19200,
38400, 57600, 115200 bps.
Parity: None*, Even, Odd.
Stop bit: 1*,2.
* Default Setting.
Type of transmission. Modbus RTU Slave*.
* Default Setting

22 MC200 Technical Manual EAAM0578EN


Insulation voltage. Max operating 560Vdc.
1KVdc on transient < 60s.
USB 2.0 Communication interface.
Type of interface. 1 USB2.0 serial port not insulated, usable in Function or Host mode.
Selection of the operating mode through SW5 dipswitch.
The USB port cannot be used as Function and Host simultaneously.
Function Mode. Connection to PC by Sices Driver.
USB Connector Type B.
Type of transmission Modbus RTU Slave.
Host Mode. Pen Driver Management.
USB Connector type A.
Max current supplied 350mA@5Vdc with overcharge automatic protection.
Host function is not yet supported.
Maximum distance. 6m (20 feet).
CAN bus Communication interface.
Type of interface. 2 CAN bus ports with galvanic insulation.
Terminal resistor connectible with S1 and S6 switch.
CAN bus0. CAN bus connection with protocol Sices for the communication with I/O
expansion modules.
CAN bus1. CAN bus connection with protocol Sices PMCBus for the communication with
other controllers.
Rated impedance. 120Ω.
Insulation voltage. Max operating 560Vdc.
1KVdc on transient < 60s.
Ethernet Communication interface.
Type of interface. 1 Ethernet interface 10/100Mbps full-duplex 10T/100Tx Auto.
HP Auto-Mdix support.
Compliant IEE802.3/802.3u (Fast Ethernet).
Compliant ISO802-3/IEEE802.3 (10BASE-T).

Insulation voltage. 1500VRMS.


HMI Communication interface (optional).
Type of interface. 1 RS485/422 serial port not insulated for the connection between the SCM
(System Control Module) device and the HMI (Human Machine Interface) panel.
Rated impedance. 120Ω.
Display.
Type of display. TFT 4.3” colour display with white leds backlight.
Resolution. 480 x 272.
Pixel size. 0,066 x 0,198 mm.
Visual area dimensions. 95 x 54 mm.
Environmental conditions.
Operating temperature. From -25°C to +60°C.
Stock temperature. From -30°C to +80°C.
Box.
Material. Nylon66 + 30% fiberglass.
Size. 247(L) x 187(H) x 70(D) mm.
Weight. 1100g.

MC200 Technical Manual EAAM0578EN 23


Protection degree. IP55 with gasket for the front panel.
IP20 for the panel interior.

3.1
Mains and generators’ bars
1Vrms.
voltages.
Currents. Min. 0.1A (it depends on the CT ratio).
Mains and generators’ bars
0.1Hz ± 50ppm, 35ppm/C typical.
frequencies.
Powers Min. 0.1 kW/kVA/kvar (it depends on the CT ratio).
Power Factors. 0.01.
Energies. 1 kWh/kvarh.

24 MC200 Technical Manual EAAM0578EN


4
4.1
The device requires permanently mounting on a panel. The rear panel of the device must be
accessible only by keys or tools and only by authorized personnel for maintenance operations.
It must be impossible to remove the controller without tools.

The mounting dimensions for the installation are 218x159mm. Four hooks with screws carry
out the mounting: once the device is positioned, insert the hooks in the holes on the sides and
tighten the screws. Pay attention not to tighten excessively the screws in order not to damage
the hook on the device.

4.2
Due to the high voltages connected to the measurement circuits of the controller, all
conductive parts of the electrical panel should be connected to the protective earthing
through permanent connections.

The installation of an overcurrent protection device is required for each phase of the mains
and generator’s bars voltage inputs. You can use 1A fuses.

MC200 Technical Manual EAAM0578EN 25


The section of the protective earthing conductor should be at least equal to the section of
cables used to wire mains or generators voltages to the control panel. In addition, it must
comply with the limit value of the overcurrent protection used.

For CAT.IV applications, the maximum phase-to-neutral voltage allowed is 300Vac, while the
phase-to-phase voltage is 520Vac. The maximum voltage related to the protective earthing is
300 Vac.

For CAT.III applications, the maximum phase-to-neutral voltage allowed is 345Vac, while the
phase-to-phase voltage is 600Vac. The maximum voltage related to the protective earthing is
600 Vac.

The device can operate in CAT.IV or CAT.III only if the supply negative terminal of the device
and the neutral terminal of the mains and generator’s bars are connected to the protective
earthing.

26 MC200 Technical Manual EAAM0578EN


5

N. NAME DESCRIPTION CONNECTOR

1 JA Communication interface 9 Poles Male Canon.


RS232.
2 JC+JB Power supply + functional 2 poles x 2,5mm2 Screw terminal +
earth. faston.
3 JD Digital outputs 1-4. 4 poles x 1,5mm2 Screw terminal.
4 JE Current inputs 1-3. 6 poles x 2,5mm2 Screw terminal.
5 JF Generators’ bars voltages. 4 poles x 2,5mm2 Screw terminal.
6 JG Mains voltages. 4 poles x 2,5mm2 Screw terminal.
7 JH Digital outputs 17-18. 6 poles x 2,5mm2 Screw terminal.
8 JI Auxiliary current input. 2 poles x 2,5mm2 Screw terminal.
9 JJ Digital outputs 15-16. 4 poles x 2,5mm2 Screw terminal.
Analogue input 7.
10 JK Analogue inputs 3-6. 9 poles x 1,5mm2 Screw terminal.
11 JL Digital inputs 1-8 8 poles x 1,5mm2 Screw terminal.
12 JM CAN bus for I/O expansions. 3 poles x 2,5mm2 Screw terminal.
13 JNA USB 2.0 Function Interface. USB – B.
14 JO Digital inputs 14-18. 6 poles x 1,5mm2 Screw terminal.
15 JP Digital inputs 9-13. 6 poles x 1,5mm2 Screw terminal.
16 JQ Digital outputs 10-14. 5 poles x 1,5mm2 Screw terminal.
17 JR Digital outputs 5-9. 5 poles x 1,5mm2 Screw terminal.
18 JS Analogue output 2. 3 poles x 2,5mm2 Screw terminal.
19 JT Analogue output 1. 3 poles x 2,5mm2 Screw terminal.

MC200 Technical Manual EAAM0578EN 27


20 JU Analogue inputs 1-2. 6 poles x 1,5mm2 Screw terminal.
22 JW RS485 Communication 4 poles x 1,5mm2 Screw terminal.
interface.
23 JX PCMBUS Interface for parallel 3 poles x 2,5mm2 Screw terminal.
functions.
24 JNB USB 2.0 Host Interface. USB – A.
25 JT Ethernet Interface. RJ45.

5.1

5.2
The connection to the functional earth JB is mandatory to guarantee the proper operation of
the device and the compliance with the EU Electromagnetic Compatibility Regulation.

The connection is functional and not protective; therefore, the cross-section of the wire can be
smaller. Connect the other end of the wire to a metal screw of the electrical panel (which must
be grounded) next to the JB or to a grounding line, using the shortest cable possible.

28 MC200 Technical Manual EAAM0578EN


5.3

The JC connector is the supply connector: connect a DC supply (usually the engine starter
batteries) to the 1-GND terminal (negative) and to the 2-+BATT terminal (positive).

The minus terminal 1-GND is the reference and the common return of the digital inputs, outputs
and current and voltage measurements. It must be connected to the protection earth. The
systems that require insulation between the battery negative and the protection earth can be
used but can generate operating problems and may require care, as the use of insulation
transformers for the voltage measurements of the mains and of the generators’ bars.

Although a built-in self-resetting fuse protects the device, we recommend using a fuse for the
protection of the positive line 2-+BATT. The power supplied by the JD static outputs flows
through the 2 +BATT positive input, so you must pay attention to the fuse dimension.

At power on, the controller automatically detects if the supply nominal voltage is 12 or 24V for
managing the related logics and alarms. In addition, the controller repeats the detection each
time you switch to the OFF/RESET mode.

NOTE: when installing, connect the supply voltage positive only after opening all fuses
available in the panel.

5.4
The controller is equipped with a series of 18 opto-insulated digital inputs, which are fully
configurable.

Besides these 18 inputs, it is possible to use the analogue inputs JK and JU as digital inputs,
if not used as measurement inputs (see par. 5.6) and, with different modes, the JJ-4 terminal
too (see par. 5.6.3).

It is possible to share the same command signal of an input with different devices (for example,
one signal for three MC200). If you use the inputs of the JO and JP connectors (positive
common), it is necessary to separate them with diodes, as in the figure below. This avoids the
wrong activation of the input when one of the devices is switched off. If the JL connector inputs
are used, the diode can be omitted as it is already provided internally.

MC200 Technical Manual EAAM0578EN 29


It’s also possible to increase the number of digital inputs by adding up to two optional DITEL
16 IN modules (connected by CAN bus) for a total of 32 digital inputs (see par.5.8).

There are also 16 “virtual” digital inputs, which do not exist on the controller or on the
expansion modules, but they are represented by the result of the logic combination of physical
or virtual inputs, outputs, alarms or logical statuses, by means of the proper programming by
BoardPrg3 or through the internal PLC. The virtual inputs can be configured as functions and
used as physical inputs; see par.5.4.4.

The status of the digital inputs, virtual inputs and inputs available through DITEL modules is
displayed at pages S.11 and S.12 (0=output not active, 1=output active).
5.4.1 JL - Digital inputs 1-8

They are a group of eight opto-insulated digital inputs with common terminal internally
connected to the positive supply terminal of the device +Vbatt. It is possible to activate the
inputs by connecting them to the battery negative (GND). When it is left floating, the input
brings itself to +Vbatt. Avoid situations where intermediate or undefined voltage levels can
occur.

These inputs already have a series diode that allows connecting them directly among them.

The inputs are wholly configurable (see par. 5.4.5).

By default, the functions of the JL input on the MC200 controller are the following:

Terminal Digital input Default function

JL-1 01 DIF.3003 - “Status of MGCB circuit breaker”.


JL-2 02 DIF.3002 - “Status of MCB circuit breaker”.
JL-3 03 DIF.0000 - “Not used”.
JL-4 04 DIF.2702 - “Enables the load function”.
JL-5 05 DIF.0000 - “Not used”.
JL-6 06 DIF.0000 - “Not used”.
JL-7 07 DIF.0000 - “Not used”.
JL-8 08 DIF.0000 - “Not used”.

30 MC200 Technical Manual EAAM0578EN


5.4.2 JP - Digital inputs 9-13

They are a group of five opto-insulated digital inputs with common available on the terminal. It
is possible to activate the inputs by connecting the terminal to the battery negative: in this way,
the common terminal JP-6 must be connected to the battery positive and the selector S3 must
be set on common positive.

Alternatively, it is possible to activate the inputs by connecting them to the battery negative: in
this case, the common terminal JP-6 must be connected to the battery negative and the
selector S3 must be set on common negative.

The five inputs are wholly configurable (see par. In fact, every digital input can have an
AND/OR logic associated, which determines its status (see par. 5.4.5).

By default, the functions of the JP input on the MC200 controller are the following:

Terminal Digital input Default function

JP-1 09 DIF.0000 - “Not used”.


JP-2 10 DIF.0000 - “Not used”.
JP-3 11 DIF.0000 - “Not used”.
JP-4 12 DIF.0000 - “Not used”.
JP-5 13 DIF.0000 - “Not used”.
JP-6 - Positive or negative common input terminal

5.4.3 JO - Digital inputs 14-18

They are a group of five opto-insulated digital inputs with common available on the terminal. It
is possible to activate the inputs by connecting the terminal to the battery negative: in this way,
the common terminal JO-6 must be connected to the battery positive and the selector S2 must
be set on common positive.

Alternatively, it is possible to activate the inputs by connecting them to the battery negative: in
this case, the common terminal JO-6 must be connected to the battery negative and the
selector S2 must be set on common negative.
The five inputs are wholly configurable (see par.5.4.5).

MC200 Technical Manual EAAM0578EN 31


By default, the functions of the JO inputs on the MC200 controller are the following:

Terminal Digital input Default function

JO-1 14 DIF.0000 - “Not used”


JO-2 15 DIF.0000 - “Not used”
JO-3 16 DIF.0000 - “Not used”
JO-4 17 DIF.0000 - “Not used”
JO-5 18 DIF.0000 - “Not used”
JO-6 - Positive or negative common input terminal

5.4.4 Virtual digital inputs


Besides 18 physical digital inputs and 32 available with the DITEL modules, the controller
manages 16 virtual digital inputs. They are managed by the controller exactly as they were
physical inputs (without limitations), but the virtual inputs status is not acquired by the
hardware, but determined via software. In fact, each virtual digital input can be associated to
an AND/OR logic that determines the status (see par. 5.5.7) or to a logic used by the PLC
program.

The status of the virtual inputs is displayed at pages S.11 (0=output not active, 1=output
active).

Example of the use of an AND/OR logic. Let us suppose we would like to activate a warning if
the mains exceed the tolerance thresholds while the MGCB is closed. Let us use the virtual
digital input #1 (as example).

 Using the BoardPrg3 software we associate an AND/OR logic configured as AND to


the virtual digital input #1, with the following list of conditions:

▪ ST.066 (“MGCB status”)

▪ ST.017 (“Mains absent or out of tolerance”).

 Therefore, the virtual digital input will be active when the MGCB is closed and the
mains is out of tolerance.

 Let us set the DIF.4001 function (“Generic warning”) within the P.2151 parameter.

 Let us set the desired delay (for example 0.5 s) within the P.2152 parameter.

 Let us set the alarm message (for example “mains voltage warning”) within the P.2153
parameter.
5.4.5 Digital inputs configuration
The digital inputs 9-18 (JO and JP) are by default configured as inputs with common plus and
therefore with activation status equal to the digital inputs 1-8 (JL). It means that all the digital
inputs are considered “active” only when the related terminal is connected to the supply
negative of the controller; they are considered “not active” when the related terminal is left
open.

The logic status of the input can be reversed with respect to the physical status by
ticking the “Reversed polarity” box in the input configuration page on BoardPrg3.

The box is only visible if the function selected is other than DIF.0000 – “Not used”.

It is also possible to reverse the logic status (always individually for each input), directly by the
controller, using the parameters:
Parameter Inputs
P.2000 01...16
P.2050 17...18
P.2100 Analogue inputs used as digital ones
P.2200 DITEL #01
P.2250 DITEL #02

32 MC200 Technical Manual EAAM0578EN


Said parameters have a bit for each output:

 A bit set to zero means that the related input is “active” when it is connected to the
negative supply of the controller.

 A bit set to one means that the related input is considered “active” when it is not
connected to anything (it will become “not active” if it is connected to the supply
negative terminal of the controller).

By default, all bits are set to zero.

Each input (both physical and virtual) has three parameters associated:

 One parameter that configures its function (P.2001 for input 1).

 A parameter that configures the delay time (P.2002 for the input 1).

 A parameter that configures a message to show on the display (P.2003 for the input
1).

See document [1] for the parameters list.

The management of the physical and virtual inputs is the same, except that the virtual inputs
cannot be inverted.

The status of the digital inputs, virtual inputs and inputs available through DITEL modules is
displayed at pages S.11 and S.12 (0=output not active, 1=output active).

The controller uses the parameters that configure the delay and the message for an input only
for certain features of that input. The following table highlights when they are used.

NOTE: in BoardPrg3, the boxes for the delay and the message are always displayed,
even if they are not used by the controller.

The input functions that start with 3xxx are related to the functioning status; those that start
with 4xxx activate alarms (alarms, unloads or warnings).

The following function, not directly linked to the operation sequences of the controller, are
selectable for any digital output:

• DIF.0101 - “Used by PLC”. It is possible to use the digital inputs of the controller only
for the PLC logics, without the controller normal operation sequence using them. In
these cases, it is possible to leave the inputs configured with the function DIF.0000
(“Not used”). Therefore, there is the risk to reuse the input for other purposes, as it
seems to be available: for this reason, there is the DIF.0101 function (to indicate the
input used, even if not directly by the controller).

Input function
Name Delay Message Description
xx.
DIF.0000 Not used. Input not used.
DIF.0101 Used by PLC. Input used by the internal PLC logic.
DIF.1001 Request for MGCB closure. It only acts in MAN mode, used to control the manual closing
of the circuit breaker. If there is no input configured with the
function DIF.1002, this input works as toggle: it commands
the closure of the breaker when the same is open and
commands the opening when the same is closed. The
controller closes the circuit breaker when the input becomes
active.
DIF.1002 Request for MGCB opening. It only acts in MAN mode, used to control the manual opening
of the circuit breaker. The controller opens the circuit breaker
when the input becomes active.
DIF.1003 MGCB controlled externally. It indicates to the controller that an external logic temporarily
controls the circuit breaker: the controller will acknowledge it
without activating faults.

MC200 Technical Manual EAAM0578EN 33


Input function
Name Delay Message Description
xx.
DIF.1004 Synchronization request MGCB. It is used when an external device controls the circuit breaker:
the external device activates this input if it wants the controller
to carry out the synchronization and supply the
“synchronized” contact (or if the controller needs to manage
the analogue input connected to an external synchronizer).
DIF.1005 MGCB closure allowed. Yes This function allows an external logic to prevent or to delay
the circuit breaker closure. If this input is configured, the
controller activates an output configured as “ready to close”
(DOF.3083) and waits for external acknowledge. If a delay is
configured for this input, after this time the controller goes on
with closure command even without acknowledgement.
DIF.1006 MGCB opening allowed. Yes This function is used only when the opening of the circuit
breaker will result in a blackout on the loads. Before opening
MGCB, the device activates an output configured as “ready to
open” (DOF.3084) and waits for external acknowledge. If a
delay is configured for this input, after this time the controller
goes on with opening command even without
acknowledgement.
DIF.1031 Request for MCB closure. It only acts in MAN mode, used to control the manual closing
of the circuit breaker. If there is no input configured with the
function DIF.1002, this input works as toggle: it commands
the closure of the breaker when the same is open and
commands the opening when the same is closed. The
controller closes the circuit breaker when the input becomes
active.
DIF.1032 Request for MCB opening. It only acts in MAN mode, used to control the manual opening
of the circuit breaker. The controller opens the circuit breaker
when the input becomes active.
DIF.1033 MCB controlled externally. It indicates to the controller that an external logic temporarily
controls the circuit breaker: the controller will acknowledge it
without activating faults.
DIF.1034 Synchronization request MCB. It is used when an external device controls the circuit breaker:
the external device activates this input if it wants the controller
to carry out the synchronization and supply the
“synchronized” contact (or if the controller needs to manage
the analogue input connected to an external synchronizer).
DIF.1035 MCB closure allowed. Yes This function allows an external logic to prevent or to delay
the circuit breaker closure. If this input is configured, the
controller activates an output configured as “ready to close”
(DOF.3081) and waits for external acknowledge. If a delay is
configured for this input, after this time the controller goes on
with closure command even without acknowledgement.
DIF.1036 MCB opening allowed. Yes This function is used only when the opening of the circuit
breaker will result in a blackout on the loads. Before opening
MGCB, the device activates an output configured as “ready to
open” (DOF.3082) and waits for external acknowledge. If a
delay is configured for this input, after this time the controller
goes on with opening command even without
acknowledgement.
DIF.2001 Command for resetting alarms. When the input becomes “active”, the controller carries out a
reset of all faults. That is equivalent to change the controller
mode to OFF/RESET and back again to the desired mode.
DIF.2002 Command for alarm acknowledgment. When the input becomes “active”, the controller silences the
horn and recognizes the faults as the ACK button was kept
pressed on the device display.
DIF.2029 TEST without load (pulse). When the input becomes “active” with the controller in AUTO,
the test of the generators is performed without load, not
depending from the value set in parameter “P.0222 – Enable
generator supply on test”. The test has a configured duration
with parameter P.0420: if set to zero, this test is never
performed. If there is a second activation of the input during
the test, the test is immediately stopped.
DIF.2030 TEST with load (pulse). When the input becomes “active” with the controller in AUTO,
the test of the generators is performed with load, not
depending from the value set in parameter “P.0222 – Enable
generator supply on test”. The test has a configured duration
with parameter P.0420: if set to zero, this test is never
performed. If there is a second activation of the input during
the test, the test is immediately stopped.

34 MC200 Technical Manual EAAM0578EN


Input function
Name Delay Message Description
xx.
DIF.2031 Request for TEST mode. When the input is “active”, the mode of the controller switches
from AUTO to TEST (the input does nothing if the controller is
not in AUTO or if the automatic intervention of the genset is
required). When it becomes inactive, the status changes back
to AUTO. The test will be performed with or without load
based on how configured with parameter P.0222.
DIF.2032 Request for REMOTE START mode. Yes If the input is “active”, the controller operating mode changes
from AUTO to REMOTE START (the input does nothing if the
controller is in OFF/RESET or MAN mode). When it becomes
inactive, the status changes back to AUTO.
DIF.2063 Full override protections. When the input activates, all protections (except some, see
[1]) that cause alarms or unloads become warnings.
DIF.2093 Select the import-export mode. When the input is active, the controller switches to the
“import/export” mode during the parallel with the mains,
whatever is the mode configured in P.0880.
DIF.2096 Transfer to the generators. When the input is active, the controller transfers the load from
the mains to the gensets, then it opens the MCB circuit
breaker.
DIF.2151 Select configuration 1. When the input becomes “active”, the parameter of the
alternative configuration 1 are copied into the work
parameters
DIF.2152 Select configuration 2. When the input becomes “active”, the parameter of the
alternative configuration 2 are copied into the work
parameters
DIF.2153 Select configuration 3. When the input becomes “active”, the parameter of the
alternative configuration 3 are copied into the work
parameters
DIF.2154 Select configuration 4. When the input becomes “active”, the parameters of the
alternative configuration are copied into the work parameters
DIF.2181 Immediate supply. It is used in plants composed by many gensets: if the input is
active, the switch of the users between mains and gensets is
carried out after the closing of the first GCB circuit breaker.
DIF.2251 Manual disconnection of loads. Each time this input become active, the “load shedding”
function disconnects one load (if possible). See the “load
shedding” description for more details.
DIF.2252 Manual re-connection of loads. Each time this input becomes active, the “load shedding”
function reconnects one load (if possible). See the “load
shedding” description for more details.
DIF.2271 Remote OFF. When this input is active, the operating mode of the controller
is forced to OFF-RESET, and it is not possible to use the
pushbuttons on the front panel to change it. Note: when this
input deactivates, if no inputs are configured with the
functions DIF.2272 and DIF.2273, the operating mode is
forced to the one set before the input activation.
DIF.2272 Remote MAN When this input is active, the operating mode of the controller
is forced into MAN and you cannot use the buttons on the
panel to change it.
DIF.2273 Remote AUTO When this input is active, the operating mode of the controller
is forced into AUTO and you cannot use the buttons on the
panel to change it.
DIF.2501 Inhibition of start. When the input is “active”, the automatic start of the
generators is inhibited. The “REMOTE START” mode is not
influenced by this function
DIF.2502 Inhibition of supply. Automatically, when this input is “active”, the opening of the
MGCB circuit breaker is forced (or the opening of all GCBs if
MGCB does not exist or is externally managed), and the
closing of MCB too.
DIF.2701 Enables remote start request. If this input is not active, the controller does not accept to go
to the “REMOTE START” mode.
DIF.2702 Enables the load function. Used in the “load management”. See document [8].
DIF.2704 Disables protections on the 4° current. When this input is “active”, the auxiliary current protection
(normally used for differential protection) is disabled.
DIF.2705 Disables protections on analogue When this input “activates”, the thresholds set on the
measures. analogue measures with bit 13 ON, in the third or sixth
configuration parameter (see par. 5.6.4) don’t cause the
intervention of the relative protections.
DIF.2706 Enables serial port commands. If this input is not “active”, the commands sent by means of
Modbus registers HOLDING REGISTER 101 and 102 are not
accepted.
DIF.2708 Enables PPR thresholds ‘1’. If this input exists but it is not active, the protections for the
parallel with the mains configured with parameters P.0922 e
P.0924 are disabled. See document [8].

MC200 Technical Manual EAAM0578EN 35


Input function
Name Delay Message Description
xx.
DIF.2712 Enables protection 27T (PPR). If this input exists and it is not active, the protection for the
parallel with the mains “27T” is disabled.
DIF.2713 Enables protection 27Q (PPR). If this input exists and it is not active, the protection for the
parallel with the mains “27U & Q” is disabled.
DIF.2721 Enable load shedding. If this input is configured but not active, the “load shedding”
function is disabled.
DIF.2722 Enable peak shaving/lopping. If this input is configured but not active, the “peak
shaving/lopping” function is disabled.
DIF.3002 Status of MCB circuit breaker. Yes It acquires the circuit breaker status which connects the
mains to the users. An input configured in this way is used to
activate a warning in the event of a discrepancy between the
controls to the circuit breaker given by the board and the
status of the same circuit breaker. Warning can be also
issued in this case or, even, depending on the configuration,
the generators can be started in case of MCB closure failure.
It is also used to detect the status of the circuit breaker when
it is commanded by external devices.
DIF.3003 Status of MGCB circuit breaker. It acquires the general circuit breaker status, which connects
the genset parallel bars to the users. It is used for the parallel
logics and to disable the “load management” if the loads are
not connected to the gensets.
DIF.3004 Status of GCB of other gen-sets. Use this input if the gensets must work in parallel with other
gensets controlled by “not Sices” controllers: indicates MC200
that at least another genset has its own GCB closed.
DIF.3101 External sensor for mains. When the input is “active”, the mains is considered “in
tolerance”
DIF.3102 No voltages on parallel bars. Used in parallel plants, where the controller cannot directly
measure the voltage on the parallel bars. The active input
indicates that there is no voltage on the bars.
DIF.3103 External protections for parallel to mains Connect the external device, which manages the protections
of parallel with the mains, to this input. The input must be
active when no protection has triggered.
DIF.3104 No voltages on loads. Used in parallel plants, where the controller cannot directly
measure the voltage on the loads. The active input indicates
that there is no voltage on the loads.
DIF.3201 General status (page 1). Yes When this input is “active”, the controller displays the text set
in the parameters associated to the input on page S.08.
DIF.3202 Important status (page 1). Yes When this input is “active”, the controller displays the text set
in the parameters associated to the input on page S.08, which
is immediately shown.
DIF.3203 General status (page 2). Yes When this input is “active”, the controller displays the text set
in the parameters associated to the input on page S.09.
DIF.3204 Important status (page 2). Yes When this input is “active”, the controller displays the text set
in the parameters associated to the input on page S.09, which
is immediately shown.
DIF.3205 General status (page 3). Yes When this input is “active”, the controller displays the text set
in the parameters associated to the input on page S.10.
DIF.3206 Important status (page 3). Yes When this input is “active”, the controller displays the text set
in the parameters associated to the input on page S.10, which
is immediately shown.
DIF.4001 Generic warning. Yes Yes When the input is active, a warning is issued: the message
shown is the one set in the parameters associated to the
input.
DIF.4002 Generic unload. Yes Yes When the input is active, an unload is issued: the message
shown is the one set by means the related “text” parameter.
DIF.4004 Generic alarm. Yes Yes When the input is active, an alarm is issued: the message
shown is the one set by means the related “text” parameter.
DIF.4005 Warning transmitted to gen-sets. Yes Yes When the input is active, a warning is issued: the message
shown is the one set in the parameters associated to the
input. All the connected genset controllers will activate the
warning “warning from master device”.
DIF.4008 Alarm transmitted to gen-sets. Yes Yes When the input is active, an alarm is issued: the message
shown is the one set by means the related “text” parameter.
All the connected genset controllers will activate the alarm
“alarm from master device”.
DIF.4021 Warning (forces MCB open). Yes Yes When the input is “active” a warning is issued: the message
shown is the one set in the parameters associated to the
input. The controller forces MCB opened.
DIF.4022 Unload (forces MCB open). Yes Yes If the input is active, an unload is issued: the message shown
is the one set in the parameters associated to the input. The
controller forces MCB opened.

36 MC200 Technical Manual EAAM0578EN


Input function
Name Delay Message Description
xx.
DIF.4024 Alarm (forces MCB open). Yes Yes When the input is “active”, if the GCB command is active, a
warning is issued: the message shown is the one set in the
parameters associated to the input. The controller forces
MCB opened.
DIF.4062 Unload (subject to override). Yes Yes When the input is “active”, an unload is normally activated. If
the Override function of the protections is activated, a warning
activates. The message shown is the one set on the
parameters associated to the input.
DIF.4064 Alarm (subject to override). Yes Yes When the input is “active”, an alarm is normally activated. If
the Override function of the protections is activated, a warning
activates. The message shown is the one set by means of the
related parameters.
DIF.4261 Production line opened. Yes When the input is “active”, the controller realises to be no
more in parallel with the mains and stops the genset with an
alarm.

5.5
The controller has eighteen digital outputs: four relay outputs (JJ and JH), four positive static
outputs (JD) and ten negative static outputs (JQ and JR). It is possible to add two DITEL
modules 16 IN, each of which manages up to two DITEL 8 OUT relay modules, for 32
additional outputs, in addition to the one on the controller.
5.5.1 JJ - Digital outputs 15-16
The outputs of the JJ connector are free (not configured) as default, and can be freely
configured by means the parameter of the controller.

The status of these outputs is displayed at pages S.13 (0=output not active, 1=active output).

The default functions of the JJ outputs are:


Terminal Digital output Type Default function
JJ-1 15 Normally open contact, of the relay 15. DOF.0000 – “Not used”.
JJ-2 - Terminal positive common input
JJ-3 16 Normally open contact, of the relay 16. DOF.0000 – “Not used”.
JJ-4 - -

In detail:
5.5.1.1 JJ-2 COMMON PLUS Common positive
Positive input common for outputs 15 and 16, internally protected by self-reset fuse: it is
therefore suggested to protect it with a correct range external fuse. It must be connected to
the positive of the power supply by means of a contact of the emergency button: that is, this
connection must be interrupted by keeping the emergency button pressed. Several emergency
buttons may be used by series connecting them to each other.

Without voltage on that input (that is, pressing the emergency button,), in operational
modes (MAN, AUTO, TEST, etc.) the device generates the alarm AL.048 “A048
Emergency Stop”. It is not possible to configure the controller to deactivate the alarm
for emergency stop.

The voltage at terminal JJ-2 is measured for the management of the relative alarm and is
displayed on page S.15 at EM-S

Attention: do not use the terminal as common negative for the two relays outputs. Inside, in
effect, are damper diodes for the opening over voltages that would enter in conduction and
could be immediately damaged.
5.5.1.2 JJ-1 Digital output 15
Positive relay output, with maximum capacity of 3A @30VDC. Integrated internal diode for
damping opening over voltages. This terminal shows the battery voltage present on connector
JJ-2; although one is already present inside, with particularly inductive loads (remote control
switches, electromagnets, etc.) it is advisable to use a damper diode for opening over voltages.

MC200 Technical Manual EAAM0578EN 37


Attention: for currents over the nominal one use an external restart relay.

The output can be freely configured by means of parameter P.3015, see paragraph 5.5.6 and
document [1] for the parameters list.
5.5.1.3 JJ-3 Digital output 16
Positive relay output, with maximum capacity of 3A @30VDC. Integrated internal diode for
damping opening over voltages. This terminal shows the battery voltage present on connector
JJ-2; although one is already present inside, with particularly inductive loads (remote control
switches, electromagnets, etc.) it is advisable to use a damper diode for opening over voltages.

Attention: for currents over the nominal one use an external restart relay.

The output can be freely configured by means of parameter P.3016, see paragraph 5.5.6 and
document [1] for the parameters list.
5.5.2 JH - Digital outputs 17-18: outputs for the command on the loads switching

The controller uses two 10A@250Vac relays in clean contact for the switching commands of
the loads. On JH connector, a clean contact in exchange for each of the two relays is available.

The default functions of the outputs on the controller are:


Terminal Digital output Type of output Default function
JH-1 Normally open contact of the relay 17. DOF.2034 - “Stable
JH-2 17 Normally closed contact of the relay 17. closing command for
MGCB”
JH-3 Common contact of the relay 17.
JH-4 Normally open contact of the relay 18. DOF.2004 - “Stable
JH-5 18 Normally closed contact of the relay 18. opening command for
MCB”
JH-6 Common contact of the relay 18.

The output 17 is necessary to (as default) connect the loads to the generator. The output 18
is necessary to (as default) connect the loads to the generator. Both the relays can be used
for other functions.

The normally closed contact of output 18 and the normally open contact of output 17 should
be used; in this way, even with deactivated controller, however the loads remain connected to
the electric mains.

For the circuit breakers management see par. 7.8

If there is only one circuit breaker, the MCB output (terminals 4... 6 of JH) is not used, it can
be therefore associated to a different function (see par. 5.5.6).

38 MC200 Technical Manual EAAM0578EN


5.5.3 JD - Digital inputs 1-4

They are four digital outputs, wholly programmable. When activated, they bring themselves to
the positive supply voltage which is on the JC-2 supply terminal. The nominal capacity of each
single output is 500mA: the total current is therefore 2A. Do never overpass these values.
The outputs are independent and individually protected from overloads, short circuits, polar
inversion and overheating. The protection of overload intervenes limiting the current peak at
an instantaneous value of 4A, to allow the activation of loads which need a higher transitory
current than the nominal. When this condition is lasting, after 150us the gradual intervention
of the thermal protection begins, until the output is turned off.
With inductive loads (power relays, electro-magnetic actuators), although already internally
present, it is advisable to use damping diodes of the opening over voltages.
All the current supplied by the outputs must be kept available by means of JC-2 +BATT;
ensure that the eventual protection fuse on the supply positive have adequate capacity
and intervention time to protect both the outputs and the device in any usage condition.
The default functions of these outputs are:
Type of Default function
Terminal Digital output
output
JD-1 01 DOF.0000 - “Not used”.
JD-2 02 Static output DOF.0000 - “Not used”.
at battery
JD-3 03 positive DOF.0000 - “Not used”.
JD-4 04 DOF.0000 - “Not used”.

5.5.4 JO - Digital inputs 5-9

They are four digital outputs, wholly programmable. When activated, they bring themselves to
the negative supply voltage which is on the JC-1 GND supply terminal. Through this terminal,
all current supplied by the active outputs flows. The nominal capacity of each output is of
280mA, while the total current with all active outputs of JR and JQ (Outputs 5-14) must be
maintained below 2A. Do never overpass these values.

The outputs are independent and individually protected from overloads, short circuits, polar
inversion and overheating. The overload protection intervenes limiting the current peak at an
instantaneous value of 2.2A. When this condition is lasting, the intervention of the thermal
protection starts, which gradually reduces the current to keep the temperature of the output
driver within its maximum limit.

With inductive loads (power relays, electro-magnetic actuators) it is advisable to use damping
diodes of the opening over voltages.

The default functions of the outputs are:

MC200 Technical Manual EAAM0578EN 39


Terminal Digital output Type of output Default function
JR-1 05 DOF.0000 - “Not used”.
JR-2 06 DOF.0000 - “Not used”.
static output to
JR-3 07 DOF.0000 - “Not used”.
battery negative.
JR-4 08 DOF.0000 - “Not used”.
JR-5 09 DOF.0000 - “Not used”.

5.5.5 JQ - Digital inputs 10-14

They are four digital outputs, totally programmable. When activated, they bring themselves to
the negative supply voltage which is on the JC-1 GND supply terminal. Through this terminal,
all current supplied by the active outputs flows. The nominal capacity of each output is of
280mA, while the total current with all active outputs of JR and JQ (Outputs 5-14) must be
maintained below 2A. Do never overpass these values.

The JQ-5 terminal can be used, alternatively to the function of output 14 as independent
hardware watch-dog output. The activation happens through the S4 selector which, if set to
ON, connects the output to the internal watch-dog circuit. If the device works properly, the
output always remains in operation (output connected to battery negative). If the device is
blocked and/or does not refresh the watch-dog circuit for a time higher than 5 seconds, the
output automatically fails. If the device is turned off, the output immediately falls without waiting
the 5 seconds’ time-out. The output is on after about 1 sec, from the controller starting. If the
watch-dog is disabled (S4=OFF) the status of the output 14 on JQ-5 terminal depends on its
configuration. In case the output 14 is programmed with a specific function and the selector
S4 is anyway set to ON (watch-dog output active), the output remains connected to the watch-
dog circuit and it will never be activated by the chosen function.
Using the output as watch-dog the functionality of output 14 is lost.

All outputs are independent and individually protected from overloads, short circuits, polar
inversion and overheating. The overload protection intervenes limiting the current peak at an
instantaneous value of 2.2A. When this condition is lasting, the intervention of the thermal
protection starts, which gradually reduces the current to keep the temperature of the output
driver within its maximum limit.

With inductive loads (power relays, electro-magnetic actuators) it is advisable to use damping
diodes of the opening over voltages.

The default functions of the outputs are:


Terminal Digital output Type of output Default function
JQ-1 05 DOF.0000 - “Not used”.
JQ-2 06 DOF.0000 - “Not used”.
Static outputs to
JQ-3 07 DOF.0000 - “Not used”.
battery negative.
JQ-4 08 DOF.0000 - “Not used”.
JQ-5 09 DOF.0000 - “Not used”.

5.5.6 Digital outputs configuration


All digital output of the controller and those of the additional DITEL modules, are individually
totally programmable.

The status of the digital outputs is displayed at pages S.13 and S14 (0=output not active,
1=output active).

40 MC200 Technical Manual EAAM0578EN


As default, all outputs activate when required by the relative function (e.g. the load shedding
outputs operates when a load must be disconnected).

Using BoardPrg3 it is possible to invert the activation by simply selecting the box “Inverted
polarity”, on the top of the configuration page of each output.

However, operating directly on the controller it is possible to invert the outputs logics (still
individually for each outputs) using the parameters:

Parameter Outputs
P.3000 01...16
P.3020 17...18
P.3200 DITEL #01
P.3250 DITEL #02

A bit to zero means that the output is normally at rest. It operates when it is required by the
associated function.

A bit to one means that the output is normally activated. It goes at rest when it is required by
the associated function.

The map of the outputs on the controller is:


BIT Hexadecimal value Digital output Terminal
1 0001 Output 01 JD-1
2 0002 Output 02 JD-2
3 0004 Output 03 JD-3
4 0008 Output 04 JD-4
5 0010 Output 05 JR-1
6 0020 Output 06 JR-2
7 0040 Output 07 JR-3
8 0080 Output 08 JR-4
9 0100 Output 09 JR-5
10 0200 Output 10 JQ-1
11 0400 Output 11 JQ-2
12 0800 Output 12 JQ-3
13 1000 Output 13 JQ-4
14 2000 Output 14 JQ-5
15 4000 Output 15 JJ-1
16 8000 Output 16 JJ-3

Bit Hexadecimal value Digital output Terminal


1 0001 Output 17 JH-1...3
2 0002 Output 18 JH-4...6

While the map for the outputs on the four DITEL 8 OUT modules is:
Bit Hexadecimal value Digital output
1 0001 Output 01
2 0002 Output 02
3 0004 Output 03
4 0008 Output 04
5 0010 Output 05
6 0020 Output 06
7 0040 Output 07

MC200 Technical Manual EAAM0578EN 41


Bit Hexadecimal value Digital output
8 0080 Output 08
9 0100 Output 09
10 0200 Output 10
11 0400 Output 11
12 0800 Output 12
13 1000 Output 13
14 2000 Output 14
15 4000 Output 15
16 8000 Output 16

Basically, if you want to invert the logic of an output it is necessary to add in the relative
parameter its corresponding value: e.g. If you want to invert the outputs 3 and 4 on the
controller, it is necessary to set P.3000 = 000C (thus 0004+0008); if you want to invert the
outputs 5 and 10 of the DITEL (16 IN + 16 OUT) second group, it is necessary to set P.3250
= 0210 (thus 0010+0200).

By default, all bits are set to zero.

The digital outputs can be used directly as command for external devices of the controller or
as signalling of operation conditions.

The following three function, not directly linked to the operation sequences of the controller,
are selectable for any digital output:

• DOF.0101 - “Used by PLC”. This function matches the digital output to the PLC
program inside the device; in this way, it is the PLC logic which commands the output,
and not the normal operation logics of the controller. Note: if the PLC program uses
some outputs, but those are not configured with function DOF.0101, the outputs will
not be commanded (but the controller signals this situation with a warning).

• DOF.0102 - “Commanded by the serial ports”. The controller does not command the
output with own internal logics, but with the commands received by means of the serial
ports.

• DOF.0103 - “Logics AND/OR”. See 5.5.7.

Following the configurable functions on digital outputs.


Output
Name Description
function xx.
DOF.0000 Not used. Output not used.
DOF.0101 Used by the PLC. Output used by the internal PLC logic.
DOF.0102 Managed by the serial ports. The controller does not command the output with own internal logics, but with the
commands received by means of the serial ports.
DOF.0103 AND/OR logics. The output status is the result of the combination of the logics AND/OR, see par. 5.5.7
DOF.1005 Request to start. This output is active when the controller needs to start generators.
DOF.2001 Minimum voltage coil for MCB (NC). See par. 7.8.
DOF.2002 Coil for opening of MCB. See par. 7.8.
DOF.2003 Coil for closure of MCB. See par. 7.8.
DOF.2004 Stable opening command for MCB. See par. 7.8.
DOF.2031 Minimum voltage coil for MGCB. See par. 7.8.
DOF.2032 Coil for opening of MGCB. See par. 7.8.
DOF.2033 Coil for closure of MGCB. See par. 7.8.
DOF.2034 Stable closing command for MGCB. See par. 7.8.
DOF.2251 Load shedding 1. This output is related to the “load shedding” function. The output is activated when the
load must be disconnected from the generators. See the “load shedding” description for
more details.
DOF.2252 Load shedding 2. This output is related to the “load shedding” function. The output is activated when the
load must be disconnected from the generators. See the “load shedding” description for
more details.
DOF.2253 Load shedding 3. This output is related to the “load shedding” function. The output is activated when the
load must be disconnected from the generators. See the “load shedding” description for
more details.

42 MC200 Technical Manual EAAM0578EN


Output
Name Description
function xx.
DOF.2254 Load shedding 4. This output is related to the “load shedding” function. The output is activated when the
load must be disconnected from the generators. See the “load shedding” description for
more details.
DOF.3001 Off/Reset. It activates when the controller is in OFF/RESET mode.
DOF.3002 Manual. It activates when the controller is in MANUAL mode.
DOF.3003 Automatic. It activates when the controller is in AUTOMATIC mode.
DOF.3004 Test. It activates when the controller is in TEST mode.
DOF.3005 Remote start. It activates when the controller is in REMOTE START mode.
DOF.3011 Not in Off/reset. It activates when the controller is in MAN or AUTO mode.
DOF.3012 One of the automatic modes. It activates when a controller is in an automatic operation mode, that is AUTO, TEST, or
REMOTE START.
DOF.3030 Voltages on loads. It activates when there is voltage on the loads.
DOF.3031 Voltage on generators. It activates when there is voltage on the bars of the generators.
DOF.3033 Mains in tolerance. It activates when the mains parameters are inside the window “mains live”.
DOF.3034 PPR ok. This output deactivates when an anomaly is diagnosed on the mains voltage which
requires the interruption of the parallel with the mains itself.
DOF.3035 First command for 27Q. It is the first command of the 27Q protection for the parallel with the mains.
DOF.3036 Second command for 27Q. It is the second command of the 27Q protection for the parallel with the mains.
DOF.3037 Parallel to mains allowed. This output activates when the mains status allows the parallel with the mains itself.
DOF.3062 Ready to supply. This output is active when loads can be connected to generators.
DOF.3081 Ready to close MCB. This output is activated before the closing of the circuit breaker only if one input is
configured as “MCB closure allowed” (DIF.1035): it is deactivated (and so the circuit
breaker will be closed) when that input is active or after the delay configured for the
input elapses.
DOF.3082 Ready to open MCB. This output is activated before the opening of the circuit breaker only if one input is
configured as “MCB opening allowed” (DIF.1036): it is deactivated (and so the circuit
breaker will be opened) when that input is active or after the delay configured for the
input elapses.
DOF.3083 Ready to close MGCB. This output is activated before closing the circuit breaker only if one digital input is
configured as “MGCB closure allowed” (DIF.1005): it is deactivated (and so the circuit
breaker will be closed) when that input is active or after the delay configured for the
input.
DOF.3084 Ready to open MGCB. This output is activated before opening the circuit breaker only if one digital input is
configured as “MGCB opening allowed” (DIF.1006): it is deactivated (and so the circuit
breaker will be opened) when that input is active or after the delay configured for the
input.
DOF.3091 Synchronisation for MGCB. It activates during the synchronisation for the closure of the MGCB circuit breaker.
DOF.3092 Synchronisation for MCB. It activates during the synchronisation for the closure of the MCB circuit breaker.
DOF.3093 Synchronization in progress. It activates during the synchronisation for the closure of the MCB or MGCB circuit
breakers.
DOF.3094 Synchronized. It activates during the synchronisation for the closure of the MCB or MGCB circuit
breakers, when the gensets are synchronous with the mains.
DOF.3096 In parallel with the mains. It activates when the gensets are supplying in parallel with the mains.
DOF.3151 Reset of the anomalies. The board activates this output for one second when the internal sequence for the
cancellation of anomalies is carried out.
DOF.3152 External horn. It activates together with the internal siren.
DOF.3153 Lamp test. It activates in OFF/RESET mode, pressing STOP button; it can be used to turn on
internal control lights of the controller, and there is one only procedure to test the control
lights.
DOF.3154 Acknowledge of the anomalies. The board activates this output for one second when the internal sequence for the
acknowledge of the anomalies is carried out.
DOF.4001 Warnings. It activates when there are warnings.
DOF.4002 Unloads. It activates when there are unloads.
DOF.4004 Alarms. It activates when there are alarms.
DOF.4005 Alarms and unloads. It activates when there are alarms or unloads.
DOF.4035 Anomalies of circuit breakers It activates when there are anomalies on the MGCB or MCB circuit breakers, that is:

013: MCB not closed.


014: MGCB not closed.
023: MCB not open.
024: MGCB not open.

5.5.7 AND/OR logics


The AND/OR logics are basically a list of boolean conditions (true/false - on/off - 1/0),
configurable by the operator (programming), evaluated by the controller and the result of which
can be assigned to a digital output or to a virtual digital input. To use the AND/OR logics with
one digital output, use the function DOF.0103.

MC200 Technical Manual EAAM0578EN 43


Note: the configuration of the AND/OR logics cannot be carried out directly from the
controller display, but it must be carried out by PC with the BoardPrg3 software.

First, the operator must decide whether the conditions list must be evaluated as AND (they
must be all verified) or as OR (at least one condition verified). It is not possible to have
mixed AND/OR logics (it is possible to do it using virtual digital inputs, see below).

Up to 30 conditions can be added. Each condition can be individually denied: in the previous
picture, for example, the controller will check the digital input 2 and the digital output 17 to be
both not active. The following conditions can be added:

 DI_XXX: logic statuses of all digital inputs (physical and virtual).

 DO_XXX: logic statuses of all digital outputs.

 AL_XXX: presence of warning/alarms.

 ST_XXX: internal statuses of the controller.

 AT_XXX: statuses connected to the thresholds on analogue measures (see par.


5.6.4).

The following chart shows the list of the internal statuses available for the AND/OR logics.
Status Description
ST_000 OFF_RESET.
ST_001 MAN.
ST_002 AUTO.
ST_003 TEST.
ST_004 AVVIAMENTO REMOTO.
ST_006 Acknowledgment of anomalies in progress.
ST_007 Reset of anomalies in progress.
ST_008 Warnings.
ST_009 Unloads.
ST_011 Alarms.
ST_012 Not recognized warnings.
ST_013 Not recognized unloads.
ST_015 Not recognized alarms.
ST_016 Mains present (voltages/frequency).
ST_017 Mains absent or out of thresholds.
ST_018 Delay for mains in thresholds.
ST_019 Mains in thresholds.
ST_020 Delay for mains absent or out of thresholds.
ST_048 Load bus-bars live (voltages).
ST_049 Generators bus-bars live (voltages).
ST_051 Protection 27Q activated.
ST_052 Mains fault protections activated (mains absent).
ST_053 Protection 27 activated (U<<, 1° threshold).
ST_054 Protection 59 activated (U>>, 1° threshold).
ST_055 Protection 81< activated (f<<, 1° threshold).
ST_056 Protection 81> activated (f>>, 1° threshold).
ST_057 Protection ROCOF activated.
ST_058 Protection VECTOR JUMP activated.

44 MC200 Technical Manual EAAM0578EN


Status Description
ST_059 Protection 27 activated (U<, 2° threshold).
ST_060 Protection 59 activated (U>, 2° threshold).
ST_061 Protection 81< activated (f<, 2° threshold).
ST_062 Protection 81> activated (f>, 2° threshold).
ST_063 Protection 27T activated.
ST_064 GCB status.
ST_065 MCB status.
ST_066 MGCB status.
ST_068 MGCB closure command (stable).
ST_069 MCB closure command (stable).
ST_070 MGCB minimum voltage coil.
ST_071 MGCB opening pulse.
ST_072 MGCB closure pulse.
ST_073 MCB minimum voltage coil.
ST_074 MCB opening pulse.
ST_075 MCB closure pulse.
ST_080 Start inhibited by contact.
ST_081 Start inhibited by clock/calendar.
ST_083 Start inhibited because it's not possible to supply without mains and mains is absent.
ST_084 Start inhibited because another genset has the GCB not opened.
ST_088 GCB closure inhibited by contact.
ST_089 GCB closure inhibited because it's not possible to supply without mains and mains is
absent.
ST_090 GCB closure inhibited by serial port.
ST_091 GCB closure inhibited because another genset has the GCB not opened.
ST_092 MGCB closure inhibited because MCB parallel failure.
ST_093 MGCB closure inhibited because no gensets available.
ST_094 MGCB closure inhibited by TEST without load.
ST_095 GCB closure inhibited by reverse synchronization.
ST_096 Ready to supply.
ST_097 MCB synchronization in progress.
ST_098 MGCB synchronization in progress.
ST_099 Synchronized.
ST_100 Ramp up in progress.
ST_101 Ramp down in progress.
ST_102 Supplying in parallel with mains.
ST_104 Supplying.
ST_108 Emergency plant.
ST_109 Parallel to grid plant.
ST_112 Sync per second.
ST_113 Sync per minute.
ST_114 Sync per hour.
ST_127 Daylight Save Time.
ST_128 Generator automatic start request.
ST_129 Generator automatic start request for MCB closing failure.
ST_130 Generator automatic start request by "peak shaving".
ST_136 Generator stop request for none automatic start request.
ST_137 Generator stop request for unloading.
ST_138 Generator stop request for alarms.
ST_139 Manual stop request.
ST_140 Stop request for island mode inhibit.
ST_141 Stop request for some GCBs "not open".
ST_144 GCB closed on genset 01.
ST_145 GCB closed on genset 02.
ST_146 GCB closed on genset 03.
ST_147 GCB closed on genset 04.
ST_148 GCB closed on genset 05.
ST_149 GCB closed on genset 06.
ST_150 GCB closed on genset 07.
ST_151 GCB closed on genset 08.
ST_152 GCB closed on genset 09.
ST_153 GCB closed on genset 10.
ST_154 GCB closed on genset 11.
ST_155 GCB closed on genset 12.
ST_156 GCB closed on genset 13.
ST_157 GCB closed on genset 14.
ST_158 GCB closed on genset 15.
ST_159 GCB closed on genset 16.
ST_160 GCB closed on genset 17.
ST_161 GCB closed on genset 18.
ST_162 GCB closed on genset 19.
ST_163 GCB closed on genset 20.
ST_164 GCB closed on genset 21.

MC200 Technical Manual EAAM0578EN 45


Status Description
ST_165 GCB closed on genset 22.
ST_166 GCB closed on genset 23.
ST_167 GCB closed on genset 24.
ST_168 GCB closed on genset 25.
ST_169 GCB closed on genset 26.
ST_170 GCB closed on genset 27.
ST_171 GCB closed on genset 28.
ST_172 GCB closed on genset 29.
ST_173 GCB closed on genset 30.
ST_174 GCB closed on genset 31.
ST_175 GCB closed on genset 32.
ST_192 Unloading on genset 01.
ST_193 Unloading on genset 02.
ST_194 Unloading on genset 03.
ST_195 Unloading on genset 04.
ST_196 Unloading on genset 05.
ST_197 Unloading on genset 06.
ST_198 Unloading on genset 07.
ST_199 Unloading on genset 08.
ST_200 Unloading on genset 09.
ST_201 Unloading on genset 10.
ST_202 Unloading on genset 11.
ST_203 Unloading on genset 12.
ST_204 Unloading on genset 13.
ST_205 Unloading on genset 14.
ST_206 Unloading on genset 15.
ST_207 Unloading on genset 16.
ST_208 Unloading on genset 17.
ST_209 Unloading on genset 18.
ST_210 Unloading on genset 19.
ST_211 Unloading on genset 20.
ST_212 Unloading on genset 21.
ST_213 Unloading on genset 22.
ST_214 Unloading on genset 23.
ST_215 Unloading on genset 24.
ST_216 Unloading on genset 25.
ST_217 Unloading on genset 26.
ST_218 Unloading on genset 27.
ST_219 Unloading on genset 28.
ST_220 Unloading on genset 29.
ST_221 Unloading on genset 30.
ST_222 Unloading on genset 31.
ST_223 Unloading on genset 32.
ST_224 Calendar 1.
ST_225 Calendar 2.
ST_226 Calendar 3.
ST_227 Calendar 4.
ST_228 Calendar 5.
ST_229 Calendar 6.
ST_230 Calendar 7.
ST_231 Calendar 8.
ST_232 Calendar 9.
ST_233 Calendar 10.
ST_234 Calendar 11.
ST_235 Calendar 12.
ST_236 Calendar 13.
ST_237 Calendar 14.
ST_238 Calendar 15.
ST_239 Calendar 16.
ST_240 Genset 01 available.
ST_241 Genset 02 available.
ST_242 Genset 03 available.
ST_243 Genset 04 available.
ST_244 Genset 05 available.
ST_245 Genset 06 available.
ST_246 Genset 07 available.
ST_247 Genset 08 available.
ST_248 Genset 09 available.
ST_249 Genset 10 available.
ST_250 Genset 11 available.
ST_251 Genset 12 available.
ST_252 Genset 13 available.
ST_253 Genset 14 available.

46 MC200 Technical Manual EAAM0578EN


Status Description
ST_254 Genset 15 available.
ST_255 Genset 16 available.
ST_256 Genset 17 available.
ST_257 Genset 18 available.
ST_258 Genset 19 available.
ST_259 Genset 20 available.
ST_260 Genset 21 available.
ST_261 Genset 22 available.
ST_262 Genset 23 available.
ST_263 Genset 24 available.
ST_264 Genset 25 available.
ST_265 Genset 26 available.
ST_266 Genset 27 available.
ST_267 Genset 28 available.
ST_268 Genset 29 available.
ST_269 Genset 30 available.
ST_270 Genset 31 available.
ST_271 Genset 32 available.
ST_997 PLC first scan.
ST_998 Always ON.
ST_999 Always OFF.

Using the virtual digital inputs, it is possible to create mixed AND/OR logics (composed by
AND or OR together). Let’s suppose we want to activate the digital output #1 when the digital
inputs #1 and #2 are active, or if the digital input #3 is active.

Fist, we must associate to the virtual digital input #1 e.g. an AND/OR logic configured as AND,
which checks that the first two inputs are both active. Then we must associate to the digital
output #1 an AND/OR logic configured as OR, which checks that the virtual digital input #1, or
the digital input #3 are active. Basically, we should use the virtual digital input #1 as “support”
for the AND condition. In this case, it is not necessary to associate any function to the virtual
digital input.

5.6
The device is equipped by two differential 0...10V voltage analogue inputs available on
terminal JU, four inputs in voltage available on terminal JK and one in voltage available on
terminal JJ-4.

All these inputs can also be configured individually as digital inputs (function AIF.0100 in
parameter P.4001 or equivalent). In this case, the analogue inputs from 1 to 7 will be additional
digital inputs from 19 to 25. The status of the virtual inputs is displayed at page S.11 (0=output
not active, 1=output active). The inputs not configured as digital will be displayed with a dash.
If set as digital (function AIF.0100 in parameter P.4001 or equivalent), the inputs are
considered active when the measured voltage is higher than 4.0Vdc; they are considered not
active when the measured voltage is lower than 3.5Vdc. They cannot therefore be activated
as the other inputs by connecting it to the mass:

MC200 Technical Manual EAAM0578EN 47


It is also possible to use two DIVIT expansion modules and three DIGRIN or DITHERM
optional expansion modules, connected via CAN bus to acquire further 8 signals of
voltage/current and up to 9 temperatures.
5.6.1 JU - Analogue inputs 1-2

They are two inputs for the measure of voltage signals for 0...10Vdc signals.

The two ANALOGUE inputs INPUT 1 and INPUT 2 are not galvanically isolated, but it is
possible to measure the signal in differential, so that they can compensate eventual
differences of measure negatives compared to the negative of GND controller. The
compensation range is -10 /+6Vdc.

The terminals REF.IN1 (JU-4) and REF.IN2 (JU-6) are internally connected to GND by means
of 1KΩ resistors; this allows to avoid their connection with the masses of the sources of voltage
signals for connections which are short and inside the control panel.

On the same connector JU, there are also one regulated +5Vdc output (JU-1) and one output
connected to the mass inside the device (JU-2). This voltage is specific for the use of
potentiometers. The total minimum resistance applicable between JU-1 and JU-2 is 10KΩ.

For configuration and uses of analogue inputs see par.5.6.4

The default functions of the inputs are:


Terminal Analogue input Type of input Default function
+5Vdc output only reserved to the only
JU-1 - - connection of trimmer/potentiometers for
analogue inputs 1 and 2.
GND output only reserved to the only
JU-2 - - connection of trimmer/potentiometers for
analogue inputs 1 and 2.
0...10Vdc voltage
JU-3
Analogue input 1 measure input AIF.0000 - “Not used”.
JU-4 JU-3 mass input
0...10Vdc voltage
JU-5
Analogue input 2 measure input AIF.0000 - “Not used”.
JU-6 JU-5 mass input

5.6.2 JK - Analogue inputs 3-6

The device is equipped with four programmable inputs (0...10Vdc) JK-2, JK-3, JK-4, JK-5.
The voltages are measured respect the negative power supply JC-1 GND. The four voltage
values measured on the terminals are displayed on page S.15.

The default functions of the outputs are:

48 MC200 Technical Manual EAAM0578EN


Terminal Analogue input Type of input Default function
JK-2 Analogue input 3 AIF.0000 - “Not used”.
JK-3 Analogue input 4 Voltage analogue AIF.0000 - “Not used”.
JK-4 Analogue input 5 inputs AIF.0000 - “Not used”.
JK-5 Analogue input 6 AIF.0000 - “Not used”.

5.6.3 JJ-4 Analogue input 07

This input acquires a voltage with measurement range from 0 to 32Vdc compared to the supply
negative of the controller (GND). Page S.15 shows the measured voltage.
5.6.4 Configuration of digital inputs (AI_CONTROLLER)
The analogue inputs can be used for the acquisition of several predefined values or to acquire
generic sensors (therefore user-adjustable). Some values can be only acquired by some
inputs (see following chat in this paragraph).

It is possible to apply to all physical analogue inputs (JU, JK, JJ e DIVIT) a conversion curve
(not to the virtual analogue inputs and to DIGRIN and DITHERM).

To each analogue input (JU, JK, JJ, DIGRIN, DITHERM, DIVIT and virtual) a set of 8
parameters is associated, to define the function type, an alternative denomination and a series
of generic thresholds and configurations usable for different functions. Following are listed, as
examples, those relative to the JK-2 input. For parameters of other inputs, refer to document
[1] or to configuration page I/O of BoardPrg3.

NOTE: On BoardPrg3 the parameters are all displayed only when the input is configured as
analogue, and not as digital. The analogue inputs of the expansion modules are only displayed
if the module is configured.

You will have:

 One parameter which configures its function (P.4017 for input JK-2).

 A parameter that configures a message to show on display (P.4018 for the input JK-
2).

 Two thresholds consisting of three parameters each:

▪ A parameter which configure the threshold value (P.4019 and P.4022 for input
JK-2).

▪ A parameter which configure the delay to manage the “out of threshold”


(P.4020 and P.4023 for input JK-2).

▪ A parameter which configure the checking options and the actions in case of
“out of threshold” (P.4021 e P.4024 for the input JK-2).

The parameter which contains a message for a given analogue input (in the example
parameter P.4018), it is displayed by the controller each time the thresholds are used to
activate alarms and/or warnings (see after). It is also used for the following functions of the
analogue inputs AIF.2001, AIF.2003 e AIF.2005. In this case, the measurement acquired will
be displayed on pages M.14, M.15 and M.16, preceded by the configured message. NOTE: it
is also possible to use function AIF.2051 instead of the three preceding ones. In this
case, the measurement acquired will be not displayed; it can be used with the
thresholds to manage digital outputs and activate warnings/alarms.

MC200 Technical Manual EAAM0578EN 49


The two thresholds are completely independent on each other. The third parameter of each
threshold is a “bit” parameter that allows you to associate to each threshold the following
options:

 Bit 0. If this bit is “OFF”, the controller checks if the measurement is higher than the
threshold. If this bit is “ON”, the controller checks if the measurement is lower than the
threshold.

 Bit 1. If this bit is “OFF”, the controller sets to OFF the internal status related to this
analogue measurement, if the measurement is out of threshold. If this bit is “ON”, the
controller sets to ON the internal status related to this analogue measurement, if the
measurement is out of threshold.

 Bit 3. If this bit is “ON”, the controller transmits the anomaly to generators also.

 Bit 4. If this bit is “ON”, the controller activates a warning if the measurements is out
of threshold.

 Bit 5. If this bit is “ON”, the controller commands an unload if the measurements is out
of threshold.

 Bit 7. If this bit is “ON”, the controller activates an alarm if the measurements is out of
threshold.

 Bit 8. If this bit is “ON”, the controller checks that MCB is closed to activate eventual
warnings/alarms configured with the preceding bits.

 Bit 9. If this bit is “ON”, the controller checks that MGCB is closed to activate eventual
warnings/alarms configured with the preceding bits.

 Bit 13. If this bit is “ON”, to activate eventual warnings/alarms configured with the
preceding bits, the controller checks the status of eventual digital inputs configured
with function “DIF.2705 – Disable the protections on analogue measurements”. The
warnings/alarms will be activated if no digital input is configured like that, or if they are
all OFF.

 Bit 15. If this bit is “ON”, the anomaly is subject to override of the protections.

It is possible to set any combination of these bits.

Using together the two thresholds and the AND/OR logics, it is possible to activate a digital
output related to the value of an analogue measurement, with hysteresis. See the example in
the next chapter for the virtual analogue inputs.

The following chart shows the list of functions matchable with the analogue inputs of the
controller.
Analogue
Thres Controller DIV DIGRIN /
Input function Name Message
holds (JU, JK, JJ-4) IT DITHERM
xx.
AIF.0000 Not used. X X X
AIF.0100 Used as digital input. X
AIF.2001 Generic sensor (page 1). X X X X X
AIF.2003 Generic sensor (page 2). X X X X X
AIF.2005 Generic sensor (page 3). X X X X X
AIF.2051 Generic sensor. X X X X X
AIF.2101 Speed offset. X X
AIF.2103 External synchronizer. X X
AIF.2105 External MCB synchronizer. X X
AIF.2107 External MGCB synchronizer. X X
AIF.2201 Voltage offset. X X
AIF.2303 Power on the mains. X X
AIF.2307 Setpoint for system BASE LOAD. X X
AIF.2309 Setpoint for system IMPORT/EXPORT. X X
AIF.2405 Setpoint for system power factor. X X

All the AIF.XXXX odd functions require the use of program BoardPrg3 for the definition or the
load of the characteristic curve of the sensor (see par. 0). The measures acquired from

50 MC200 Technical Manual EAAM0578EN


DITHERM/DIGRIN modules that are already expressed in °C and don’t need any conversion
are exceptions.
5.6.5 Virtual digital inputs (AI_VIRTUAL)
The controller, besides the physical analogue inputs, also manages 8 virtual analogue inputs.
They are managed by the controller exactly as they were physical inputs (without limitations),
but the virtual inputs status is not acquired by the hardware, but determined via software.

The purpose of the virtual analogue inputs is multiple:

 To allow the activation of warnings/alarms related to the internal available


measurements.

 To activate digital outputs based on the value of the internal available measurements.

 To check some functions of the controller through PLC.

It is possible to operate in two ways to assign a value to the virtual analogue inputs:

• Using the internal PLC. In this case, it is necessary to assign a standard function to
the virtual analogue input (function lower than AIF.4001).

For example, we can use the PLC program to modify the power setpoint for the parallel
with the mains based on a temperature acquired from an external sensor. It is
necessary:

o To set parameter P.4051 (function for virtual analogue input #1) to value 2309
(AIF.2309 – Setpoint for system BASE LOAD). The controller will therefore
use the value of virtual analogue input #1 as power setpoint for the parallel
with the mains.

o Using the internal PLC, create a logic which writes into the virtual analogue
input #1 the power setpoint corresponding to the external temperature
acquired.

• Assigning a value which is major or equal to 4001 (AIF.4001) to the parameter


“function” of the virtual analogue input. In this case, the controller “copies” the value
of the measurement identified from the previous parameter in the virtual analogue
input: on this measurement, it is then possible to manage the thresholds to activate
digital outputs and anomalies.

The following chart shows the list of functions matchable with the analogue inputs of the
controller.
Virtual Analogue
Name Message Thresholds
Input function xx.
AIF.0000 Not used
AIF.2001 Generic sensor (page 1). X X
AIF.2003 Generic sensor (page 2). X X
AIF.2005 Generic sensor (page 3). X X
AIF.2051 Generic sensor. X X
AIF.2101 Speed offset.
AIF.2103 External synchronizer.
AIF.2105 External MCB synchronizer.
AIF.2107 External MGCB synchronizer.
AIF.2201 Voltage offset.
AIF.2303 Power on the mains.
AIF.2307 Setpoint for system BASE LOAD.
AIF.2309 Setpoint for system IMPORT/EXPORT.
AIF.2405 Setpoint for system power factor.

AVF.4001 Generators/bus frequency. X X


AVF.4006 Generators/bus voltage L1-L2. X X
AVF.4007 Generators/bus voltage L2-L3. X X
AVF.4008 Generators/bus voltage L3-L1. X X
AVF.4009 Generators/bus voltage L-L average. X X
AVF.4012 Mains frequency. X X
AVF.4017 Mains voltage L1-L2. X X
AVF.4018 Mains voltage L2-L3. X X

MC200 Technical Manual EAAM0578EN 51


Virtual Analogue
Name Message Thresholds
Input function xx.
AVF.4019 Mains voltage L3-L1. X X
AVF.4020 Mains voltage L-L average. X X
AVF.4023 Current L1. X X
AVF.4024 Current L2. X X
AVF.4025 Current L3. X X
AVF.4026 Auxiliary current (or neutral current). X X
AVF.4031 Active power L1. X X
AVF.4032 Active power L2. X X
AVF.4033 Active power L3. X X
AVF.4034 Total active power. X X
AVF.4041 Total apparent power. X X
AVF.4047 Total reactive power. X X
AVF.4058 Total power factor (calculated from kW and kVA). X X
AVF.4059 Total cos(Φ) (calculated from kW and kvar). X X
AVF.4063 Generators/bus active energy (partial). X X
AVF.4065 Generators/bus reactive energy (partial). X X
AVF.4069 Mains active imported energy (partial). X X
AVF.4071 Mains reactive imported energy (partial). X X
AVF.4073 Mains active exported energy (partial). X X
AVF.4079 Mains reactive exported energy (partial). X X
AVF.4105 Battery voltage. X X

It is not possible to use functions major than 4000 for the configuration of physical
analogue inputs.

Using together the two thresholds and the AND/OR logics, it is possible to activate a digital
output related to the value of an analogue measurement, with hysteresis. Let’s assume to
activate a digital output if the mains frequency goes over 50.5 Hz. It is first necessary to
manage a minimum hysteresis on the threshold. Otherwise when the mains frequency is next
to the threshold, the output would keep on activating and deactivating for minimum variation
of the frequency itself. Let’s assume to activate the output if the frequency goes over 50.5 Hz
and turn off the output if the frequency is lower than 50.3 Hz. To do so, we use for example
the virtual analogue input #1 which has been configured to contain the mains frequency.

Let’s set the parameters as follows:

 P.4051 (function #1): 4001 (AIF.4001).

 P.4052 (message #1): “”.

 P.4053 (threshold #1): 50.5 Hz

 P.4054 (delay #1): 0.5 sec

 P.4055 (configuration #1): 0002 (bit 1 OFF, bit 2 ON)

 P.4056 (threshold #2): 50.3 Hz

 P.4057 (delay #2): 0.5 sec

 P.4058 (configuration #2): 0001 (bit 1 ON, bit 2 OFF)

The first threshold is used to activate the internal status associated to the analogue input.
Having a look to the configuration parameter, we can see that:

 Bit 0 OFF (checks that the measurement is higher than the threshold).

 Bit 1 ON (activates the internal status in “out of Threshold” condition).

The second threshold is used to deactivate the internal status associated to the analogue
input. Having a look to the configuration parameter, we can see that:

 Bit 0 ON (checks that the measurement is lower than the threshold).

 Bit 1 OFF (deactivates the internal status in “out of Threshold” condition).

52 MC200 Technical Manual EAAM0578EN


With the previous program, therefore, the controller will activate the internal status related to
the analogue input when the measurement is higher than 50.5 Hz per 0,5 seconds; it will
deactivate the internal status when the measurement is lower than 50.5 Hz per 0,5 seconds.

Using AND/OR logics (see par. 5.5.7), it is possible to “copy” the internal status on a physical
output.
5.6.6 Conversion curves
The conversion curves are a tool which allows to convert a numeric value in another numeric
value. They can be used for analogue inputs and for the analogue outputs, for two purposes:

 To convert the acquired value from an analogue input (physical) which is on the
controller or on the optional expansion modules from electric value to real unit of
measure of the sensor.

 To convert an internal measurement of the controller to a percentage value before


writing it on an analogue output.

Note: the configuration of the AND/OR logics cannot be carried out directly from the
controller display, but it must be carried out by PC with the BoardPrg3 software.

The curves, once created, can be saved on a file to use them later even on other
controllers.

The figure above shows a conversion curve associated to an analogue output. The analogue
output has been configured with function AOF.3101 (“Frequency of the generators/bus”). With
this configuration, the output will be 10% for a generators frequency lower than or equal to 45
Hz, 90% for a frequency higher than or equal to 55 Hz; for frequency values included between
45 Hz and 55 Hz, the output will take a value between 10% and 90%.

You can add up to 32 points in the graph, thus creating also non-linear curves. Note, in the
example, that the configured curve has two horizontal segments at the beginning and at the
end, obtained inserting two equal values in column “After”, corresponding to two different
values in column “Before”. This is not mandatory, but it allows you to set a saturation limit on

MC200 Technical Manual EAAM0578EN 53


one end or on both ends of the curve. In fact, the controller extends to infinity the first and last
segments of the curve. Being horizontal, whatever value the measure “to convert” assumes,
you will obtain the same value of the “converted” measure. In the previous example, for any
frequency lower than 45 Hz, the analogue output will be set at 10%. If from the example above
you remove the first point (44 Hz 10%), the horizontal segment would not be at the beginning
of the curve: in this case, if the frequency should drop below 45 Hz, the analogue output would
drop below the 10%.

The BoardPrg3 software allows you (by means of the first buttons on top left) to save the curve
on file to be able to use it again in other applications. It is therefore possible to make an archive
of the conversions associated to the sensors used.

In case the curve is associated to a physical analogue input configured with functions
AIF.2001, AIF.2003 e AIF.2005 (“generic sensor”), the measurement converted will be
displayed on pages M.14, M.15 and M.16: in this case, it is also possible to specify (through
the conversion curve) how many decimal digits the displayed value and its unit of measure
must have.

5.7

The analogue outputs 1 and 2 are provided for interfacing external devices equipped with
analogue input in voltage or current.

The output voltage can be controlled through TR1 and TR2 potentiometers, between a
minimum of ±1VDC and a maximum of ±10VDC. These potentiometers, therefore, define the
maximum of the analogue outputs.

The outputs can be positive or negative (symmetrical type) if connected VOUT+ and VOUT-,
or only positive (asymmetrical type) if connected between VOUT+ and 0V.

The outputs are galvanic isolated (floating voltage source).

The minimum load impedance is 10 kOhm.

The default functions of the outputs on the controller are:


Terminal Digital output Type of output Default function
VOUT1+: Analogue signal in voltage AOF.1000 – “Not used”.
JT-1
with positive polarity.
0V: Internal GND reference of the
JT-2 01
isolated output.
VOUT1-: Analogue signal in voltage with
JT-3
negative polarity.
VOUT2+: Analogue signal in voltage AOF.1000 – “Not used”.
JS-1
with positive polarity.
0V: Internal GND reference of the
JS-2 02
isolated output.
VOUT2-: Analogue signal in voltage with
JS-3
negative polarity.

5.7.1 Configuration of the analogue outputs


Each analogue output (the two of MC200 controller and the four of the DANOUT module) are
all completely configurable. To each output a parameter is associated (e.g. P.6001 for output
1), which configure the function (see doc.[1]).

54 MC200 Technical Manual EAAM0578EN


To all analogue outputs it is possible to apply a conversion curve.

The following functions, not directly linked to the operation sequences of the controller, are
selectable for any digital output:

• AOF.0101 - “Used by PLC”. This function matches the analogue output to the PLC
program inside the device; in this way, it is the PLC logic which commands the output,
and not the normal operation logics of the controller. Note: if the PLC program uses
some outputs, but those are not configured with function AOF.0101, the outputs will
not be commanded (but the controller signals this situation with a warning).

• AOF.0102 - “Managed by serial ports”. The controller does not command the output
with own internal logics, but with the commands received by means of the serial ports.

The following chart shows the list of functions matchable with the analogue outputs:
Analogue output function
Name
xx.
AOF.0000 Not used.
AOF.0101 Used by the PLC.
AOF.0102 Managed by serial ports.
AOF.1000 Speed governor.
AOF.1001 Speed governor (with curve).
AOF.1002 Voltage regulator.
AOF.1003 Voltage regulator (with curve).
AOF.3101 Frequency of the generators/bus.
AOF.3111 Voltage of the generators/bus.
AOF.3121 Active power of the generators/bus.
AOF.3201 Frequency of the mains.
AOF.3211 Voltage of the mains.
AOF.3221 Active power of the mains.

When functions AOF.3101 and following are used, you must configure the proportion between
the selected measure (voltage, frequency, etc.) and the % value by means of the conversion
curves (see par. 5.6.6).

5.8
Using the connection CAN bus-0 EXBUS (JM) it is possible to connect the following optional
additional modules to the device:

• 3 DITHERM/DIGRIN modules:

o DITHERM: 3 galvanically insulated thermocouples for the temperature


measurement.

o DIGRIN: 3 galvanically insulated Pt100 sensors for the temperature


measurement.

• 2 DIVIT modules: 4 galvanically insulated analogue inputs 0...5V/0...10V –


0...10mA/0...20mA

• 1 DANOUT modules: 4 galvanically insulated analogue outputs 0...5V/0...10V –


0...10mA/0...20mA

• 2 DITEL 16IN modules: 16 digital inputs optoinsulated (total 32 inputs). To each DITEL
16IN module it is possible to connect 2 DITEL modules 8 OUT relays for a total of 32
digital outputs. It is not possible to use the output modules without their relative input
module.

For configurations to do on the modules, refer to the relative user manuals.

Below we use the name DITEMP to refer to a temperature measurement module (DITHERM
or DIGRIN).

To use the modules on it is necessary to set the number of modules which are with the
parameters.

MC200 Technical Manual EAAM0578EN 55


• P.0141: number of modules DITEL 16 IN (with eventual modules OUT) (max. 2).

• P.0142 the number of DITEMP modules (i.e. DITHERM or DIGRIN) (maximum 3).

• P.0143: the number of DIVIT modules (maximum 2).

• P.0144: the number of DANOUT modules (maximum 1).

Once configured the presence of the modules, they look like digital or analogue inputs or
outputs and are managed as those present on the controller.

For the relative parameters see doc [1].

In program BoardPrg3, once the presence of a module is configured, it appears on menu I/O
in the left column, with single inputs/outputs ready to be configured.

It is necessary, though, to clarify about DIVIT modules. They can measure any value: it is
necessary to convert the measure done (Volt or mA) to the real unit of measure of the acquired
value. Such a conversion can be done directly in the module (DIVIT), or on the MC200. Ensure
you don’t have a double conversion.

It is suggested to:

• Configure the module DIVIT to transmit a percentage value. In the example below, a
channel configured to acquire a signal 0-10 mA, will transmit “0” at 0 mA and “100” at
10 mA.

• On the MC200, use a conversion curve to convert from a % value to the real unit of
measure.

56 MC200 Technical Manual EAAM0578EN


5.9
The connection to the public grid happens though the JG connector of the controller. The
connection to the generators bus happens though the JF connector of the controller.

The controller uses phase L1 (terminals JG-3/JF-3) and L2 (terminal JG-2/JF-2) to measure
the frequency.

For CAT.III use, the maximum working voltage is 300Vac (phase-neutral) and 520Vac
(phase to phase). The maximum voltage compared to the protection earth is 300Vac.

If working voltages are greater than these values, step-down transformer must be used to
respect the specified limits. The nominal voltages on the primary and secondary of the VT are
configurable with parameters P.0117 and P.0118 for the mains and parameters P.0103 and
P.0104 for the generators bus. It is suggested to use voltage transformers having a nominal
voltage of 400V on the secondary (this solution can preserve the best available measurement
precision of the board).

In alternative, it is possible to use VT, with secondary sides of 100V. In this case, it is
necessary to configure parameter P.0152 (for the mains) and P.0151 (for the generators bus)
for the operation at 100V. The controller will adapt the internal gain to optimize the voltage
measurement on the nominal value set in these parameters.

It is also possible to use the Aron insertion of the VTs, which uses only two transformers,
instead of three (see par. 5.9.4). In this case, it is necessary not to use the neutral connection.

Attention! Do not connect JG/JF measurement input to TA with 400V secondary sides
or directly to the voltage 400V when the device is configured to read at 100V nominal
voltage (parameters P0.152/P.0151 set to 1). The device could be damaged.

The following chapters show all the possible wirings for the alternator. In the example, it is
supposed that each internal winding provides 115 Vac. The possible connections are:
5.9.1 Star or Wye (three phases, four wires)

This kind of wiring assumes the presence of the Neutral line. If the alternator is Wye-wired but
the neutral line is not distributed, leave terminal JF-4 / JG-4 unconnected: the controller
internally creates a virtual Neutral point; in this case, if the L-N voltage measures are not
required, set P.0129 or P.0128 to zero.

MC200 Technical Manual EAAM0578EN 57


Pages M.02/M.03 normally show the line-line voltages. Press the ENTER pushbutton to see
the line-neutral voltages, press it again to go back to line-line voltages.
5.9.1.1 High Wye

Parameters:

Mains Generators bus Value Description

P.0119 P.0101 3 Number of phases

P.0129 P.0128 1-Yes Is the neutral connected to the controller?

P.0116 P.0102 400 Nominal voltage (L-L)


2
(115 ×2) × √3

Available voltage measures:

Measure Nominal value Page for mains Page for generators bus

L1-L2 400 M.02 M.03

L2-L3 400 M.02 M.03

L3-L1 400 M.02 M.03

L1-N 230 M.02 M.03

L2-N 230 M.02 M.03

L3-N 230 M.02 M.03

N-GND - M.02 M.03

5.9.1.2 Low Wye

Parameters:

58 MC200 Technical Manual EAAM0578EN


Mains Generators bus Value Description

P.0119 P.0101 3 Number of phases

P.0129 P.0128 1-Yes Is the neutral connected to the controller?

P.0116 P.0102 200 Nominal voltage (L-L)


2
115 × √3

Available voltage measures:

Measure Nominal value Page for mains Page for generators bus

L1-L2 400 M.02 M.03

L2-L3 400 M.02 M.03

L3-L1 400 M.02 M.03

L1-N 230 M.02 M.03

L2-N 230 M.02 M.03

L3-N 230 M.02 M.03

N-GND - M.02 M.03

5.9.2 Delta (three phases, three wires)

MC200 Technical Manual EAAM0578EN 59


5.9.2.1 High Delta

Parameters:

Mains Generators bus Value Description

P.0119 P.0101 3 Number of phases

P.0129 P.0128 0 - No Is the neutral connected to the controller?

P.0116 P.0102 400 Nominal voltage (L-L)


2
(115 ×2) × √3

Available voltage measures:

Measure Nominal value Page for mains Page for generators bus

L1-L2 400 M.02 M.03

L2-L3 400 M.02 M.03

L3-L1 400 M.02 M.03

5.9.2.2 Low Delta

Parameters:

Mains Generators bus Value Description

P.0119 P.0101 3 Number of phases

P.0129 P.0128 0 - No Is the neutral connected to the controller?

P.0116 P.0102 200 Nominal voltage (L-L)


2
115 × √3

60 MC200 Technical Manual EAAM0578EN


Available voltage measures:

Measure Nominal value Page for mains Page for generators bus

L1-L2 200 M.02 M.03

L2-L3 200 M.02 M.03

L3-L1 200 M.02 M.03


5.9.3 Single phase (one phase, two wires)

5.9.3.1 High Single Phase

Parameters:

Mains Generators bus Value Description

P.0119 P.0101 1 Number of phases

P.0129 P.0128 1-Yes Is the neutral connected to the controller?

P.0116 P.0102 230 Nominal voltage (L-N)

115 × 2

Available voltage measures:

MC200 Technical Manual EAAM0578EN 61


Measure Nominal value Page for mains Page for generators bus

L1-N 230 M.02 M.03

N-GND - M.02 M.03

5.9.3.2 Low Single Phase

Parameters:

Mains Generators bus Value Description

P.0119 P.0101 1 Number of phases

P.0129 P.0128 1-Yes Is the neutral connected to the controller?

P.0116 P.0102 115 Nominal voltage (L-N)

115

Available voltage measures:

Measure Nominal value Page for mains Page for generators bus

L1-N 115 M.02 M.03

N-GND - M.02 M.03

5.9.4 Aron insertion of voltmetric transformers


Both for the generators bus and for the mains voltage measurement inputs, it is possible to
use the Aron insertion of the voltmetric transformers; this allows to use two transformers
instead of three. The connection is possible both with the measurement inputs set to 100Vac
and with 400Vac nominal voltage.

The diagram of the Aron connection is the following:

62 MC200 Technical Manual EAAM0578EN


The diagram is the same both for the generators bus and for the mains; it is necessary to
select the Delta connection mode (see above).

5.10

5.10.1 JE - Currents measurement inputs 1-3


The current measurement must happen by means of external current transformers (CT). Do
not connect voltage conductors to JE. The measurement happens through current
transformers inside the device.

To these terminals, external current transformers with 5Aac or 1Aac secondary can be
connected: internally, the controller guarantees the same measurement precision with both
types of transformer.

Each current measurement requires a power of about 1VA: however, 5VA CTs are suggested
to compensate the losses along the connection cables.

The maximum current measurable directly from the device is 7Aac. Over this threshold the
measure circuit saturates. The controller can measure (with progressively decreasing
precision) up to 15Aac though, e.g. to measure overcurrents or short circuit currents on the
plant, using an algorithm of compensation of saturation of the circuits of measurement.

• Connect to JE-1 terminal to hot pole of CT connected on phase L1.

• Connect to JE-2 terminal to cold pole of CT connected on phase L1.

• Connect to JE-3 terminal to hot pole of CT connected on phase L2.

• Connect to JE-4 terminal to cold pole of CT connected on phase L2.

• Connect to JE-5 terminal to hot pole of CT connected on phase L3.

• Connect to JE-6 terminal to cold pole of CT connected on phase L3.

For one-phase connections, JE-3, JE-4, JE-5, JE-6 terminals can be left free.

Normally, JE connector is used for the measurement of the currents (and the powers) on the
mains; its use is however configurable by means parameter P.0124:

MC200 Technical Manual EAAM0578EN 63


• 0: the CTs are located on the generators bus.

• 1: the CTs are located on the loads lines.

• 2 (default): the CTs are located on the mains lines.

Parameters P.0107 and P.0139 allows to configure the transformation ratio of the external
current transformers. For example, if we use 50/5 current transformers, set P.0107=50 and
P.0139=5.
5.10.1.1 Aron insertion of current transformers
It is possible, independently from the connection of the voltmeter transformers, to connect
current transformers configured as Aron insertion. This allows to use only two current
transformers instead of three.

The diagram of the Aron connection is the following:

5.10.2 JI - Currents measurement input 4


The device allows to acquire a fourth current measurement, usable e.g. for a differential
protection. By default, the fourth measure is not used.

JI input type varies depending on the controller has been ordered with or without the toroid
option (code E620215011000). This option is only on demand.
5.10.2.1 Controller without option E620215011000
Parameter P.0109 must be set to “0 - CT”.

The current measurement must happen only by means of external current transformers (CT).
Do not connect voltage conductors to JI. The measurement happens through current
transformers inside the device.

To these terminals, external current transformers with 5Aac or 1Aac secondary can be
connected: internally, the controller guarantees the same measurement precision with both
types of transformer.

The current measurement requires a power of about 1VA: however, 5VA CTs are suggested
to compensate the losses along the connection cables.

The maximum current measurable directly from the device is 7Aac. Over this threshold the
measure circuit saturates. The controller can measure (with progressively decreasing
precision) up to 15Aac though, e.g. to measure overcurrents or short circuit currents on the
plant, using an algorithm of compensation of saturation of the circuits of measurement.

To acquire the current the connector JI is used:

• Connect to JI-1 terminal the hot pole of external CT.

64 MC200 Technical Manual EAAM0578EN


• Connect to JI-2 terminal the cold pole of external CT.

Parameters P.0108 and P.0135 allows to configure the transformation ratio of the external
current transformers. For example, if we use 50/5 current transformers, set P.0108=50 and
P.0135=5.
5.10.2.2 Controller with option E620215011000
Parameter P.0109 must be set to “1 - Toroid”.

The current measurement must happen only by means of an external toroid. Do not connect
voltage conductors to JI and JE.

The maximum current measurable directly from the device is 0,1Aac. Over this threshold the
measure circuit saturates. Use one toroid with a transformation ratio which guarantees
currents lower than this threshold on the secondary.

To acquire the current the connector JI is used:

• Connect to JI-1 terminal the hot pole of external toroid.

• Connect to JI-2 terminal the cold pole of external toroid.

Parameters P.0108 and P.0135 allows to configure the transformation ratio of the external
toroid. For example, if we use 500/1 toroid, set P.0108=500 and P.0135=1.

The cold pole of the toroid (JI-2) must also be connected to the supply negative of the
controller.
5.10.2.3 Use of the fourth current
Parameter P.0130 allows to tell the controller where is located the transformer which acquires
this measurement.

• 0: the CT is located on the generators bus.

• 1: the CT is located on the loads lines.

• 2 (default): the CT is located on the mains lines.

The most important parameter to be configured is parameter P.0131 though, that allows to
establish which use of current measurement you want to do:

• P.0131 = 0 (“Not used”) The controller disables the measurement of the fourth current,
which will not be shown on display.

• P.0131 = 1 (“General purpose”). The controller displays the current measurement


done on page M.04 with the lettering “Ax”.

• P.0131 = 2 (“Neutral”). The controller displays the current measurement done on page
M.04 identifying as “An”.

• P.0131 = 4 (“Power measure”). The controller interprets the measurement like the
current circulating on L1 phase of the selected source (P.0130) and shows it on page
M.04 with the lettering “Ax”. The controller also calculates the active power (kW)
circulating on L1 phase of the selected source. Finally, for three-phase systems, it
multiplies the calculated power by three, assuming that the load is uniformly shared
on the three phases. If it was not like this, it is possible to apply a correction factor
(P.0132), which allows to increase the calculated power (if P.0132 > 1) or to decrease
it (if P.0132 < 1), to let it the closest to real. The calculated active power is shown on
page M.01.

Settings 1 and 2 allow to establish a threshold on the auxiliary current (P.0367 e P.0368). It is
possible to configure a digital input with function DIF.2704 - “Disable protections on fourth
current”. If the input is active, the thresholds, even if set, are ignored and do not activate
anomalies in case of overpassing.

MC200 Technical Manual EAAM0578EN 65


5.11
The device is equipped with many communication ports for the connection to PC, modem,
mains, etc.

MC200 is provided with:

• One USB 2.0 serial port not insulated, which can be used in Function or Host mode:

o Function: (JNA, USB B connector): connection with PC for FW update and


programming of device parameters.

o Host (JNB, USB A connector): Pen Drive management (up to today not
available)

• One RS232 (JA) serial port with DB9 male connector usable for the interfacing with
an external device equipped with RS232 interface. The maximum length of the cable
is 12 mt.

• One RS485 serial port (JW) with galvanic insulation; the maximum connection length
in optimal conditions is 1200 mt. The 120ohm terminal resistor is integrated and can
be inserted through S5 selector. The use of a shielded cable with 120ohm impedance
is required (e.g. BELDEN 3105A Multi-conductor-EIA Industrial RS-485PLT/CM).

• One CAN bus port (JM) with galvanic insulation for the communication with additional
optional modules (DITEL, DITHERM, DIGRIN e DIVIT). The 120ohm terminal resistor
is integrated and can be inserted through S1 selector. The specific use of the shielded
cable is required (e.g. HELUKABEL 800571).

• One CAN bus port (JX) with galvanic insulation for the communication with other
devices for genset/mains/tie breaker control. The 120ohm terminal resistor is
integrated and can be inserted through S6 selector. The specific use of the shielded
cable is required (e.g. HELUKABEL 800571).

• One Ethernet port (JY) with RJ45 connector for 10/100 Mbps Ethernet nets
connections.

For details related to the communications see specific paragraphs and document [3].

For CAN bus connections see documents [5] e [6].


5.11.1 JA - Serial port 1 RS232

RS232 JA connector (serial port 1) can be used for the interfacing with an external device
equipped with RS232 interface, e.g. a modem or a PC. The maximum distance of the
connection is 12 mt.

The connection can be used for the device parameter programming through BoardPrg3
program or for the connection to a supervision program as SicesSupervisor3.

66 MC200 Technical Manual EAAM0578EN


For the functions and protocols implemented, refer to document [3]. Connector diagrams as
follows:

• JA_01: not connected

• JA_02 RXD

• JA_03 TXD

• JA_04 DTR

• JA_05 GND

• JA_06 DSR

• JA_07 RTS

• JA_08: not connected

• JA_09: not connected

To configure the use of the serial port 1 it is necessary to set the following parameters:

• P.0451: use of serial port 1

• P.0452: Modbus address serial port 1

• P.0453: Baud rate serial port 1

• P.0454: Setting serial port 1

• P.0470: Modbus register orders for serial port 1

The description of these parameters is on document [3].


5.11.1.1 GSM analogue Modem
The analogue/GSM modem must be connected to serial port 1 (JA connector). The modem
must be selected among the types tested by SICES.

For the use of a GSM modem it is necessary that the operator inserts a SIM card of any phone
operator. It is important that on the SIM card the PIN code is disabled: insert the SIM into
a phone and disable the PIN code before inserting it into the phone.

The SIM type to insert depends on the use of the modem:

• If you want to use only SMS messages, any SIM is suitable.

• If you want to use the data exchange with a pc through an analogue modem (classic
modem 56k for example), it is necessary a SIM which allows that kind of data. The
data exchange happens through the phone channel, but the mobile operators can
enable/disable the passage of the data on phone both on the calls done and on those
received. Normally, the passage of the data on phone is available on SIM M2M
(machine to machine), but it is better to check with your own operator anyway.
Attention: if you talk about data with your phone operator, he would mean the
data on TCP/IP protocol (those of the Smartphone), but they are not the data
needed, though.

In any case, the connection of the GSM antenna is necessary.

For the use of SMS or data transmission through phone see document [3].

MC200 Technical Manual EAAM0578EN 67


5.11.2 JW - Serial port 2 RS485

The device is equipped with a RS485 serial port (serial port 2) galvanically insulated and
independent from serial port 1 (RS232), usable to connect via Modbus to a PC or other
devices.

For details on RS485 connections, its usage and its parameter programming, refer to
document [3].

Connections:

• JW 1-2: connection RS485 A+

• JW 3-4: connection RS485 B-

The RS485 connection needs a 120Ohm termination resistor on both ends of the cable. The
device has integrated resistor; to insert it, it is necessary to act on selector S5. The galvanic
insulation guarantees the operation security of the connection also among distant devices and
with different mass potentials compared with the controller. The maximum connection length
is 1200m: it is also function of the set transmission baud rate, though. The use of a special
shielded cable is provided (see 4.2) with shielded filter connected to earth.

To configure the use of the serial port 2 it is necessary to set the following parameters:

• P.0451: use of serial port 2

• P.0472: Modbus address serial port 2

• P.0473: Baud rate serial port 2

• P.0474: Setting serial port 2

• P.0475: Modbus register orders for serial port 2

The description of these parameters is on document [3].

On serial port 2 cannot be connected a modem; for the rest, it is possible to use it for the same
connections possible from RS232 serial port using RS485/RS232 adaptors or RS485/USB
when necessary.
5.11.3 JNA - USB Serial port: function mode

The USB protocol specifications don’t allow its use in the permanent industrial field due to the
limited length of the cable and of the elevated sensibility to electric disturbs also on PC side.
For this reason, the USB connection cable must be inserted only when it is necessary
to operate on the device and can be removed from the JNA connector when the
operation has finished.

68 MC200 Technical Manual EAAM0578EN


The USB connection with a PC is used for two purposes:

• Firmware upgrade.

• Parameter configuration.

Upgrading the device firmware is a specific operation of SICES srl; besides the FW to be
inserted, it requires a procedure and special programs. Also, it must not be done by the
installator, except for specific cases previously agreed with Sices.

The USB port can be used for the programming of parameters with BoardPrg3 program, in
alternative to the RS232/RS485 serial connection or Ethernet.

It is necessary that on the PC to be connected the driver CDC_Sices_Win.inf supplied by


SICES is installed; for the driver installation, refer to document [7].

Once installed the driver, the PC will detect the controller as a new serial port, to be used
exactly as it was a RS232 serial port.

The configuration parameters are:

• P.0478: Modbus address USB serial port.

• P.0479: Modbus registers order for USB serial port.


5.11.4 JY - Ethernet port 10 100Mbps

The Ethernet port with RJ45 connector is provided for data connection via LAN. For details on
net connection and protocol, refer to document [3].

It is possible to connect the device inside a LAN or directly to a PC (point to point connection).
The connection makes possible the use of SicesSupervisor3 supervision SW, BoardPrg3
configuration and all available functionalities through the TCP/IP Modbus protocol.

The connection of the device inside a LAN also allows to maintain updated the internal
calendar with UTC, besides the possibility to assign a public IP address (static or dynamic)
directly to the device itself.

Parameters for the configuration.


Parameter Name Default
P.0500 IP Address. Set it only if DHCP protocol is not 192.168.0.1
required (otherwise this field is filled by the DHCP
server): set the IP address assigned to the
controller.
P.0501 Subnet mask. Set it only if DHCP protocol is not 255.255.255.0
required (otherwise this field is filled by the DHCP
server): set the value used by the network the
controller is connected to.
P.0502 Network Gateway. Set it only if DHCP protocol is 0.0.0.0
not required (otherwise this field is filled by the
DHCP server): set the value used by the network
the controller is connected to.

P.0503 Modbus/TCP Port. Indicate the port on which the 502


controller can accept incoming Modbus/TCP
communications. The port 502 is standard for

MC200 Technical Manual EAAM0578EN 69


Modbus/TCP protocol: change it only when
required.
P.0505 Order of the Modbus registers. When 32-bit 0-LSWF
information is required, it establishes if the 16 more
significant bits must be sent first, or those less
significant.

P.0504 Web server Port. Indicate the port on which the 80


controller can accept incoming HTTP
communications. The port 80 is standard for HTTP
protocol: change it only when required. Currently
not supported.

P.0509 NTP server address. Set the IP address of the 0.0.0.0


server that provides updated date/time.
P.0508 NTP Server port. Set the port on which the NTP 123
server is listening. The port 123 is standard for NTP
protocol: change it only when required.

P.0510 Primary DNS server. Set it only if DHCP protocol is 0.0.0.0


not required (otherwise this field is filled by the
DHCP server): set the IP address of the primary
DNS server (server who provides the translation
service among names and IP addresses).
P.0511 Secondary DNS server. Set it only if DHCP protocol 0.0.0.0
is not required (otherwise this field is filled by the
DHCP server): set the IP address of the secondary
DNS server (server who provides the translation
service among names and IP addresses).

P.0514 DHCP server address. Set to “255.255.255.255” if 0.0.0.0


DHCP protocol is required (any other value disables
that protocol).
P.0513 DHCP server port. Set the port on which the DHCP 67
server is listening. The port 67 is standard for
DHCP protocol: change it only when required.
P.0456 Plant name. If DHCP protocol is used, the controller
can be contacted from the Network using this
name.

To reach the device inside a LAN net, it is necessary to configure at least parameters P.0500,
P.0501 e P.0502. It is possible to proceed in two ways:

• It is possible to manually configure the three above mentioned parameters, with


congruent values with the network to which we connect (the sub-net mask and the
router/gateway are specific of each network, the IP address must be univocal in the
network). To proceed this way, it is necessary that parameter P.0514 is set to 0.0.0.0.

• It is possible to dynamically acquire from the network the values for the three above
mentioned parameters. To do so, it is necessary that the controller can connect to a
DHCP server (Dynamic Host Configuration Protocol). To proceed this way, it is
necessary that parameter P.0514 is set to 255.255.255.255 and that parameter
P.0513 is set to 67 (67 is the standard port for the DHCP server, if your server uses a
different port, set it in P.0513). Also, parameter P.0456 must contain the name to
which server DHCP will match the IP address (see after DNS description).

Once the controller has valid values for parameters P.0500, P.0501 and P.0502 (see page
S.05), can be contacted through Modbus-TCP protocol on the assigned IP address and on
TCP port configured with P.0503, for example with the supervision SW (SicesSupervisor3)
and of configuration (BoardPrg3). When using DHCP protocol, the controller will be reachable
through the Modbus-TCP protocol both on IP address and on the configured name, on P.0503
port.

70 MC200 Technical Manual EAAM0578EN


The controller also supports the DNS protocol (Domain Name System). The DNS system is a
system used for the conversion of the names of the network knots in IP addresses and vice-
versa. To use the DNS system, it is required:

• If you don’t use a DHCP server (see above), it is necessary to set the IP address of
the DNS server in P.0510 (it is possible to set the address of a secondary DNS server
in P.0511).

• If you use a DHCP server (see above), the IP address of the DNS server is acquired
by the controller directly from the DHCP server.

Parameters P.0508 and P.0509 allows to set the IP address and the port to be used to connect
to a NTP server (Network Time Protocol), in such way to keep synchronized and updated the
internal calendar with date and time of the reference time zone (that is, of the UTC time).
Setting one or both parameters to zero the function will be disabled. For more details refer to
the document 9.3.1.

The real IP addresses (those configured manually or those obtained by DHCP server) are
visible on page S.05.

5.12
For the connections below mentioned, use a cable suitable for CAN bus (see documents [5]
[6]).
5.12.1 JM - CAN bus port 0

This interface is used for the connection to expansion modules DITHERM, DIGRIN, DIVIT,
DITEL, DANOUT.

The CAN bus interface is galvanically insulated.

Connections:

• Connect terminal JM-1 to terminal CAN_H of the expansion modules.

• Connect terminal JM-3 to terminal CAN_L of the expansion modules.

Connect the shielding mesh of the shielded cable to the protective earth or to signal on both
sides.

MC200 Technical Manual EAAM0578EN 71


The CAN bus connection needs a 120Ohm termination resistor on both ends of the cable. The
terminal resistor is integrated in our controller; to insert it, you need to act on switch S1. NOTE:
the termination must always be inserted, unless the connection carries on towards other
devices and the controller is not one of the two extremes.

We recommend the use of a proper shielded cable (e.g. HELUKABEL 800571).

For the configuration of the additional expansion modules, see par. 5.8.
5.12.2 JX - CAN bus port 1

This CAN bus interface must be used to connect among themselves all SICES
genset/mains/bus coupler controllers): through this communication channel (PMCB – Power
Management Communication Bus), the controllers exchange all necessary data to manage
the parallel functions (see document [8]).

The CAN bus interface is galvanically insulated.

Connections:

• Connect terminal JX-1 to terminal CAN_H of the other SICES controllers.

• Connect terminal JX-3 to terminal CAN_L of the other SICES controllers.

Connect the shielding mesh of the shielded cable to the protective earth or to signal on both
sides.

The CAN bus connection needs a 120Ohm termination resistor on both ends of the cable. It
is therefore necessary to insert such resistance only on the first and on the last SICES
controller. Note: the connection of the controllers can never be star but it must be daisy chain.
The terminal resistor is integrated in our controller; to insert it, you need to act on switch S6.

We recommend the use of a proper shielded cable (e.g. HELUKABEL 800571).

Use the parameters of menu 8 for the parallel functions (parameter P.0800 enables/disables
this CAN bus interface).

72 MC200 Technical Manual EAAM0578EN


6
6.1

Fig. 1 - Front Panel

The controls consist of 12 buttons.

The front panel also has some luminous indicators.

MC200 Technical Manual EAAM0578EN 73


6.2

Pushbutton Function
The controller is disabled; all anomaly signals are disabled. The MGCB circuit
OFF/RESET breaker is opened (if it exists and is managed by the controller). The MCB
PROGRAM circuit breaker is closed (if it exists and is managed by the controller).
You can program the parameters.
The controller is set for manual generators control.
MODE UP
Press the START button to start the generators (if MGCB circuit breaker exists
and is opened, the generators close their GCB and work in parallel).
Press the STOP button to stop the generators (that will stop after GCB has
MAN been opened and the engine has been cooled).
Press the MCB button for manual opening/closing of the circuit breakers that
connects the mains to the loads.
Press the MGCB button for manual opening/closing of the circuit breakers that
connects the generators bus to the loads.
MODE The controller automatically manages the gensets operation, so they will be
DOWN started if required by the operating conditions.
By pressing the START button it is possible to activate/deactivate the TEST
AUTO TEST mode. If not otherwise configured, it does not close the MGCB circuit breaker.
The STOP button, if not otherwise configured, causes the stop of the gensets
and the activation of an alarm.
In programming mode, it cancels the changes made to a variable value, brings
up the previous menu level, or exits programming mode. If it is pressed for at
least two seconds in any menu, you exit the programming mode retaining the
current menu position for further programming access.
If it is pressed in any window, it displays the status information on the upper
line (displaying them cyclically).
Depending on the selected page, if pressed together with the ENTER button
for at least 5 seconds while in OFF/RESET mode, it can reset counters to
zero, reload default values of the programming parameters or cancel history
logs, force exit from BUS OFF mode of the CAN bus.
When used during the keyboard regulation function, it aborts the function.
Navigation buttons of the multifunction display. These buttons let you select
the previous or next page on the display in all modes, except in the
PROGRAM AND HISTORY LOG mode.
Horizontal navigation buttons: in PROGRAM mode, they are used to
position the cursor when entering the strings. Used in combination with the
ESC/SHIFT button, they allow to adjust the contrast:
ESC/SHIFT + LEFT: to decrease the contrast (lighten).
ESC/SHIFT + LEFT: to increase the contrast (darken).
Vertical navigation buttons: in PROGRAM and HISTORY LOG they allow
to scroll the menus and the variables / registrations. You can
increase/decrease the value of the variable. Used in combination with
ESC/SHIFT button, they allow to scroll through the menus ten entries at a time
or increase/decrease the variables ten units at a time.

74 MC200 Technical Manual EAAM0578EN


Pushbutton Function
In the PROGRAM menu, you can enter the programming mode and open a
submenu, change a variable or parameter, and confirm the operation.
In ARCHIVE menu, it allows to activate the HISTORY LOG menu and allows
the entrance in the selected archive.
It allows to “accept” eventual anomaly signalling on the memory while turning
on.
When there is an alarm, by pressing the button you deactivate the siren. A
further press of the button recognises the presence of an anomaly and resets
any alarm signals if the operating conditions have returned to normal. Alarms
can only be reset by activating the "OFF/RESET" mode.
The pushbutton only works in manual.
It allows to command the opening and the closing of the MCB circuit breaker
(if it exists and is managed by the controller). If the synchronization is required
for closing, by pressing the pushbutton the synchronization sequence is
activated. By pressing it during the paralleling with the mains, it allows to open
the MCB circuit breaker: if it is possible, the controller transfers the load to the
gensets before opening of the circuit breaker.
The pushbutton only works in manual.
It allows to command the opening and the closing of the MGCB circuit breaker
(if it exists and is managed by the controller). If the synchronization is required
for closing, by pressing the pushbutton the synchronization sequence is
activated. By pressing it during the paralleling with the mains, it allows to open
the MGCB circuit breaker: if it is possible, the controller transfers the load to
the mains before opening of the circuit breaker.
If MGCB does not exist or is externally managed, it is possible to use this
button for opening /closing the GCB circuit breakers of the generators: this
function must be enabled by means bit 3 of parameter P.0495.
In MAN mode, it can be used to start all the gensets “controlled by MC200”.
In AUTO mode, if automatic gensets start is not required, it changes the
operating mode to TEST. If automatic gensets start is required, it can be used
to restart gensets controlled by MC200 that are stopped for a low load
condition.
In TEST mode, it changes the operating mode from TEST to AUTO.
Together with the STOP pushbutton, at the power up it allows entering the
controller special functions.
In OFF/RESET mode, the pushbutton turns all leds on (to check if there are
any faults).
In MAN mode, it is used to stop all the gensets “controlled by MC200”.
In AUTO, TEST and REMOTE START modes, the controller normally issues
an alarm (A007) and stops all gensets “controlled by MC200” (this behaviour
can be disabled by means bit 0 of parameter P.0495).
Together with the START pushbutton, at the power up it allows entering the
controller special functions.

MC200 Technical Manual EAAM0578EN 75


6.3
It is possible to modify the brightness of the light indicators (all together) using parameter
P.0496: the higher the parameter value, the brighter the light indicators. The value can be set
between 1 to 10 (default value = 5).

LED OFF LED steady ON LED flashing


  

Signalling Function
 The controller is in the OFF/RESET operating mode.
Flashing at 50% on: it indicates that you are accessing the

PROGRAMMING menu.
 The controller is in another operating mode.

 The controller is in the MANUAL operating mode.

 The controller is in another operating mode.

 The controller is in the AUTOMATIC operating mode.


Flashing at 50% on: the controller is in the TEST operating
mode.

Flashing at 90% on: the controller is in the REMOTE START
operating mode.
 The controller is in another operating mode.
 There is at least one active alarm or unload.

 Flashing at 50% on: there is at least one active warning.

 There are no anomalies.

At least one Modbus or Modbus/TCP communication is running



over the serial ports, the USB port or the ETHERNET port.

 No Modbus nor Modbus/TCP communications are running.

 The CAN bus interface is active and in ERROR-ACTIVE mode.

Flashing at 25% on: there are communication errors, the CAN


bus interface is in ERROR-PASSIVE mode.

Flashing at 75% on: there are communication errors, the CAN
bus interface is in BUS-OFF mode.
The load shedding function is enabled, and at least one load

has been disconnected.
The load shedding function is disabled or no loads have been

disconnected.
 Mains voltages are steadily within the tolerance range.
 No mains voltages.
Flashing at 50% on: during transition between the previous two

statuses.

76 MC200 Technical Manual EAAM0578EN


Signalling Function
Flashing at 25% on: mains voltages under tolerance thresholds.

Flashing at 75% on: mains voltages above tolerance thresholds.

 The MCB circuit breaker is opened (or it does not exist).

 The MCB circuit breaker is closed.

Flashing at 25% on: MCB opened after a closing command.

 Flashing at 75% on: MCB closed after an opening command.

Flashing at 50% on: during synchronization (it flashes in


alternation with the BUS LIVE).
 Voltages are present on the loads.
 No voltages on the loads.
Flashing at 50% on: during the synchronization (it flashes in
alternance with MGCB during the direct synchronization,

flashes in alternance with MCB during the reverse
synchronization).
 The MGCB circuit breaker is opened.
 The MGCB circuit breaker is closed (or it does not exist).
Flashing at 25% on: MGCB opened after a closing command.
Flashing at 75% on: MGCB closed after an opening command.

Flashing at 50% on: during synchronization (it flashes in
alternation with the BUS LIVE).
 Voltages are present on the generators bus.

 No voltages on the generators bus.

MC200 Technical Manual EAAM0578EN 77


6.4
6.4.1 LCD lighting
The back-light lamp is managed by the controller, which switches it off the after a
programmable time (P.0492) if no buttons are pressed in the meantime. Press any button to
switch the lamp on again, (we recommend using the ESC/SHIFT button as it has no function
when used alone). This function can be disabled by setting parameter P.0492 to 0.

Using parameter P.0493 it is possible to force the lamp always on when at least one generator
is running.
6.4.2 Contrast adjustment
Depending on the environmental temperature conditions, the contrast may require adjustment
to correctly view the display.

Press in sequence the ESC/SHIFT + LEFT buttons to reduce the contrast (lighten), press the
ESC/SHIFT + RIGHT buttons to increase it (darken).
6.4.3 Colours scheme
As a default, the controller shows all information on the display using a blue background. It is
possible to modify this logic, though, using parameter P.0499:

• P.0499 = 0: blue background.

• P.0499 = 1: black background.

• P.0499 = 2: white background.

The colour of the messages depends on the background colour and on the type of information
displayed.
6.4.4 Mode navigation
The display has different visualization modes composed by different pages.

Mode Description Page


identifier

PROGRAMMING Programming P.XX

PLC Information on PLC program L.XX

STATUS Status information S.XX

MEASURES Electrical measurements M.XX

PMCB Pages related to parallel functions. B.XX

HISTORY History logs H.XX

78 MC200 Technical Manual EAAM0578EN


Generally, the navigation among the modes happens through UP and DOWN buttons.

To view the pages inside the mode, use the LEFT and RIGHT buttons.

In some modes (P.XX and H.XX), to view the pages press the ENTER button first, and then
use the UP and DOWN buttons to navigate between pages.

Fig. 3 - Mode navigation

If the UP and DOWN buttons must be used to manage the functions within the page, the
ENTER button must be pressed to activate the said functions, and the ESC/SHIFT button to
deactivate them.
6.4.5 Display area layout (ref. to fig. 4)

KEY: M.07 ENERGY METERS _


1 - Status bar
2 - Data area 1 Partial: 0 kWh

0 kvarh
2 Total: 0 kWh

0 kvarh
Exported energy

Fig. 4 - Display areas

6.4.6 Top status bar (ref. to fig. 5)


The top status bar contains information on navigation and/or some status information.
KEY:
1a - Mode identifier
1b - Page identifier M.07 ENERGY METERS _
1c - Page title
1c
1a
1b

Fig. 5 - Top status bar

MC200 Technical Manual EAAM0578EN 79


The current mode is shown in the relevant field of the top status bar (1a). The mode identifier
(1a), and the page identifier (1b) identify and refer to the page so there is no chance of error.
The title (1c) provides a description in the current language of the content of the page.

Pressing the ESC/SHIFT button, the controller replaces the title (while the button is held) with
a status message. By double clicking the ESC/SHIFT button, the title is replaced with a status
message so long as you remain on that page. If the bit 6 of parameter P.0495 is activated, the
controller automatically replaces the title with a status message if there is at least one pending
status message with a waiting time (countdown); if the operator selects a new page, the
controller shows the title for two seconds, then it shows the status message again.

80 MC200 Technical Manual EAAM0578EN


6.5
6.5.1 Programming (P.XX)
The controller manages a relevant number of parameters, which allows the constructor, the
installator and the final customer to configure it based on plant specific needs. This document
does not contain the list of parameters (even if many of them are mentioned in the description
of the different controller functions), but refer to document [1], for a detailed description. Here
is described the general structure of the programming and the operating procedure which
allows to read and/or modify the parameters.

To access the parameter modification mode, select page P.02 with UP and DOWN vertical
scroll buttons, then press ACK/ENTER to activate it.

To exit the programming menu and go back to the main window, press button ESC/SHIFT.

WARNING: Assigning an incorrect value to one or more parameters can cause


malfunctions, damage to things or injury to people. The parameters must only be
changed by qualified personnel. Parameters may be password protected (see par.
6.5.1.2).
6.5.1.1 Organization

P.05 PROGRAMMING _
KEY:
1 - Status bar
1
2 - Current menu 2.1 Mains sensor ____________ _4/12
3 - Current parameter 2
4 - Parameter value 5 – Access
level 0236-Mains low frequency threshold (%)

3 [90.0]
4
(45.00 Hz)
5 ______________________________________
Access level: maker
6
Fig. 6 - Display areas

The first line under the top status bar identifies the current menu (2) with the menu number
and the relevant text. A pair of numbers is displayed on the right of this line (4/12 in the
example). The first indicates which entry of the menu is selected or which page is displayed,
the second indicates how many entries or pages can be displayed in the present
menu/submenu.

Each programming parameter (3) has a 4-digit numeric code (e.g. P.0236) to identify the
variables regardless of the language used. The current value of the parameter is displayed
below the description (4), between brackets. If the parameter configures a value that is a
percentage of another item, the controller shows the equivalent value in the measurement unit
of the reference item (5).

The last row shows the access level currently acknowledged to the operator (6).
6.5.1.2 Protection password
Access to the programming mode can be controlled by 4 different password levels, which are
listed in order of priority.

• SICES password.

• MAKER password.

• INSTALLER password.

MC200 Technical Manual EAAM0578EN 81


• USER password.

Each parameter of the controller is associated to a protection level (in document [1] this
association is indicated in column “ACC” with a letter “S” to indicate SICES level, “C” for
constructor, “I” for installator and “U” for final user).

A parameter associated to SICES level is modifiable only setting SICES password. A


parameter associated to the maker level can be modified only by the maker himself (or with
the SICES password). A parameter associated to the installer level can be modified by the
maker and the installer (or with the SICES password). A parameter associated to the end user
lever can be modified by the maker, the installer, and the end user (or with the SICES
password).

The general rule says that the parameters are modifiable only when the controller is in
“OFF/RESET” mode. Some parameters are an exception and can be modified regardless of
the status of the controller board, including when the generators are running. Generally, if a
parameter cannot be modified, its value will be between “<” and “>”, whilst if modifiable, it is
between “[” and “]”: this is valid also for the password restrictions.

The operator who should modify a parameter, must first let the controller recognise him as
“SICES”, “maker”, “installer” or “user”, dialling the right password in parameter P.0000 (menu
“1.1.1 - Authentication”). After this operation, he will be able to modify the parameters. The set
access code remains in P.0000 memory for about 10 minutes after programming has been
completed. After this time, it will be automatically reset and it should be set again to enter a
new programming.

It is possible to customize the password through parameters P.0001 (maker), P.0002 (installer)
and P.0003 (user), available on menu “1.1.2 Password configuration”. The value “0” for these
parameters indicates password not set. The SICES password instead, it is a special password,
pre-assigned and supplied together with the controller. The password supplied with the
controller is always valid. On demand, SICES can provide a second password, only valid for
2 hours’ operation, though. After this time, a new password must be asked to SICES.

To obtain the password, the operator should ask SICES, indicating the “Serial number” of the
controller, together with the “Internal code” displayed on page S.03, as shown below:

S.03 BOARD STATUS _

Friday 26/May/2017 11:35:43

Serial number: 0000201CD5DD


System Controller S/W: EB02502700051
Measure Engine Software: EB02502520102
Internal code: 5217
Internal temperature: 41.4°C
Battery voltage: 27.1V
Language: [ENGLISH]

If a password gets lost, it is possible to reconfigure it by logging in with the higher-level


password. For this reason, we advise against not setting at least the “maker” password
(P.0001): is, in effect, someone else sets it or another lower password (even only for
distraction) without communicate it, it will no longer be possible to modify any
parameter. By knowing the “maker” password, it will be possible to nullify or modify
the other passwords. Contact our service centre if the “maker” password is lost.

The following examples show all combinations of password assignment.

Example 1: P.0001 =0 P.0002 =0 P.0003 =0

Any operator is considered “maker”, without setting anything in P.0000. Therefore, all
parameters, except for the special ones, can be changed by anyone (this is the default
mode).

82 MC200 Technical Manual EAAM0578EN


Example 2: P.0001 =0 P.0002 =0 P.0003 =UUU

No parameter is modifiable. When the user enters the “UUU” code in P.0000, he would be
considered “user”, but as no password is associated to the “installer” and the “maker”, the
controller considers him as “maker”. After entering this code, all parameters, except for the
special ones, can be modified.

Example 3: P.0001 =0 P.0002 =III P.0003 =UUU

No parameter is modifiable. When the user enters “UUU” in P.0000, he is considered “user”
and can modify only the parameters associated to “user”. If user enters “III” the board
considers it “maker” because there is no password for “maker”. After entering this code, all
parameters, except for the special ones, can be modified.

Example 4: P.0001 =CCC P.0002 =III P.0003 =UUU

No parameter is modifiable. When the user enters “UUU” in P.0000, he is considered “user”
and can modify only the parameters associated to “user”. If the user enters “III”, he can
modify all parameters associated to “installer” and “user”. When entering “CCC”, the
operator is identified as “maker” and can modify all parameters, excluding the critical ones
of the controller.

Example 5: P.0001 =CCC P.0002 =0 P.0003 =0

No passwords are associated to the user and the installer. The parameters associated to
user and installer are free programmable, without entering any code in P.0000. To modify
maker associated parameters you must enter “CCC” in P.0000.

Example 6: P.0001 =0 P.0002 =III P.0003 =0

As no password is associated to the user, the parameters associated are freely


programmable, without entering any code in P.0000. When the user enters “III” in P.0000,
he can modify all parameters because there is no password for “maker”. After entering this
code, all parameters, except for the special ones, can be modified.

Example 7: P.0001 =CCC P.0002 =III P.0003 =0

As no password is associated to the user, the parameters associated are freely


programmable, without entering any code in P.0000. When the user enters “III” in P.0000,
he can modify all parameters associated to “installer” and “end user”. When entering “CCC”
in P.0000, the operator is identified as “maker” and can modify all parameters, excluding
critical ones.

Example 8: P.0001 =CCC P.0002 =0 P.0003 =UUU

No parameter is modifiable. When the user enters the “UUU” code in P.0000, the controller
considers him “user”, but as no password is associated to “installer”, it considers him
“installer”. He can modify all parameters associated to the end user and the installer. When
entering “CCC” in P.0000, the operator is identified as “maker” and can modify all
parameters, excluding critical ones.

The parameter value can always be read, but the modification can be carried out only if
P.0000 contains a proper password. Parameters P.0001, P.0002, P.0003 and P.0469 are
excluded: they are not displayed in case P.0000 does not contain a proper password.

Parameter P.0469 (password for serial ports) is viewable and/or modifiable only from
operator panel and, at least, with installer rights.
6.5.1.3 Operating procedure
This procedure will describe the keyboard and display use.

MC200 Technical Manual EAAM0578EN 83


P.05 PROGRAM _

Main menu ____________________1/07

1 System
2 Sequence
3 Protections
4 Auxiliary functions
5 Communication
_______________________________________
Access level: maker

 1 (SYSTEM). The menu 1-SYSTEM allows first to indicate how the controller is connected
to the mains and to the generator bus, and the plant type. It is most important to correctly
set these parameters as nearly all thresholds for the protection activation are expressed
in percentage compared to them.

 2 (SEQUENCE). Working sequence configuration can be modified through the menu 2-


SEQUENCE. In this menu, the threshold percentages can be set, the time of acquisition
and enabling/disabling of the functions related to the operation sequences.

 3 (PROTECTIONS). Protections management is accessible through the menu 3-


PROTECTION. As to this, it is important to know that, to enable/disable a protection, you
may simply modify the associated time, leaving the threshold unchanged: by setting the
time to zero, the protection is disabled. However, this general rule provides some
exceptions. Refer to the chapter dedicated to the anomalies, par. 0, which describes each
disabling mode.

 4 (AUXILIARY FUNCTIONS). All that is not about the configuration of the system, the
sequence and protections is configurable from menu 4-AUXILIARY FUNCTIONS. In this
menu are other menus which configure calendars and history logs.

 5 (COMMUNICATION): In this menu are the communication settings for the serial ports,
for the ETHERNET port, for the USB port and the configuration for the modem.

 6 (PLC): The menu 6 - PLC Shows the setpoints defined in the currently loaded PLC
program. If no PLC program is loaded, or if it does not define any setpoint, this menu is
hidden.

 8 (PARALLEL): The menu 8-PARALLEL allows to configure all the functions related to
the parallel with the mains or among gensets.
6.5.1.3.1 Access to programming

The programming is accessible in any operation status of the controller, while the parameter
modification is generally possible only with the controller in OFF/RESET. To enter in
programming mode, it is required to act on ▲ and ▼ pushbuttons until the programming
screen appear (P.02).

If you are in a mode which puts some limitation in the use of the vertical scroll pushbuttons, it
might be necessary to press one or more times the ESC/SHIFT pushbutton (e.g. when viewing
history logs or during operations).

Then press ENTER to enter programming.

At the start of the procedure, the menu o the variable used at the last exit from programming
is shown (at first entrance the main menu is shown). This is true if the programming procedure
has been previously abandoned changing the operation mode of the controller in MAN or
AUTO or after a maximum time of permanence without operating in programming or keeping
ESC/SHIFT pressed for more than two seconds.

84 MC200 Technical Manual EAAM0578EN


6.5.1.3.2 Menu selection

The name of the current menu is always shown in the first line, followed by the numeric ID of
the selected item and the number of menu items. The further lines of the display are used to
view the menu items, that is, the submenus. The item selected is drawn in REVERSE. Using
▲ and ▼ pushbuttons, the menu scrolls respectively towards the top or bottom index items,
in a cyclical way (that is, pressing ▲ from the first item you pass to the last and vice-versa).

Pressing ACK/ENTER button, you enter a selected submenu (the one highlighted), pressing
ESC/SHIFT you leave the menu (going back to the previous menu or leaving the programming
to the basic screen if you were already on the main menu).
6.5.1.3.3 Parameters selection

The name of the current menu is always shown in the first line, followed by the numeric Id of
the selected item and the number of menu items. The next display lines are all used to view a
single parameter:

• Fourth and fifth rows show the univocal parameter code (four decimal digits) followed
by the description in the current language.

• The seventh line shows, aligned on the right, the value of the variable, enclosed
between square brackets or “< >”.

• For some parameters, on the ninth line, a value someway connected to the current
value of the parameter is shown. For example, in the case of the low mains frequency
threshold (P.0236), the equivalent voltage is shown, calculated from the mains
nominal voltage (P.0116) and by the parameter itself (%). This additional value is often
displayed when the parameter is expressed as percentage compared to some other
value to show the absolute value.

• The last line of the display shows the protection level given to the operator (SICES,
maker, installer or user).

Using ▲ and ▼ buttons, the menu scrolls respectively towards the top or bottom index items,
in a cyclical way (that is, pressing ▲ from the first item you pass to the last and vice-versa).
Pressing ACK/ENTER button, the modification procedure of the parameter activates (see next
paragraph), pressing ESC/SHIFT button you leave the menu (going back to the previous
menu).
6.5.1.3.4 Modification of a parameter

A parameter can be modified only if shown between squared brackets ([]); if between “<>”, it
cannot be modified. In this case, it could be necessary to set a suitable password or to put the
controller in OFF/RESET mode.

Once visualized a parameter, to start modifying it, it is necessary to press the ACK/ENTER
pushbutton. To confirm the new value, it is necessary to press ACK/ENTER; to cancel the
modification and go back to the original value just press ESC/SHIFT.

There are the following types of parameter:

• Bits: Some parameters are managed in bit. Each bit at 1 enables a function and each
bit at 0 disables a function. Up to 16 bit can be used. A hexadecimal value is attributed
to each bit. The parameter must be set with the result of the sum of the hexadecimal
values linked to the functions to be enabled. The setting happens as described for the
strings, with the exception that it is possible to select only hexadecimal characters
(0...9, A....F).

In the description of these parameters, there will be a chart like the following:
Bit Value Description
1 0001 Enable function 1
2 0002 Enable function 2
3 0004 Enable function 3
4 0008 Enable function 4

MC200 Technical Manual EAAM0578EN 85


5 0010 Enable function 5
6 0020 Enable function 6
7 0040 Enable function 7
8 0080 Enable function 8
9 0100 Enable function 9
10 0200 Enable function 10
11 0400 Enable function 11
12 0800 Enable function 12
13 1000 Enable function 13
14 2000 Enable function 14
15 4000 Enable function 15
16 8000 Enable function 16

If the operator wants to:

 Disable all functions: he must set 0000 in the related parameter.

 Enable the functions from 1 to 8: the value to be set is given by the hexadecimal
sum 0001+0002+0004+0008+0010+0020+0040+0080 = 00FF.

 Enable e.g. functions 3, 4, 6 and 8: the value to be set is given by the sum of
0004+0008+0020+0080 = 00AC.

 Numeric: the value is modifiable using ▲▼ buttons, respectively to increase or


decrease the value of one unit (if these buttons are pressed together with ESC/SHIFT,
the value will be increased or decreased of ten units at a time). The modification is
cyclical: trying to increase the value when it is already at the maximum, it passes to
the minimum, and vice-versa.

 Numerical with selection among a default list (e.g. the number of phases of the
mains): it is valid what said for the numerical parameters, considering that the ▲▼
buttons allows to pass to the following /previous value in the default list (pressed with
ESC/SHIFT button, allow to pass to the value which follows/precedes the current one
of ten positions).

 Numeric selected in a number-string couples list (e.g. the function of a digital


input): same as the previous point.

 Time: it is valid what said for the numeric parameter, except for the fact that the
controller manages the increasing/decreasing keeping valid values (e.g. increasing
from 00.59” to “01.00” and not to "00.60").

 Strings (e.g. phone numbers): in this case the visualizer highlights (in reverse) the
character selected on the string. The ▲▼ pushbuttons work on the selected character
(passing to next/previous character of the ASCII table or jumping by ten positions
ahead/back if ESC/SHIFT is pressed too), whereas ◄► pushbuttons allow selecting
the character to modify. Characters ASCII from 32 (space) to 127 (escape) are
settable. Characters ASCII (over 127) and those of control (from zero to 31) are
not settable.

 Hexadecimal strings (e.g. the bit polarity of the outputs): as for string parameters,
but the selectable parameters are only “0-9” and “A-F” (these last in capital letters
only).
6.5.1.3.5 Set up limits

The operator does not have to worry about verifying that the set value is acceptable for the
controller since it is not possible to set not acceptable values.

This is valid for each single parameter; it is possible, though, to set two or more parameters in
contradictory or incompatible way. The operator must verify that this does not happens.

86 MC200 Technical Manual EAAM0578EN


6.5.1.3.6 Exit from programming

There are three ways to exit the programming:

• Press ESC/SHIFT n times to climb up again to the main menu and then press it again
to exit the programming. Coming a next time into programming, it will be show main
menu.

• Keep ESC/SHIFT pressed for two seconds from any position: you will exit immediately
the programming and you will find yourself exactly at the same point at the next
entrance.

• Changing the controller mode to AUTO or MAN: next entry will be exactly in same
point.
6.5.1.4 Loading default values

WARNING: This procedure reloads in a permanent way the default parameters in


function of the access rights.

In certain situations, it can be useful to reload the default parameters. To do so, it is necessary
to select first the OFF/RESET mode, enter programming, then keep the ACK/ENTER and
ESC/SHIFT buttons pressed at the same time and consecutively for five seconds. A message
on the display will indicate to the operator the happened reloading of the default values. The
default values are only reloaded for those parameters for which you have access rights.

MC200 Technical Manual EAAM0578EN 87


6.5.2 PLC (L.XX)
Pages from L.01 to L.07 contain the information related to the PLC logic and are only displayed
if on the controller is installed a valid PLC program. Refer to [10] for information on PLC.
6.5.2.1 L.01 PLC

L.01 PLC _

PLC version: 1.01


Compiler version: 2.01
Editor version: 2.04
Last modification: 28-04-2016 13:45:00
PLC avg/max time: 1.250ms 1.452ms
Title: New Project
Description:

This page contains information of the PLC program installed in the device, as:

• The title and the description of the PLC program.

• The date of the last modification.

• The version of the PLC firmware, of the compilator and of the editor.

• The medium/maximum time of execution. These times are reset automatically when
the PLC program is sent to the controller, or it is possible to force the reset by pressing
ACK/ENTER + ESC/SHIFT buttons at the same time for five seconds.
6.5.2.2 L.02 PLC LOGIC

L.02 PLC LOGIC _


PLC block: [AND-001]
<out> |DI_VIRTUAL_01 | 0
<in> |DI_CONTROLLER_01 | 1
<in> |DI_CONTROLLER_02 | 0
| | |
| | |
| | |
| | |
| | |

This page shows information about a single PLC block.

In the second row on the right the selected block is shown, with format “TYPE-NUMBER”. To
select the PLC block, press ACK/ENTER, then use ▲▼ buttons to search for the PLC block
wanted; confirm by pressing ACK/ENTER again.

All parameters of the PLC block selected are shown in the following lines (one line for each
parameter):

• The first column identifies the type of parameter used (input/output).

• The second column identifies the resource associated to the parameter. The
resources are normally shown with SICES codification (e.g. the digital input 1 is
identified as DI_CONTROLLER_01). In the PLC program, it is possible to associate
symbols (nicknames) to the resources. It is possible to view the symbols in the second

88 MC200 Technical Manual EAAM0578EN


column, in place of SICES codes: press ACK/ENTER (as to select a different PLC
block) and press ◄►; confirm with ACK/ENTER button.

• The third column shows the current value of the resource. For digital resources, if the
viewed value is in REVERSE, it means that the relative parameter is denied.
6.5.2.3 L.03 VIRTUAL INPUTS

L.03 VIRTUAL INPUTS _

| 1 8 9 16___________
|
PLC: | 00000000 00000000
|
|
|
|
|
|
This page shows to status of all virtual digital inputs (that is, those inputs the status of which
has not been acquired by the hardware, but is determined by the PLC program).
6.5.2.4 L.04 DIGITAL FLAGS

L.04 DIGITAL FLAGS _


PLC: | |___________
1| 00000000 00000000| 16
17| 00000000 00000000| 32
33| 00000000 00000000| 48
49| 00000000 00000000| 64
65| 00000000 00000000| 80
81| 00000000 00000000| 96
97| 00000000 00000000| 112
113| 00000000 00000000| 128

This page shows the status of all temporary digital variables (DT_XXX) available for the PLC
program. Many pages which alternate every 2 seconds are available to view all digital flags.
Keeping ESC/SHIFT pressed, you can stop the rotation of the pages (keeping on the display
the page currently viewed).
6.5.2.5 L.05 DIGITAL STATUSES

L.05 DIGITAL STATE _


PLC: | |___________
1| 00000000 00000000| 16
17| 00000000 00000110| 32
33| 00110000 00000000| 48
49| 00001000 00000000| 64
65| 00000000 00000000| 80
81| 00000000 00111000| 96
97| 00100000 00000000| 112
113| 00000000 00000000| 128

MC200 Technical Manual EAAM0578EN 89


This page shows the value of all internal status of the controller (ST.XXX) available for the
PLC program). Many pages which alternate every 2 seconds are available to view all digital
statuses. Keeping ESC/SHIFT pressed, you can stop the rotation of the pages (keeping on
the display the page currently viewed).
6.5.2.6 L.06 VIRTUAL ANALOGUE

L.06 VIRTUAL ANALOGUE _

#1: --------.--
#2: --------.--
#3: --------.--
#4: --------.--
#5: --------.--
#6: --------.--
#7: --------.--
#8: --------.--

This page shows to value of all virtual analogue inputs (that is, those inputs the heat of which
has not been acquired by the hardware, but is determined by the PLC program).
6.5.2.7 L.07 NUMERICAL SUPPORT

L.07 NUMERICAL SUPPORT _

#01: 0 #02: 0
#03: 0 #04: 0
#05: 0 #06: 0
#07: 0 #08: 0
#09: 0 #10: 0
#11: 0 #12: 0
#13: 0 #14: 0
#15: 0 #16: 0
#17: 0 #18: 0

This page shows the status of all temporary numeric variables (AT_XXX) available for the PLC
program. Many pages which alternate every 2 seconds are available to view all numeric
supports. Keeping ESC/SHIFT pressed, you can stop the rotation of the pages (keeping on
the display the page currently viewed).

90 MC200 Technical Manual EAAM0578EN


6.5.3 Status information (S.XX)
In this mode, the information on the system status are supplied. You can scroll through the
various pages using the LEFT and RIGHT buttons.
6.5.3.1 S.01 STATUS
Page S.01 (STATUS) shows system status information. Part of this information is displayed in
the upper title bar if you press and hold the ESC/SHIFT button. It contains:

 Working mode of the controller (MAN, AUTO, etc.).

 The status of the operation sequence (idle, starting the gensets etc.).

 The status of protections for the parallel with the mains.

 The electric mains status (absent, low, high, etc.).

 The eventual presence of inhibition to start the generators.

 The eventual presence of inhibition to connect the loads to the generators.

 The eventual activation of protections override.

 The signalling of some genset in condition of “GCB not open”.

For many information, a time is also shown; for example, during the generators stopping cycle
the lasting time is shown at the end of that cycle.
6.5.3.2 S.02 ANOMALIES
The page S.02 (ANOMALIES) is automatically displayed in case a new anomaly arises. For
every anomaly, it is shown:

 The date/hour the anomaly activated.

 A letter identifying the type of it:

o “A”: alarm.

o “U”: unload.

o “W”: Warning.

 A three-digit numeric code that uniquely identify the anomaly. This code flashes if the
anomaly has not been acknowledged yet with ACK/ENTER.

 An alphanumeric description, based on the currently selected language and that in


some cases can be customized through the controller parameters.

Each anomaly uses two lines of the display. The anomaly shown on the top is the more recent
in chronological order. If space is not sufficient to show all the pending anomalies, only the
most recent ones are shown. To see also the other, you must:

 Press the ACK/ENTER pushbutton.

 Use the ▲▼ pushbuttons to scroll the anomalies.

 Press ESC/SHIFT to leave the mode.

Some anomalies can show additional diagnostic information. This information is automatically
viewed if an anomaly is active: if there are many anomalies active, use the procedure
described above to select the single anomalies and see the eventual additional diagnostic
information regarding the selected anomaly. The anomalies with additional diagnostic
information are:

• 273 (Parameters not coherent or not set). It shows an additional message helping to
understand the problem.

MC200 Technical Manual EAAM0578EN 91


• 252 (EXBUS: some modules are missing). It shows an additional message that
identifies the configured expansion module, that does not communicate with MC200.

• 253: (EXBUS: some measures are missing). It shows an additional message that
identifies the acquisition channel and the expansion module from which we expect to
receive a measure, which is lacking instead.

• 254 (EXBUS: duplicated address). It shows an additional message that identifies the
type and the address of the expansion module that is connected twice to MC200.

• 255 (EXBUS: sensor disconnected). It shows an additional message that identifies the
channel of acquisition and the expansion module which is sending the information of
“broken wire”.

• 900 (PLC parameters not coherent or not set). It shows an additional message helping
to understand the problem.
6.5.3.3 S.03 BOARD STATUS
This page is dedicated to the information of the device and contains:

 The current date and hour in extended format (flashing is the clock is not valid).

 The serial number univocal for the controller.

 The codes of the software currently uploaded on the controller (see par. 1.6).

 The internal code necessary to obtain a temporary SICES level password (see 6.5.1.2).

 The internal temperature of the controller.

 The power supply voltage.

 The language currently used by the device. It is also possible to select a different
language: press ACK/ENTER button, select the language with buttons ▲ and ▼ and
confirm with ACK/ENTER button. Note: MC200 is supplied only with ENGLISH, ITALIAN
and PORTUGUESE languages. With BoardPrg3 program it is possible to transfer other
languages to the controller.
6.5.3.4 S.04 SERIAL COMMUNICATION
This page is dedicated to the status of the communication towards the serial ports and the
USB port. In the case of operating problems, check the information in this page.

For each port the status (stand-by, communicating, etc.) and the counter of receiving errors
are displayed. To reset an error counter, you must:

 Press ACK/ENTER: the controller highlights the error counter of the serial port
COM1.

 Use the vertical arrows to highlight the counter to be reset.

 Press ACK/ENTER + ESC/SHIFT for 5 seconds: at the end, the controller resets the
counter.

 Press ESC/SHIFT.

If a modem is connected to the controller, is also shown:

 The modem model.

 In case of a GSM modem:

o The name of the telephone provider.

o The GSM signal level.

92 MC200 Technical Manual EAAM0578EN


6.5.3.5 S.05 NETWORK
This page is dedicated to the status of the connection and communication on the ETHERNET
interface.

The controller shows:

 The status of the connection:

o “idle”: no communication running, and Ethernet cable disconnected.

o “idle-linked”: no communication running, and Ethernet cable connected.


o “Communic. In progress”: communication running.

 The MAC address of the physical net interface.

 The IP address of the controller, the address of the router/gateway, the Subnet-mask
and the DNS server address. Those values can be the ones set with the parameters
of the controller, or those dynamically acquired by server DHCP (see 5.11.4).
6.5.3.6 S.07 CAN bus
This page displays the status of the CAN bus interfaces of the controller. MC200 has two
interfaces. Each interface displays

 The communication status of the bus. There are three possible signalling:

o ERROR-ACTIVE: normal operation.

o ERROR-PASSIVE: communication is working despite faults (errors).

o BUS-OFF: Gen-set has interrupted the connection to the bus due to too many
errors.

 Communication error counters are displayed. The counters of the instantaneous


transmission/reception errors and the maximum values reached are displayed. It is
possible to reset the maximum values (and force the output status of BUS-OFF) by
pressing for 5 seconds the buttons ACK/ENTER and ESC/SHIFT. Since two CAN
interfaces are present, it is necessary to select the desired CAN interface first and
then reset the counters: to select an interface press ACK/ENTER digit and use ▲ and
▼ digits.
6.5.3.7 S.08-09-10 GENERIC STATUS
These pages are dedicated to the view of the generic statuses acquired through the digital
inputs, configured with functions DIF.3201 and DIF.3202 (page 1), DIF.3203 and DIF.3204
(page 2), DIF.3205 and DIF.3206 (page 3).

The page uses one line for each configured input. If more than 6 inputs are configured, the
controller will display all of them in rotation (6 at a time) every 2 seconds: keeping ESC/SHIFT
button pressed you stop the rotation. If there are no configured inputs on a page, the page is
not displayed.

On each line, the controller shows the configured text for the digital input and the logical status
of it.

If you use functions DIF.3202, DIF.3204 and DIF.3206, when the input changes from non-
active to active, the controller forces the view of the relative page.
6.5.3.8 S.11 DIGITAL INPUTS
This page shows the status of:

 Digital inputs of the controller.

 Analogue inputs used as digital (if they are not used as digital they are displayed with
dashes).

MC200 Technical Manual EAAM0578EN 93


 Virtual digital inputs.
Pressing ACK/ENTER button, it is possible to change (cyclically) the ways the controller
shows the inputs:

 LOGICAL STATE: the controller shows the input’s logic level (active or inactive) used
in the management of the operating sequence.

 PHISICAL STATE: the controller shows the electrical level (active or inactive, or high
or low) present on the input; this can be the opposite in comparison to the
corresponding logic state. Displayed in REVERSE.

 FOR FUNCTION: the controller shows a list of functions associated to the digital
inputs, showing the logic status (1/0) relative to each function, independently from the
input associated to the functions. If more than 9 functions are configured, the controller
will display all of them in rotation (9 at a time) every 2 seconds: keeping ESC/SHIFT
button pressed you stop the rotation.
6.5.3.9 S.12 DIGITAL INPUTS
This page is only shown if some DITEL modules have been configured (see 5.8). It displays
the status of the digital inputs acquired from DITEL digital modules. If a DITEL module does
not communicate correctly, the controller will display some dashes in place of the input’s
status. Pressing ACK/ENTER button, it is possible to change (cyclically) the ways the
controller shows the inputs:

 LOGICAL STATE: the controller shows the input’s logic level (active or inactive) used
in the management of the operating sequence.

 PHISICAL STATE: the controller shows the electrical level (active or inactive, or high
or low) present on the input; this can be the opposite in comparison to the
corresponding logic state. Displayed in REVERSE.
6.5.3.10 S.13 DIGITAL OUTPUTS
This page shows the status of the digital outputs of the controller. Pressing the ACK/ENTER
button, it is possible to change (cyclically) the ways the controller shows the outputs:

 LOGICAL STATE: the controller shows the output’s logic level (active or inactive)
used in the management of the operating sequence.

 PHISICAL STATE: the controller shows the electrical level (active or inactive, or high
or low) present on the output; this can be the opposite in comparison to the
corresponding logic state. Displayed in REVERSE.

 FOR FUNCTION: the controller shows a list of functions associated to the digital
outputs, showing the logic status (1/0) relative to each function, independently from
the output associated to the functions. If more than 9 functions are configured, the
controller will display all of them in rotation (9 at a time) every 2 seconds: keeping
ESC/SHIFT button pressed you stop the rotation.
6.5.3.11 S.14 DIGITAL OUTPUTS
This page is only shown if some DITEL modules have been configured (see 5.8). It displays
the status of the digital outputs acquired from DITEL digital modules. If a DITEL module does
not communicate correctly, the controller will display some dashes in place of the output’s
status. Pressing ACK/ENTER button, it is possible to change (cyclically) the ways the
controller shows the outputs:

 LOGICAL STATE: the controller shows the output’s logic level (active or inactive)
used in the management of the operating sequence.

 PHISICAL STATE: the controller shows the electrical level (active or inactive, or high
or low) present on the output; this can be the opposite in comparison to the
corresponding logic state. Displayed in REVERSE.

94 MC200 Technical Manual EAAM0578EN


6.5.3.12 S.15 ANALOGUE INPUTS
The page shows the value of the analogue inputs of the controller (connectors JU, JK and JJ),
of the emergency stop (EM-S) and of the terminal JK-1. Pressing ACK/ENTER button, it is
possible to change (cyclically) the ways the controller shows the inputs:

 PHYSICAL STATE: Foe each input a measure in Volt is displayed.

 FOR FUNCTION: the controller shows a list of functions associated to the analogue
inputs, showing the real acquired value, independently from the input associated to
the functions. If more than 9 functions are used for the analogue inputs, the controller
will display all of them in rotation (9 at a time) every 2 seconds: keeping the
ESC/SHIFT button pressed you stop the rotation.
6.5.3.13 S.16 ANALOGUE INPUTS
This page is only shown if some DITHERM or DIGRIN modules have been configured (see
5.8).
On the left side, the type of module connected is shown ((DIGRIN, DITHERM or DITEMP if
the module does not communicate correctly). On the right side, it shows the temperatures
acquired by the modules. They can be replaced by:
 “------“: if the expansion module does not transmit the measurement.
 “OPEN”: if the module signals that the sensor is disconnected.
 “+OVER”: if the module signals that the input signal has a too high value, symptom of
a fault.
 “-OVER”: if the module signals that the input signal has a too low value, symptom of
a fault.
6.5.3.14 S.17 ANALOGUE INPUTS
This page is only shown if some DIVIT modules have been configured (see 5.8).
On the right side, it shows the measures acquired by the modules (without any conversion).
They can be replaced by:
 “------“: if the expansion module does not transmit the measurement.
 “OPEN”: if the module signals that the sensor is disconnected.
 “+OVER”: if the module signals that the input signal has a too high value, symptom of
a fault.
 “-OVER”: if the module signals that the input signal has a too low value, symptom of
a fault.
6.5.3.15 S.18 ANALOGUE OUTPUTS
This page shows the percentage value currently associated to the two analogue outputs of the
controller.

Pressing ACK/ENTER you arrive to a view per function: the controller shows a list of the
functions associated to the analogue outputs, displaying the analogue value relative to each
function, independently from the output associated to the functions. If more than 9 functions
are used for the digital outputs, the controller will display all of them in rotation (9 at a time)
every 2 seconds: keeping the ESC/SHIFT button pressed you stop the rotation.
6.5.3.16 S.19 ANALOGUE OUTPUTS
This page is only shown if some DANOUT modules have been configured (see 5.8).
It shows the percentage value currently associated to the four analogue outputs of each
DANOUT module (the real corresponding electrical measure depends on the configuration
done inside the module DANOUT). The values are shown in reverse if the DANOUT module
is not communicating correctly.

MC200 Technical Manual EAAM0578EN 95


6.5.3.17 S.20 MAINS PROTECTIONS
The page is displayed only if the type of plant considers the parallel with the mains.

It displays the status of all protections of parallel with the mains. The disabled protections are
not displayed. For each protection enabled, the controller displays the initial (for example
“27<<”): it is displayed in reverse if the protection has trip (mains out of tolerance).

Possible codes are: “27<<”, “27<”, “27T”, “27Q”, “59>”, “59>>”, “81<<”, “81<”, “81>”, “81>>”,
“81R”, “VJ”, “DI” (by contact). See document [8].

96 MC200 Technical Manual EAAM0578EN


6.5.4 Electrical measurements (M.XX)
In this mode, all the measurements taken by the controller on the electric lines are shown. You
can scroll through the various pages using the LEFT and RIGHT buttons.
6.5.4.1 M.01 SYSTEM
This page displays a wiring diagram of the system, highlighting:

 The mains, the generators bus and the loads. The background colour of the symbols
indicated the status of the voltage on the mains, on the generators bus or on the loads:

o White: voltage/frequency off.

o Yellow: voltage/frequency on out of tolerance.

o Green: voltage/frequency on and in tolerance.

 The GCB, MCB and MGCB circuit breakers. The symbol of the circuit breaker shows:

o The open/close status.

o The discrepancy between the status and the circuit breaker command (in this
case, the two circuit breaker’s points of contacts flash).

o The possibility to use the synchronization to close the circuit breaker (if the
synchronization can be used, the two circuit breaker’s points of contacts are
empty squares, otherwise they are full).

 The power flows, displayed as arrows, in all the parts of the plant. Each arrow points
to the power direction. The arrow flashes (to indicate an anomaly) of negative power
on the loads and on the generators bus.

 The active power measurement and of the power factor in the different parts of the
plant.

 The active power and the power factor setpoints for the operation in parallel with the
mains.

With parameter P.0494 it is possible to customise the page, hiding one or more of the previous
information.
6.5.4.2 M.02 MAINS
In this page are displayed the voltages, the frequency and the rotation sense of the mains
phases. The information displayed depends on the configuration.

 Three phase system (P.0119=3) with neutral connected to the controller (P.0129=1).
The controller displays the three concatenated voltages, the frequency, the sense of
rotation and the neutral-battery voltage. Pressing the ACK/ENTER button, in place of
the concatenated voltages, the phase voltages are displayed (press the ACK/ENTER
button again to go back to concatenates).

 Three-phase system (P.0119=3) without neutral (P.0129=0). The controller displays


the three concatenated voltages, the frequency and the sense of rotation.

 Single-phase system (P.0119=1). The controller displays the phase voltage, the
frequency and the neutral-battery voltage.

Under each concatenated or phase voltage, the controller also displays a bar showing
graphically the current voltage with respect to the nominal voltage: on the bar are also
represented eventual thresholds. The colour with which the bar is filled is green if the voltage
is in tolerance, yellow if it is out of tolerance.

On the right bottom an icon is shown which immediately permits to identify that the page is
relative to the MAINS measurements.

MC200 Technical Manual EAAM0578EN 97


6.5.4.3 M.03 GENERATORS BUS
In this page are displayed the voltages, the frequency and the rotation sense of the generators
bus phases. The information displayed depends on the configuration.

 Three phase system (P.0101=3) with neutral connected to the controller (P.0128=1).
The controller displays the three concatenated voltages, the frequency, the sense of
rotation and the neutral-battery voltage. Pressing the ACK/ENTER button, in place of
the concatenated voltages the phase voltages are displayed (press the ACK/ENTER
button again to go back to the concatenated).

 Three-phase system (P.0101=3) without neutral (P.0128=0). The controller displays


the three concatenated voltages, the frequency, the sense of rotation.

 Single-phase system (P.0101=1). The controller displays the phase voltage, the
frequency and the neutral-battery voltage.

Under each concatenated or phase voltage, the controller also displays a bar showing
graphically the current voltage with respect to the nominal voltage: on the bar are also
represented eventual thresholds. The colour with which the bar is filled is green if the voltage
is in tolerance, red if it is out of tolerance.

On the right bottom an icon is shown which immediately permits to identify that the page is
relative to the GENERATORS BUS measurements.
6.5.4.4 M.04 CURRENTS
In this page, phase currents are displayed (one or three) measured by the controller. At the
bottom-right corner, the controller shows one symbol which immediately permits to identify the
real source of the currents (mains, loads or generators bus).

Under each phase current, the controller also displays a bar showing graphically the current
measure with respect to the nominal current: on the bar are also represented eventual
thresholds. The colour with which the bar is filled is green if the current is in tolerance, red if it
is out of tolerance.

For three-phase systems also the negative sequence current is displayed.

If the fourth current is suitably configured, the controller will also display:

 Ax: auxiliary current (visible if P.0131=1 or P.0131=4).

 An: neutral current (visible if P.0131=2).


6.5.4.5 M.05 POWERS
The active powers and power factors are shown, total and phase by phase (for single-phase
systems only the total values are shown).

At the bottom-right corner, the controller shows one symbol which immediately permits to
identify the real source of the powers (mains, loads or generators bus).
6.5.4.6 M.06 POWERS
The apparent and reactive powers are shown, total and phase by phase (for single-phase
systems only the total values are shown).

At the bottom-right corner, the controller shows one symbol which immediately permits to
identify the real source of the powers (mains, loads or generators bus).
6.5.4.7 M.07 ENERGY METERS
In this page the active and reactive energy counters (partial and total) exported by the plant
to the mains are shown.

On this page, you can reset to zero the partial counters individually. To do so, it is necessary
to:

98 MC200 Technical Manual EAAM0578EN


 Press the ACK/ENTER button: one of the counters will result highlighted.

 Use the vertical scrolling UP and DOWN buttons to select the counter to be reset.

 Press the ACK/ENTER button and ESC/SHIFT buttons for 5 seconds.

 Press the ESC/SHIFT pushbutton.

At the bottom to the right, the display shows an icon which identifies the mains, to allow you
to easily distinguish this page from the next, which have an identical structure.
6.5.4.8 M.08 ENERGY COUNTERS
In this page the active and reactive energy counters (partial and total) imported from the
mains to the plant are shown.

On this page, you can reset to zero the partial counters individually. To do so, it is necessary
to:

 Press the ACK/ENTER button: one of the counters will result highlighted.

 Use the vertical scrolling UP and DOWN buttons to select the counter to be reset.

 Press the ACK/ENTER button and ESC/SHIFT buttons for 5 seconds.

 Press the ESC/SHIFT pushbutton.

At the bottom to the right, the display shows an icon which identifies the mains, to allow you
to easily distinguish this page from the next, which have an identical structure.
6.5.4.9 M.09 ENERGY METERS
In this page the active and reactive energy counters (partial and total) exported by the
generators to the plant are shown.

On this page, you can reset to zero the partial counters individually. To do so, it is necessary
to:

 Press the ACK/ENTER button: one of the counters will result highlighted.

 Use the vertical scrolling UP and DOWN buttons to select the counter to be reset.

 Press the ACK/ENTER button and ESC/SHIFT buttons for 5 seconds.

 Press the ESC/SHIFT pushbutton.

At the bottom to the right, the display shows an icon which identifies the generators, to allow
you to easily distinguish this page from the previous, which have an identical structure.
6.5.4.10 M.10 ENERGY METERS
In this page the reactive energy counters (partial and total) imported by the generators from
the plant are shown.

On this page, you can reset to zero the partial counters individually. To do so, it is necessary
to:

 Press the ACK/ENTER button: one of the counters will result highlighted.

 Press the ACK/ENTER button and ESC/SHIFT buttons for 5 seconds.

 Press the ESC/SHIFT pushbutton.

At the bottom to the right, the display shows an icon which identifies the generators, to allow
you to easily distinguish this page from the previous, which have an identical structure.

MC200 Technical Manual EAAM0578EN 99


6.5.4.11 M.11 REGULATIONS
This page is useful in the parallel applications. It displays the generators bus and mains
voltages and frequencies at the same time. It is then possible to modify the offsets for the
speed and voltage:

 Press the ACK/ENTER button: one of the values is highlighted.

 Using the ACK/ENTER button or ◄► buttons, you select the other value (cyclically).

 Using ▲ and ▼ buttons, it is possible to modify the selected value (if pressed together
with ESC/SHIFT the modification is quicker).

 Press the ESC/SHIFT button to end the modification.

The modification is automatically interrupted if you don’t press any digits for 10 seconds.

Note: some of these setpoints can be acquired from the analogue inputs: in this case
on this page they are shown, but it is not possible to modify them.
6.5.4.12 M.12 SYNCHRONISATION
This page shows the necessary information for the synchronization.
On the right side, the controller displays a gauge which graphically shows a synchronoscope,
indicating the current phase through a needle.
On the left side, the controller displays the current phase difference through a horizontal bar,
which act as a synchronoscope. Usually it shows phase angles between -180° and +180°.
When the phase error falls below 20°, the bar is reduced to show angles between -20° and
+20° (in this case the bar is on black background). Under the bar 5 small rectangles are shown.
The first three indicate if the voltage, frequency and phase differences allow the closure of the
circuit breaker (if the rectangle is grey, the difference is too high and the circuit breaker cannot
be closed, if it is green the difference is in tolerance). The fourth one indicates a possible
mismatch of phase-rotation direction (also in this case the grey rectangle indicates that the
circuit breaker cannot be closed). When all the first four rectangles are entirely “green”, the
status of the system is correct to close the circuit breaker: so, the fifth rectangle becomes
green and the board controls the closing of the circuit breaker.
Still on the left side, the controller displays numerically the difference of phase, frequency and
voltage between gensets and mains.
On the bottom of the page there are offsets for the speed and voltage. If these values are not
related to an analogue input, it is possible to directly modify them from this page (see previous
paragraph). In this way, it is possible to make a manual synchronization.
6.5.4.13 M.13 SETPOINTS
This page shows and allows to modify (in a unique point) all the applicable setpoints for the
plant, relative to the frequency, to the voltage, to the active power and to the power factor. It
is useful because on page M.01 are instead shown only the significant setpoints in a given
moment. For example, if a plant can operate both in BASE LOAD mode and in
IMPORT/EXPORT mode, on page M.01 only the setpoints relative to the active operation
mode will be shown, while on page M.13 they will all be shown: in this way, the operator can
set the setpoints before changing the operation mode. The displayed and modifiable setpoints
(if not acquired from analogue inputs) are:

 Offset of speed (P.0840).

 Offset of voltage (P.0867).

 Setpoint of active power for the SYSTEM BASE LOAD (P.0858) and for the SYSTEM
IMPORT EXPORT (P.0859) modes.

 Setpoint of power factor for the SYSTEM BASE LOAD and for the SYSTEM IMPORT
EXPORT modes (P.0860).

100 MC200 Technical Manual EAAM0578EN


The setpoints are only shown if they are not acquired from analogue inputs and if they are
included in the plant configuration.
6.5.4.14 M.14-15-16 EXTERNAL MEASURES
These pages are dedicated to the displaying of the measurements acquired from the analogue
inputs configured as "generic sensor". The operator has the option to acquire measures that
are not in any way linked to the controller, and to show them on the display. It can also group
them (by any standard), and display them on one of the 3 available pages.

The division of the measures on the different pages is done via the function configured in the
analogue inputs:

 AIF.2001: page M.14.

 AIF.2003: page M.15.

 AIF.2005: page M.16.

The controller shows one measurement per line: it shows the text configured for the analogue
input (P.4002 for the analogue 1), followed by the unit of measure and by the measure itself.
If more than 9 measurements are associated to one of these pages, the controller shows them
all, rotating them every 2 seconds: keep the ESC/SHIFT button pressed to stop the rotation
on the current view.

MC200 Technical Manual EAAM0578EN 101


6.5.5 Measurement from CAN bus PMCB (B.XX)
These pages show the measurement and the statuses acquired by the CAN bus PMCB, which
connects among them all SICES devices.
6.5.5.1 B.01 DEVICES ON PMCB
This page shows the list of the mains controllers, of the genset controllers and of the tie breaker
controllers recognised on the CAN bus PMCB connection. It is useful for diagnostic purposes.

On the top, the PMCB addresses of all mains controllers (MCxxx) are displayed. In the middle,
the PMCB addresses of all gensets controllers (GCxxx and DSTxxxx) are displayed. On the
bottom, the PMCB addresses of all tie breaker controllers (BTBxxx) are displayed.

The board shows the message "Mains controllers on the PMCB" in “reverse” if is working on
MC200 mode (P.9606 = 1).
6.5.5.2 B.02-03-04-05 GENSETS
These pages show the significant data of each genset controller that operates on the PMBC
CAN bus. Each page shows up to 8 gensets. Only the relevant pages are shown. It is used
one line for each genset, which contains:

• The PMCB address of the genset. MC200 shows the PMCB address in “reverse” if,
now, it is not able to manage this genset (for example if the related genset controller
is in OFF_RESET mode or has some alarms).

• The nominal power of the genset.

• The active and reactive power supplied by the genset.

• The working hours of the engine.

• The status of the generator (stopped, load sharing etc.).

If the parameter P.9606 is set to zero, MC200 acts as the old MC100 controller:

In AUTO mode, MC200 starts and stops the generators as required by the loads. Using
these pages, the operator can modify this behaviour. For each generator, the operator can
select one of these operating modes:

• Automatic management (default). MC200 starts/stops the generator as required


by load. In this case, a “blank field” is shown on the display between PMCBUS
address and nominal power of the selected generator.

• Generator always working. Whatever the load is, this generator must work. In this
case, a “full square” is shown on the display between the genset address and the
nominal power of the selected genset.

• Generator always stopped. Whatever the load is, this generator must be stopped.
In this case, an “empty square” is shown on the display between the genset
address and the nominal power of the selected genset.

It is possible to choose the desired operating mode for each generator directly from these
pages:

• Press ACK/ENTER pushbutton:

• By using ▲▼pushbuttons, select the desired genset.

• Change the desired operating mode using ◄►pushbuttons.

• Press ESC/SHIFT to exit selection mode.

Note: if no buttons are pressed for 60 seconds, the selecting procedure is automatically
finished.

102 MC200 Technical Manual EAAM0578EN


6.5.5.3 B.06 TOTALS ON PMCB
This page shows the totals calculated on all the genset controllers connected on CAN bus
PMCB. The following are shown:

 The total nominal power of the supplying gensets (MDPt, kW).

 The current load ratio of the generators bus (DPRt, %).

 The total active power supplied (kW).

 The total reactive power supplied (kvar).

 The total active energy (kWh, sum of energy counters of all genset control boards).

 The total reactive energy (kvar, sum of energy counters of all genset control boards).
6.5.5.4 B.07 LOAD FUNCTION
This page is dedicated to the functions of “load management” (see [8]). By the term “load
management” is intended the capacity of the system to start/stop the gensets to only have the
strictly necessary gensets running to supply the load (with a small margin, but not too much).
This page shows some information relevant for this function.

The information shown is:

 The enabling for this controller of the “load management” function.

 The “load management” mode currently selected (it establish the criteria with which
the genset to be started are chosen).

 The “master” (it is the primary genset, the one which would not be ever stopped). For
some “load management” modes this information is not displayed.

 Based on the selected mode, the controller can show in how many hours (or at which
time) the system will select a new “master” genset.

 The list of the genset controllers, ordered based on the priority (first the genset with
major priority, the last to be stopped). For some “load management” modes this
information is not displayed.

It is possible to manually select the “master” genset directly from this page:

 Press the ACK/ENTER button.

 Use ▲▼buttons to select the address of the “master” genset selected.

 Confirm with ACK/ENTER button.


6.5.5.5 B.08 LOAD MANAGEMENT
This page is dedicated to the functions of “load management” (see [8]). By the term “load
management” is intended the capacity of the system to start/stop the gensets to only have the
strictly necessary gensets running to supply the load (with a small margin, but not too much).
This page shows some information relevant for this function.

The information shown is:

 The power supplied by the gensets (percentage with respect to the maximum power
the gensets currently running can afford).

 The threshold (%) to compare with the power calculated at the previous point, over
which a new genset must be started (or it is necessary to pass to a combination of
gensets with a higher nominal power).

 The power supplied by the gensets (percentage relative to the maximum) calculated
in case the less priority genset is stopped (or combination of gensets with less nominal
power).

MC200 Technical Manual EAAM0578EN 103


 The threshold (%) to compare with the power calculated at the previous point, under
which a new genset must be started (or it is necessary to pass to a combination of
gensets with a lower nominal power).

Some of these measurements can be viewed in reverse to indicate an “out of threshold”


situation (which can require the start or stop of the genset).

When possible, the controller displays also the remaining time to the start of a new genset or
to the stop of one of the running gensets.
6.5.5.6 B.09 LOAD SHEDDING
This page is dedicated to the functions of “load shedding”. By the term “load shedding” is
intended the capacity of the system to disconnect/re-connect part of the loads if the generators
are not able to supply them. This page shows some information relevant for this function:

 The status of each group of loads (connected/disconnected). The function can


manage up to four groups.

 The status of this function (enabled/disabled).

 The power (%) supplied by the gensets, related to the thresholds for the disconnection
and re-connections of the groups of loads.

Some of these measurements can be shown in reverse to indicate an “out of threshold”


situation (which can require the disconnection or the re-connection of a group of loads).

When possible, the controller displays also the remaining time to the disconnection or the re-
connection of a group of loads.
6.5.5.7 B.10 PEAK SHAVING
This page is dedicated to the functions of “peak shaving” or “peak lopping”. By these terms is
intended the capacity of the system to start/stop the gensets when the consumption of the
loads from the mains is too high, in a way to limit the loads consumption from the mains. This
page shows some information relevant for this function:

 The status of this function (enabled/disabled).

 The power (%) of the loads, related to the thresholds for starting/stopping the
generators.

Some of these measurements can be viewed in reverse to indicate an “out of threshold”


situation (which can require the start or stop of the gensets).

When possible, the controller displays also the remaining time to the start of a new genset or
to the stop of one of the running gensets.

104 MC200 Technical Manual EAAM0578EN


6.5.6 History logs (H.xx)
During the operation, apart from the OFF/RESET mode, the controller makes periodic
registration or on event, partially configured with the programming parameters.

The controller manages three types of archive:

1. Events.

2. Analogue measures.

3. Maximum peaks.

These archives can be accessed in any function mode and status of the controller. To select
the function, use the buttons ▲ and ▼ until the HISTORY ARCHIVE (H.01) base page is
shown.

If you are in a mode which limits the use of vertical scrolling buttons, it might be
necessary to press ESC/SHIFT button one or more times.

Then press the ACK/ENTER button to activate the mode (pass to page “H.03”). At the starting
of the procedure, the menu with the different archive function is shown.
6.5.6.1 Archive selection

H.03 HISTORY LOGS _


HISTORY LOGS 1/03

1 Events
2 Trend
3 Peaks

The second line always shows the numeric indication of the function selected and the number
of functions in the menu. The next lines are all used to show the selectable functions. The
selected item is highlighted in negative (REVERSE).
Using ▲ and ▼ buttons, the menu scrolls respectively towards the top or bottom index items,
in a cyclical way (that is, pressing ▲ from the first item you pass to the last and vice-versa).

Pressing ACK/ENTER button the selected function activates (the one highlighted in negative),
pressing ESC/SHIFT you go back to page “H.01”.
6.5.6.2 Pages for events
In the moment in which some events happen (previously configured), the controller adds a
registration in this archive. The registration always contains date/hour, numeric code which
identifies the event and the controller status. Through BoardPrg3 program, it is possible to
select which other information must be registered at every event. It is possible to add maximum
44 information. The capacity of the archive depends on how many information are memorized
at every event: with default configuration, by the way, the total capacity is 523 registrations. If
the archive is full and a new event occurs, the less recent is overwritten.

Parameter P.0441 allows to select which events must be registered. It is a parameter


configurable at bit:
Bit Hexadecimal Firmware Description
value version
0 01 01.00 Board operating mode.
1 02 01.00 Mains status.

MC200 Technical Manual EAAM0578EN 105


2 04 01.00 Generators bus status.
3 08 01.00 Mains fault protections.
4 10 01.00 Circuit breakers status.
5 20 01.00 Circuit breakers commands.
6 40 1.00 Start/stop requests.
7 80 01.00 Load disconnect.
8 100 01.00 Diagnostics.

A chart follows with the codes for all possible events.

Code Versio Even if Registration cause.


n blocked.
EVT.1001 01.00 Yes OFF_RESET.
EVT.1002 01.00 Yes MAN.
EVT.1003 01.00 Yes AUTO.
EVT.1004 01.00 Yes TEST.
EVT.1005 01.00 Yes REMOTE START.

EVT.1010 01.00 Mains not present.


EVT.1011 01.00 Mains present.
EVT.1012 01.00 Mains in tolerance.

EVT.1013 01.00 Inhibition for start active (from configurable input).


EVT.1014 01.00 Inhibition for start not active (from configurable input).

EVT.1020 01.00 Genset not present.


EVT.1021 01.00 Genset present.
EVT.1022 01.00 Generator in tolerance.

EVT.1030 01.00 MGCB close command.


EVT.1031 01.00 MGCB open command.
EVT.1032 01.00 MGCB closed.
EVT.1033 01.00 MGCB open.

EVT.1035 01.00 MCB close command.


EVT.1036 01.00 MCB open command.
EVT.1037 01.00 MCB closed.
EVT.1038 01.00 MCB open.

EVT.1050 01.00 Manual start command.


EVT.1051 01.00 Manual stop command.
EVT.1052 01.00 Automatic start command.
EVT.1053 01.00 Automatic stop command.
EVT.1054 01.00 TEST start command from digital input.
EVT.1055 01.00 TEST stop command from digital input.
EVT.1056 01.00 TEST start command from communication port.
EVT.1057 01.00 TEST stop command from communication port.
EVT.1058 01.00 TEST start command from clock/calendar.
EVT.1059 01.00 TEST stop command from clock/calendar.
EVT.1060 01.00 TEST start command from SMS.
EVT.1061 01.00 TEST stop command from SMS.
EVT.1062 01.00 Automatic start command for failure to close MCB.

EVT.1074 01.00 Yes Reset


EVT.1075 01.00 Not valid clock (but used by some functions).
EVT.1076 01.00 Yes Update clock/calendar.
EVT.1077 01.00 Yes New power on of the controller.
EVT.1078 01.00 Yes Default values of parameters reloaded.

EVT.1080 01.00 Inhibition for supply activated (from configurable input).

106 MC200 Technical Manual EAAM0578EN


EVT.1081 01.00 Inhibition for supply not activated.

EVT.1082 01.00 Protection override activated.


EVT.1083 01.00 Protection override deactivated.

EVT.1086 01.00 Yes Clock updated for daylight saving time.


EVT.1087 01.00 Yes Clock updated for standard time.

EVT.1091 01.00 Mains loss protection “27 U<<” tripped.


EVT.1092 01.00 Mains loss protection “59 U<<” tripped.
EVT.1093 01.00 Mains loss protection “81 f<<” tripped.
EVT.1094 01.00 Mains loss protection “81 f<<” tripped.
EVT.1095 01.00 Mains loss protection “81 R” (Df/Dt) tripped.
EVT.1096 01.00 Mains loss protection “Vector Jump” tripped.
EVT.1098 01.00 Mains loss protection (from contact) tripped.
EVT.1099 01.00 Mains loss protection restored.
EVT.1100 01.00 Mains loss protection “27 U<” tripped.
EVT.1101 01.00 Mains loss protection “59 U>” tripped.
EVT.1102 01.00 Mains loss protection “81 f<” tripped.
EVT.1103 01.00 Mains loss protection “81 f>” tripped.
EVT.1104 01.00 Mains loss protection “27T” tripped.
EVT.1105 01.00 Mains loss protection “27 U<& Q?" tripped.

EVT.1151 01.00 Mains loss protection “27 U<” restored.


EVT.1152 01.00 Mains loss protection “59 U>>” restored.
EVT.1153 01.00 Mains loss protection “81 f<<” restored.
EVT.1154 01.00 Mains loss protection “81 f>>” restored.
EVT.1155 01.00 Mains loss protection “81 R” (Df/Dt) restored.
EVT.1156 01.00 Mains loss protection “Vector Jump” restored.
EVT.1158 01.00 Mains loss protection (by contact) restored.
EVT.1160 01.00 Mains loss protection “27 U<” restored.
EVT.1161 01.00 Mains loss protection “59 U>” restored.
EVT.1162 01.00 Mains loss protection “81 f<” restored.
EVT.1163 01.00 Mains loss protection “81 f>” restored.
EVT.1164 01.00 Mains loss protection “27T” restored.
EVT.1165 01.00 Mains loss protection “27 U<& Q?” restored.

EVT.1201 01.00 Inhibition for supply activated (from mains out of


thresholds).
EVT.1202 01.00 Inhibition for supply activated (from communication
ports).
EVT.1203 01.00 Inhibition for supply activated (for some GCB not
opened).
EVT.1204 1.00 Inhibition for supply activated (for reverse
synchronization).

EVT.1221 01.00 Inhibition for start active (from clock/calendar).


EVT.1222 01.00 Inhibition for start not active (from clock/calendar).
EVT.1223 01.00 Inhibition for start active (for mains out of tolerance for
SPtM and MPtM plants).
EVT.1224 01.00 Inhibition for start not active (for mains out of tolerance
for SPtM and MPtM plants).
EVT.1225 01.00 Inhibition for start active (for GCB not opened).
EVT.1226 01.00 Inhibition for start not active (for GCB not opened).

EVT.1291 01.00 Load function: new master genset.

EVT.1321 01.00 Load shedding: load #1 disconnected.


EVT.1322 01.00 Load shedding: load #1 re-connected.
EVT.1323 01.00 Load shedding: load #2 disconnected.

MC200 Technical Manual EAAM0578EN 107


EVT.1324 01.00 Load shedding: load #2 re-connected.
EVT.1325 01.00 Load shedding: load #3 disconnected.
EVT.1326 01.00 Load shedding: load #3 re-connected.
EVT.1327 01.00 Load shedding: load #4 disconnected.
EVT.1328 01.00 Load shedding: load #4 re-connected.

EVT.1321 01.00 Number of gensets connected to bus PMCB varied

EVT.1331 01.00 Peak shaving: request to start the generators.


EVT.1332 01.00 Peak shaving: request to stop the generators.

The column “even if blocked” indicates which events are anyway recorded even if the records
are blocked (see 6.5.6.4)

All the anomalies are recorded into the events log. They are recorded with their own numerical
code, added to:

• 2000: if the anomaly is a warning.

• 3000: if the anomaly is an unload.

• 5000: if the anomaly is an alarm.

For example, anomaly 273 will be recorded as "2273" when it is activated as a warning, as
"5273" if it is activated as an alarm. By viewing the event directly from the controller, the event
code "2273" is automatically displayed as "W273", the code 5273 is displayed as "A273".

With the default configuration, each time that an event is recorded, the controller also records
the following info (this list can be modified by means of the BoardPrg3 program):

• Date/Time.

• Event code.

• Operating mode of the controller.

• Presence of voltage on the generators bus.

• Mains status.

• MGCB circuit breaker command and status.

• MCB circuit breaker command and status.

• Mains phase-to-phase voltages and frequency.

• Generators bus phase-to-phase voltages and frequency.

• The three phase currents.

• The total (apparent, active and reactive) powers and the total power factor.

• The nominal power, the active power and the reactive power of the generators with
GCB closed (totals).

• The power supply voltage.

Using the ▲▼ buttons to scroll cyclically trough all recordings. Each event has many
information pages (depending on the configuration). Pressing the ◄► buttons allows you to
scroll through the pages related to the event.

The structure of the upper part of the pages is the same for all pages. The following figure
shows the first page.

108 MC200 Technical Manual EAAM0578EN


H.09 HISTORY LOGS _
1 Events 1/01(523)

28/04/16 15:41:03 >


E1077: New power on
OFF-RESET
Generators: absent
Mains: present
MGCB opened
MCB closed

The common part contains:

• The second line shows which event is currently displayed, the total number of
recorded events and the maximum size of the archive. The most recent event is
associated to the highest number.

• The next line shows the date/time of the recording.

• The next line shows the numeric code of the event and its description (variable
depending on the selected language).

The content below the dashed line depends on the information configured for the record; with
the default configuration, five pages are used:

Page 1. It shows the statutes of the system at the time when the event was recorded: the
controller operating mode and the statutes of the generators, of the mains and of the circuit
breakers.

Page 2. It shows the frequency and the voltages of the mains. It also shows the frequency and
the L1-L2 voltage of the generators bus.

Page 3. It shows the L2-L3 and L3-L1 phase-to-phase voltage of the generators bus, the phase
currents and the total apparent power (kVA).

Page 4. It shows the total active power (kW), the total reactive power (kvar) and the total power
factor. It also shows the nominal power, the active power and the reactive power of the
supplying generators.

Page 5. It shows the power supply voltage.

The information that were not available at the time of recording are displayed with dashes.
6.5.6.3 Pages for analogues
MC200 records a series of analogue measurements and statuses at regular intervals. The
recording interval is configurable, and different intervals can be configured for when at least
one generator has its GCB closed and for when all generators have their GCB opened:

• P.0442: interval (in seconds) for the recording into the archive of analogue
measurements, used when at least one generator has its GCB closed.

• P.0443: interval (in seconds) for the recording into the archive of analogue
measurements, used when all generators have their GCB opened.

Each record always contains the date/time and the status of the controller. By means of the
BoardPrg3 program, it is possible to select which information must be recorded. It is possible
to add 44 information max. The capacity of the archive depends on the information recorded
on event: however, with the default configuration the full capacity is 523 records. If the archive
is full and a new event occurs, the oldest is overwritten.

With default configuration, the values recorded are:

MC200 Technical Manual EAAM0578EN 109


• Date/Time.

• Event code.

• Operating mode of the controller.

• Presence of voltage on the generators bus.

• Mains status.

• MGCB circuit breaker command and status.

• MCB circuit breaker command and status.

• Mains phase-to-phase voltages and frequency.

• Generators bus phase-to-phase voltages and frequency.

• The three phase currents.

• The total (apparent, active and reactive) powers and the total power factor.

• The nominal power, the active power and the reactive power of the generators with
GCB closed (totals).

• The power supply voltage.

Using the ▲ and ▼ buttons to scroll cyclically trough all recordings. Each record has a variable
number of information pages (based on the configuration). By pressing ◄► buttons it is
possible to navigate on the pages related to recording.

The structure of the upper part of the pages is the same for all four. The following figure shows
the first page.

H.15 HISTORY LOGS _


1 Trends 1/01(523)

28/04/16 15:41:03 >

OFF-RESET
Generators: absent
Mains: present
MGCB opened
MCB closed

The common part contains:

• The second line shows which record is currently displayed, the total number of
recorded registrations and the maximum size of the archive. The most recent record
is associated to the highest number.

• The next line shows the date/time of the recording.

The content below the dashed line depends on the information configured for the record; with
the default configuration, 5 pages are used:

Page 1. It shows the statutes of the system at the time when the event was recorded: the
controller operating mode and the statutes of the generators, of the mains and of the circuit
breakers.

Page 2. It shows the frequency and the voltages of the mains. It also shows the frequency and
the L1-L2 voltage of the generators bus.

110 MC200 Technical Manual EAAM0578EN


Page 3. It shows the L2-L3 and L3-L1 phase-to-phase voltage of the generators bus, the phase
currents and the total apparent power (kVA).

Page 4. It shows the total active power (kW), the total reactive power (kvar) and the total power
factor. It also shows the nominal power, the active power and the reactive power of the
supplying generators.

Page 5. It shows the power supply voltage.

The information that were not available at the time of recording are displayed with dashes.
6.5.6.4 Locked recordings
The controller does not perform recordings in the archive of analogues and in the archive of
events if it is in OFF/RESET mode and when a shutdown or an unload have been activated.
Exceptions are some event codes (highlighted by the wording “Yes” in the column “even if
blocked” of the table in 6.5.6.2) and all anomalies. When the recordings are locked, all the
windows of the History logs display an intermittent “Locked” message. To unlock the
recordings, it is necessary cancel all anomalies and set the board in MAN or AUTO.
6.5.6.5 Pages for peaks
The controller makes a series of maximum and minimum peaks for some significant values.

 Total active power: the maximum peak is recorded, having the date/time and the
measure of the engine coolant temperature (if available) associated.

 Currents: the maximum peaks of individual phases are recorded, having the date/time
and power factor of that phase associated.

 Controller temperature: the minimum and the maximum peaks are recorded, with
date/time associated.

To display all records, the controller uses only one page of the display.

H.21 HISTORY LOGS _


3 Maximum peaks 1/06

Maximum power

21/03/2016 16:01:06 180 kW

The second line shows the record currently displayed, out of the total number of records (the
maximum number of records is 6).

The fourth line shows a description of the peak record currently displayed.

• Maximum power.

• Maximum current (L1).

• Maximum current (L2).

• Maximum current (L3).

• Minimum board temperature.

• Maximum board temperature.

MC200 Technical Manual EAAM0578EN 111


The sixth line shows the date and the time of the record, the value of the record (power,
current, etc.) On the eighth line a second value can be recorded together with the main value:

• The power factors on single phases are recorded together with the currents.

The information that were not available at the time of recording are displayed with dashes.

Using the ▲ and ▼ pushbuttons it is possible to scan all the records. The buttons ◄
and ► are not used because the controller uses only one page of the display.
6.5.6.6 Exit from archives visualization
There are two ways to exit from archive visualization:

 Press ESC/SHIFT n times to go to page H.01

 Changing operating mode of the controller.

In both cases, it will be shown the page H.01, from which it is possible to pass to the status
and measurements visualization with ▲ and ▼ pushbuttons.
6.5.6.7 Reset of archives
To reset an archive, it is first necessary to show it and then keep ACK/ENTER and ESC/SHIFT
pressed for 5 seconds up to when the controller shows a message of happened reset on the
display. The archive of maximum peaks does not reset: when ACK/ENTER and ESC/SHIFT
are pressed for 5 seconds on this archive, the controller forces as maximum peak the current
value of the measurements.

112 MC200 Technical Manual EAAM0578EN


6.6
The device allows to select the language to use for all writings displayed on the multifunctional
viewer. Currently, 5 languages are supported: Italian, English, Portuguese, French and
Spanish (English as default). The directly available languages are only: English, Italian and
Portuguese. The others can be transferred to the controller (one at a time) though BoardPrg3
software. See 6.5.3.3 for the language selection procedure.

MC200 Technical Manual EAAM0578EN 113


7
The rest of the chapter will describe the actions of MC200 on the MCB and MGCB circuit
breakers and the commands sent to the gensets controllers via CAN bus PMCB.

MC200 can send some commands (via CAN bus PMCB) to the gensets controllers. Almost
these commands are sent to the genset controllers only if they are “managed by MCxxx”.

MC200 uses a different way (respect the old MC100) for starting and stopping the generators
through the PMCB CAN bus. The new system provides more functionalities, but requires an
updated firmware also an all the genset controllers (GCxxx or DSTxxxx). For this reason,
MC200 can emulate the old MC100.

• P.9506 = 1. In this configuration, MC200 emulates the old MC100.

A controller is “managed by MCxxx” if:

• It doesn’t have alarms, deactivations or unloads.

• It is not in OFF/RESET, MAN or TEST mode.

• The contact “inhibition for start” is active.

• It does not have requests of “inhibition for supply the loads” (by contact or by
communication ports).

• It does not have REMOTE START requests, if not received by MCxxx.

• It does not have the contact to enable the REMOTE START mode, or it is
active.

To request the start of a genset, MCxxx sends a “REMOTE START” request to the
related genset controller (for this reason a controller must have the “REMOTE START”
function enabled to be “managed by MCxxx”).

To request the stop of a genset, MCxxx removes the request of “REMOTE START” to
the related controller. The controller will stop the genset if:

• There are no requests of REMOTE START and TEST.

• There are no requests of automatic intervention, or the request of “automatic


start inhibition” by contact is active.

The two previous conditions are necessary to get the genset controller “managed by
MCxxx”.

In some conditions, and only if MGCB is present, MCxxx can request the opening of
the GCB circuit breakers of the gensets controllers. To do this, MCxxx sends a
command of “load inhibition” to the genset controllers. When the opening of the GCB
circuit breakers is not required, MCxxx removes the request of “load inhibition”: the
genset controllers will close the GCB circuit breakers only if there are no requests of
“load inhibition” (necessary condition to get the genset controller “managed by
MCxxx”).

• P.9506 = 0. In this configuration, MC200 uses the new command system, that
provides enhanced functionalities.

A controller is “managed by MCxxx” if:

• It doesn’t have alarms, deactivations or unloads.

• It is in AUTO mode (not in TEST or in REMOTE START mode).

• It does not have requests of “inhibition for start” (by contact or by Modbus).

114 MC200 Technical Manual EAAM0578EN


• It does not have requests of “inhibition for supply the loads” (by contact or by
Modbus).

To request the start of the gensets (all controlled ones), MC200 sends an “automatic
start request” over the CAN bus. In the same way, to stop the gensets (all controlled
ones), it removes the “automatic start request” from the CAN bus. The genset will stop
if:

• Its controller is in AUTO mode.

• There are no requests of automatic intervention, or the request of “start


inhibition” by contact or Modbus is active.

In some conditions, and only if MGCB is present, MC200 can request the opening of
the GCB circuit breakers of the gensets controllers. To do this, MC200 sends a
command of “inhibition for supply the loads” to the genset controllers. When the
opening of the GCB circuit breakers is not required, MC200 removes the request of
“inhibition for supply the loads”: the genset controllers will close the GCB circuit
breakers only if there are no requests of “inhibition for supply the loads”.

7.1
Five modes are available for the device management.
 OFF_RESET: the MGCB is open to disconnect the gensets from the loads and/or the
mains (if it exists and if it is commanded by MC200). The MCB is closed to connect
the loads to the mains (if it exists and if it is commanded by MC200). MC200 removes
all the requests of gensets start. All anomalies are cancelled and it is possible to
access the programming to modify the parameters.
 MAN: the start and the stop of the gensets are managed by the operator. The
opening/closing of the two circuit breakers (if they are present and commanded by
MC200) are managed by the operator. The controller automatically activates the
synchronization procedure (if required) following the manual command of a circuit
breaker closing by the operator. The protections are active: MC200 is always able to
open the MGCB circuit breaker (if present) and remove the requests of gensets start.
The access to programming is allowed, but only some parameters can be modified.
 AUTO: the start and the stop of the gensets and the opening/closing of the MGCB
and MCB circuit breakers are managed by the controller (the operator cannot
intervene). All the protections are enabled. The access to programming is allowed, but
only some parameters can be modified.
 TEST: this operating mode differs from AUTO, as MC200 still requires the start of the
gensets, without considering that the conditions of the plant require the automatic
intervention of the gensets or not (the “automatic intervention inhibition” are ignored
in this mode). By parameter P.0222, it is possible to choose if the controller has or has
not to connect the load to generators. When the controller goes back to AUTO (when
the test ends), the loads are automatically switched on the mains and the gensets are
stopped with the normal procedure. If possible, the switch of the loads between mains
and gensets is carried out by avoiding their black-out. The controller will pass
automatically from TEST to AUTO if the conditions for an automatic gensets
intervention are verified. The access to programming is allowed, but only some
parameters can be modified.
 REMOTE START: this operating mode differs from AUTO, as MC200 still requires the
start of the gensets, without considering that the conditions of the plant require the
automatic intervention of the gensets or not (the “automatic intervention inhibition” are
ignored in this mode). If there are no requests of “inhibition to take the load”, the loads
are switched on the gensets. The operator cannot command the circuit breakers
manually. When this operating mode is deactivated, the controller goes back to AUTO
and, if the automatic intervention of the gensets is not requested, the controller opens
the MGCB circuit breaker and removes the start requests of the gensets. The access
to programming is allowed, but only some parameters can be modified.
The operation mode can be selected in three different ways:

MC200 Technical Manual EAAM0578EN 115


 Using “MODE ▲” and “MODE ▼” buttons on the controller. The buttons must be
pressed continuously for at least half a second to force the mode change. The buttons
are disabled if at least one of the inputs described at the following point exists and is
active (on the first line of the display a flashing key shaped icon is shown).

 Using one or more configured inputs with the following functions:


▪ DIF.2271 “OFF from remote”.
▪ DIF.2272 “MAN from remote”.
▪ DIF.2273 “AUTO from remote”.
When one of these inputs is active, the controller mode is forced and it is no longer
possible to use either the buttons on the panel or the Modbus commands to modify it
(on the first line of the display a flashing key shaped icon is shown).
When none of these inputs is active, it becomes possible again to use the buttons and
the Modbus commands to change the operation mode.
If there are more active inputs at the same time, the priority is given to the input which
forces OFF/RESET, followed by the one which forces MAN, and then the one which
forces AUTO.
It is not mandatory to use all three inputs. For example, it is possible to use only one
input to force the AUTO status; when the input is active, the controller is always in
AUTO, when the input deactivates the controller remains in AUTO, but it is possible
to use the buttons to pass to MAN or OFF/RESET.
If it is used only the input to force OFF/RESET mode, the controller acts
differently: when the input is active, the controller is always in OFF/RESET
mode, and when the input goes back on standby, the controller goes back to
the mode it was in prior to input activation.

 By Modbus commands. The commands are only managed if none of the above
described inputs is active. The commands can be protected by a password (P.0004)
which must be entered before any command, and they can be deactivated through a
digital input (DIF.2706). To send the command it is necessary to write in sequence
(within 5 seconds):

▪ HOLDING REGISTER 101: write the password configured with the parameter
P.0004.

▪ HOLDING REGISTER 102: write the value:

▪ “1” to require the OFF/RESET mode.

▪ “2” to require the MAN mode.

▪ “3” to require the AUTO mode.


To enable the TEST mode requires the controller being first set to AUTO without any automatic
start request. All possible TEST activation modes are described below. If in TEST mode, the
AUTO/TEST indicator flashes at a duty of 50%. You can shift to TEST mode as follows:

 Pressing the START pushbutton. Shifting to TEST mode is immediate. To return to


AUTO mode, press again the START pushbutton. If the TEST duration (P.0420) is
configured (different from zero), this test ends automatically after the time indicated.
Parameter P.0222 establishes if the generators are connected to the loads or not.

 When a digital input configured with function DIF.2031 “Request of Test mode”
activates, the controller shifts to TEST and returns to AUTO when it deactivates.
Parameter P.0222 establishes if the generators are connected to the loads or not.

 By using a digital input configured with the function DIF.2029 (“Request for the test
mode without load - impulse”). The controller evaluates the input activation moment
(impulse): the controller switches to TEST when this input activates and goes back to
AUTO at the end of the time configured in P.0420 (if P.0420 is set to zero, the test is
not carried out). If there is a second activation of the input during the test, the test is

116 MC200 Technical Manual EAAM0578EN


immediately stopped. During this test, the controller doesn’t connect the generators to
the loads, independently from the value configured in P.0222.

 By using a digital input configured with the function DIF.2030 (“Request for the test
mode with load - impulse”). The controller evaluates the input activation moment
(impulse): the controller switches to TEST when this input activates and goes back to
AUTO at the end of the time configured in P.0420 (if P.0420 is set to zero, the test is
not carried out). If there is a second activation of the input during the test, the test is
immediately stopped. During this test, the controller connects the generators to the
loads, independently from the value configured in P.0222.

 By properly configuring the parameters:

▪ P.0418: Test enable days.

▪ P.0419: Test start time.

▪ P.0420: Test duration.

They allow selecting the days of the week and a time slot within which the working
mode switches from AUTO to TEST. In this case, the passage to TEST is automatic
in the scheduled days and hour. The controller returns to AUTO when the TEST time
interval ends. Parameter P.0222 establishes if the generators are connected to the
loads or not.

 By means of a proper command via SMS (see [3]). To use this feature, the parameter
P.0420 “Test duration” shall not be set to zero (it indicates in effect the duration of the
test). In this case, the controller shifts from TEST after receiving the SMS and returns
to AUTO after the time P.0420. Parameter P.0222 establishes if the generators are
connected to the loads or not.

 From a Modbus command. The controller shifts to TEST when it receives the
command, returns to AUTO when it receives the opposite command or when it
considers the connection interrupted (60 seconds without messages). The commands
can be protected by a password (P.0004) which must be entered before any
command, and they can be deactivated through a digital input (DIF.2706). To send
the command it is necessary to write in sequence (within 5 seconds):

▪ HOLDING REGISTER 101: write the password configured with the parameter
P.0004.

▪ HOLDING REGISTER 102: write the value:

▪ “12” to require the vacuum TEST mode.

▪ “14” to require the load TEST mode.

▪ "21" to return to AUTO.

To activate the REMOTE START mode, the controller must be in AUTO or in TEST mode.
Moreover, it is possible to configure an input with DIF.2701 function ("enable remote start
request"): if the input exists, it should be active. This mode can be activated in one of the
following modes:

 By means of the digital input configured with the function DIF.2032 (“remote start
request”). If input is active, the REMOTE START mode is entered and it is leaved
deactivating the input.

 By means of a proper command via SMS (see [3]). In this case, the controller shifts to
REMOTE START as soon as it receives the SMS and returns to AUTO when it
receives the opposite command. In this case, it is mandatory to configure an input with
function DIF.2701 (“enable remote start request”): the input must be active (normally
wired on a switch at control panel front to enable the remote commands).

MC200 Technical Manual EAAM0578EN 117


 By properly configuring the parameters P.0426, P.0427 and P.0428, it is possible to
define an hour range within which the working mode automatically switches to
REMOTE START. Parameter P.0426 allows to establish in which days of the week
this function is active. The remaining two allow to set an hour range valid for all
selected days. The range start time (P.0427) refers to the days set in P.0426, while
the range end time (P.0428) refers to the same day, if its value is higher than P.0427,
or to the following day if lower (across midnight). Moreover, setting P.0427 and P.0428
to the same value, you define a full day range.

 By a Modbus command. The controller shifts to REMOTE START once it receives the
command, returns to AUTO when it receives the opposite one (it remains in REMOTE
START if the connection interrupts before receiving the opposite command). In this
case, it is mandatory to configure an input with function DIF.2701 (“enable remote
start request”): the input must be active (normally wired on a switch at control panel
front to enable the remote commands). The commands can be protected by a
password (P.0004) which must be entered before any command, and they can be
deactivated through a digital input (DIF.2706). To send the command it is necessary
to write in sequence (within 5 seconds):

▪ HOLDING REGISTER 101: write the password configured with the parameter
P.0004.

▪ HOLDING REGISTER 102: write the value:

▪ “13” to require the REMOTE START mode.

▪ "21" to return to AUTO.

7.1.1 Events and signalling


The controller records the following events if the working mode changes (if enabled with bit 0
of P.0441 parameter):

 EVT.1001: the new mode is “OFF/RESET”.

 EVT.1002: the new mode is “MAN”.

 EVT.1003: the new mode is “AUTO”.

 EVT.1004: the new mode is “TEST”.

 EVT.1005: the new mode is “REMOTE START”.

Some functions are available for the configuration of the digital outputs related to the operation
mode of the controller:

 DOF.3001 - “OFF/RESET”. The board activates this output when in OFF/RESET


mode.

 DOF.3002 - “Man”. The board activates this output when in MAN mode.

 DOF.3003 - “Auto”. The board activates this output when in AUTO mode.

 DOF.3004 - “Test”. The board activates this output when in TEST mode.

 DOF.3005 - “REMOTE START”. The board activates this output when in REMOTE
START mode.

 DOF.3011 - “Not in OFF/RESET”. The board activates this output when in AUTO or
MAN mode.

 DOF.3012 - “One of the automatic modes”. It activates when a controller is in an


automatic operation mode, that is AUTO, TEST, or REMOTE START.
Also, the controller operates with AND/OR logics through the following internal statuses:

118 MC200 Technical Manual EAAM0578EN


 ST.000 - “OFF/RESET”.

 ST.001 - “manual”

 ST.002 - “Automatic”.

 ST.003 - “Test”.

 ST.004 - “remote start”.

MC200 Technical Manual EAAM0578EN 119


7.2
The controller needs to know if there are voltages on the generators bus to enable or not the
synchronization when it must close a circuit breaker. The following terms are used:

• “Dead” bus: no voltages on generators bus.

• “Live” bus: voltages on generators bus.

The controller can detect the presence of voltage on the generators bus through its three-
phase sensor (JF) or through an external sensor.

Note: if there is an external sensor, the internal one is ignored.

Note: if the controller must synchronize the gensets with the mains, it is necessary to
use the internal sensor (or an external synchronizer).

The gensets bus status is displayed by means of the led GENERATORS BUS LIVE.

7.2.1 External sensor


Use a digital input configured with the function DIF.3102 (“No voltages on gensets”): when the
input is active, the generators bus is considered “without voltage”.

7.2.2 Internal sensor


The controller uses the parameters to configure the sensor:

• P.151: it indicates whether the full-scale voltage is 400V or 100V.

• P.0101: it indicates if the generators bus is three-phase (3) or single-phase (1).

• P.0102: gensets nominal voltage. Its value must be the nominal phase-to-phase
voltage for three-phase systems and phase–to–neutral voltage for single-phase
systems.

• P.0103: primary value (Vac) of possible voltage transformers connected to the JF


connector.

• P.1104: secondary value (Vac) of possible voltage transformers connected to the JF


connector.

• P.0128: it indicates whether the neutral line is connected to the JF terminal.

For the connection of the voltage lines, see paragraph 5.9.

Note: set the nominal voltage to a value different from zero.

The controller uses a fixed threshold, 9% of nominal voltage (with a 3% hysteresis).


Generators bus is considered “dead” if all voltages (P.0101) are below the 9% threshold, it is
“live” if at least one voltage is above 12% (9 + 3). With default parameters, generators bus is
“dead” if all voltages are lower than 36 V; it is “live” if at least one voltage is greater than 48 V.

For three-phases system, the previous tests are performed on the phase-phase voltages. If
enabled with P.0328 (<> 0) the same tests are performed on the phase-nutral voltages also.

7.2.3 Events and signalling


The controller records the following events if the working mode changes (if enabled with bit 2
of P.0441 parameter):

 EVT.1020: no voltages on the generators bus.

 EVT.1022: voltages on the generators bus.

The following functions, for the configuration of the digital outputs, are related to the generators
bus voltage:

120 MC200 Technical Manual EAAM0578EN


• DOF.3031 (“Voltage on gensets”): the output is active when there are voltages on the
generators bus.

7.3
The controller needs to know if there are voltages on loads bus to enable or not the
synchronization when it must close the circuit breakers. The following terms are used:

• “Dead” bus: no voltages on loads bus.

• “Live” bus: voltages on loads bus.

The controller is not able to directly detect voltages on the loads (except when MGCB is not
used or always closed). Usually, it recreates this status according to the voltage detected on
the mains and on the generators bus, and to the circuit breakers status.

If preferred (and for safety reasons also), it is possible to use one digital input configured with
the function DIF.3104 (“No voltage on loads”) to acquire this information. Loads bus is “live” if
this input is “not active” (logical state).

The loads status is displayed by means of the signal led BUS LIVE.

7.3.1 Signalling
The following functions for the configuration of the digital outputs are related to loads bus
voltage:

• DOF.3030 (“Voltage on loads”): the output is active when there are voltages on the
loads.

MC200 Technical Manual EAAM0578EN 121


7.4
The controller acquires mains voltages and frequency, for three main purposes:

• “AMF”. The controller must detect all anomalies about the mains to start the
generators and make them supply the loads. In the same way, the controller detects
when mains voltages and frequency are back to their operating values to connect
loads to mains and stop the generators.

• “Protections for the parallel with the mains (PPR)”. The controller must detect the
“loss of mains” while generators are in parallel with mains, to disconnect them from
the mains (generator can in this case supply loads or not depending on plant
configuration). In the same way, when generators are disconnected from the mains,
the controller detects when mains voltages and frequency are back to their operating
values to put generators in parallel with mains again.

• For synchronization purpose.

The controller uses different sets of parameters for these purposes.

Normally, the controller uses its internal sensor (JG) to measure the mains. For the first two
functions, it’s possible to use an external sensor alternatively (for the synchronization you must
use the internal sensor).

There are some parameters for the configuration of the internal sensor that do not depend on
its use:

• P.0105: nominal frequency (Hz).

• P.0152: it indicates if the full scale for the inputs is 400V or 100V.

• P.0119: it indicates if the mains is three-phase (3) or single-phase (1).

• P.0116: nominal voltage. Its value must be the nominal phase-to-phase voltage for
three-phase systems and phase–to–neutral voltage for single-phase systems.

• P.0117: primary value (Vac) of possible voltage transformers connected to the JG


connector.

• P.0118: secondary value (Vac) of possible voltage transformers connected to the JG


connector.

• P.0129: it indicates whether the neutral line is connected to the JG connector or not.

For the connection of the voltage lines, see paragraph 5.9.

Note: set the nominal voltage to a value different from zero.

The mains status is displayed by means of the signal led MAINS LIVE.

7.4.1 Automatic Mains Failure


This function must detect all anomalies on the mains voltage, to start the gensets and connect
the loads to them.

Usually, this function is not used if the gensets are in parallel with the mains, Anyhow, if the
parallel protections trip while the gensets are in parallel with the mains, the mains is considered
“off” for AMF purpose too.

The parameter P.9504 allows to set whether to use the internal sensor (”0”) or the external
one (”1”).
7.4.1.1 External sensor
To use an external mains sensor, P.9504 must be set to 1.

122 MC200 Technical Manual EAAM0578EN


The external mains sensor must be connected to a digital input configured with the function
DIF.3101 (“External sensor for mains”). Mains is “in tolerance” when this input is “active”
(logical state), is “Absent” when the input is “not active”.
7.4.1.2 Internal sensors
To define the mains status, the controller can carry out up to four different checks. They are
described below one by one (with examples).
7.4.1.2.1 Frequency check

Parameter Description Default value Frequency (Hz)


P.0105 Nominal frequency 50 Hz 50.00
P.0236 Low frequency threshold 90.0 % 45.00
P.0237 High frequency threshold 110.0 % 55.00
P.0201 Hysteresis 2.5 % 1.25

The hysteresis is applied:

• Upwards the low frequency threshold (so, with parameters default values, between
45.00 Hz and 46.25 Hz).

• Downwards the high frequency threshold (so, with parameters default values,
between 53.75 Hz and 55.00 Hz).

Considering these values, we can detect the following bands:


0.00 V .
Band A: absent
45.00 V .
Band B: hysteresis
46.25 V .
Band C: in tolerance
53.75 V .
Band D: hysteresis
55.00 V .
Band G: high
xxx V .

If the frequency is in the B or D bands, the controller maintains its previous status (hysteresis).
For example, if the voltage was in C band and now it is in D band, it is considered “in tolerance”
anyway. If instead, the frequency was in A band and now it is in B band, it is considered “off”.
7.4.1.2.2 Voltages check

Parameter Description Default value Voltage (Vac)


P.0119 Number of phases 3 -
P.0116 Nominal voltage 400 Vac 400
P.9505 Presence threshold 17.5 % 70
P.0203 Low voltage threshold 80.0 % 320
P.0204 High voltage threshold 110.0 % 440
P.0201 Maximum hysteresis 2.5 % 10

The hysteresis is applied:

• Upwards the mains presence threshold (so, with parameters default values, between
70 Vac and 80 Vac).

• Upwards the low voltage threshold (so, with parameters default values, between 320
Vac and 330 Vac).

• Upwards the high voltage threshold (so, with parameters default values, between 430
Vac and 440 Vac).

MC200 Technical Manual EAAM0578EN 123


Considering these values, we can detect the following bands:
0 V .
Band A: absent
70 V .
Band B: hysteresis
80 V .
Band C: low
320 V .
Band D: hysteresis
330 V .
Band E: in tolerance
430 V .
Band F: hysteresis
440 V .
Band G: high
XXX V .

If the voltages are in the B, D or F bands, the controller maintains its previous status
(hysteresis). For example, if the voltage was in E band and now it is in D band, it is considered
“in tolerance” in any case. If instead, the voltage was in C band and now it is in D band, it is
considered “low”.

Such statuses are managed for each phase.

For three-phases system, the previous tests are performed on the phase-phase voltages. If
enabled with P.0244 (<> 0) the same tests are performed on the phase-nutral voltages also.
7.4.1.2.3 Asymmetry check

Parameter Description Default value Voltage (Volt)


P.0116 Nominal voltage 400 Vac 400
P.0238 Voltage unbalance threshold 10.0 % 40

On three-phase systems, it is possible to consider the mains “out of tolerance” if the three
phase-to-phase voltages differs from each other (in absolute value) more than the threshold
set. The check is disabled for single-phase systems.

Note: MC200 does not carry out any check on the phase angles, but only on the phase-to-
phase voltages.

This threshold does not use any hysteresis. With the parameters default values, if the
difference between two phase-to-phase voltages in absolute value is higher than 40 Vac, the
mains is considered out of tolerance; otherwise, it is considered in tolerance.
7.4.1.2.4 Cycling sense

Parameter Description Default value


P.0239 Required phase sequence 0-Nothing

In three-phase systems, it is possible to consider the mains “out of tolerance” if the phases
cycling sense is different from what specified in the parameter P.0239. In single-phase system,
this control is disabled.

To disable this control, simply set the parameter P.0239 to “0-None”.

With the parameter P.0239, it is possible to select the cycling sense required by the mains: “1-
Clockwise” or “2-Counter-clockwise” The mains is considered “out of tolerance” if the cycling
sense is different from the one set.
7.4.1.2.5 Internal sensor status

To diagnose the mains “global” status, the following algorithms are utilized, shown in their
computing order:

• If frequency and all voltages are in the “Off” status, the general status is “Off” too.

124 MC200 Technical Manual EAAM0578EN


• If frequency and all voltages are in the “In tolerance” status, the general status is “In
tolerance” too. In this case, if the cycling sense or unbalance checks don’t give positive
results, the mains is considered “Low”.

• If frequency or at least one voltage is in the “High” status, the general status is
“High” too.

• If no one of the previous conditions is verified, the global status is “Low”.


7.4.1.3 Mains general status
Whatever method is used to acquire the instantaneous status of the mains (internal or external
sensor), for the operating logics of the plant the general status of the mains is described in
four phases:

Mains in
tolerance
Mains out of tolerance
The time set with
P.0205 is elapsed (0
seconds in MAN)

Mains in tolerance
Delay mains
Delay mains failure
presence Mains in tolerance

The time set with P.0206 is


Mains out of elapsed (two seconds if at
Mains out of tolerance tolerance least one generator is “ready
to supply” or has its GCB
closed, 0 seconds if MGCB
exists and is closed).

7.4.1.4 Events
The controller records the following events if the mains status changes (if enabled with bit 1 in
P.0441):

• EVT.1010: the new mains status is permanently “off or out of tolerance”.

• EVT.1011: the new mains status is “present or in tolerance”.

• EVT.1012: the new mains status is permanently “in tolerance”.


7.4.1.5 Signals
The following functions for the configuration of the digital outputs are connected to the mains
status:

• DOF.3033 (“Mains in tolerance)”): the output is activated if the mains is permanently


in tolerance, or during the delay for the “mains out of tolerance”.

7.4.2
This function must detect an anomaly on the mains voltage while the gensets are in parallel
with the mains, to disconnect the gensets from the mains.

It is possible to use the internal sensor of the controller or an external protection.

See document [8] for the description of these protections.

MC200 Technical Manual EAAM0578EN 125


7.5
Synchronization is used when a circuit breaker must be closed and there are voltages on both
sides of it. Synchronization can be divided into two separate functions:

• Check for differences in phase, frequency, voltages and phase sequence between
generators and mains, to allow a safe closure of the circuit breaker.

• Voltages and frequency regulations, to minimize differences in voltages, frequency


and phase.

The controller can handle both functions, but, if needed, allows one or both to be managed
externally.

7.5.1 Synchro-check
Before closing a circuit breaker, this function checks the differences in voltages, frequency,
phase and cycling sense between the mains and the gensets are within the thresholds
configured; if yes, the circuit breaker can be closed in safety, otherwise it cannot be closed.

The controller performs these checks if:

• It directly manages frequency and phase regulations.

• Frequency and phase regulations are managed externally, but the parameter P.0846
forces MC200 to manage the synchro-check.

In these cases, the circuit breaker closure command (MCB o MGCB) is issued only when the
“synchronized” status is detected.

The controller does not perform these checks if frequency and phase regulations are managed
externally, and parameter P.0846 configures the controller not to manage the synchro-check.
In this case, the circuit breaker closing command is immediately issued, as MC200 supposes
that an external synchro-check inhibits the physical closing of the circuit breaker if not
synchronized.

Obviously, synchronization will never start if one or both side of the circuit breaker are “dead”
(without voltages).

Parameter P.0846 allows forcing the use of the MC200 synchro-check with externally
managed frequency and phase regulations (its value is ignored if the controller manages the
regulation processes). It allows to force the MC200 synchro-check of the circuit breakers (MCB
or MGCB) individually or together (if preferred). By default, MC200 synchro-check is always
forced by the parameter P.0846.

If the internal synchro-check is forced, but the controller cannot perform it, the warning W273
(incoherent parameter) is issued.

MC200 performs six different checks before allowing the circuit breaker closure: only when all
checks are correct, the circuit breaker will be closed.

Voltages in tolerance check

Voltages (both mains and generators ones) must be inside configured thresholds. For
example, if we have 200 V on both mains and generators, but nominal voltages are 400 V, the
circuit breaker will not be closed, even if voltage difference is zero. This check can be
configured with:

• P.0301: minimum voltages threshold (%).

• P.0303: maximum voltages threshold (%).

These thresholds are displayed in percentage. These thresholds are percentage of P.0116 for
mains voltages, and of P.0102 for genset voltages).

126 MC200 Technical Manual EAAM0578EN


Each voltage measure is compared with these thresholds: if at least one of them is out of
thresholds, the circuit breaker cannot be closed (this situation is shown on display page M.12
by an empty rectangle).

Voltage differences check

If all voltages are inside the configured thresholds, the controller calculates the differences
between generators and mains voltages and allows the closure of the circuit breaker only if
the differences are below the threshold P.0841. This parameter allows to set the maximum
voltage difference (%).

The controller analyses the differences between the voltages measured (mains phase L1 -
genset phase L1, etc.) and it displays them in percentage with respect to the gensets voltage.
The circuit breaker can be closed only if all differences (%) are below the threshold configured
by parameter P.0841 (with a fixed hysteresis of 1%). If at least one difference is higher than
the threshold, the closing is not allowed. Obviously, in a single-phase system, the controller
will consider the existing one only.

The controller can work also with different nominal voltages between mains and generators
(this happens when a transformer is placed between them). In this situation, both voltages
(mains and generators) are converted into percentages of their own nominal, and the controller
makes the comparison between those percentages: if the mains voltages are 95% of their
nominal, also the generators voltages should be 95% of their nominal.

The result of this check (and of the one described above) is displayed in page M.12 by the
rectangle that indicates the voltage difference:

• Empty rectangle: voltages or voltage differences are out of thresholds.

• Full rectangle: voltages and voltage differences are inside thresholds.

Frequency in tolerance check

Frequencies (both mains and generators ones) must be inside configured thresholds. For
example, if we have 40 Hz on both mains and generators, but nominal frequencies are 50 Hz,
the circuit breaker will not be closed, even if frequency difference is zero. This check can be
configured with:

• P.0305: minimum frequency threshold (%).

• P.0307: maximum frequency threshold (%).

These thresholds are percentage of P.0105.

Mains and generators frequency are compared with these thresholds: if at least one of them
is out of thresholds, the circuit breaker cannot be closed (this situation is shown on display
page M.12 by an empty rectangle).

Frequency difference check

If all frequencies are in tolerance, the controller calculates the frequency differences between
mains and generators and it allows the closing only if lower than the threshold configured with
the parameter P.0843. This parameter allows to set a max difference in Hz.

The controller analyses the differences between the frequencies measured, and it compares
them with the threshold P.0843 (with a fixed 0,1Hz hysteresis): if the difference is higher than
the threshold, the closing is not allowed.

The frequency status (the results of this check and of the previous one) is shown on the display
page M.12, by the second small rectangle from the left (the one identified by the “Hz” label):

• Empty rectangle: frequencies or frequency differences are out of thresholds.

• Full rectangle: frequencies and frequency differences are inside thresholds.

Phase difference check

MC200 Technical Manual EAAM0578EN 127


The controller must evaluate the phase difference between mains and generators, and allow
closing the circuit breaker only when this difference is below the threshold configured by
parameter P.0842 (with a fixed hysteresis of 1 degree). P.0842 allows setting the maximum
phase difference in degrees

The result of this check is shown on the display page M.12, by the third small rectangle from
the left (the one identified by the “°” label):

• Empty rectangle: phase difference is out of thresholds.

• Full rectangle: phase difference is inside thresholds.

Sometimes, the plants do use transformers. These transformers can introduce a phase error
in voltages. So, it is possible that synchronizing on their primary side, we have a phase error
on the secondary side. If the controller regulates for 0° on secondary side, voltages on the
circuit breaker may be not synchronized. Parameter P.0845 allows setting a fixed phase offset.
If different from zero, the controller regulates for x° on the secondary side, to have 0° on
primary side. The parameter P.0845 allows to set (with a sign) the compensation of the
transformers phase error (+/-180°).

Phases sequence check.

Only for three-phase plants, the controller checks for the same phases sequence on
generators and mains. The circuit breaker can be closed only if the same phases sequence is
detected. No parameters are provided for this check.

The result of this check is shown on the display page M.12, by the forth small rectangle from
the left (the one identified by two arrows):

• Empty rectangle: different phase sequences.

• Full rectangle: same phase sequences.

Circuit breaker closing enabled.

MC200 detects a “synchronized” status only when all previous checks (or all the ones
applicable) give correct results, consecutively for the time configured by parameter P.0844.
When MC200 removes its consent, it does not reactive it for at least one second.

The “closure enable” condition is shown on the display page M.12, by the fifth small rectangle
from the left (the one identified by two arrows):

• Empty rectangle: closure not allowed.

• Full rectangle: closure allowed.

Note: circuit breaker closure is enabled only when the controller first detects a “not
synchronized” status and then a “synchronized status”. This protects the plants from wiring
errors. If MC200 directly manages frequency and phase regulations, it automatically forces
generators to go in a “not synchronized” status first, and then in a “synchronized” status.
7.5.1.1 Signals
It’s possible to configure an output to signal the synchronism condition externally. This output
will be activated during synchronization only, when the controller activates the internal “closure
enable” status. The output is configured with the function DOF.3094 (“Synchronized”).

7.5.2 Voltages, frequency and phase regulations


To synchronize generators with mains, it is needed to work on:

• On generator voltages, to make them equal to mains: this avoids current circulation
(reactive) when the circuit breaker will be closed. Normally, the gensets voltages
should be a little bit higher than mains voltages, to supply (little) reactive power from
gensets while closing.

128 MC200 Technical Manual EAAM0578EN


• On generators frequency, to minimize differences on phase and frequency from
mains.

The controller can manage both voltage and frequency regulations on generators, by the CAN
bus link. Thus, it can minimize differences in voltages, frequency and phase between mains
and generators, to allow a safe closure of the circuit breaker.

Note: the gensets controllers always accept these commands, even if they are “not
managed by MCxxx”.

Note: these commands are transmitted on CAN bus only during the synchronization.

It is not mandatory using MC200 for this function: if preferred (or if it is needed because, for
example, mains voltages are not acquired by MC200), an external analogue synchronizer can
be used (GAC or other).
7.5.2.1 Using external synchronizer
Analogue synchronizers act on generator frequency by a command signal. It is possible to
connect this signal directly to an analogue input of all genset controllers. Alternatively,
(suggested option), it is possible to connect this signal to an analogue input of the controller,
which will transfer it via CAN bus to the genset controllers.

Each synchronizer has its own signal type. MC200 can interact only with signals in direct
voltages 0-10 Vdc. Some synchronizers have different command signals:

• Current signals (4-20 mA, +/-10 mA). It is simple to convert these signals in Volts DC
applying a resistor on them.

• PWM. Not managed by MC200.

• Up/Down. These synchronizers use two digital outputs to request an increase or a


decrease of speed. They can be managed using PLC function, with the DIPOT block
that converts up/down commands into a virtual analogue input.

Within the 0-10 Vdc range, MC200 is fully configurable: for example, MC200 can acquire a 3
to 6 Vdc signal and convert it to -4 to +4 Hz change on gensets. MC200 can be also configured
to decrease generators frequency when the synchronizer signal increases (and vice-versa).

To use an external synchronizer, an analogue input of MC200 must be correctly configured.


For example, let’s suppose to use a GAC synchronizer and connect it to the analogue input 1
(see paragraph [1] for parameters related to analogue inputs):

• P.4001 - “Function of analogue input 1”. This parameter allows selecting the analogue
input function. For external synchronizers, three functions are available:

o AIF.2105: if the external synchronizer should be used for the MCB closing
only (MGCB synchronization is managed by MC200).

o AIF.2107: if the external synchronizer should be used for MGCB closing only
(MCB synchronization is managed by MC200).

o AIF.2103: if the external synchronizer should be used for the closing of both
MCB and MGCB circuit breakers.

• P.1842 - “Analogue input 1 minimum value”. GAC synchronizer works between 0 and
10 V, so this parameter must be set to 0%.

• P.1843 - “Analogue input 1 maximum value”. GAC synchronizer works between 0 and
10 V, so this parameter must be set to 100%.

In this way, we configured the input. Now, we must configure the conversion of the
measurement from Vdc to Hz. The speed regulation command over CAN bus is a percentage
value: 0% corresponds to 4 Hz less then nominal frequency, 100% corresponds to 4 Hz over
nominal frequency (so 50% corresponds to nominal frequency). So, it is necessary to convert
the signal 0-10 Vdc in a percentage value. GAC synchronizer decreases its command signal

MC200 Technical Manual EAAM0578EN 129


to speed-up generators. So, the following conversion curve must be linked to the analogue
input 1:

In the previous example, the GAC synchronizer can change generators frequency of +/- 4 Hz.
If in the previous table we replace the 100% with 75% and the 0% with 25%, the maximum
change of frequency should be +/- 2 Hz. By setting the curve in an asymmetric way, it is
possible to compensate electrical offsets (GAC should give a 5 Vdc signal to request the
nominal frequency, it may be 5.1 or 4.9).

During the synchronization phase, the controller will change the gensets frequency as required
by the external synchronizer.

Note: now, there is no support for the genset voltage regulation by an external synchronizer.
This function, if it is enabled, is always managed by MC200.

Note: it is possible to use two different external synchronizers for MCB and MGCB, by wiring
them to two different analogue inputs configured with codes DIF.2105 and DIF.2107. For each
input is possible to set a specific conversion curve.
7.5.2.2 Using internal synchronizer
Phase/Frequency regulation

The controller regulates the gensets frequency to equalize the two frequencies and reset the
phase difference between gensets and mains.

A PI regulator is used to manage the frequency and reset the phase error. It works on phase
difference, and can be configured with the following parameters:

• P.0849 - “Gain for phase control loop”.

• P.0850 - “Integrative factor for phase control loop”.

These parameters must be adapted to get the best response from the system. They have the
same functions of trimmers on analogue synchronizers.

Note: when you are setting these parameters, be sure the circuit breaker cannot be closed.
Do that by opening fuses (if available) or by setting parameter P.0842 to zero.

Voltage regulation

The same concepts explained in the previous paragraph are valid also for voltage regulation.
Parameters provided for the voltage PI regulator are:

• P.0868 - “Voltage matching gain”.

• P.0869 - “Voltage matching integrative factor”.

If both parameters are “0”, no voltage regulation is available during synchronization.

130 MC200 Technical Manual EAAM0578EN


7.5.2.2.1 PI regulator

The controller uses two PI regulators internally to regulate the voltage and the speed of the
gensets for the synchronization operations. All internal PI regulators can be configured with
two parameters:

• The factor proportional to the current error (P) is also called “gain”.

• The factor related to the integral in the error delay (I) is also called “integrative factor”.

In the previous paragraph, there are the parameters associated to each PI regulator.

These two parameters for each PI regulator should be “adjusted” during the installation
procedure. In fact, they depend on different factors: the type of engines, the alternator powers,
the type of alternators; different parameters could be necessary for similar systems.

The definition of these parameters is not particularly critical if carried out with method.
Unfortunately, the empirical adjustment (called Ziegler-Nichols) requires to measure the
oscillation period of the measurement (frequency, voltage), which is not always possible (or
simple) to do.

For this reason, besides the empirical method, we suggest a simplified method that should
help carrying out in a valid way the parameters choice.

The PI regulator parameters can be modified even if the plant is working, by the user panel. It
is suggested to carry out the modifications by using the BoardPrg3 program, which is available
for free on our SICES website.
7.5.2.2.1.1 Complete method

1) Set “P” at an initial value (0,100) and “I” at 0,000.

2) Increase “P” until the adjusted measurement start to oscillate (for example, if you are
adjusting the PI that manages the speed during the synchronization, increase “P” until
it seems to hear that the engines accelerate / slow down). Decrease/increase the
value “P” until an oscillation point is determined (a good estimate is sufficient).

3) Measure the oscillation period (the time between two consecutive peaks of speed).

4) Set “P” at a slight lower value than the one resulted by the division of the current value
by 2.2.

5) Set “I” at the value calculated by dividing 1.2 for the period of oscillation measured
before (in seconds). A lower value can be set at a lower value, decreasing its
performance but increasing the stability range.

6) Further adjustments could be necessary. Check how the system reacts in case of low,
medium or high load. In case there still is a system instability, reduce the “P” value
again.
7.5.2.2.1.2 Simplified method

To avoid the problem of measuring the oscillation period, you can proceed by referring to what
has been described before, up to the point 6 included, except for the point 3 and 5. At point 5,
increase/decrease “I” (after having adjusted “P” at point 4) until getting the best performances.
7.5.2.2.1.3 General notes

The parameter “P” is not able to guarantee a good adjustment alone. To reduce the error, “P”
should be increased, but over a set threshold, the systems becomes unstable. The value “P”
defined with the described method usually is the best relation between stability and
performance.

For a good adjustment, it is necessary to set the factor “I”. Even little values of the parameter
“I” change the system performance. The value, obtained by the procedure described, usually
supplies the best performances. Anyhow, it is not critical and it can be set in a greater range
of values.

MC200 Technical Manual EAAM0578EN 131


Consider that the factor “I” accumulates the adjustment errors: delay in the recovery of the
error can cause over-shoots or under-shoots. Very high values of “I” bring to the oscillation of
the system.

Once you found the value that supplies a good performance, try to decrease it until the
performance decreases under the waited minimum. Then select an intermediate value in this
range.

In some case, it would be necessary to start a procedure with a minimum value of “I” to
guarantee a level of adjustment suitable with the operation of the system. A very low value of
“I” (0.01) can be used with light effects on the procedure.

7.5.3 Digital inputs for synchronization


MC200 allows configuring digital inputs with two special functions related to synchronization:

• DIF.1034 (“Synchronization request for MCB”).

• DIF.1004 (“Synchronization request for MGCB”).

These inputs must be used when the related circuit breaker is not managed by MC200, but
you want to use PI regulators of MC200 for synchronization. When the input is “active” (logical
state), if all necessary conditions for synchronization are present, MC200 starts the
synchronization process and signals it to external devices using up to four digital outputs (see
next paragraph).

7.5.4 Digital outputs for synchronization


MC200 allows configuring digital outputs with the following special functions related to
synchronization:

• DOF.3091 (“Synchronization for MGCB”). It is used when MGCB is managed by


MC200 but an external synchronizer must be used. When MC200 starts
synchronization process, this output become “active” and can be used to
supply/enable the external synchronizer. When synchronization ends, the output
become “not active”.

• DOF.3092 (“Synchronization for MCB”). It is used when MCB is managed by MC200


but an external synchronizer must be used. When MC200 starts synchronization
process, this output become “active” and can be used to supply/enable the external
synchronizer. When synchronization ends, the output become “not active”.

• DOF.3093 (“Synchronization in progress”). It is used when MCB/MGCB is managed


by MC200 but an external synchronizer must be used. When MC200 starts
synchronization process, this output become “active” and can be used to
supply/enable the external synchronizer. When synchronization ends, the output
become “not active”.

• DOF.3094 (“Synchronized”). This output can be used in case the synchro-check of


the controller is used for a circuit breaker closing (MCB or MGCB), which is
commanded by an external logic. This output can be “active” only during
synchronization process, when MC200 detects the “synchronized” status between
mains and generators. Outside synchronization process, or when generators are not
synchronized with mains, this output is “not active”. This output should be wired to the
external logic that physically closes the circuit breaker (be aware that the output
become “not active” after circuit breaker has been closed).

• DOF.0103 (AND/OR logics) with the status:

o ST.097: synchronization in progress for MCB closure.

o ST.098: synchronization in progress for MGCB closure.

o ST.099: synchronized status detected.

132 MC200 Technical Manual EAAM0578EN


7.5.5 Automatic synchronization
This description refers to the operation in AUTO, TEST and REMOTE START. It also refers
to the operation in MAN if the parameter P.0848 (“automatic synchronization in manual mode”)
is set to “1”.

If the internal synchronizer is used, the controller regulates voltage and frequency to get the
“synchronized” status: if the “synchronized” status persists for 10 seconds and the circuit
breaker doesn’t close, MC200 changes generators frequency to force a “not synchronized”
status, then starts to synchronize again. This avoids problems when using external synchro-
checks in addition to the MC200 one: it is possible that some external synchro-checks don’t
allow the closure because they haven’t detected any “unsynchronized” status before.

MC200 allows configuring the maximum duration of synchronizations for the two circuit
breakers:

• P.0852: MGCB synchronization maximum time.

• P.0853: MCB synchronization maximum time.

The duration of the synchronization phase on a circuit breaker is managed only in automatic
mode (not MAN) and if the related delay is different from zero; in this case an anomaly is
activated:

• W272 – “MCB synchronization failure”. It is always a warning. The controller can


decide to close MCB without synchronization (opening MGCB or GCB), depending on
the type of plant and on the configuration (P.9515).

• X271 – “MGCB synchronization failure”. If MGCB is directly managed from MC200, it


is an alarm, otherwise it is a warning.

7.5.6 Manual synchronisation


This description refers to the operation in MAN if the parameter P.0848 (“automatic
synchronization in manual mode”) is set to “0”.

The user must manually regulate the gensets voltage and frequency until the “synchronized”
status is detected (this check is always carried out by the controller).

MC200 provides two parameters that allow voltages and frequency regulations on the
generators:

• P.0867 - “Voltage offset”.

• P.0840 - “Speed offset”.

Both are expressed as percentage (between 0 and 100%). The first allows changing
generators voltages of +/-20 Volt; the second allows changing generators frequency of +/- 4
Hz (the real voltages and frequency ranges depend on single genset controller settings).
Setting both to 50%, generators work to their nominal voltages and frequency.

These parameters can be directly changed on display page M.12 (provided for
synchronization). It is possible to simplify the procedure using two potentiometers instead of
the parameters. The following is needed:

Voltage

• Configure an analogue input with the function AIF.2201 (“Voltage offset”) (parameter
P.4001 for analogue input 1).

• Associate the input to a conversion curve, which converts the voltage of the analogue
input into a voltage correction (%).

After these configurations, you can change the voltage offset between 0 and 100% by
moving the potentiometer between 0 and 10 Vdc (the current voltage offset is shown on
page M.12), and consequently you can change the gensets voltage. Note: once you have

MC200 Technical Manual EAAM0578EN 133


configured an analogue input with the function AIF.2201, the parameter P.0867 is no more
used.

Frequency.

• Configure an analogue input with the function AIF.2101 (“Speed offset”) (parameter
P.4001 for analogue input 1).

• Associate the input to a conversion curve, which converts the voltage of the analogue
input into a speed correction (%).

After these configurations, you can change the speed offset between 0 and 100% by
moving the potentiometer between 0 and 10 Vdc (the current speed offset is shown on
page M.12), and consequently you can change the gensets frequency. Note: once you
have configured an analogue input with the function AIF.2101, the parameter P.0840 is
no more used.

Manual synchronization procedure is:

• Start the gensets (by pressing the START button on the panel).

• Select the page M.12 on the display (this can be carried out also by giving a manual
closing command of the circuit breaker – MCB/MGCB pushbutton or digital inputs
configured for MCB/MGCB).

• Use parameters P.0868 and P.0840 (or the related potentiometer, if configured) to
synchronize the gensets to the mains. When MC200 signals a synchronism status,
send a new closing command (pushbutton or related digital input): the circuit breaker
will be closed.

7.5.7 MCB synchronization failure


Parameter P.9515 configures the actions of the controller in case of failure of the
synchronization for the MCB circuit breaker closing.

• “0 – No blackout”. By setting this value, you configure the controller to avoid any
blackout on the loads (in AUTO modes). After having activated the warning of MCB
synchronization failure (W272), the controller keeps the loads connected to the
gensets. When the operator will acknowledge the warning, MC200 will try again to
close MCB through the synchronization.

• “1 – Short blackout”. By setting this value, you allow a short blackout on the loads
when the mains is back. Basically, after having activated the warning of MCB
synchronization failure (W272), the controller opens the MGCB circuit breaker (or it
forces the opening of the GCB circuit breakers) to be able to close MCB without
synchronization. Once MCB is closed, if the gensets intervention is still required,
MC200 will try to close MGCB with synchronization (or it will allow again the GCB
closing - with synchronization).

134 MC200 Technical Manual EAAM0578EN


MC200 Technical Manual EAAM0578EN 135
7.6
In automatic mode, MC200 determines, based on the type of system and the current
conditions, whether to start the generators. In these conditions, it is possible to force the
stopping of the generators by using the "inhibition to automatic intervention" function.

This internal function, once activated, takes priority over any other function: the generators will
be shut down and it will not possible to restart them. The function operates in AUTO mode,
but not in TEST and REMOTE START modes. The activation of this function does not result
in the activation of anomalies.
It is possible to activate this function in different ways, described in the following paragraphs.
The “INHIBIT” lock symbol ( ) is shown on the up right corner of the display, when an inhibition
is active.
7.6.1 Inhibition from contact
The controller can use a digital input programmed for inhibiting the gen-sets automatic
operation (function DIF.2501 – “Inhibition of start”). In case of an “active” input, the generators
are never automatically started, not even if the plants condition requires it.

Use parameter P.0207 to set a delay between input's physical activation and this function's
logic activation: the delay can only be applied if the controller is in AUTO mode, otherwise the
delay is null.

Use parameter P.0208 to set a delay between input's physical de-activation and this function's
logic de-activation: in case at least one generator is already running, the delay is two seconds
(fixed); in case at least one GCB is closed, the delay is null.

When function DIF.2501 is configured for a digital input, the acquisition of this input is
subordinated to the set time in P.0207and/or P.0208; the acquisition time related to the
digital input is ignored.
The board records any status variation of this inhibition to start in the event log (if enabled with
bit 6 of P.0441 parameter):

 EVT.1013: Inhibition active

 EVT.1014: Inhibition not active


7.6.1.1 Differences between and Inhibition
The two functions have different operating logic and purposes. The first emulates the internal
mains sensor behaviour, the second is used to explicitly impede the start of the system
whatever the mains status; this reflects to the status signalling, which, in this way, remains
more coherent with the real status of the system.
7.6.2 Inhibition from clock
By using P.0421, P.0422 and P.0423 parameters, it is possible to select the days of the week
and a time interval during which the generators are enabled to work. Outside this time interval
(and during not-selected days), the “inhibition to automatic intervention” function of the
generators is active (and then the generators will be stopped).
Parameter P.0421 allows to set the generators' weekly operation days. The remaining two
parameters allow to set an hour range valid for all selected days. The range start time (P.0422)
refers to the days set in P.0421, while the range end time (P.0423) refers to the same day, if
its value is higher than P.0422, or to the following day if lower (across midnight). Moreover,
setting P.0422 and P.0423 to the same value, you define a full day range.
The board records any status variation of this inhibition to start in the event log (if enabled with
bit 6 of P.0441 parameter):

• EVT.1221: inhibition activated

• EVT.1222: inhibition deactivated

136 MC200 Technical Manual EAAM0578EN


7.6.3 Inhibition to load management
In systems where more generators work in parallel, it is possible to use the "load
management", which activates only the generators needed to meet the power required by
loads in specific times That is, exceeding generators are stopped even though, for example, it
is an emergency plant and mains is Off. The “load management” uses the “inhibition to
automatic intervention” function to stop generators.
7.6.4 Inhibition due to mains failure
In systems where the generators work only in parallel with the mains, should the mains fail,
the controller would force the opening of the MGCB circuit breaker and, after a configurable
waiting time (P.0899), it would activate the “inhibition to automatic intervention” to stop the
generators until the mains is again "within tolerance".

The controller records every variation of this specific inhibition:

• EVT.1223: inhibition activated

• EVT.1224: inhibition deactivated


7.6.5 circuit breaker
In systems where more generators work in parallel, a generator's GCB circuit breaker might
not open when the generator must be stopped. In this condition, notwithstanding the stop
command, the engine would keep running with all external services unpowered (oil pumps and
the like). In these conditions, it is possible to inhibit the closure of MGCB (P.0805), and to force
its opening in case it is already closed: the generators are stopped (by means of the “inhibition
to automatic intervention”) waiting until the problem is solved.

The controller records every variation of this specific inhibition:

• EVT.1225: inhibition activated.

• EVT.1226: inhibition deactivated.


7.6.6 Signalling
The controller makes the statuses of the single “inhibition to automatic interventions” available
for the AND/OR logics, through the following internal statuses:

• ST.080: from contact.

• ST.081: from clock/calendar.

• ST.083: it’s not possible to work in island mode and mains failure.

• ST.084: for GCB circuit breaker not open.

7.7
In automatic mode, once the generators have been started, the controller normally tries to
close the MGCB circuit breaker (if it exists). In these conditions, it is possible to force the
opening of the MGCB by using the “inhibition to supply the loads” function. Note: if the MGCB
circuit breaker is not present in the plant, these inhibitions will act on the GCBs of the
generators.

This internal function acts in all automatic modes (AUTO, TEST and REMOTE START). The
activation of this function does not result in the activation of anomalies.

If the "inhibition to supply the loads" is activated when MGCB is already closed, the controller
tries to open it, by carrying out generators power discharge first (if possible).

It is possible to activate this function in different ways, described in the following paragraphs.

The controller records an event when the "inhibition to supply the loads" is deactivated:

MC200 Technical Manual EAAM0578EN 137


• EVT.1081: inhibition deactivated
7.7.1 Inhibition from contact
It is possible to configure a digital input through DIF.2502 function (“inhibition to supply loads”).
When this input is active, the inhibition to supply the loads is active.

The controller records an event when this inhibition is activated:

• EVT.1080: inhibition activated (by contact).


7.7.2 Modbus commands
These commands can be enabled by a digital input configured with function DIF.2706
("Enables serial ports commands": if this input exists, it should be active. The commands can
be protected with a password (P.0004) which must be entered before any command. To send
the command it is necessary to write in sequence (within 5 seconds):

• HOLDING REGISTER 101: write the password configured with the parameter P.0004.

• HOLDING REGISTER 102:

o “31” or “32” inhibition to supply the loads (it forces MGCB open).

o “33” to deactivate the inhibition to the automatic supply.

The control remains active for 30 seconds from the time it is received by the controller: it is
therefore necessary to repeat it about every 25 seconds until the inhibition to power load
should be kept active.

The controller records an event when this inhibition is activated:

• EVT.1202: inhibition activated.


7.7.3 Due to mains failure
In systems where the generators work only in parallel with the mains, (see [8]), if the mains
fail, the controller will force the immediate opening of the MGCB circuit breaker, and will
activate the “inhibition to supply the loads” to avoid its closure. The inhibition will be cancelled
when the mains is "within tolerance" again.

The controller records an event when this inhibition is activated:

• EVT.1201: inhibition activated


7.7.4 circuit breaker
In systems where more generators work in parallel, a generator's GCB circuit breaker might
not open when the generator must be stopped. In this condition, notwithstanding the stop
command, the engine would keep running with all external services unpowered (oil pumps and
the like). In these conditions, it is possible to inhibit the closure of MGCB (P.0805), and to force
its opening in case it is already closed: the controller activates the “inhibition to supply the
loads” to impede the closure (or force the opening) of MGCB.

The controller records an event when this inhibition is activated:

• EVT.1203: inhibition activated


7.7.5 Inhibition for synchronization on MCB
In a system composed of more than one generator, that can supply both in island mode and
in parallel with the mains (MSB + MSTP or MPtM + MSB), some external logics (among which
another MC200) can act on generators voltage and frequency to synchronize the generators
bus to the mains, to close the MCB or MGCB circuit breakers. At this stage, the controller
activates the “inhibition to supply the loads” if its own MGCB is open: in this way, it avoids its
closure, in order not to disturb the ongoing synchronization.

138 MC200 Technical Manual EAAM0578EN


The controller records an event when this inhibition is activated:

• EVT.1204: inhibition activated


7.7.6 Inhibition for MCB synchronization failure
If the parameter P.9515 allows a short blackout on the loads in case of MCB synchronization
failure, the controller must open MGCB to close MCB without synchronization: to force the
opening of MGCB, it uses an “inhibition to supply the loads”.
7.7.7 s
If parameter P.9503 configures the MGCB circuit breaker as “powered by the generators”, if
there are no voltages un the generators bus and there are no GCB closed (detected by the
CAN bus), the controller must open MGCB: to force its opening, it uses an “inhibition to supply
the loads”.
7.7.8
If the controller is in TEST mode, and the “TEST without load” has been selected, the controller
must open MGCB: to force its opening, it uses an “inhibition to supply the loads”.
7.7.9 Signalling
The controller makes the statuses of the single "inhibition to supply the load" available, for
AND/OR logics, through the following internal statuses:

• ST.088: from contact.

• ST.089: it’s not possible to work in island mode and mains failure.

• ST.090: for commands from the serial port.

• ST.091: for GCB not opened.

• ST.092: for MCB synchronization failure.

• ST.093: for “no supplying generators”.

• ST.094: for “TEST without load”.

MC200 Technical Manual EAAM0578EN 139


7.8
The controller has four channels for the measurement of the currents (three main channels
and one auxiliary). The operator can specify the electrical lines they are connected to:

• P.0124: it selects the electrical lines to which the three main channels are connected.

• P.0130: it selects the electrical line to which the auxiliary channel is connected.

Both parameters support the following values:

• 0: on the electrical lines of the generators (MGCB).

• 1: on the electrical lines of the loads.

• 2: on the electrical lines of the mains (MCB).

The controller can perform power measurements, using all four channels. For the auxiliary
channel, the controller assumes that it is connected to the line L1 of the source selected by
the parameter P.0130; if such source is three-phases, the controller multiplies the calculated
powers by 3, assuming the loads are correctly shared among the electrical lines. If it is not,
the operator can correct the calculations using parameter P.0132:

total kW = L1 kW * 3 * P.0132.

Depending on what configured by means parameters P.0124 and P.0130, the controller
assigns the calculated powers to the mains, to the loads or to the generators (MGCB).
7.8.1 Power measurements on the generators
The controller calculates (from the data received through the CAN bus link) the total active
and reactive powers supplied by the generators. Then, it calculates the power factor and the
load type from these powers. This information is shown on page M.01 under the icon of the
GCB circuit breaker (if closed).
7.8.2 Power measurements on the mains
The controller can acquire the active power measurement of the mains in different ways,
evaluated in that order:

• From an analogue input configured with the function AIF.2303 (“Power on the mains”).

• By the three main current measurement channels, if P.0124 is set to 2.

• By the auxiliary current measurement channel, if P.0130 is set to 2.

The controller can acquire the reactive power measurement of the mains in different ways,
evaluated in that order:

• By the three main current measurement channels, if P.0124 is set to 2.

• By the auxiliary current measurement channel, if P.0130 is set to 2.

The controller can acquire the power factor and the load type measurement of the mains in
different ways, evaluated in that order:

• Measured by the controller using the three main current measurement channels, if
P.0124 is set to 2.

• Calculates from the active and reactive power on the mains (if both available).

This information is shown on page M.01 under the icon of the MCB circuit breaker (if closed).
7.8.3 Power measurements on MGCB
The controller can acquire the active and reactive power measurements on the MGCB in
different ways, evaluated in that order:

140 MC200 Technical Manual EAAM0578EN


• By the three main current measurement channels, if P.0124 is set to 0. In this case,
the controller also measures the power factor and the load type.

• By the auxiliary current measurement channel, if P.0130 is set to 2. In this case the
controller calculates the power factor and the load type from the active and reactive
power on the MGCB (if both available).

This information is shown on page M.01 under the icon of the MGCB circuit breaker (if closed).
7.8.4 Power measurements on the loads
The controller can acquire the active and reactive power measurements on the loads in
different ways, evaluated in that order:

• By the three main current measurement channels, if P.0124 is set to 1. In this case,
the controller also measures the power factor and the load type.

• By the auxiliary current measurement channel, if P.0130 is set to 1. In this case the
controller calculates the power factor and the load type from the active and reactive
power on the MGCB (if both available).

This information is shown on page M.01 near the icon of the loads.
7.8.5 Calculated powers
The controller can so manage up to four power measurements (mains, loads, MGCB and
generators) but it can measure only two of them (one more is calculated from the data received
from the CAN bus link). So, the forth one must be calculated from the others.

If the controller cannot acquire the powers on the MGCB, it can “copy” them from the powers
supplied by the generators, if MGCB is closed and no other MCxxx controller has its own
MGCB closed (thus, all the power supplied by the generators is flowing through this MGCB).

If the controller cannot acquire the powers on the loads, it can get them in the following ways:

• If MCB is opened and MGCB is closed: the powers on the loads is the same as the
power on the MGCB.

• If MCB is closed and MGCB is opened: the powers on the loads is the same as the
power on the mains.

• If MCB is closed and MGCB is closed: if the powers on the mains and on the MGCB
are both available, the controller can calculate the power on the loads as their sum. It
can then calculate the power factor and the load type from the calculated active and
reactive power.

MC200 Technical Manual EAAM0578EN 141


7.9
The controller can manage both MCB and MGCB circuit breakers. Anyway, it accepts that
these circuit breakers could be controlled by external logics (steadily or temporarily).

MGCB circuit breaker is optional for all kinds of plant:

• If it exists, the related lamp shows its status.

• If it does not exist, the controller considers it existent, externally managed and always
closed. In this case, the related lamp is always switched on.

MCB circuit breaker is never optional.

• For “island” only plants (“MPM”) it is not managed. The related lamp is always
switched off.

• For all other plant types, MCB always exists, and the related lamp shows its status. If
it is configured as not existing, the controller signals a wrong configuration by the
warning 237 and it considers it existent, externally managed and always opened. In
this case, the related lamp is always switched off.

Both circuit breakers can be managed by the controller or by external devices. If they are
managed by external devices, their statuses must be connected to MC200 (otherwise, it will
signal again a wrong configuration by the warning 273).

Through the P.0854 parameter it is possible to configure the way MC200 must manage the
MGCB circuit breaker:

• 0: not managed.

• 0: the circuit breaker is managed by the controller, that cannot use synchronization to
close it.

• 1: the circuit breaker is managed by the controller, that can use synchronization to
close it

• 2: the circuit breaker is controlled by an external device, and the controller cannot use
synchronization to close it.

• 3: the circuit breaker is controlled by an external device, and the controller can use
synchronization to close it.

At the same way, through P.0855 parameter, it is possible to configure the way the controller
must manage MCB circuit breaker (see previous description).
7.9.1 Digital outputs
7.9.1.1 Circuit breakers commands
Four different commands can be used for the management of the MCB breakers:

 DOF.2001 - “Minimum voltage coil for MCB (NC)”. This function can be used to supply
the minimum voltage coil (if any) of the circuit breaker. The controller enables this
output when it wants to open the breaker, and disables it when it wants to close the
breaker: the real closing command will be activated with at least 0.5 seconds after the
disabling of this output. A contact which is normally closed should therefore be used,
so that when the controller is not supplied, the minimum voltage coil is enabled and
the breaker can be closed. If the breaker should open without any explicit command
from the controller (for example for the trip of its protections), it is possible to configure
a delay between the breaker opening and the activation of this command (P.0246, for
default set to zero): this function is useful for some small size breakers to acquire the
TRIP contact (which resets immediately as soon as the breaker is commanded in
opening).

142 MC200 Technical Manual EAAM0578EN


 DOF.2002 - “Coil for opening of MCB”. The controller enables this output when it wants
to open the circuit breaker: the output goes back in standby once the circuit breaker
feedback indicates that it is open (or when the opening time-out expires).

 DOF.2003 - “Coil for closing MCB”. The controller enables this output when it wants
to close the circuit breaker (ensuring that the function DOF.2001 has been active for
at least 0.5 seconds): the output goes back in standby once the circuit breaker
indicates that it is closed (or when the closing time-out expires, or the synchronism
condition no longer exists).

 DOF.2004 - “Stable opening command for MCB”. The controller activates this output
when it wants to open the circuit breaker: the output remains activated even with the
circuit breaker is opened. The controller disables this output when it wants to close
the breaker (by assuring that the possible DOF.2001 function is active for at least 0.5
seconds): the output remains disabled even when the circuit breaker is closed.
Therefore, for the MCB breaker to close with the controller unpowered, the normally
closed contact must be used. Use this function with contactors, not with the motorized
breakers.

Four different commands can be used for the management of the MGCB breakers:

 DOF.2031 - “Minimum voltage coil for MGCB”. This function can be used to supply
the minimum voltage coil (if any) of the circuit breaker. The controller enables this
output when it wants to close the breaker, and disables it when it wants to open the
breaker: the real closing command will be activated with at least 0.5 seconds after the
enabling of this output. If the breaker should open without any explicit command from
the controller (for example for the trip of its protections), it is possible to configure a
delay between the breaker opening and the activation of this command (P.0247, for
default set to zero): this function is useful for some small size breakers to acquire the
TRIP contact (which resets immediately as soon as the breaker is commanded in
opening).

 DOF.2032 - “Coil for opening of MGCB”. The controller enables this output when it
wants to open the circuit breaker: the output goes back in standby once the circuit
breaker feedback indicates that it is open (or when the opening time-out expires).

 DOF.2033 - “Coil for closing MGCB”. The controller enables this output when it wants
to close the circuit breaker (ensuring that the function DOF.2031 has been active for
at least 0.5 seconds): the output goes back in standby once the circuit breaker
indicates that it is closed (or when the closing time-out expires, or the synchronism
condition no longer exists).

 DOF.2034 - “Stable closing command for MGCB”. The controller activates this output
when it wants to close the circuit breaker (by assuring that the possible DOF.2031
function is active for at least 0.5 seconds): the output remains activated even with the
circuit breaker is closed. The controller disables this output when it wants to open the
breaker: the output remains disabled even when the circuit breaker is opened. Use
this function with contactors, not with the motorized breakers.

Of course, it is not necessary to use all possible commands for the circuit breakers. It is
important that the controller, if it must command the circuit breaker, manages both the opening
and the closing command. The possibilities are:

• Only the stable command.

• The stable command and the minimum voltage coil.

• The closure command and the minimum voltage coil.

• The closure command and the opening command.

MC200 Technical Manual EAAM0578EN 143


• The closure command, the opening command and the minimum voltage coil.

It is possible to use different commands for the two circuit breakers.

The following table shows the statuses of all commands, during each phases of the circuit
breaker management. It is referred to MGCB circuit breaker: remember that “minimum voltage
coil” and “static command” works in the opposite way for MCB circuit breaker.
Circuit Minimum Opening Closing Stable
breaker voltage coil coil command
coil
Opened
Closing X X X
Closed X X
Opening X

As in the previous table, the controller activates different commands when the circuit breaker
is “open” or “closed”. If the circuit breaker status changes, the controller should change some
of its commands to follow the new status. This is dangerous because the circuit breaker status
is acquired by a digital input, and so possible problems could bring to faulty statuses:

• If circuit breaker status changes from “closed” to “opened”, the controller can follow
the new status without big problems. In fact, even if the “opened” status is a “wrong”
information (due to disturbs, broken wires and so on), the only problem is an
unnecessary opening of the circuit breaker: in AUTO mode, the controller will re-close
the circuit breaker if required by plant status. In this case, the controller does not
activate anomalies.

• If the controller detects the status of closed circuit breaker while it is open, the actions
depend on the fact that there is an output for “stable command”.

o “Stable command” not used. To adjust the commands, the controller would
only have to activate the “minimum voltage coil”. This operation alone does
not generate the circuit breaker closing, so it can be carried out without
problems. In this case, the controller does not activate anomalies.

o “Stable command” used. To adjust the commands, the controller would


have to activate the “stable command”. This operation generates the circuit
breaker closing (without any control), so it cannot be carried out. In this case,
the controller activates an anomaly.
7.9.1.1.1 Minimum delays between commands

The controller grants that the following delays between commands are respected:

• Half second between minimum voltage coil and any closure commands.

• The delay configured by parameter P.0220 (“Contactors holding time”) between an


opening command and the next closure command (if set to zero 0.5 seconds are
used).

• The delay configured by parameter P.0220 (“Contactors holding time”) between a


closure command and the next opening command (if set to zero 0.2 seconds are
used).

• The delay configured by parameter P.0219 (“Contactors swap delay”) between the
opening command of one circuit breaker and the closure command of the other circuit
breaker.

Moreover, opening and closure commands are never set together.


7.9.1.2 External consents
Two functions are provided, related to the MCB circuit breaker management:

144 MC200 Technical Manual EAAM0578EN


 DOF.3081 - “Ready to close MCB”. This function allows an external logic to prevent
or to delay the circuit breaker closure. This output is activated before the closing of
the circuit breaker only if one input is configured as “MCB closure allowed” (DIF.1035):
it is deactivated (and so the circuit breaker will be closed) when that input is active or
after the delay configured for the input elapses.

 DOF.3082 - “Ready to open MCB”. This function is used only when the opening of the
circuit breaker will result in a blackout on the loads, and allows an external logic to
prevent or to delay the circuit breaker opening. This output is activated before the
opening of the circuit breaker only if one input is configured as “MCB opening allowed”
(DIF.1036): it is deactivated (and so the circuit breaker will be opened) when that input
is active or after the delay configured for the input elapses.

Two functions are provided, related to the MGCB circuit breaker management:

 DOF.3083 - “Ready to close MGCB”. This function allows an external logic to prevent
or to delay the circuit breaker closure. This output is activated before the closing of
the circuit breaker only if one input is configured as “MGCB closure allowed”
(DIF.1005): it is deactivated (and so the circuit breaker will be closed) when that input
is active or after the delay configured for the input elapses.

 DOF.3084 - “Ready to open MGCB”. This function is used only when the opening of
the circuit breaker will result in a blackout on the loads, and allows an external logic
to prevent or to delay the circuit breaker opening. This output is activated before the
opening of the circuit breaker only if one input is configured as “MGCB opening
allowed” (DIF.1006): it is deactivated (and so the circuit breaker will be opened) when
that input is active or after the delay configured for the input elapses.
7.9.1.3 Request for synchronization
If a circuit breaker is managed by the controller, but an external synchronizer should be used,
it is possible to use some digital outputs of the controller to enable the external synchronizer.
The following functions are available for the configuration of the digital outputs:

 DOF.3091 - “Synchronization for MGCB”.

 DOF.3092 - “Synchronization for MCB”.

 DOF.3093 - “Synchronization in progress”.

On the contrary, if a circuit breaker is externally managed but the internal synchronizer should
be used, the following function can be used to signal the “synchronized” status:

 DOF.3094 - “Synchronized”.

For more details see document [8].


7.9.2 Digital inputs
The digital inputs of the controller can be used for various purposes, within the scope of the
management of the circuit breakers.
7.9.2.1 Acquiring breakers status
Three functions are available to get the feedback of the circuit breakers:

• DIF.3002 - “Status of MCB circuit breaker”. Use this function to get the feedback of
the circuit breaker (active input when the circuit breaker is closed).

• DIF.3003 - “Status of MGCB circuit breaker”. Use this function to get the feedback of
the circuit breaker (active input when the circuit breaker is closed).

It isn’t always mandatory to connect the feedback of the circuit breakers to the controller: it
depends on the type of plant (see the document [8]). If the controller gets the feedbacks, it will
use them to:

 Issuing failed opening or failed closing warnings (MCB and MGCB).

MC200 Technical Manual EAAM0578EN 145


 For its own operating sequence.

 It is also used to detect the status of the circuit breakers when they are commanded
by external devices.

 To show the status of the circuit breakers on the front panel LEDs.

The delay associated to the input (P.2002 for input 1 or equivalent parameter for the other
inputs) is used as maximum time for opening or closing the breaker.

In theory, for those plants that don’t do the parallel with the mains, the controller might also
operate without these feedbacks. In this case, the controller considers that the breaker is
closed as soon as the closure command is activated; it considers that it is open as soon as
the opening command is activated. As a matter of facts, it is always better to connect the
feedback.

Through parameter P.0847 it is possible to define if the MCB breaker is supplied by mains
voltage. In this case, with mains off, MCB opens, but the controller does not activate the
relative warning of MCB closure failed. In the same way, through parameter P.9503 it is
possible to define if the MGCB breaker is supplied by the generators bus voltage. In this case,
with generators bus off, MGCB opens, but the controller does not activate the relative warning
of MGCB closure failed
7.9.2.2 Temporary override of the management of the circuit breakers
It is possible to use some digital inputs to communicate to the controller that the management
of one or both circuit breakers is temporarily managed by an external device (even if P.0854
and P.0855 parameters indicate that the circuit breaker is controlled by the controller):

 DIF.1003 - “MGCB controlled externally”.

 DIF.1033 - “MCB controlled externally”.

Until the input is active, the board never tries either to open or close the circuit breaker: but, if
the circuit breaker is externally opened/closed, the controller will adapt its own commands to
the new status of the circuit breaker, in order not to cause any unwanted opening/closure when
the input is deactivated.
7.9.2.3 Manual controls for the circuit breakers
It is possible to connect to the digital inputs of the controller some external buttons to
open/close the circuit breakers. The controller will use these inputs (only in MAN) exactly in
the same way as the MCB and MGCB buttons present on the panel.

 DIF.1001 - “Request for MGCB closure”.

 DIF.1002 - “Request for MGCB opening”.

 DIF.1031 - “Request for MCB closure”.

 DIF.1032 - “Request for MCB opening”.


7.9.2.4 Request for synchronization
If a circuit breaker isn’t managed by the controller, it will be anyway possible to take advantage
of the internal synchronization function (see document [8]). When the external logic wants to
close a circuit breaker and synchronization is required, it should ask the controller for the
synchronization, by activating a digital input. The following functions are available to configure
the digital input:

 DIF.1004 - “Synchronization request for MGCB”.

 DIF.1034 - “Synchronization request for MCB”.

For more details refer to the document [8].

146 MC200 Technical Manual EAAM0578EN


7.9.2.5 External consents
The controller, before opening/closing the circuit breakers, can accept consents from outside.
The following functions are available to configure the digital input:

 DIF.1005 - “MGCB closure allowed”.

 DIF.1006 - “MGCB opening allowed”.

 DIF.1035 - “MCB closure allowed”.

 DIF.1036 - “MCB opening allowed”.

See the description in Errore. L'origine riferimento non è stata trovata..

7.9.3 Management logic


7.9.3.1 MCB command logic
The controller always allows the opening of MCB.

The closing of MCB is possible only if all the following conditions are checked:

• MCB is not forced to open as “interface device”.

• Only in AUTO, if MCB is configured as “supplied by mains” (P.0847 = 0).

o The mains must be live and in tolerance per the AMF thresholds.

o If the plant requires the parallel with the mains and it is configured as interface
device, the mains must be in tolerance per the parallel thresholds.

The parameter P.0248 allows to select the timing for MCB opening, when the controller is in
AUTO mode (for the emergency service to the mains):

• P.0248=0.

o Plant without MGCB: following a mains failure, the controller will open MCB
when at least one generator is “ready to supply”.

o Plant with MGCB: following a mains failure, the controller will open MCB just
before closing MGCB.

• P.0248=1: following a mains failure, the controller will open MCB as soon as the
“mains failure delay” is elapsed.

If the MCB closing is possible, the controller can carry it out in three ways, as described below.

With synchronization. This happens if all the following conditions are checked:

• Only in MAN and AUTO.

• If the plant requires the parallel with the mains (P.0802 >= 7).

• If the synchronization on MCB is enabled (P.0855 = 2 or 4).

• If the mains is in tolerance per the parallel thresholds. Note: in MAN, it is enough that the
mains is in tolerance; in AUTO, it must be in the time configured in P.0903.

• If there is voltage on the loads bus.

• If MGCB exists, it must be closed.

• If there is voltage on the generators bus.

MC200 Technical Manual EAAM0578EN 147


• If an external synchronizer has not been configured, at least a GCB circuit breaker must
be closed.

• If MCB is externally managed (P.0855 = 4), the digital input that requires the
synchronization must be active (function DIF.1034).

• If the gensets are not in parallel with the mains by another MCxxx (MC200 does not allow
the simultaneous parallel with two mains).

Directly without synchronization. This happens if all the following conditions are checked:

• If it is not possible to close the circuit breaker with the synchronization (see above).

• If MCB is managed by the controller.

• If there is no voltage on the loads bus.

• If MGCB does not exist, or if it exists but it is closed:

o If there is no voltage on the generators bus.

o If there are no gensets with GCB closed.

o If the plant requires the parallel with the mains (otherwise, the controller does
not allow the simultaneous closing of MCB and MGCB).

With changeover (opening MGCB). This happens if all the following conditions are checked:

• If it is not possible to close the circuit breaker with the synchronization (see above).

• If it is not possible to close the circuit breaker without synchronization (see above).

• If MCB is managed by the controller (P.0855 = 1 or 2).

• If MGCB exists (P.0854 <> 0):

o MGCB must be managed by the controller (P.0854 = 1 or 2).

• If MGCB does not exist (P.0854 <> 0):

o If P.9506 is set to one, all controllers with GCB closed must be “managed by
MCxxx”, so that MC200 can force the opening of GCB.

o There shouldn’t be gensets with GCB closed, managed by controllers that are
not connected to CAN bus PMCB.

If none of the three ways can be used, MCB cannot be closed.


7.9.3.2 MGCB command logic
The controller always allows the opening of MGCB.

The closing of MGCB is possible only if all the following conditions are checked:

• MGCB is not forced to open as “interface device”.

• Only in AUTO, if MGCB is configured as “supplied by gensets” (P.9503 = 0).

o There must be voltage on the generators bus.

o At least one GCB must be closed.

If the MGCB closing is possible, the controller can carry it out in three ways, as described
below.

With synchronization. This happens if all the following conditions are checked:

148 MC200 Technical Manual EAAM0578EN


• Only in MAN and AUTO.

• If the plant requires the parallel with the mains (P.0802 >= 7).

• If the synchronization on MGCB is enabled (P.0854=2 or 4).

• If there is voltage on the loads bus.

• If MCB is closed.

• If the mains is in tolerance according to the mains parallel thresholds.

• If there is voltage on the generators bus.

• If an external synchronizer has not been configured, at least one GCB circuit breaker must
be closed.

• If MGCB is externally managed (P.0855 = 4), the digital input that requires the
synchronization must be active (function DIF.1004).

• If the warning W271 is not active (“MGCB synchronization failure”).

• If the gensets are not in parallel with the mains by another MCxxx (MC200 does not allow
the simultaneous parallel with two mains).

Directly without synchronization. This happens if all the following conditions are checked:

• If it is not possible to close the circuit breaker with the synchronization (see above).

• If MGCB is managed by the controller.

• If there is no voltage on the loads bus, or on the generators bus and there are no
gensets with GCB closed.

• If MCB is closed:

o If there is no voltage on the loads bus.

o If there are no gensets with GCB closed.

o If the plant requires the parallel with the mains (otherwise, the controller does
not allow the simultaneous closing of MCB and MGCB).

o The protections for the parallel with the mains must not be active.

• If MCB is open:

o If the plant allows to supply the loads in island mode (P.0802 <> 8).

With changeover (opening MGCB). This happens if all the following conditions are checked:

• If it is not possible to close the circuit breaker with the synchronization (see above).

• If it is not possible to close the circuit breaker without synchronization (see above).

• If MGCB is managed by the controller (P.0854 = 1 or 2).

• If MCB is managed by the controller (P.0855 = 1 or 2).

• If the plant allows to supply the loads in island mode (P.0802 <> 8).

If none of the three ways can be used, MGCB cannot be closed.


7.9.3.3 Management logic in OFF/RESET mode
If there is a MGCB circuit breaker managed by the controller, and it is closed, the controller
commands its opening.

MC200 Technical Manual EAAM0578EN 149


If there is a MCB circuit breaker managed by the controller, and it is open, in OFF/RESET
mode it can be closed without synchronization only: the controller waits for the gensets to be
disconnected from the loads and then it commands its closing. To have MCB closed, all the
following conditions must be checked:

• There must be no voltage on the bus of both loads and mains; otherwise, it’s
impossible to close without synchronization.

• If there is a MGCB circuit breaker and it is commanded by the controller, it must be


open.

• If there is not a MGCB circuit breaker, or it is closed but it is externally managed, all
GCB circuit breakers must be open.

The controller removes the request of start for the gensets: this usually causes the immediate
opening of the GCB circuit breakers. This opening may happen after the phase of fast unload
of the power if the following condition are met:

• MGCB does not exist, or it is closed (externally managed or in case of opening failure):
the load is still connected to the gensets.

• There are some gensets “not managed by MCxxx” with GCB closed, which must stay
in parallel.
7.9.3.4 Management logic in MAN mode
The command of all circuit breakers is possible only if there are no active alarms and unloads
(otherwise, the controller acts as in OFF/RESET).

If the MCB circuit breaker exists and it is managed by the controller, it is possible to request
its manual opening and closing in different ways:

• By using the MCB button on the controller panel. This command works as a toggle: it
commands the opening if the circuit breaker is closed, it commands the closing if the
circuit breaker is open.

• By using the digital inputs of the controller (to connect external buttons that allow the
manual opening/closing of the circuit breakers). It is possible to use the following
functions to configure the digital inputs:

o DIF.1032 - “Request for MCB opening”.

o DIF.1031 - “Request for MCB closing”.

These commands act on shifting the input from “not active” to “active”, not on the
steady “active” state. It is possible to use both opening/closing commands or just the
closing one. If only the closing command is used, it acts as “toggle”: it commands the
breaker opening if it is closed, or its closing if it is open.

• By Modbus commands. The commands can be protected by a password (P.0004)


which must be entered before any command, and they can be deactivated through a
digital input (DIF.2706). To send the command it is necessary to write in sequence
(within 5 seconds):

o HOLDING REGISTER 101: write the password configured with the parameter
P.0004.

o HOLDING REGISTER 102: write the value:

▪ “41”: it requires the immediate opening of MCB (without the loads


transfer from the mains to the generators).

▪ “42”: it requires the opening of MCB (with the loads transfer from the
mains to the generators).

150 MC200 Technical Manual EAAM0578EN


▪ “43”: it requires the closure of MCB (with or without the
synchronization).

• By using a proper “SMS” (see document [3]).

If the MGCB circuit breaker exists and it is managed by the controller, it is possible to request
its manual opening and closing in different ways:

• By using the MGCB button on the controller panel. This command works as a toggle:
it commands the opening if the circuit breaker is closed, it commands the closing if the
circuit breaker is open.

• By using the digital inputs of the controller (to connect external buttons that allow the
manual opening/closing of the circuit breakers). It is possible to use the following
functions to configure the digital inputs:

o DIF.1002 - “Request for MGCB opening”.

o DIF.1001 - “Request for MCGB closing”.

These commands act on shifting the input from “not active” to “active”, not on the
steady “active” state. It is possible to use both opening/closing commands or just the
closing one. If only the closing command is used, it acts as “toggle”: it commands the
breaker opening if it is closed, or its closing if it is open.

• By Modbus commands. The commands can be protected by a password (P.0004)


which must be entered before any command, and they can be deactivated through a
digital input (DIF.2706). To send the command it is necessary to write in sequence
(within 5 seconds):

o HOLDING REGISTER 101: write the password configured with the parameter
P.0004.

o HOLDING REGISTER 102: write the value:

▪ “31”: it requires the immediate opening of MGCB (without the loads


transfer from the generators to the mains).

▪ “32”: it requires the opening of MGCB (with the loads transfer from
the generators to the mains).

▪ “33”: it requires the closure of MGCB (with or without the


synchronization).

• By using a proper “SMS” (see document [3]).

Note: if MGCB does not exist, or if it is managed by the controller, the manual
commands described previously works on the GCB circuit breakers of the controllers
that are “managed by MCxxx” (if enabled by bit 3 of parameter P.0495).

It is always possible to command the manual opening of the circuit breakers.

If the MCB opening is required while the gensets are in parallel with the mains, the controller
tries to transfer the loads from the mains to the gensets, then opens MCB. If, during the loads
transfer, the opening of the circuit breaker is required again (button or active digital input for a
second), the MCB circuit breaker is immediately open.

If the MGCB opening is required while the gensets are in parallel with the mains, the controller
tries to transfer the loads from the gensets to the mains (by setting 0 kW as power setpoint),
then opens MGCB. If, during the unload ramp, the opening of the circuit breaker is required
again (button or active digital input for a second), the MGCB circuit breaker is immediately
open.

MC200 Technical Manual EAAM0578EN 151


Normally, it is always possible to command the manual closing of the circuit breakers. As
described in the previous paragraphs, the controller checks if it can close the circuit breaker
with the synchronization or directly without synchronization. If it cannot close it in these ways,
check if it can close it with the switch: so, it is possible that the controller opens MCB to be
able to close MGCB or vice versa (this behaviour must be enabled by the bit 2 of the parameter
P.0495).

The controller activates some warnings for opening or closing failure of the circuit breakers if
it acquires their feedback. In case of MCB circuit breaker opening failure, the controller
activates the warning W023. In case of MGCB circuit breaker opening failure, the controller
activates the warning W024. If the controller commands the closing of MCB without
synchronization, and MCB does not close, the controller activates the warning W013. If the
controller commands the closing of MGCB without synchronization, and MGCB does not close,
the controller activates the warning W013.
7.9.3.5 Management logic in AUTO mode
In automatic modes, the controller autonomously decides if it should start/stop the gensets
and open/close the circuit breakers, according to the type of plant, the mains voltage and the
status of the digital inputs.

In the automatic management of the circuit breakers (not in manual), even if the circuit
breakers are managed by the controller, it is possible to limit the opening/closing externally. In
details:

MCB circuit breaker

• If there is a digital input configured with the function DIF.1036 (“MCB opening
allowed”), normally the controller waits for this digital input to be activated before
opening the circuit breaker.

The controller ignores the approval if at least one of the following conditions is
checked:

o The controller is in OFF/RESET mode.

o The controller is in MAN mode.

o The MGCB circuit breaker does not exist, or it exists but it is closed.

o The MCB circuit breaker must be opened immediately after the trip of the
protections for the parallel with the mains.

In the other cases, the procedure followed by the controller is:

o It activates a possible configured output with the function DOF.3082 (“Ready


to open MCB”), to signal the external logic its need to open the circuit breaker.

o It waits that the configured digital input with the function DIF.1036 becomes
active; this wait lasts for the time configured for the input (P.2001 for input 1).
If the time configured is 0, the wait lasts forever.

o It commands the opening of the circuit breaker.

• If there is a digital input configured with the function DIF.1035 (“MCB closing allowed”),
normally the controller waits for this digital input to be activated before closing the
circuit breaker.

The controller ignores the approval if at least one of the following conditions is
checked:

o The controller is in OFF/RESET mode.

o The controller is in MAN mode.

152 MC200 Technical Manual EAAM0578EN


o There are active alarms or unloads.

o The intervention of the gensets is not required and MCB has not been opened
by the controller (so MC200 should close it again).

In the other cases, the procedure followed by the controller is:

o It activates a possible configured output with the function DOF.3081 (“Ready


to close MCB”), to signal the external logic its need to close the circuit breaker.

o It waits that the configured digital input with the function DIF.1035 becomes
active; this wait lasts for the time configured for the input (P.2001 for input 1).
If the time configured is 0, the wait lasts forever.

o It commands the closing of the circuit breaker (with or without


synchronization).

MGCB circuit breaker

• If there is a digital input configured with the function DIF.1006 (“MGCB opening
allowed”), normally the controller waits for this digital input to be activated before
opening the circuit breaker.

The controller ignores the approval if at least one of the following conditions is
checked:

o The controller is in OFF/RESET mode.

o The controller is in MAN mode.

o The MGCB circuit breaker must be opened immediately after the trip of the
protections for the parallel with the mains.

o There are active alarms or unloads.

o The intervention of the gensets is not required and MGCB has not been closed
by the controller (so MC200 should open it again).

In the other cases, the procedure followed by the controller is:

o It activates a possible configured output with the function DOF.3084 (“Ready


to open MGCB”), to signal the external logic its need to open the circuit
breaker.

o It waits that the configured digital input with the function DIF.1006 becomes
active; this wait lasts for the time configured for the input (P.2001 for input 1).
If the time configured is 0, the wait lasts forever.

o It commands the opening of the circuit breaker.

• If there is a digital input configured with the function DIF.1005 (“MGCB closing
allowed”), normally the controller waits for this digital input to be activated before
closing the circuit breaker.

The controller ignores the approval if at least one of the following conditions is
checked:

o The controller is in OFF/RESET mode.

o The controller is in MAN mode.

In the other cases, the procedure followed by the controller is:

o It activates a possible configured output with the function DOF.3083 (“Ready


to close MGCB”), to signal the external logic its need to close the circuit
breaker.

MC200 Technical Manual EAAM0578EN 153


o It waits that the configured digital input with the function DIF.1005 becomes
active; this wait lasts for the time configured for the input (P.2001 for input 1).
If the time configured is 0, the wait lasts forever.

o It commands the closing of the circuit breaker (with or without


synchronization).

Notes MCB

If this circuit breaker exists and is managed by the controller, it is normally kept closed. The
controller opens it only in some cases, depending on plant configuration:

• Parallel to mains. MCB is opened only if the mains fails and if MCB is configured as
interface device. Additionally, it can be opened if the “transfer to gensets” mode is
selected after the loads are entirely moved to the gensets.

• Stand-by supply. MCB is opened before the MGCB closing (or GCB closing in case
MGCB does not exist), to manage the load switch between mains and gensets. In the
same way, MCB is closed after MGCB has been opened (or GCB if MGCB does not
exist); if configured as “synchronizable”, the controller will try to close it with
synchronization, before opening MGCB.

Notes MGCB

If this circuit breaker exists and it is managed by the controller, the controller closes it (if
required) with different time, depending on conditions and plant configuration.

• Parallel to mains. Normally the controller closes MGCB (without synchronization)


before generator’s GCB. This is the best solution, because it avoids multiple
synchronization on each genset. This cannot be done if:

o For any reason, at least one GCB is already closed when the controller must
close MGCB.

o MGCB is supplied by the gensets bus (P.9503=0).

o The operator has selected to close GCB before MGCB by parameter P.9513.

o If MGCB cannot be closed without synchronization, the controller waits that at


least one GCB is closed, and then closed MGCB with synchronization.

Pay attention to wrong configurations: if MGCB is configured as “not


synchronized” and “supplied by generators bus”, the controller will never be able
to close it in parallel with grid (it will be necessary to open MCB, close MGCB
without synchronization and then close MCB with synchronization).

• Stand-by supply. The controller closes MGCB (without synchronization) after the
gensets GCB are closed. Parameter P.0806 allows configuring the timings for MGCB
closure:

• By setting it to 0, the controller closes MGCB after the first circuit breaker GCB
has been closed (“immediate supply”).

• By setting it to 30000, the controller waits the closing of GCB of all the available
gensets “managed by MC200”, then it closes MGCB (“end parallel supply”). In this
case, the nominal power of generators is not checked.

• By setting it to an intermediate value, the controller waits that the nominal power
of all gensets with GCB closed is greater than the set value, and then closes
MGCB. Note: if all GCB are closed, the available power is lower than the threshold,
the controller activates a warning (W008) and then closes MGCB.

• It is also possible to use a digital input configured with the function DIF.2181
(“Immediate supply”), to force the MGCB closing after the first GCB, whatever is
the value set in parameter P.0806.

154 MC200 Technical Manual EAAM0578EN


7.9.4 Events and signalling
The controller will record any variation of the command and of the status of the circuit breakers
in the event archive, if it is enabled respectively through the bits 4 and 5 of P.0441 parameter:

 EVT.1030: MGCB close command

 EVT.1031: MGCB open command

 EVT.1032: MGCB closed.

 EVT.1033: MGCB open.

 EVT.1035: MCB close command

 EVT.1036: MCB open command

 EVT.1037: MCB closed.

 EVT.1038: MCB open.


The controller makes commands and statuses of the circuit breakers available, for AND/OR
logics, through the following internal statuses:

 ST.065 - "MCB status"

 ST.066 - "MGCB status"

 ST.068 - “MGCB closure command (stable)”.

 ST.069 - “MCB closure command (stable)”.

 ST.070 - “MGCB minimum voltage coil”.

 ST.071 - "MGCB opening pulse”.

 ST.072 - "MGCB closure pulse”.

 ST.073 - “MCB minimum voltage coil”.

 ST.074 - "MCB opening pulse”.

 ST.075 - "MCB closure pulse”.

MC200 Technical Manual EAAM0578EN 155


7.10
The controller, for its operating sequences, must know if there are gensets that have their GCB
closed. Usually, the controller acquires this information via CAN bus PMCB. In case there are
gensets that are not connected to the CAN bus link, it is possible to use a digital input
configured with the function DIF.3004 (“Status of GCB of other gensets”): if this input is active,
the controller considers there is at least one genset with GCB closed.

7.11
The controller does not implement any regulations on active power. No PI regulators are
provided for active power: the controller selects the power setpoint for generators, and the
power regulation task is performed by each genset controller.

The controller can adjust the active power setpoint for generators through the CAN bus link.
This setpoint is used by the genset controllers only when generators are in parallel with mains.
When they are in “island mode”, the genset controllers automatically manage load sharing
(without MC200) between available generators, as a percentage of their nominal power.

Important note:

• P.9506 = 1: only the controllers “managed by MCxxx” use the power setpoint
transmitted by MC200. The controllers not “managed by MCxxx” use the proper local
setpoint. The controller considers this info when calculating the power setpoint
transmitted to the genset controllers.

• P.9506 = 0: the MC200 controller transmits its power setpoint as “SYSTEM BASE
LOAD”. It is automatically managed by the genset controllers, taking care of the ones
that are working in a different mode.

Important note: if a plant is composed by more MCxxx, the system allows the parallel with
the mains only on one of them. If the circuit breakers would be all managed externally, there
could be more MCxxx managing the parallel with the mains: in this case, the power setpoint
used by the gensets is the one transmitted from the MCxxx controller with minor PMCB
address.

There are three different operating modes for the parallel with the mains, described in the
following.

Important note: whatever is the mode selected on the controller, it corresponds to a power
setpoint for the genset controllers.
7.11.1 BASE LOAD
This term is used to indicate the working mode where the power setpoint for generators is
selected by the operator and it is not influenced by the local loads.

To select this mode, set parameter P.0880 to “1”.

In this mode, the operator selects the power setpoint for the plant using parameter P.0858,
directly as kW. Values up to 30 MW can be selected. The parameter can be modified also in
MAN o AUTO modes, and directly from display page M.01.

Alternatively, it is possible to use a controller analogue input to configure the setpoint. This
input can be connected to a potentiometer, or any external device that should adjust the power
setpoint of the plant.

To use the analogue input, do the following:

• Configure an analogue input with the function AIF.2307 (“Setpoint for system BASE
LOAD”) (parameter P.4001 for analogue input 1).

• Associate a conversion curve to the analogue input, to convert the acquired voltage
to a kW setpoint. For example:

156 MC200 Technical Manual EAAM0578EN


After this configuration, by moving the potentiometer between 0 and 5 Vdc the power setpoint
varies between 0 and 3000 kW (the setpoint is displayed on page M.01 but cannot be modified
from the controller panel). Note: once you have configured an analogue input with the
function AIF.2307, the parameter P.0858 is no more used.
7.11.2 IMPORT/EXPORT
This term indicates the working mode in which the power setpoint configured by the operator
is referred to the interconnection point with the mains and not to the gensets: the setpoint for
the gensets is calculated from the selected setpoint and the current power on mains. It is
mandatory that the controller can measure the power on mains.

To select this mode, set parameter P.0880 to “2”.

Otherwise you can set the parameter P.0880 to “1” (“BASE LOAD”) and use a digital input to
switch the working mode between “BASE LOAD” and “IMPORT/EXPORT”. The input must be
configured with the function DIF.2093 (“Selects the import-export mode”): when the input is
“active” (logical status) the working mode is “IMPORT/EXPORT”, when it is “not active” the
working mode is “BASE LOAD”.

The operator can select the power setpoint on mains by using parameter P.0859, directly as
kW. It allows setting values up to +/-10 MW. A positive value means that the plant should
import power from mains, while a negative value indicates that power should be exported to
mains. A setpoint equal to zero selects no power transfers over mains: generators should
supply only local loads. The parameter can be modified also in MAN o AUTO modes, and
directly from display page M.01.

Alternatively, it is possible to use a controller analogue input to acquire the setpoint. This input
can be connected to a potentiometer, or any external device that must adjust the power
setpoint of the plant. To use the analogue input, do the following:

• Configure an analogue input with the function AIF.2309 (“Setpoint for system
IMPORT/EXPORT”) (parameter P.4001 for analogue input 1).

• Associate a conversion curve to the analogue input, to convert the acquired voltage
to a kW setpoint. For example:

MC200 Technical Manual EAAM0578EN 157


After this configuration, by moving the potentiometer between 0 and 5 Vdc the power setpoint
varies between -2000 kW (exported) and 2000 kW (imported) (the setpoint is displayed on
page M.01 but cannot be modified from the controller panel). Note: once you have
configured an analogue input with the function AIF.2309, the parameter P.0859 is no
more used.

The power setpoint for the gensets depends on the loads connected. So, it may happen that
with few loads, the gensets should supply a very low power. In this case, the engines do not
work well and if the situation does not change for a long time, they can get damaged. With the
parameter P.0904, it is possible to configure a minimum value of power that the controller
should require from gensets when they are in parallel with the mains in IMPORT/EXPORT
mode.
7.11.3 Transfer to generators
This term indicates a temporary mode that consists in configuring the power currently
consumed by the loads as power setpoint for the gensets. Once the gensets reach the setpoint
(so the mains is no more supplying the loads), the controller opens the mains circuit breaker
(MCB) and the loads are supplied by the gensets.

To select this mode, set parameter P.0880 to “3”. Otherwise you can set this parameter to “1”
(“BASE LOAD”) or “2” (“IMPORT/EXPORT”) and use a digital input to switch the working mode
to “Transfer to generators”. This input must be configured with the function DIF.2096 “Transfer
to gensets”: when the input is “active” (logical status) the working mode is “Transfer to
generators”, when it is “not active” the working mode is the previous one.

This working mode is different if the controller acquires the power on mains or not:

• If the controller acquires the power on mains, the power setpoint for the generators is
calculated as in “IMPORT/EXPORT” mode, assuming 0 kW setpoint on mains. When
generators reach the setpoint no power is flowing on the mains: the MCB circuit
breaker can be opened without load transients on generators.

• If the controller does not acquire the power on mains, the operator must set the power
value required by the loads with the parameter P.0858 (or act on the related analogue
input). This setpoint will be transmitted to the gensets. Once generators reach this
setpoint, MCB circuit breaker will be opened: if setpoint is near actual loads, no load
transients will happen on generators.

Note: if generators are not able to reach the setpoint (because too loads are applied) MCB
circuit breaker will never be opened.

This temporary phase ends when the gensets reach the setpoint or after the configured
maximum delay (unless the gensets cannot supply the power required): the duration of the
ramp (P.0879) is considered as maximum delay for this management (anyhow, MCB is open
only if the gensets can take the load). It is also possible to add a delay by means parameter
P.9517: the controller opens MCB only when the power supplied by the generators reached
the setpoint continuously for this delay. The default value for this parameter is zero.

158 MC200 Technical Manual EAAM0578EN


7.11.4 Load and unload ramps
The controller does not manage directly the load ramps, but this function is managed by the
gensets controllers.

When the gensets are supplying in parallel with the mains and the MGCB circuit breaker
should be opened, the controller commands the unloading process to gensets (if no alarms
are activated).

The command consists in setting a power reference to the gensets. This reference is
calculated in different ways for the two following conditions:

• There is another MCxxx with MGCB closed. In this case, the gensets are supplying
the loads of more than one MCxxx simultaneously. So, the controller cannot bring the
gensets power to zero, because it would connect the loads of all MCxxx with MGCB
closed to only one mains transformer, which could be overcharged. The controller can
proceed in two ways:

o The controller measures the power that flows through its own MGCB. In this
case, the controller calculates the power setpoint for the gensets to bring to
zero the power that flows through the MGCB. When the power is close to
zero, the controller opens the MGCB, avoiding load transfers on both gensets
and mains transformers.

o The controller does not measure the power that flows through its own MGCB.
In this case, it simply opens its own MGCB: anyhow, this leads to a load
transfer on both gensets and mains transformers.

• There are no other MCxxx with MGCB closed. In this case, the controller requests to
gensets an active power reference equal to 0%. When the gensets power is close to
zero, the controller opens the MGCB, avoiding load transfers on both gensets and
mains transformers.

Then the generator control devices manage by itself the unload ramp for their generators. The
controller waits for the end of the unloading process and then opens the MCB circuit breaker.
The unloading process is terminated when:

• In case there are other MCxxx with MGCB closed and this MC200 does not measure
the power on the MGCB circuit breaker. In this case, the unload ramp is not carried
out.

• In case there are no gensets with GCB closed, the controller stops the unload ramp.

• If the parallel with the mains is not allowed: the unload ramp can last maximum 0.5
seconds.

• If you have configured a maximum duration for the parallel with the mains (parameter
P.0890): the unload ramp is immediately stopped after the gensets are in parallel as
per the time configured.

• If the power supplied by the gensets “managed by MCxxx” is lower than the threshold
set in P.0878 (the power is calculated as sum of the active powers divided by the sum
of the nominal powers of all gensets supplying). The power supplied by the gensets
not “managed by MCxxx” is ignored. In case the controller measures the power on
MGCB and there are other MCxxx with MGCB closed, the controller checks that the
power on MGCB is lower than P.0878. It is also possible to add a delay by means
parameter P.9517: the controller opens MGCB only when the power supplied by the
generators reached the setpoint continuously for this delay. The default value for this
parameter is zero.

Note: if P.9605 is set to 1, the active power setpoint for the unloading procedure is
managed through the SYSTEM BASE LOAD mode. The genset controllers manage
this setpoint by themselves, taking care of the ones that are working in different
modes; however, the setpoint is probably near to zero and, if there are gensets
working in a different mode, it is possible that the system can’t reach it: this is the

MC200 Technical Manual EAAM0578EN 159


reason for which, to detect the end of the unload, only the generators “managed by
MCxxx” are considered.

• After the time configured with parameter P.0879 is elapsed from the start of the
process (this is only a timeout, normally MGCB is opened early for the reaching of
power setpoint).

The controller does not change the setpoint for the reactive power (see paragraph below)
during the unload ramp. Whatever is the cos(ɸ) required to the controllers, this corresponds in
a null value of reactive power when the active power supplied by a genset tends to zero: so,
the reactive power unload is indirectly managed by the genset controllers.

7.12
The controller does not implement any regulations on reactive power. No PI regulators are
provided for reactive power: the controller selects the reactive power setpoint for generators,
and the voltage and reactive power regulation tasks are performed by each genset controller.

The reactive power setpoint is not expressed as kvar, it is set as a “power factor”, called also
cos(Φ).

The controller can select the cos(Φ) setpoint for generators through the CAN bus link. This
setpoint is used by the genset controllers only when generators are in parallel with mains.
When they are in “island mode”, the genset controllers automatically manage reactive power
sharing (without MC200) between available generators, as a percentage of their nominal
power.

The setpoint sent by MC200 over the CAN bus is the same for all generators: each genset
controller will convert this setpoint to kvar (based on current active power of that generator);
then it will provide voltage control loop to move generator reactive power to the required kvar.

On MC200, operator selects the setpoint for cos(Φ) using parameter P.0860 (“Reference for
system cos(Φ)”). It allows selecting values between “0.7 inductive” and “0.9 capacitive”. The
parameter can be modified also in MAN o AUTO modes, and directly from display page M.01.
To set a capacitive cos(Φ), the formula “2 - cos(Φ)” must be used. For example, to select a
cos(Φ) equal to 0.95c, the real number is 2.00 – 0.95  1.05.

Alternatively, it is possible to use a controller analogue input to configure the setpoint. This
input can be connected to a potentiometer, or to any external device that must adjust the
cos(Φ) setpoint of the plant. To use the analogue input, do the following:

• Configure an analogue input with the function AIF.2405 (“Setpoint for system power
factor”) (parameter P.4001 for analogue input 1).

• Associate a conversion curve to the analogue input, to convert the acquired voltage
to a kW setpoint. For example:

After this configuration, by moving the potentiometer between 0 and 5 Vdc the cos(Φ) setpoint
varies between 0.70 inductive and 0.90 capacitive (the setpoint is displayed on page M.01 but

160 MC200 Technical Manual EAAM0578EN


cannot be modified from the controller panel). Note: once you have configured an analogue
input with the function AIF.2405, the parameter P.0860 is no more used.

Important note:

• P.9506 = 1: only the controllers “managed by MCxxx” use the cos(Φ) setpoint
transmitted by MC200. The controllers not “managed by MCxxx” use the proper local
setpoint.

• P.9506 = 0: MC200 transmits the cos(Φ) setpoint for the SYSTEM BASE LOAD mode.
The genset controllers manage this setpoint by themselves, taking care about the
ones that are working in a different mode. In this way, the total system cos(Φ) will be
the one required by MC200.

MC200 Technical Manual EAAM0578EN 161


7.13
Usually, the controller can start/stop the gensets and eventually force the opening of the GCB
circuit breakers through commands on the CAN bus PMCB line. It is possible to use also some
digital outputs for this purpose. The controller has the following two functions for the
configuration of the digital outputs:

• DOF.1005 (“Request to start”). The controller activates this output each time the
intervention of the gensets is required (both in MAN and AUTO). It deactivates this
output when the intervention of the gensets is no longer required. It is possible to wire
this output on the digital inputs of the gensets controllers to command the start/stop
of the engines.

• DOF.3062 (“Ready to supply”). The controller activates this output to signal that it is
possible to connect the loads to the gensets. The output activates only in AUTO, TEST
and REMOTE START, if there are no “load inhibitions” in the following cases:

o If there is a MGCB circuit breaker:

▪ If MGCB is closed, the output is active.

▪ If MGCB is open, the output is active when the nominal power of the
gensets with GCB closed is enough to supply the loads.

o If there is not a MGCB circuit breaker:

▪ If at least one GCB is closed, the output is active.

▪ if no GCB is closed:

• If there is a MCB circuit breaker but it is externally managed,


and the plant does not consider the parallel with the mains:

o If MCB is closed: the output activates when all


gensets “managed by MCxxx” are started; if there
are no gensets “managed by MCxxx”, the output
activates when at least one genset is started.

o If MCB is open, the output is active when the nominal


power of the gensets with GCB closed is enough to
supply the loads.

• In other cases, the output activates when the nominal power


of the gensets with GCB closed is enough to supply the loads.

Usually, the controller can modify the speed and voltage of the gensets through commands
on the CAN bus PMCB line. It is possible to use also some analogue outputs for this purpose.
The controller has the following functions for the configuration of the analogue outputs:

• AOF.1000 (“Speed regulator”). The controller manages this output for sending speed
commands to the genset controllers. The output can be adjusted by the following
parameters:

o P.0831: if set to zero, the output increases to request an increase of the


speed. If set to 1, the output decreases to request an increase of the speed.

o P.0856: it allows to specify the minimum value for the output (%).

o P.0857: it allows to specify the maximum value for the output (%).

• AOF.1001 (“Speed regulator (with curve)”). The controller manages this output for
sending speed commands to the genset controllers. The output can be adjusted by
means a conversion curve.

162 MC200 Technical Manual EAAM0578EN


• AOF.1002 (“Voltage regulator”). The controller manages this output for sending
voltage commands to the genset controllers. The output can be adjusted by the
following parameters:

o P.0861: if set to zero, the output increases to request an increase of the


voltage. If set to 1, the output decreases to request an increase of the voltage.

o P.0862: it allows to specify the minimum value for the output (%).

o P.0863: it allows to specify the maximum value for the output (%).

• AOF.1003 (“Voltage regulator (with curve)”). The controller manages this output for
sending voltage commands to the genset controllers. The output can be adjusted by
means a conversion curve.

MC200 Technical Manual EAAM0578EN 163


7.14
This paragraph describes all the plant types managed by MC200, selectable by parameter
P.0802. The controller manages only plant types with more than one genset; anyhow, it is
possible to work (with this plants) even with only one genset. The following notes are valid for
all types of plant:

• See paragraph 7 for the list of the conditions, so that a genset controller is considered
“managed by MCxxx” (remember that, in any case, the genset controllers should be
at least in AUTO to be “managed by MCxxx”).

• The gensets “managed by MCxxx” can be started only if MC200 is not in OFF/RESET
and if there are no blocks and/or unloads.

• In MAN, the operator can start/stop the gensets “managed by MCxxx” with the buttons
START and STOP. To start/stop the gensets not “managed by MCxxx”, use the
related controllers.

• See paragraph 7.9 for a list of the minimum conditions that allow the closing of the
MCB circuit breaker.

• See paragraph 7.9 for a list of the minimum conditions that allow the closing of the
MGCB circuit breaker.

• See paragraph 7.9 for the description of the manual commands for the circuit
breakers.

• See paragraph 7.9 for the anomalies of the circuit breakers opening/closing failure.

• See paragraph 7 for the anomalies of the circuit breakers synchronization failure.

The plants are divided according to the necessary conditions for the automatic intervention of
the gensets. From this point of view, there are three types of plant:

• “Island mode” production plant. The term “island mode” indicates the situation in which
one or more gensets supply a load, without being in parallel with the mains. The
automatic intervention of the plant is always required, independently from the mains
status. The parallel with the mains is not allowed.

• “Emergency” plant. The automatic intervention of the gensets is required in case of


anomalies of the mains. The parallel with the mains is allowed, even if it is not the
normal operation for this type of plant.

• Plant for the production “in parallel with the mains”. The automatic intervention of the
plant is required only if the mains is live and in tolerance. The supply in “island mode”
is not allowed.

The following table shows a recap of all types of plant, according to what has been said:

Production Parallel
Production Supply in
in parallel with the
P.0802 in island AMF island mode
with the mains
mode allowed
mains allowed
MPM X No Yes
MSB X No Yes
MSB + MSTP X X Yes Yes
MPtM X Yes No
MPtM + MSB X X Yes Yes

The acronyms indicated in the first column will be described in detail below. It is important to
understand well the difference between the plants “MSB + MSTP” e “MPtM + MSB”: they

164 MC200 Technical Manual EAAM0578EN


allow, in fact, both the supply in “island mode” and the supply in “parallel with the mains”. The
difference consists in the mode in which the automatic intervention of the genset is required:

• The plant “MSB + MSTP” is an “emergency” plant and so the gensets will be started
(automatically) only in case of mains anomaly. To put the gensets in parallel with the
mains, you need to force the start when the mains is live (through the REMOTE
START or TEST mode).

• The plant “MPtM + MSB” is both a “supply in island” and production “in parallel with
the mains” plant. Automatically, the gensets are started when the mains is in tolerance
and when it is out of tolerance or off: in the first case, the plant will be “in parallel with
the mains”, in the second case, it will be “in island mode”.

The different types of plant will be described in detail below. Gensets automatic start inhibition
7.14.1 MPM (Multiple Prime Mover)
This type of plant requires the production in “island mode”. They are the typical gensets of the
building sites, where the operator decides when the gensets must supply or not. The parallel
with the mains is not allowed.

Parallel functions Available

Synchronization for MGCB. Not available.

Synchronization for MCB. Not available.

Protections for the parallel with the mains. Not available.

Management of the active power in parallel with the Not available.


mains.

Management of the power factor in parallel with the Not available.


mains.

Function “transfer to gensets”. Not available.

In this type of plant, the controller ignores the mains and MCB status. It is not possible to close
the MGCB circuit breaker with synchronization: this means that the controller does not allow
the MGCB closing if, in case of wrong wiring, it detects the simultaneous presence of voltage
on both sides of the circuit breaker.

Automatic sequence

The automatic intervention of the genset is required in the following conditions:

• In AUTO: if no “inhibition to start” is active.

• In TEST and REMOTE START: always, ignoring the “inhibition to start”.

When there are gensets ready to supply, the controller must decide if closing the MGCB circuit
breaker or not (if it exists). The circuit breaker should be always closed, except for the following
cases:

• There are active alarms or unloads.

• The stop of the gensets is required.

• There is an active “inhibition to supply the load”.

If the opening of MGCB is not required, the controller must decide in which moment to close
the circuit breaker: see the description of the parameter P.0806 at paragraph 7.9.3.5.

The logic of normal operation in AUTO (if the controller manages the MGCB circuit
breaker) will be:

MC200 Technical Manual EAAM0578EN 165


1. MGCB open, gensets “managed by MCxxx” stopped. If the automatic intervention
of the plant is required, the procedure skips to point 2.

2. MGCB open, gensets “managed by MCxxx” starting. If there are no gensets


“managed by MCxxx”, the procedure skips to point 3. Otherwise, the controller waits
that at least one genset “managed by MCxxx” is ready to supply and then the
procedure skips to point 3. It is possible to set a maximum duration for the gensets
starting with the parameter P.9511. If this parameter is different from zero, and the
starting phase lasts more than the value configured, the controller activates the
warning W022. During the waiting, in case of alarms or unloads, or if the automatic
intervention is no longer required, the procedure skips to point 8.

3. MGCB opened. If the gensets must be stopped (alarms or unloads, or if the automatic
intervention is no longer required), the procedure skips to point 8. If there are requests
of “inhibition to supply the load”, the procedure stays at this point. Otherwise, it
continues:

• To point 4, if there is no voltage on loads bus.

• Stay in this point if there is voltage on the loads bus (rare, as MGCB is opened
and MCB does not exist).

4. MGCB open, waiting for gensets. The controller checks if the number of gensets
with GCB closed and their nominal power correspond to what has been configured in
parameter P.0806. If they correspond (or if there are no other genset “managed by
MCxxx” that could close their GCB), the procedure skips to point 5. During the waiting,
in case of alarms or unloads, or if the automatic intervention is no longer required, the
procedure skips to point 8.

5. Closing without synchronization of MGCB (three attempts). In case of closing


failure, the alarm A014 is activated (MGCB not closed) and the procedure skips to
point 8. Otherwise, the procedure continues to point 6.

6. MGCB closed. In case of alarms or deactivations, or if there are requests of “inhibition


to supply the loads”, the procedure skips to point 7. If the automatic intervention of the
genset is no longer required, the procedure skips to point 7.

7. Opening of MGCB (three attempts): if MGCB opens, the procedure skips to point 3.
If MGCB does not open, the alarm A024 is activated (MGCB not closed) and the
procedure skips to point 8.

8. Stopping. The controller removes the start request for the gensets “managed by
MCxxx”. If there are other MCxxx requiring the use of the gensets, the procedure ends
at point 1. Otherwise, the controller waits for the gensets stopping. It is possible to set
a maximum duration for this waiting: if the parameter P.9512 is set to a value different
from zero, the controller waits in this status for the time configured. If the gensets do
not stop within this time, the controller activates a warning W021 and the procedure
ends at point 1. If the automatic intervention of the genset is required again, the
procedure continues from point 2.

The logic of normal operation in AUTO (if the controller does not command the MGCB
circuit breaker) will be:

1. Gensets “managed by MCxxx” stopped. If the automatic intervention of the plant is


required, the procedure skips to point 2.

2. Gensets “managed by MCxxx” starting. If there are no gensets “managed by


MCxxx”, the procedure skips to point 3. Otherwise, the controller waits that at least
one genset “managed by MCxxx” is ready to supply and then the procedure skips to
point 3. It is possible to set a maximum duration for the gensets starting with the
parameter P.9511. If this parameter is different from zero, and the starting phase lasts
more than the value configured, the controller activates the warning W022. During the
waiting, in case of alarms or unloads, or if the automatic intervention is no longer
required, the procedure skips to point 4.

166 MC200 Technical Manual EAAM0578EN


3. Supplying. In case of alarms or deactivations, or if the automatic intervention of the
gensets is no longer required, the procedure skips to point 4. If there are requests for
“inhibition to supply the loads”, the procedure stays in this status: if MGCB is closed,
the requests of inhibition are transformed in opening commands of the GCB circuit
breakers of the controllers “managed by MCxxx”.

4. Stopping. The controller removes the start request for the gensets “managed by
MCxxx”. If there are other MCxxx requiring the use of the gensets, the procedure ends
at point 1. Otherwise, the controller waits for the gensets stopping. It is possible to set
a maximum duration for this waiting: if the parameter P.9512 is set to a value different
from zero, the controller waits in this status for the time configured. If the gensets do
not stop within this time, the controller activates a warning W021 and the procedure
ends at point 1. If the automatic intervention of the genset is required again, the
procedure continues from point 2.
7.14.2 MSB (Multiple Stand By)
This type of plant requires one or more gensets to carry out the emergency to mains service.
The controller starts the gensets if the mains is “out of tolerance” with respect to the time
configured; it stops them if the mains is “in tolerance”. If configured by means parameter
P.9514, the controller can require the intervention of the gensets even in case of closing failure
of the MCB circuit breaker. The parallel with the mains is not allowed.
Parallel functions Available

Synchronization of MGCB. Not available

Synchronization for MCB. Not available

Protections for the parallel with the mains. Not available

Management of the active power in parallel with the Not available


mains.

Management of the power factor in parallel with the Not available


mains.

Function “transfer to gensets”. Not available

It is not possible to close MCB and MGCB with synchronization: this means that the controller
does not allow the circuit breaker closing if the other is closed. Moreover, it does not allow the
closing of any circuit breaker if, for a wrong wiring, it detects the simultaneous presence of
voltage on both sides of the circuit breaker.

Automatic sequence

The automatic intervention of the gensets is required in the following conditions:

• In AUTO: if no “inhibition to start” is active and if:

o The mains is “out of tolerance”.

o The mains is live but the controller is not able to close the MCB circuit breaker
(if configured by means parameter P.9514).

• In TEST and REMOTE START: always, ignoring the “inhibition to start”.

When there are gensets ready to supply, the controller must decide if let the gensets supply
the load. This should be always done except when:

• There are active alarms or unloads.

• The stop of the gensets is required.

• There is an active “inhibition to supply the loads”.

MC200 Technical Manual EAAM0578EN 167


If the supply of the load from the gensets is required, the controller must decide when to carry
out the switch. The controller never closes MGCB before GCB. Parameter P.0806 allows
configuring when to close the circuit breaker (see 7.9.3.5).

The logic of normal operation in AUTO (if MC200 manages both MCB and MGCB circuit
breakers) will be:

1. MCB closed, MGCB open, gensets “managed by MCxxx” stopped. If the


automatic intervention of the plant is required, the procedure skips to point 2.

2. MCB closed, MGCB open, gensets “managed by MCxxx” starting. If there are no
gensets “managed by MCxxx”, the procedure skips to point 3. Otherwise, the
controller waits that at least one genset “managed by MCxxx” is ready to supply and
then the procedure skips to point 3. It is possible to set a maximum duration for the
gensets starting with the parameter P.9511. If this parameter is different from zero,
and the starting phase lasts more than the value configured, the controller activates
the warning W022. During the waiting, in case of alarms or unloads, or if the automatic
intervention is no longer required, the procedure skips to point 12.

3. MCB closed, MGCB open. If the gensets must be stopped (alarms or unloads, or if
the automatic intervention is no longer required), the procedure skips to point 12. If
there are requests of “inhibition to supply the loads”, the procedure stays at this point.
Otherwise, the procedure continues to point 4.

4. Gensets wait. The controller checks if the number of gensets with GCB closed and
their nominal power correspond to what has been configured in parameter P.0806. If
they correspond (or if there are no other genset “managed by MCxxx” that could close
their GCB), the procedure skips to point 5. If the gensets must be stopped (alarms or
unloads, or if the automatic intervention is no longer required), the procedure skips to
point 12.

5. MCB opening (three attempts) In case of opening failure, the alarm A023 is activated
(MCB not opened) and the procedure skips to point 12. Otherwise, the procedure
continues to point 6.

6. MCB open, MGCB closed. The controller waits for the time configured with
parameter P.0219, then it continues to point 7. If the gensets must be stopped (alarms
or unloads, or if the automatic intervention is no longer required), the procedure skips
to point 11. If there is an inhibition to supply the loads, the procedure skips to point
11.

7. MGCB closing (three attempts). In case of closing failure, the alarm A014 is activated
(MGCB not closed) and the procedure skips to point 11. Otherwise, the procedure
continues to point 8.

8. MCB open, MGCB closed. In case of alarms or deactivations, or if there are no


requests of “inhibition to supply the loads”, the procedure skips to point 9. If the
automatic intervention of the genset is no longer required, the procedure skips to point
9.

9. Opening of MGCB (three attempts): if MGCB opens, the procedure skips to point 10.
If MGCB does not open, the alarm A024 is activated (MGCB not opened) and the
procedure skips to point 12.

10. MCB open, MGCB closed. The controller waits for the time configured with
parameter P.0219, then it continues to point 11.

11. MCB closing (three attempts) In case of closing failure, the alarm A013 is activated
(MCB not closed) and the procedure skips to point 12. Otherwise, the procedure
continues to point 3.

12. Stopping. The controller removes the start request for the gensets “managed by
MCxxx”. If there are other MCxxx requiring the use of the gensets, the procedure ends
at point 1. Otherwise, the controller waits for the gensets stopping. It is possible to set
a maximum duration for this waiting: if the parameter P.9512 is set to a value different

168 MC200 Technical Manual EAAM0578EN


from zero, the controller waits in this status for the time configured. If the gensets do
not stop within this time, the controller activates a warning W021 and the procedure
ends at point 1. If the automatic intervention of the genset is required again, the
procedure continues from point 2.

The logic of normal operation in AUTO (if MC200 manages the MCB circuit breaker only)
will be:

1. MCB closed, gensets “managed by MCxxx” stopped. If the automatic intervention


of the plant is required, the procedure skips to point 2.

2. MCB closed, gensets “managed by MCxxx” starting. If there are no gensets


“managed by MCxxx”, the procedure skips to point 3. Otherwise, the controller waits
that at least one genset “managed by MCxxx” is ready to supply and then the
procedure skips to point 3. It is possible to set a maximum duration for the gensets
starting with the parameter P.9511. If this parameter is different from zero, and the
starting phase lasts more than the value configured, the controller activates the
warning W022. During the waiting, in case of alarms or unloads, or if the automatic
intervention is no longer required, the procedure skips to point 8.

3. MCB closed. If the gensets must be stopped (alarms or unloads, or if the automatic
intervention is no longer required), the procedure skips to point 8. If there are requests
of “inhibition to supply the loads”, the procedure stays at this point. If MGCB is closed,
the procedure continues to point 5 to open the MCB circuit breaker immediately
(otherwise, the controllers cannot close GCB because the plant does not require the
parallel with the mains). Otherwise, the procedure continues to point 4.

4. Gensets waiting (MGCB open). The controller checks if the number of gensets with
GCB closed and their nominal power correspond to what has been configured in
parameter P.0806. If they correspond (or if there are no other genset “managed by
MCxxx” that could close their GCB), the procedure skips to point 5. If the external logic
closes MGCB, the procedure immediately skips to point 5. If the gensets must be
stopped (alarms or unloads, or if the automatic intervention is no longer required), the
procedure skips to point 8.

5. MCB opening (three attempts) In case of opening failure, the alarm A023 is activated
(MCB not opened) and the procedure skips to point 8. Otherwise, the procedure
continues to point 6.

6. MCB open. In case of alarms or deactivations, or if the automatic intervention of the


genset is no longer required, the procedure skips to point 7. If there are requests for
“inhibition to supply the loads” and MGCB is closed, the requests of inhibition are
transformed in opening commands of the GCB circuit breakers of the controllers
“managed by MCxxx”.

7. MCB closing (three attempts) In case of closing failure, the alarm A012 is activated
(MCB not closed) and the procedure skips to point 8. Otherwise, the procedure
continues to point 3.

8. Stopping. The controller removes the start request for the gensets “managed by
MCxxx”. If there are other MCxxx requiring the use of the gensets, the procedure ends
at point 1. Otherwise, the controller waits for the gensets stopping. It is possible to set
a maximum duration for this waiting: if the parameter P.9512 is set to a value different
from zero, the controller waits in this status for the time configured. If the gensets do
not stop within this time, the controller activates a warning W021 and the procedure
ends at point 1. If the automatic intervention of the genset is required again, the
procedure continues from point 2.

Note: the described sequences are valid if the parameter P.0248 is set to zero. If it is set to 1,
the MCB circuit breaker will be opened as soon as the mains become steadily “out of
thresholds”, to protect the loads against wrong voltages/frequency.

MC200 Technical Manual EAAM0578EN 169


7.14.3 MSB+MSTP (Multiple Stand By + Multiple Short Time Parallel)
This type of plant is like the previous one: it requires one or more gensets to carry out the
emergency service to mains. The controller starts the gensets if the mains is “out of tolerance”
with respect to the time configured; it stops them if the mains is “in tolerance”. If configured by
means parameter P.9514, the controller can require the intervention of the gensets even in
case of closing failure of the MCB circuit breaker.

With respect to the MSB plant, the controller allows the parallel with the mains.

Usually, the parallel with the mains is temporary (P.0880=0): it is used to avoid a black-out on
the loads during their switch from gensets to mains (when it is back) or from mains to gensets
(in case of forced intervention in TEST or REMOTE START). In this case, the maximum
duration for the parallel with the mains is 1 second: anyhow, it can be configured with the
parameter P.0890. Please read the description of the warning W207 that is related with this
parameter.

This type of plant allows also the parallel with the mains (if P.0880 is different from zero).
Usually, you use this function to test the gensets (TEST) without disconnecting the loads from
the mains. In this case, there is no limit in the parallel duration.

Function Available

Synchronization of MGCB. Available.

Synchronization for MCB. Available.

Protections for the parallel with the mains. Available.

Management of the active power in parallel with the Available.


mains.

Management of the power factor in parallel with the Available.


mains.

Function “transfer to gensets”. Available.

Automatic sequence

The automatic intervention of the gensets is required in the following conditions:

• In AUTO: if no “inhibition to start” is active and if:

o The mains is “out of tolerance”.

o The mains is live but the controller is not able to close the MCB circuit breaker
(if configured by means parameter P.9514).

• In TEST and REMOTE START: always, ignoring the “inhibition to start”.

When there are gensets ready to supply, the controller must decide if let the gensets supply
the load. This should be always done except when:

• There are active alarms or unloads.

• The stop of the gensets is required.

• There is an active “inhibition to supply the loads”.

If the supply of the loads from the gensets is required, the controller must decide when to carry
out the switch. The controller never closes MGCB before GCB. Parameter P.0806 allows
configuring when to close the circuit breaker (see 7.9.3.5).

The logic of normal operation in AUTO (if MC200 manages both circuit breakers) will be:

170 MC200 Technical Manual EAAM0578EN


1. MCB closed, MGCB open, gensets “managed by MCxxx” stopped. If the
automatic intervention of the plant is required, the procedure skips to point 2.

2. MCB closed, MGCB open, gensets “managed by MCxxx” starting. If there are no
gensets “managed by MCxxx”, the procedure skips to point 3. Otherwise, the
controller waits that at least one genset “managed by MCxxx” is ready to supply and
then the procedure skips to point 3. It is possible to set a maximum duration for the
gensets starting with the parameter P.9511. If this parameter is different from zero,
and the starting phase lasts more than the value configured, the controller activates
the warning W022. During the waiting, in case of alarms or unloads, or if the automatic
intervention is no longer required, the procedure skips to point 17.

3. MCB closed, MGCB open. If the gensets must be stopped (alarms or unloads, or if
the automatic intervention is no longer required), the procedure skips to point 17. If
there are requests of “inhibition to supply the loads”, the procedure waits in this point.
Otherwise, it continues:

• To point 12 if it is possible to close MGCB with the synchronization and the


parallel with the mains is allowed (P.0880 > 0).

• To point 4 in other cases.

4. MCB closed, MGCB open, genset waiting. The controller checks if the number of
gensets with GCB closed and their nominal power correspond to what has been
configured in parameter P.0806. If they correspond (or if there are no other genset
“managed by MCxxx” that could close their GCB), the procedure skips to point 5 and
it is not possible to close MGCB with synchronization; otherwise, to point 12. If the
gensets must be stopped (alarms or unloads, or if the automatic intervention is no
longer required), the procedure skips to point 17. If there are inhibitions, the procedure
skips to point 3.

5. MCB opening, MGCB open (three attempts). In case of opening failure, the alarm
A023 is activated (MCB not opened) and the procedure skips to point 17. Otherwise,
the procedure continues to point 6.

6. MCB open, MGCB closed. If the gensets must be stopped (alarms or unloads, or if
the automatic intervention is no longer required), the procedure skips to point 10. If
there is an inhibition to supply the loads, the procedure skips to point 10. Otherwise,
the controller waits for the time configured with parameter P.0219, then it continues to
point 7.

7. MGCB closing without synchronization (three attempts). In case of closing failure,


the alarm A014 is activated (MGCB not closed) and the procedure skips to point 10.
Otherwise, the procedure continues to point 8.

8. MCB open, MGCB closed. If there are alarms or unloads, requests of inhibition to
supply the loads or the automatic intervention of the gensets is no longer required, the
procedure continues:

• To point 9 if it is not possible to close MCB with synchronization.

• To point 11 if it is not possible to close MCB with synchronization.

9. Opening of MGCB, MCB open (three attempts): if MGCB opens, the procedure skips
to point 6. If MGCB does not open, the alarm A024 is activated (MGCB not opened)
and the procedure skips to point 17.

10. MCB closing without synchronization (three attempts) In case of closing failure,
the alarm A013 is activated (MCB not closed) and the procedure skips to point 17.
Otherwise, the procedure continues to point 3.

11. MCB closing with synchronization. This phase lasts maximum P.0853 seconds. If
during this time MCB closes, the procedure skips to point 13. Otherwise, the controller
activates the warning W272 (“synchronization failure on MCB”): the controller will not

MC200 Technical Manual EAAM0578EN 171


allow the synchronization for the MCB closing if the operator does not “acknowledge”
this warning. The procedure goes back to point 8.

12. MGCB closing with synchronization This phase lasts maximum P.0852 seconds. If
during this time MGCB closes, the procedure skips to point 13. Otherwise, the
controller activates the warning W271 (“synchronization failure on MGCB”): the
controller will not allow the synchronization for the MGCB closing if the operator does
not “acknowledge” this warning. The procedure goes back to point 3.

13. MCB closed, MGCB closed If the gensets must be stopped for an alarm, the
procedure skips to point 16. If some unloads are activated, the automatic intervention
is no longer required, or some requests of “inhibition to supply the loads” are activated,
the procedure continues to point 15. If the parallel with the mains is not allowed (or
the maximum time allowed for the parallel with the mains expires), the procedure
continues to point 14. If the “transfer to gensets” mode is active, when the gensets
reach the power setpoint configured by MC200, the procedure continues to point 14.

14. MCB opening, MGCB closed (three attempts). In case of opening failure, the alarm
A023 is activated (MCB not opened) and the procedure skips to point 17. Otherwise,
the procedure continues to point 8.

15. MCB closed, MGCB closed, power unload If the parallel with the mains is not
allowed (or the maximum time allowed for the parallel with the mains expires), the
procedure continues to point 16. During this phase, the controller establishes a power
setpoint equal to 0 kW for the gensets. Then, it controls the active power supplied by
the gensets “managed by MCxxx”: when it goes under the threshold P.0878, the
procedure continues to point 16. In any case, the maximum duration of this phase can
be configured with the parameter P.0879: when the time is up, whatever the power
supplied by the gensets is, the procedure continues to point 16. If there are not alarms
or unloads, the requests of “inhibition to power load” are not activated and the
automatic intervention is required, the procedure continues to point 13.

Note: if P.9605 is set to 1, the active power setpoint for the unloading procedure is
managed through the SYSTEM BASE LOAD mode. The genset controllers manage
this setpoint by themselves, taking care of the ones that are working in different
modes; however, the setpoint is probably near to zero and, if there are gensets
working in a different mode, it is possible that the system can’t reach it: this is the
reason for which, to detect the end of the unload, only the generators “managed by
MCxxx” are considered.

16. Opening of MGCB, MCB closed (three attempts): if MGCB opens, the procedure
skips to point 3. If MGCB does not open, the alarm A024 is activated (MGCB not
opened) and the procedure skips to point 17.

17. Stopping. The controller removes the start request for the gensets “managed by
MCxxx”. If there are other MCxxx requiring the use of the gensets, the procedure ends
at point 1. Otherwise, the controller waits for the gensets stopping. It is possible to set
a maximum duration for this waiting: if the parameter P.9512 is set to a value different
from zero, the controller waits in this status for the time configured. If the gensets do
not stop within this time, the controller activates a warning W021 and the procedure
ends at point 1. If the automatic intervention of the genset is required again, the
procedure continues from point 2.

The logic of automatic normal operation (if MC200 manages MCB only) will be:

1. MCB closed, gensets “managed by MCxxx” stopped. If the automatic intervention


of the plant is required, the procedure skips to point 2.

2. MCB closed, gensets “managed by MCxxx” starting. If there are no gensets


“managed by MCxxx”, the procedure skips to point 3. Otherwise, the controller waits
that at least one genset “managed by MCxxx” is ready to supply and then the
procedure skips to point 3. It is possible to set a maximum duration for the gensets
starting with the parameter P.9511. If this parameter is different from zero, and the
starting phase lasts more than the value configured, the controller activates the

172 MC200 Technical Manual EAAM0578EN


warning W022. During the waiting, in case of alarms or unloads, or if the automatic
intervention is no longer required, the procedure skips to point 9.

3. MCB closed. If the gensets must be stopped (alarms or unloads, or if the automatic
intervention is no longer required), the procedure skips to point 9. If there are requests
for “inhibition to supply the loads”, the procedure stays in this status: if MGCB is
closed, the requests of inhibition are transformed in opening commands of the GCB
circuit breakers of the controllers “managed by MCxxx”; the gensets will download the
power before opening GCB.

MGCB opened. The controller checks if the number of gensets with GCB closed and
their nominal power correspond to what has been configured in parameter P.0806. If
they correspond (or if there are no other genset “managed by MCxxx” that could close
their GCB):

• If there is a digital input to require the synchronization of MGCB, the procedure


stays in this status waiting for the request. When the request is active, the
procedure skips to point 8.

• If there is no digital input (and MGCB cannot be closed with synchronization),


the procedure continues to point 4.

MGCB closed: the controller checks:

• There are gensets with GCB closed. If the parallel with the mains is not
allowed (or the maximum time allowed for the parallel with the mains expires),
the procedure continues to point 4. If the “transfer to gensets” mode is active,
when the gensets reach the power setpoint configured by MC200, the
procedure continues to point 4.

• There are no gensets with GCB closed. If there are gensets ready to supply,
but the mains is out of tolerance (so, the gensets cannot close their GCB with
synchronization), the procedure continues to point 4.

4. MCB opening (three attempts). In case of opening failure, the alarm A023 is activated
(MCB not opened) and the procedure skips to point 9. Otherwise, the procedure
continues to point 5.

5. MCB open. The actions depend on the MGCB status.

MGCB opened. If there are alarms or unloads, requests of “inhibition to supply the
loads” or the automatic intervention of the genset is no longer required, the procedure
continues to point 6. Otherwise, the procedure stays in this status.

MGCB closed. If there are alarms or unloads, the procedure skips to point 9. If there
are “inhibition to supply the loads”, or the automatic intervention is not required, the
controller continues to point 7 if it is possible to use the synchronization for the closing
of MCB; otherwise, it waits for MGCB or GCB to open.

6. MCB closing without synchronization (three attempts) In case of closing failure,


the alarm A013 is activated (MCB not closed) and the procedure skips to point 9.
Otherwise, the procedure continues to point 3.

7. MCB closing with synchronization This phase lasts maximum P.0853 seconds. If
during this time MCB closes, the procedure skips to point 3. Otherwise, the controller
activates the warning W272 (“synchronization failure on MCB”): the controller will not
allow the synchronization for the MCB closing if the operator does not “acknowledge”
this warning. The procedure goes back to point 5.

8. MGCB closing with synchronization This phase lasts maximum P.0852 seconds. If
during this time MGCB closes, the procedure skips to point 13. Otherwise, the
controller activates the warning W271 (“synchronization failure on MGCB”): the
controller will not allow the synchronization for the MGCB closing if the operator does
not “acknowledge” this warning. The procedure goes back to point 5.

MC200 Technical Manual EAAM0578EN 173


9. Stopping. The controller removes the start request for the gensets “managed by
MCxxx”. If there are other MCxxx requiring the use of the gensets, the procedure ends
at point 1. Otherwise, the controller waits for the gensets stopping. It is possible to set
a maximum duration for this waiting: if the parameter P.9512 is set to a value different
from zero, the controller waits in this status for the time configured. If the gensets do
not stop within this time, the controller activates a warning W021 and the procedure
ends at point 1. If the automatic intervention of the genset is required again, the
procedure continues from point 2.

Note: the described sequences are valid if the parameter P.0248 is set to zero. If it is set to 1,
the MCB circuit breaker will be opened as soon as the mains become steadily “out of
thresholds”, to protect the loads against wrong voltages/frequency.
7.14.4 MPTM (Multiple Parallel to Mains)
This is a plant for the production in parallel with the mains. The controller starts the gensets if
the mains status allows the parallel; it disconnects the gensets from the mains if the protections
of parallel with the mains are activated (see 7.4.2); it stops the gensets if the mains status
does not allow the parallel for P.0899 seconds.

The supply in “island mode” is not allowed: so, if the protections of parallel with the mains are
activated, the controller opens the MGCB circuit breaker anyway (if it exists), whatever is the
interface device selected with parameter P.0900. We suggest to select MGCB as interface
device (P.0900=2).

The parallel with the mains must be continue, so the parameter P.0880 must be set at a value
different from zero.

Parallel functions Available

Synchronization for MGCB. Available.

Synchronization for MCB. Not available.

Protections for the parallel with the mains. Available.

Management of the active power in parallel with the Available.


mains.

Management of the power factor in parallel with the Available.


mains.

Function “transfer to gensets”. Not available.

Automatic sequence

The automatic intervention of the gensets is required in the following conditions:

• In AUTO: if there is no “inhibition to start” and the mains status allows the parallel with
the mains.

• In TEST and REMOTE START: always, ignoring the “inhibition to start” and the mains
status.

When there are gensets ready to supply, the controller must decide if connect the gensets to
the mains. This should be always done except when:

• There are active alarms or unloads.

• The stop of the gensets is required.

• There is an active “inhibition to supply the loads”.

The logic of normal operation in automatic mode (if the controller manages both circuit
breakers and if MGCB is the interface device) will be:

174 MC200 Technical Manual EAAM0578EN


1. MCB closed, MGCB open, gensets “managed by MCxxx” stopped. If the
automatic intervention of the plant is required, the procedure skips to point 2.

2. MCB closed, MGCB open, gensets “managed by MCxxx” starting. If there are no
gensets “managed by MCxxx”, the procedure skips to point 3. Otherwise, the
controller waits that at least one genset “managed by MCxxx” is ready to supply and
then the procedure skips to point 3. It is possible to set a maximum duration for the
gensets starting with the parameter P.9511. If this parameter is different from zero,
and the starting phase lasts more than the value configured, the controller activates
the warning W022. During the waiting, in case of alarms or unloads, or if the automatic
intervention is no longer required, the procedure skips to point 9.

3. MCB closed, MGCB open. If the gensets must be stopped (alarms or unloads, or if
the automatic intervention is no longer required), the procedure skips to point 9. If
there are requests of “inhibition to supply the loads”, the procedure waits in this point.
If the mains is out of tolerance, the procedure waits in this point (after P.0899 seconds,
an “inhibition to start” is activated to automatically removes the request of
intervention). Otherwise, it continues:

• To point 4, if you decided to close the MGCB circuit breaker before the GCB
one (by means of the parameter P.9513) and if there are no GCB closed.

• To point 5 if it is not possible to close MGCB with synchronization.

• In the other cases, it stays in this status.

4. MGCB closing without synchronization (three attempts). In case of closing failure,


the alarm A014 is activated (MGCB not closed) and the procedure skips to point 9.
Otherwise, the procedure continues to point 6.

5. MGCB closing with synchronization. This phase lasts maximum P.0852 seconds.
If during this time MGCB closes, the procedure skips to point 6. Otherwise, the
controller activates the warning W271 (“synchronization failure on MGCB”): the
controller will not allow the synchronization for the MGCB closing if the operator does
not “acknowledge” this warning. The procedure goes back to point 3. If during the
waiting the mains is out of tolerance, the procedure goes back to point 3.

6. MCB closed, MGCB closed. If alarms or the protections for the parallel with the mains
are activated, the procedure continues to point 8. If some unloads are activated, the
automatic intervention is no longer required, or some requests of “inhibition to supply
the loads” are activated, the procedure continues to point 7.

7. MCB closed, MGCB closed, power unload. During this phase, the controller selects
a power setpoint equal to 0 kW for the gensets. Then, it controls the active power
supplied by the gensets “managed by MCxxx” (expressed in percentage): when it
goes under the threshold P.0878, the procedure continues to point 8. In any case, the
maximum duration of this phase can be configured with the parameter P.0879: when
the time is up, whatever the power supplied by the gensets is, the procedure continues
to point 8. If there are no alarms or unloads, there are no requests of “inhibition to
supply the loads”, the mains is permanently in tolerance and the automatic
intervention is required, the procedure goes back to point 6.

Note: if P.9605 is set to 1, the active power setpoint for the unloading procedure is
managed through the SYSTEM BASE LOAD mode. The genset controllers manage
this setpoint by themselves, taking care of the ones that are working in different
modes; however, the setpoint is probably near to zero and, if there are gensets
working in a different mode, it is possible that the system can’t reach it: this is the
reason for which, to detect the end of the unload, only the generators “managed by
MCxxx” are considered.

8. Opening of MGCB, MCB closed (three attempts): if MGCB opens, the procedure
skips to point 3. If MGCB does not open, the alarm A024 is activated (MGCB not
opened) and the procedure skips to point 9.

MC200 Technical Manual EAAM0578EN 175


9. Stopping. The controller removes the start request for the gensets “managed by
MCxxx”. If there are other MCxxx requiring the use of the gensets, the procedure ends
at point 1. Otherwise, the controller waits for the gensets stopping. It is possible to set
a maximum duration for this waiting: if the parameter P.9512 is set to a value different
from zero, the controller waits in this status for the time configured. If the gensets do
not stop within this time, the controller activates a warning W021 and the procedure
ends at point 1. If the automatic intervention of the genset is required again, the
procedure continues from point 2.
7.14.5 MPTM+MSB (Multiple Parallel to Mains + Multiple Stand By)
In this type of plant, the gensets can supply both in “island” and in “parallel with the mains”
mode. it is like the MSB + MSTP plant. The differences are:

• This plant is not an emergency plant; so, the request of the gensets automatic
intervention is not related to the mains status.

• The parallel with the mains must be allowed (P.0880 > 0).

As the supply in island mode is allowed, it is suggested (but not compulsory) to select MCB
as interface circuit breaker (P.0900 = 2).

Parallel functions Available

Synchronization of MGCB. Available.

Synchronization for MCB. Available.

Protections for the parallel with the mains. Available.

Management of the active power in parallel with the Available.


mains.

Management of the power factor in parallel with the Available.


mains.

Function “transfer to gensets”. Available.

Automatic sequence

The automatic intervention of the gensets is required in the following conditions:

• In AUTO: if no “inhibition to start” is active.

• In TEST and REMOTE START: always, ignoring the “inhibition to start”.

When there are gensets ready to supply, the controller must decide if let the gensets supply
the load. This should be always done except when:

• There are active alarms or unloads.

• The stop of the gensets is required.

• There is an active “inhibition to power load”.

See 7.14.3 for an example of operating logic.

176 MC200 Technical Manual EAAM0578EN


MC200 Technical Manual EAAM0578EN 177
7.15
Note: this description is valid only if the parameter P.9506 is set to one. If it is set to 1,
see the document [8].

“Load function” is the ability of MC200 to automatically start/stop the gensets “managed by
MCxxx” according to the power required by the load or by the setpoint for the parallel with the
mains. The display pages B.07 and B.08 are related to this function.

Note: the gensets controllers have their own “load function”, but it is disabled when
they are managed by MCxxx. If, at a precise moment, the gensets “managed by MCxxx”
are in parallel with the gensets not “managed by MCxxx”, all with the load function
enabled, the two managements may conflict.

Load function, if enabled, works on all plant types:

• In parallel with mains, load function starts the correct number of generators to allow
the system supplying power as requested by the setpoint, starting/stopping additional
generators if setpoint changes. Note: in “BASE LOAD” mode, the setpoint can only be
changed by the operator, while in “IMPORT/EXPORT” mode it changes also if some
loads are added or removed.

• In “island mode”, load function starts the generator as required by current loads,
starting/stopping additional generators on changes.

Load function is enabled only in AUTO and REMOTE START modes. So, in MAN or TEST
modes generators are never stopped due to load (switching from AUTO or REMOTE START
to MAN or TEST the currently started generators are kept running).

In AUTO and REMOTE START modes, load function is normally enabled. It is possible, but
not compulsory, to configure an input with the function DIF.2702 “Enables the load function” If
this input is configured, load function is disabled when the input is “not active” (logical state).
If the input is not configured or if it is “active”, load function is enabled.

If a MGCB circuit breaker exists, load function is disabled if this circuit breaker is opened: in
this situation, no loads are connected to generators and load function could stop them.

The main purposes of the load function are:

• Start the correct number of generators to supply the required power.

• Grant that all generators will be used, not always the same ones.
7.15.1 Starting/stopping generators to meet power requests
MC200 allows configuring two thresholds (%) related to load function:

• P.0826 - “Activation load threshold”.

• P.0828 - “Deactivation load threshold”.

The second threshold must be lower than the first one. They should be set to quite the same
value; the purpose of difference is only to define a hysteresis, to avoid unnecessary start/stop
if active power changes around the thresholds.

MC200 calculates the system total power % dividing the sum of active powers of each
generator by the sum of their nominal powers (both are transmitted by the genset controllers
over the can bus):
n

 ADP x
DPRt  xn1
 MDP
x 1
x

178 MC200 Technical Manual EAAM0578EN


n: number of generators with GCB closed.

ADPx: generator x active power.

MDPx: generator x nominal power.

DPRt: System total power %.

Note: these calculations are carried out on all genset supplying, not only on those
managed by MCxxx.

When the total percentage power (DPRt) is higher than the threshold P.0826 for the time set
with the parameter P.0827 (“Activation load delay”), MC200 must start one new genset
“managed by MCxxx”.

To decide to stop one genset “managed by MCxxx”, MC200 first selects the genset to be
stopped (hereinafter identified as genset y) and then it calculates the percentage power ratio
% the system will supply if the generator would be stopped.
n

 ADP x
DPRtn  n
x 1

 MDP  MDP
x 1
x y

n: number of generators with GCB closed.

y: generator to be stopped.

X: it indicates any genset, except for the genset y.

ADPx: generator x active power.

MDPx: generator x nominal power.

MDPy: generator y nominal power.

DPRtn: system total power ratio % if generator y is stopped.

Note: these calculations are carried out on all genset supplying, not only on those
managed by MCxxx.

When this system total power (DPRtn) is lower than threshold P.0828 for the time set by
parameter P.0829 (“Deactivation load delay”), MC200 stops the generator y.

Parameter P.0820 (“Minimum number of gensets started”) allows selecting the minimum
number of started generators, whatever is the load: MC200 never stops generators (indeed it
may start some of them) if currently started generators are less or equal to the desired number.
Note that minimum value for this parameter is “1”, so at least one generator is always running.
Note: these calculations include all genset supplying, not only on those managed by
MCxxx.

Every time a GCB circuit breaker is opened or closed, MC200 stops checking the power (and
so no genset will be started/stopped) for the time set with the parameter P.0830 (“Initial delay”):
in this way, the system has time for stabilization.

If automatic genset supply is required when all generators are stopped (for example when
mains become “absent” in emergency plants), MC200 always starts all available generators.

Note: by pressing START on MC200, the load function is temporary suspended, by forcing the
start of all available gensets “managed by MCxxx”. Once all generators are supplying, load
function will stop unnecessary ones. This possibility is useful each time the operator knows in
advance that an increase of power is needed: he can start all generators and, when all are
supplying, new loads can be added or the power setpoint can be increased. In this way, you
will have the necessary power whenever you need it, even in AUTO mode and with the load
function enabled.

MC200 Technical Manual EAAM0578EN 179


7.15.2 Selecting generators
The gensets “not managed by MCxxx” are always “excluded” from the load function.

Normally, instead, all generators “managed by MCxxx” are involved in load function. It is
possible to manual exclude some “managed” generators from load function (forcing them
always stopped or always running). This manual operation must be performed on display
pages from B.02 to B.05, which show details about each generator (see description in 6.5.5.2).
Note: the manually excluded generators list is not saved on non-volatile memory. At power on,
all “managed” generators are included in load function.

Note: MC200 can stop all generators involved in load function. This happens when at least
P.0820 “not managed” generators are running, and there is no power request for other
gensets.

The logics described below work only on gensets that, at a given time, are included in the load
function (and so implicitly “managed by MCxxx”).

To ensure that all generators are used (not always the same ones), MC200 assigns a priority
to them:

• Low priority generators are started for last and stopped for first.

• High priority generators are started for first and stopped for last.

• The highest priority generator, at a given time, is called “master”.

MC200 implements three different techniques for assigning priorities to generators, selectable
by parameter P.0822 (“Load function mode”).
7.15.2.1
Set “1” in parameter P.0822 to select this mode.

In this mode, the operator manually selects the “master” genset using parameter P.0823
(“Master genset address”). Other gensets priorities are automatically assigned depending on
addresses. Suppose generators 1 to 8 are present on the plant. Suppose also that generators
3, 4 and 7 are excluded from load function (see previous paragraph). The remaining gensets
are:

1, 2, 5, 6, 8.

If the operator selects the genset “5” as “master”, the priority list will be:

5, 6, 8, 1, 2.

If the operator selects the genset “8” as “master”, the priority list will be:

8, 1, 2, 5, 6.

If the operator selects the genset “1” as “master”, the priority list will be:

1, 2, 5, 6, 8.

The priority list is made by following the order address of gensets (increase order) starting
from the “master” up to the highest one; then starting from the lowest to the one preceding the
“master”.
7.15.2.2
Set “2” in parameter P.0822 to select this mode.

In this mode, the operator can always manually select the “master” genset using parameter
P.0823. At the time configured by the parameter P.0824 (“Master genset change time”),
however, MC200 will select a new “master”. The new “master” selected is the one following
the old “master” in the priority list (obviously among the gensets included in the load function).

180 MC200 Technical Manual EAAM0578EN


Let’s suppose that the priority list set in P.0823 is “5,6,7,1,2”; the new “master” genset will be
the genset “6”.

You can assign priorities to the following gensets as described above.

In this mode, the “rotation” of generators happens once a day.


7.15.2.3
Set “3” in parameter P.0822 to select this mode.

In this mode, the operator can always manually select the “master” genset using parameter
P.0823. After the number of hours configured with parameter P.0825 “Master genset batch
hours”, MC200 will select a new “master”. The new “master” is the one following the old
“master” in the priority list (obviously among the generators included in load function).

Let’s suppose that the priority list set in P.0823 is “5,6,7,1,2”; the new “master” genset will be
the genset “6”.

You can assign priorities to the following gensets as described above.

In this mode, the “rotation” of generators happens every x hour.


7.15.2.4
When a new “master” is selected, a new priority list is built. At this time, it is possible that some
lower priority generators are running, while some high priority generators are stopped. In this
case, MC200 grants that first the high priority generators will be started and loaded, and then
the low priority ones will be stopped. In this way, there will be no problems on power supply.
7.15.2.5 Events
The controller records the event EVT.1291 when the master genset is changed (if configured
with the bit 8 of the parameter P.0441).

MC200 Technical Manual EAAM0578EN 181


7.16
The purpose of “load shedding” function is to manage some digital outputs of MC200, to
connect/disconnect part of loads from the generators, when generators are not able to supply
all loads. Display page B.09 is related to this function.

This function is normally enabled; it is disabled in the following situations:

• If the controller is in MAN or OFF/RESET mode.

• In parallel to mains operations (the eventually extra loads are supplied by mains).

• If a digital input is configured with the function DIF.2721 “Enable load shedding” and
the input is “not active” (logical status). If the input is not configured, or if it is “active”,
the function is enabled.

• If no digital outputs of MC200 are configured for “load shedding”. Four functions are
available for digital outputs configuration:

o DOF.2251 (“Load-shedding 1”).

o DOF.2252 (“Load-shedding 2”).

o DOF.2253 (“Load-shedding 3”).

o DOF.2254 (“Load-shedding 4”).

It is possible to manage up to four groups of loads. Remember that the same function
(DOF.2251 - DOF.2254) can be assigned to more than one output: in this way, a single logical
group of loads can be connected/disconnected from the gensets by using more than one circuit
breaker at the same time.

Outputs are “active” when MC200 needs to disconnect loads from generators, they are “not
active” when loads can be re-connected.

If less than four outputs are used, configure them continuously starting with function
DOF.2251. For example, if you would like to use two outputs, configure them with the functions
DOF.2251 and DOF.2252. If you accidentally use the functions DOF.2251 and DOF.2253,
only the first output configured with the function DOF.2251 will be used. If you use the functions
DOF.2252 and DOF.2253, no output will be associated to the function “load shedding”
(because the function DOF.2251 is missing).

Loads must be assigned to outputs depending on their priority:

• The output configured with the function DOF.2251 should be used for lowest priority
loads: it is the first activated (to disconnect a load) and the last deactivated (to re-
connect a load).

• The output configured with the function DOF.2254 should be used for highest priority
loads: it is the last activated (to disconnect a load) and the first deactivated (to connect
a load).

If “load shedding” function is disabled and some of its digital outputs are configured, these
outputs are “not active” to avoid disconnection of loads.
7.16.1 All loads management
Normally MC200 can connect or disconnect one group of loads at a time. There are some
situations, however, where all loads are connected or disconnected at the same time. Loads
are all disconnected (independently by actual power) when:

• In “island mode”, in the moment the MGCB circuit breaker closes.

• In “island mode”, if the MGCB circuit breaker does not exist or it is closed but no GCB
are closed, in the moment the first GCB circuit breaker closes.

182 MC200 Technical Manual EAAM0578EN


• When passing from “parallel to mains” to “island mode” (at the opening time of MCB).

In the same way, all outputs are deactivated at the same time when:

• Each time loads are separated from generators by any circuit breakers.
7.16.2 Single load management
MC200 provides two thresholds (%) related to “load shedding”:

• P.1181 - “Load disconnect threshold”.

• P.1183 - “Load re-connect threshold”.

The second threshold must be lower than the first one. P.1181 threshold must be set at the
maximum allowed power per generator (%). P.1183 threshold must be calculated depending
on loads connected/disconnected, to avoid that when a load is connected the total power
becomes greater than P.1181 and so load is disconnected again, and so on.

MC200 calculates the system total power % by dividing the sum of active powers supplied by
all the gensets (included the ones not “managed by MCxxx”) by the sum of their nominal
powers (both pieces of information are transmitted by the gensets controllers on CAN bus):
n

 ADP x
DPRt  xn1
 MDP
x 1
x

n: number of generators with GCB closed.

ADP: generator x active power.

MDP: generator x nominal power.

DPRt: System total power %.

When the system total power (DPRt) is higher than the threshold P.1181 for the time set by
parameter P.1182 (“Load disconnect delay”), MC200 disconnects the lowest priority loads (see
above for load priorities).

MC200 can be configured to automatically or manually re-connect the loads. This choice is
available by parameter P.1186 (“Load re-connect mode”):

• 0 – “Automatic”. MC200 checks system power before allowing loads connection. The
system total power (%) must be less than the P.1183 threshold, for the time set by
parameter P.1184 (“Load re-connect delay”).

• 1 – “Manual”. Note: this option needs for a digital input configured for “load connection
command” (see in the following).

Each time a group of loads is connected/disconnected from generators, MC200 stops


monitoring the power (and so no other loads can be connected/disconnected) for the time set
by parameter P.1185 (“Initial delay”), to allow system stabilization.
7.16.3 Manual commands
MC200 allows configuring two digital inputs to be used for “load shedding” manual commands.
Functions to be used for the inputs configuration are:

• DIF.2251 (“Manual disconnection of loads”).

• DIF.2252 (“Manual disconnection of loads”).

Note: these inputs are managed both in MAN and AUTO modes.

MC200 Technical Manual EAAM0578EN 183


Both inputs work on activation and not on the state of the input (the function related to the
input is executed once when input state changes form “not active” to “active” – logical state).

The activation of input configured as DIF.2251 will result in the disconnection of the lowest
priority load (the next activation will disconnect the next load and so on until all loads are
disconnected).

The activation of input configured as DIF.2252 will result in the re-connection of the highest
priority load (the next activation will re-connect the next load and so on until all loads are
connected).
7.16.4
If “not-motorized” circuit breakers are used to connect/disconnect loads, MC200 is not able to
automatically re-connect loads. In this case parameter P.1186 must be set to “0”: when MC200
detects that a group of loads can be re-connected, it automatically deactivates its output and
the circuit breaker is no more forced “open”. The operator can then manually close the circuit
breaker.
7.16.5 Events
If it is configured with the bit 7 of the parameter P.0441, the controller records the following
events related to the unload function:

• EVT.1301: load #1 has been disconnected.

• EVT.1302: load #1 has been connected.

• EVT.1303: load #2 has been disconnected.

• EVT.1304: load #2 has been connected.

• EVT.1305: load #3 has been disconnected.

• EVT.1306: load #3 has been connected.

• EVT.1307: load #4 has been disconnected.

• EVT.1308: load #4 has been connected.

184 MC200 Technical Manual EAAM0578EN


7.17
These names identify the function available in MC200 that allows to monitor the active power
on the loads; when it becomes greater than a threshold, MC200 starts the generators and
connects them to the loads: the loads will be partly or totally supplied by the generators (MCB
opening is also available). When the active power on the loads falls below a second threshold,
MC200 connects the loads to the mains, transfers the loads from the generators to the mains
and stops the generators.

The function must be enabled by means parameter P.1171 (different from zero).

Moreover, it is possible to use a digital input (physical or virtual) to dynamically enable this
function: use the function DIF.2722 for configuring the digital input. If such an input exists, it
must be activated (logic status) to enable the “peak shaving/lopping” function.

The “peak shaving/lopping” function monitors the active power on the loads; the controller,
this, must be able to measure this power (or to calculate it, see 7.8.4). If this measure is not
available, the function is disabled.

Finally, the thresholds P.1172 and P.1174 must be carefully configured (the second one must
be greater than the first one), otherwise the “peak shaving/lopping” function is disabled,

If the function is enabled, MC200 starts the generator if the active power on the loads is higher
than the threshold P.1172 consecutively for the time P.1173. In the same way, MC200 stops
the generator if the active power on the loads is lower than the threshold P.1174 consecutively
for the time P.1175.

The page B.10 shows details for this function (the page is visible only if the function is enabled).
7.17.1 Power management
Once the gensets have been started and the MGCB has been closed, MC200 actions depend
on the “active power management” configuration (P.0880, see 7.11).
7.17.1.1
In this case, MC200 keeps the generators in parallel to the mains. The generators will provide
a fixed power (as set by parameter P.0858 or acquired by means an analogue input configured
as AIF.2307); the remaining part of the loads will be supplied by the mains. Attention: if the
SYSTEM BASE LOAD setpoint should be greater than the loads, the generators will export
active power on the mains.
7.17.1.2
In this case, MC200 keeps the generators in parallel to the mains. A fixed power will be
imported from the mains to supply the loads (setpoint set by parameter P.0859 or acquired by
means an analogue input configured as AIF.2309); this setpoint could also be 0. The remaining
part of the loads will be supplied by the generators. In this case, if the power on the loads
should be less than the setpoint, the generators will supply 0 kW.
7.17.1.3 Transfer to the generators
In this case, MC200 does not keep the generators in parallel to the mains. After closing MGCB,
MC200 will transfer the loads from the mains to the generators (see 7.11.3) and then it will
open MCB circuit breaker.
7.17.2 Events
If it is configured with the bit 6 of the parameter P.0441, the controller records the following
events related to the “peak shaving/lopping” function:

• EVT.1331: “peak shaving/lopping” function requires the starting of the generators.

• EVT.1332: “peak shaving/lopping” function does not require the starting of the
generators.

MC200 Technical Manual EAAM0578EN 185


8
This chapter describes all the anomalies managed by the controller. Some of these act as
protections for the loads or for the generators. There are also signalling of specific events in
the plant management. Before describing them in detail, some definitions are required.
We define three typologies of anomaly:
 Warnings: these anomalies do not require stopping the generators. They point out to
situations that are not dangerous at the moment, but the operator must take some
action because, if ignored, they could degenerate in one of the following categories.

 Unloads: these anomalies require stopping the generators. As they do not create
problems for the loads and the gensets, in parallel operations opening of the power
connection is preferably performed after power unloading. This is performed by
unloading ramp. However, it is not possible to restart the generators until the anomaly
has not been acknowledged.
 Alarms: these anomalies require stopping the generators. They create hazards for
the loads and/or for the generators. For this reason, the controller opens immediately
the MGCB circuit breaker (without discharging the power from the generator), and
stops the generators with standard procedure, i.e. with the cooling cycle. It is not
possible to restart the generators until the anomaly is acknowledged.

An alarm can be activated if no other alarms are already active (there are some exceptions,
which will be listed below). Unloads and warnings can be present.
For activating unloads, alarms or other unloads should not be present. Some other warnings
can be active.
For activating a warning, alarms or unloads should not be present. Some other warnings can
be active.

When an anomaly activates, the controller performs the following:

 It activates the internal horn and, if configured, also the external one. To this purpose,
it is possible to configure an output of the controller with function DOF.3152 (“External
horn”). The output is controlled together with the internal acoustic signalling; the aim
is to use a more powerful signalling or a lamp.

 Prompts the page S.02 ANOMALIES on the multifunction display. This page shows
the fault numeric code and the current language text related to the anomaly. The
numeric code flashes to indicate that the anomaly hasn't been recognized by the
operator yet.

 It activates the flashing of the “ALARM” light, if the anomaly belongs to the warning
category, or it switches that light fixed on in case of unloads and alarms.

 If the anomaly isn't a warning, it disconnects the generators from users or from the
parallel bars (with or without power discharge) and it stops the generators (with or
without cooling cycle).

The following operations can be carried out on an anomaly:

 Silence the horn.

 Acknowledge it: this informs the controller that the operator has acknowledged the
event.

 Reset: this informs the controller that the anomaly is no longer active.
The multifunction display shows the anomaly until the operator “acknowledges” it, even if the
relevant cause is no longer present (sequence ISA2C). The controller automatically resets all
the acknowledged warnings when their cause is no longer active.

186 MC200 Technical Manual EAAM0578EN


8.1
The horn can be silenced in three ways:

 Pressing the ACK/ENTER pushbutton. This operation does not acknowledge the
anomaly, which continues to flash on the display.

 With a digital input configured with DIF.2002 function (“Command for alarm
acknowledgement”). The acoustic signalling is silenced when the input passes from
“not active” to “active”.

 Using a Modbus command. The commands can be protected by a password (P.0004)


which must be entered before any command and can be deactivated through a digital
input (DIF.2706). To send the command it is necessary to write in sequence (within 5
seconds):

▪ HOLDING REGISTER 101: write the password configured with the parameter
P.0004.

▪ HOLDING REGISTER 102: enter the value “51”.


The management of the hooter is anyway linked to the value of P.0491 parameter (“Horn
duration”).

 If set to zero, the horn will be never activated.

 If set to 999, the horn will be activated when a new anomaly arises and deactivated
through the above-described procedure.

 If set to a value between 1 and 998, the horn will be activated when a new anomaly
arises and deactivated through the described procedure above, or when the
configured time has elapsed.

Silencing the horn does not mean to acknowledge the anomaly: it remains, in effect, flashing
on page S.02 ANOMALIES.

8.2
The anomaly (sequence ISA2C) can be identified in three ways:

 By pressing the ACK/ENTER button on the board panel. If you push this key when the
horn is on, it stops the horn: it should be pressed a second time to “recognize” the
anomaly.

 With a digital input configured with DIF.2002 function (“Command for alarm
acknowledgement”). It is acknowledged when the input passes from “not active” to
“active”.

 Using a Modbus command. The commands can be protected by a password (P.0004)


which must be entered before any command and can be deactivated through a digital
input (DIF.2706). To send the command it is necessary to write in sequence (within 5
seconds):

▪ HOLDING REGISTER 101: write the password configured with the parameter
P.0004.

▪ HOLDING REGISTER 102: enter the value “52”. NB: this control also silences
the horn, in case it is active.
When the anomaly has been acknowledged, it stops flashing on page S.02 ANOMALIES. After
being identified, if it is a warning, it is automatically cancelled if the cause is no more present.
Otherwise, if the cause disappears before the anomaly has been acknowledged, it remains on
the display.

MC200 Technical Manual EAAM0578EN 187


8.3
An anomaly can be cancelled only when the cause that activated it is no more present.

The controller automatically resets all the acknowledged warnings when their cause is no
longer active.

On the contrary, to cancel unloads and alarms, it is necessary to follow one of the below
procedures:

 By moving the key switch on OFF/RESET position.

 Using a digital input configured with the feature DIF.2001 - “Command for resetting
alarms”. When the input becomes “active”, the controller carries out a reset of all faults.

 Using a Modbus command. The commands can be protected by a password (P.0004)


which must be entered before any command and can be deactivated through a digital
input (DIF.2706). To send the command it is necessary to write in sequence (within 5
seconds):

▪ HOLDING REGISTER 101: write the password configured with the parameter
P.0004.

▪ HOLDING REGISTER 102: enter the value “53”.

 By using an “SMS” command (see document [3]).

8.4
Each anomaly is registered (with its own code) in the event log.

Some functions are available for the configuration of the digital outputs related to the
anomalies:

 DOF.3151 (“Reset of anomalies”). The controller activates this output for one second when
the internal sequence for the cancellation of anomalies is carried out. With this procedure,
it is also possible to reset externally managed anomalies.

 DOF.3152 (“External horn”). This output is activated and deactivated along with the
internal horn. It can be used to control a more powerful horn and/or a lamp.

 DOF.3154 (“Acknowledge of the anomalies”). The controller activates this output for one
second when the internal sequence of faults acknowledgement is carried out. This
procedure can be used to acknowledge also some possible faults managed by other
devices externally.

 DOF.4001: the output will be activated if at least a warning is active.

 DOF.4002: the output will be activated if at least an unload is active.

 DOF.4004: the output will be activated if at least an alarm is active.

 DOF.4005: the output will be activated if at least an alarm or an unload are active.

 DOF.4035: the output will be activated if at least an anomaly linked to circuit breakers is
active. What follows is the list of anomalies that activate this output:

▪ 013 (“MCB not closed”).

▪ 014 (“GCB not closed”).

▪ 023 (“MCB not open”).

▪ 024 (“GCB not open”).

188 MC200 Technical Manual EAAM0578EN


The board makes available the following internal statuses, related to anomalies, for AND/OR
logics:

 ST.006: the output will be activated for a second after a command of faults
acknowledgement.

 ST.007: the output will be activated for a second after a command of faults reset.

 ST.008: Warnings cumulative.

 ST.009: Unload cumulative.

 ST.011: Alarm cumulative.

 ST.012: Non-acknowledged warnings cumulative.

 ST.013: Non-acknowledged unloads cumulative.

 ST.015: Non-acknowledged alarms cumulative.

8.5

WARNING: the use of this function can cause serious damages to the generators.
SICES cannot be considered anyway liable due to malfunctioning and damages to
things and/or people occurred because of the utilization of the OVERRIDE function.

This term defines the capacity of the controller of temporarily disabling (in particular conditions
and on specific request) a series of protections. The OVERRIDE function, when is activated,
turns a set of alarms and unloads into simple “warnings”: in this way, the board indicates,
anyway, the presence of problems, but doesn't reduce the supplying capacity of the
generators. In some situations, in fact, supply to users is put before the preservation of the
engines. You should consider, for example, hospitals: there are situations in which it is
preferable to damage the engines, and supply power for the longest period possible, rather
than safeguarding the engines, but leaving operating rooms without light.

The board manages the protections OVERRIDE request through digital inputs. Use the
following function to configure the digital inputs:

• DIF.2063 (“Full protections Override”).

The OVERRIDE function turns a specific set of alarms/unloads into "warnings". The document
[1] has a table indicating all the controller anomalies: the column “OVER” indicates, for each
anomaly, if it is subject to the OVERRIDE functions.

Besides what indicated in the table, the OVERRIDE function also affects "generic" anomalies
connected to analogue and digital inputs. The following functions for the configuration of digital
inputs activate anomalies that are subject to protections OVERRIDE too:

 DIF.4062 - “Unload (subject to OVERRIDE)”.

 DIF.4064 - “Alarm (subject to OVERRIDE)”.

As to protections activated through thresholds on analogue measures, it is possible to subject


these anomalies to protections OVERRIDE through the bit 15 of the threshold configuration
parameter (P.4005 for the first threshold on the first analogue input).

The board will show a message on “S.01” page when the OVERRIDE function is activated.

The board records an event each time an OVERRIDE request is activated (EVT.1082).
Moreover, it records an event among the records, whenever the OVERRIDE request ceases
(EVT.1083).

MC200 Technical Manual EAAM0578EN 189


8.6
The board manages a significant number of digital input, by considering also the expansion
modules (DITEL) that it can manage. Every input can be used to activate anomalies. These
anomalies are divided into two kinds:

• Specific. They are configured with functions DIF.4261 and following. The board
knows the modes through which these anomalies should be managed, and already
has some default error messages (that cannot be configured) connected to each
anomaly.

• Generic. They are configured through DIF.4001 through DIF.4064 functions. As to


these anomalies, the operator should configure the message that will be shown on the
display. Moreover, by using the appropriate functions, the board will be instructed
regarding the way it should manage the anomaly.

Specific anomalies will be described in the following paragraphs: in the description, the
parameters relevant to the digital input #1 (P.2001, P.2002 e P.2003) will be always referred
to. The document [1] has a table that shows the parameters to be used for every digital input.

What stated above is true also for generic anomalies. They will not be described in the
following paragraphs, because they will be infinite repetitions of the same description for each
input. On the contrary, they are described here, by indicating parameters for input #1 of the
controller.

The board assigns numeric codes 701 through 806 to generic anomalies linked to digital inputs
(the document [1] has a table that shows the code for each input). By utilizing the parameter
that configures the function (P.2001), it is possible to select the type of anomaly (warning,
unload or alarm) and to define the conditions for the anomaly management. Warning: by
setting the delay to “0”, the anomaly is disabled. In the list below, the functions for the
configuration of digital inputs, used to manage generic anomalies, are indicated. They are
grouped three by three: the three functions for each group define the type of anomaly (see
document [1] for the list of functions).

 DIF.4001, DIF.4002, DIF.4004. The board will activate this anomaly if the digital input
is uninterruptedly active for the configured (P.2002) time span.

 DIF.4005, DIF.4008. The board will activate this anomaly if the digital input is
uninterruptedly active for the configured (P.2002) time span. An anomaly of the same
type is also activated by all the genset controllers connected through the CAN bus
link.

 DIF.4021, DIF.4022, DIF.4024. The board will activate this anomaly if the digital input
is uninterruptedly active for the configured (P.2002) time span. These anomalies force
the opening of the MCB circuit breaker.

 DIF.4062, DIF.4064. The board will activate this anomaly if the digital input is
uninterruptedly active for the configured (P.2002) time span. The anomaly is subject
to the engine protections OVERRIDE and to total OVERRIDE, too (see 8.5).

8.7
The board can manage a high number of analogue inputs, also considering those acquired by
DIGRIN, DITHERM and DIVIT expansion modules.

For each analogue input, it allows setting two thresholds on the acquired measure, and each
threshold can activate an anomaly. These are generic anomalies, since the controller doesn't
know how to manage them and hasn't default warning messages. They will not be described
in the following paragraphs, because they will be infinite repetitions of the same description
for each analogue input. On the contrary, they are described here, by indicating parameters
for input 1.

The controller assigns numeric codes 301 through 554 to generic anomalies linked to
analogue inputs (the document [1] has a table that shows the code of each input).

190 MC200 Technical Manual EAAM0578EN


First, the operator should configure the error message that will be shown on the board display
when the anomaly is activated. It should use P.4002 parameter, the only one for the two
thresholds. The controller will add an initial wording to the configured message:

 “High value:” if the anomaly is activated when the measure is higher than the
threshold.

 “Low value:” if the anomaly is activated when the measure is lower than the threshold.

For each analogue input, there are six parameters available for the management of thresholds,
three for each threshold (P.4003, P.4004 and P.4005 for the first threshold of the first analogue
input; P.4006, P.4007 and P.4008 for the second threshold of the first analogue input).

Besides the threshold value (P.4003 or P.4006) and the delay to be managed (P.4004 or
P.4007), the operator must configure the operations connected to the threshold (P.4005 o
P.4008). The parameter that configures the actions is managed through bits (every bit
enables/disables a function connected to the threshold). For the description of these
parameter, see 5.6.4.

Warning: by setting the delay to “0”, the anomaly isn't disabled.

8.8
NOTE: as it is not possible to define either which digital or analogue inputs (of the controller
or on additional modules) will be used or which function they are going to perform, refer to the
following list as an example of the first configurable input. The presence of symbol (*) or the
indication “or equivalent for the other inputs” aside a parameter indicates that it varies
according to the configured input.

From this point on, words enabling and activation will be utilized:

 Enabling an anomaly means that the minimum necessary conditions that the controller
should verify to observe the provoking cause.

 Activating an anomaly means the verification of the provoking cause, after the
enabling has happened.

Typology: Warning
Related parameters: P.0805
To disable: -
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly when it detects (from information sent over CAN bus PMCB)
that at least one genset is in a “GCB not opened” condition (GCB closed while an opening
command is active). In this situation, the parameter P.0805 selects the actions on the MGCB
circuit breaker:

• “0”. This setting forces an MGCB opening (and obviously avoids next MGCB
closures).

• “1”. This setting avoids MGCB closures (but doesn’t force MGCB opening if already
closed).

• “2”. Use this setting when you want that the “GCB not open” condition is not involved
in the MGCB management.

Note: the gensets controllers have its own equivalent parameter to configure actions
on GCB.

Typology: Alarm

MC200 Technical Manual EAAM0578EN 191


Related parameters: P.0495
To disable: Bit 0 of P.0495=1
Enabled if: AUTO, TEST, REMOTE START.

The protection is enabled if bit 0 of parameter P.0495 is set to 0. It is activated when pressing
the STOP button on MC200, or if a stop command is received from Modbus.

Typology: Warning
Related parameters: P.0806
To disable: P.0806 = 0 o P.0806 = 30000
Enabled if: MAN, AUTO, TEST, REMOTE START.

This anomaly is enabled only if MGCB circuit breaker exists, and if it is managed by MC200.
Moreover, it is enabled only when generators must supply in “island” mode. MC200 activates
this anomaly before MGCB closure, if all available generators are supplying but the sum of
their nominal powers is lower than the power requested with parameter P.0806. It signals that
generators may be unable to supply all loads. Values “0” and “30000” of P.0806 are special;
they disable this anomaly. The value “0” configures MC200 to close MGCB as soon as one
GCB is closed; the value “30000” forces MC200 to wait for all available generators are
supplying (whatever their power is).

Typology: Warning
Related parameters: P.2001 (or equivalent for other inputs)
To disable: P.2001 <> DIF.3002
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly after three consecutive closing commands without results (in
MAN after the first attempt). It cannot be directly disabled: it can be disabled only by not
configuring an input to acquire the circuit breaker status (but this is possible only in certain
situations).

Typology: Warning / alarm


Related parameters: P.2001 (or equivalent for other inputs)
To disable: P.2001 <> DIF.3003
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly after three closing commands of the circuit breaker without
result (in MAN mode after the first attempt): it is a warning in MAN mode and an alarm in the
other modes. It cannot be directly disabled: it can be disabled only by not configuring an input
to acquire the circuit breaker status (but this is possible only in certain situations).

Typology: Warning / unload / alarm


Related parameters: P.9502 P.9521 P.9522 P.9523 P.9524
To disable: P.9502 = 0 o P.9522 = 0 o P.9523 = 0
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly when at least one of the mains currents is higher than the
configured threshold.

The threshold (P.9521) is a percentage of the nominal current of the system, set by parameter
P.9502. The threshold can be configured between 0% and 999%, with 0.1% resolution.

192 MC200 Technical Manual EAAM0578EN


The delay (P.9522) of the protection can be set between 0 and 4000 seconds, with 0.1
seconds’ resolution. If the delay is set to zero, the protection is disabled: so, the minimum
delay is 0.1 seconds.

Parameter P.9524 selects the typology:

• 1: Warning.

• 2: Unload.

• 4: Alarm.

• 8: Alarm sent also to all gensets.

The protection can work in four different ways, as selected by parameter P.9523:

1. This value selects a “fixed time” protection. The anomaly is activated when at least
one current is higher than the threshold P.9521 for the time P.9522. Note: the check
is made both on instantaneous and average current values; if one or both is higher
than the threshold the protection can be activated.

2. This value selects the same protection of the previous one: the only difference is that
the real threshold is decreased respect to the configured one if the voltages are lower
than the nominal.

120,00%

100,00%
Tensione (% della nominale)

80,00%

60,00%

40,00%

20,00%

0,00%
0,00% 20,00% 40,00% 60,00% 80,00% 100,00% 120,00%
Soglia reale (% della soglia impostata)

3. This value selects a time-related maximum current protection (it activates so much
more quickly how much higher is the overload). The used curve is named
EXTREMELY INVERSE, and implements an I2t function.

We define a maximum current threshold (P.9521), and the maximum time the
generator can work with this current (P.9522). If the current is lower than the defined
threshold, the protection is not activated. If the current become greater than the
threshold, the protection is activated with a time inversely proportional with the entity
of the over current. To correctly set the thresholds, follow the following steps:

▪ You must set the nominal current of the system (P.9502).

▪ Configure the maximum current threshold by the P.9521 parameter, as a


percentage of the nominal current.

MC200 Technical Manual EAAM0578EN 193


▪ Configure the intervention time for the protection in the P.9522 parameter: the
protection will be activated exactly after the time you’ve configured if the
current is constantly equals to the P.9521 threshold multiplied by 2.
To calculate the intervention time for a preferred current, please use the following
formula:

P.9522
tI  2
 I 
  1
 P.9521 
“I” is the current in the circuit.

You must keep in mind that the board calculates the integral value of the current in the
time, so all the current samples over the threshold concur to determine the intervention
time, with their instantaneous weight as defined in the previous formula. The only way
to verify exactly this formula is thus to switch instantaneously from a normal load
situation to an over load situation.

The following graph shows the used curve, with P.9522 set to 60 seconds (I is the
maximum current):

Tempo intervento

1000

100
Intervention time (seconds) I

10

0,1
1 10
Multiple of I

4. This value selects the same protection of the previous one: the only difference is that
the real threshold is decreased respect to the configured one if the voltages are lower
than the nominal (see description for value 2).

Typology: Warning / unload / alarm


Related parameters: P.9502 P.9525 P.9526 P.9527 P.9528
To disable: P.9502 = 0 o P.9526 = 0 o P.9527 = 0
Enabled if: MAN, AUTO, TEST, REMOTE START.

The same as anomaly “016”, with the parameter listed above.

Typology: Warning

194 MC200 Technical Manual EAAM0578EN


Related parameters: P.9512
To disable: P.9512 = 0
Enabled if: MAN, AUTO, TEST, REMOTE START.

This anomaly is activated when at least one genset managed by MC200 is still running after
the delay set in the parameter P.9512 from the stop command.

Typology: Warning
Related parameters: P.9511
To disable: P.9511 = 0
Enabled if: MAN, AUTO, TEST, REMOTE START.

This anomaly is activated when none of the gensets managed by MC200 is running after the
delay set in the parameter P.9511 from the start command.

Typology: Warning / alarm


Related parameters: P.2001 (or equivalent for other inputs)
To disable: P.2001 <> DIF.3002
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly in the following situations:

• If MC200 manages the circuit breaker, but it is closed by an external logic (not in MAN
mode). The anomaly is set only if the “static command” is used to manage the circuit
breaker. In this case the controller activates an alarm with a delay of 0.5 seconds.

• After three opening commands of the circuit breaker without result (only one attempt
in MAN mode): in this case, it is a warning in MAN mode and an alarm in the other
modes.

It cannot be directly disabled: it can be disabled only by not configuring an input to acquire the
circuit breaker status (but this is possible only in certain situations).

Typology: Warning / alarm


Related parameters: P.2001 (or equivalent for other inputs)
To disable: P.2001 <> DIF.3003
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly in the following situations:

• If MC200 manages the circuit breaker, but it is closed by an external logic (not in MAN
mode). The anomaly is set only if the “static command” is used to manage the circuit
breaker. In this case the controller activates an alarm with a delay of 0.5 seconds.

• After three opening commands of the circuit breaker without result (only one attempt
in MAN mode): in this case, it is a warning in MAN mode and an alarm in the other
modes.

It cannot be directly disabled: it can be disabled only by not configuring an input to acquire the
circuit breaker status (but this is possible only in certain situations).

Typology: Warning
Related parameters: P.0362 P.0363
To disable: P.0363 = 0

MC200 Technical Manual EAAM0578EN 195


Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly when power supply voltage drops down under the threshold
P.0362 for the time set with parameter P.0363. Note: the threshold P.0362 is expressed as a
percentage of the supply rated voltage, which is configurable but it is automatically selected
by the controller between 12 and 24 Vdc. Selection is made when the controller is powered
and every time it is forced in OFF/RESET mode. A nominal voltage of 12 V is selected if power
supply voltage is lower than 17 V.

Typology: Warning
Related parameters: P.0364 P.0365
To disable: P.0365 = 0
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly when power supply voltage grows up over the threshold P.0364
for the time set with parameter P.0365. Note: the threshold P.0364 is expressed as a
percentage of the supply rated voltage, which is configurable but it is automatically selected
by the controller between 12 and 24 Vdc. Selection is made when the controller is powered
and every time it is forced in OFF/RESET mode. A nominal voltage of 12 V is selected if power
supply voltage is lower than 17 V.

Type: Alarm
Parameters connected: P.0108 P.0135 P.0131 P.0367 P.0368
To disable: P.0368 = 0
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is enabled if a valid current measure is configured. Both P.0108 and P.0135
should be different from zero, and P.0131 should be set to 1 or 2. Moreover, the protection
can be disabled through a digital input configured through DIF.2704 function (“disable
protections on the fourth current”): if the digital input exists and is activated, the protection will
be disabled.

The protection will be activated if, per the previous conditions, the measure of current stays
above P.0367 threshold uninterruptedly for the time P.0368.

Type: Alarm

Parameters connected: P.0361


To disable: -
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is always enabled.

It will be activated if, per the previous conditions, the input dedicated to the emergency stop
(JJ 2) remains idle, continuously for the configured time (P.0361).

Note: this anomaly can be activated also with an already active shutdown.

Typology: Warning
Related parameters: P.0366
To disable: P.0366 = 255.0
Enabled if: MAN, AUTO, TEST, REMOTE START.

196 MC200 Technical Manual EAAM0578EN


MC200 activates this anomaly when its internal temperature is greater than the threshold
P.0366, even for a very little time.

Type: Warning
Parameters connected: P.0418 P.0421 P.0422 P.0423 P.0426
To disable: -
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is always enabled.

It is activated if the controller recognizes the clock status as not valid and the functions related
to the clock, such as the weekly test (P.0418), the time to enable operations (P.0421, P.0422,
P.0423) or the time to force intervention (P.0426) have been configured.

To deactivate it, you need to set the clock.

Type: Warning
Parameters connected: P.0141 P.0142 P.0143 P.0144
To disable: -
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is enabled if the CAN bus is activated (P.0141 or P.0142 or P.0143 or P.0144
<> 0).

It activates if the internal CAN controller switches to BUS-OFF status due to bus
communication errors.

Typology: Warning
Related parameters: -
To disable: -
Enabled if: MAN, AUTO, TEST, REMOTE START.

This anomaly is activated each time the CAN bus internal interface of the controller switches
to the BUS-OFF status. Normally the “BUS-OFF” condition is related to wiring problems (short
circuits between CAN-H and CAN-L lines, for example).

Typology: Warning
Related parameters: P.9501
To disable: -
Enabled if: MAN, AUTO, TEST, REMOTE START.

This anomaly is activated when two or more MCxxx devices are connected to the same can
bus line, and they have the same address for PMCB (parameter P.9501).

Typology: Warning
Related parameters: P.0803
To disable: P.0803 = 0
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 Technical Manual EAAM0578EN 197


MC200 activates this anomaly if the number of genset controllers communicating over the can
bus PMCB is different from what configured by parameter P.0803. In this case, parameter
P.0804 can be used to inhibit MGCB closure (but not to force its opening). By setting the
parameter P.0803 to “0”, you disable this command.

Typology: Warning
Related parameters: P.0890
To disable: P.0890 = 0
Enabled if: MAN, AUTO, TEST, AVVIAMENTO REMOTO.

MC200 activates this anomaly if P.0890 has been set to a value different from zero, and the
duration of the parallel to the grid was longer than this parameter. MC200 opens the MGCB
circuit breaker and doesn’t allow its closure until the operator acknowledges this warning.
MC200 can activate this warning even when the function “transfer to gensets” is enabled, if at
the end of the configured delay the power is not yet transferred to the gensets (because the
nominal power of the gensets is not enough for the loads): in this case, if the power on the
loads would decrease (or if new gensets became available), MC200 will close again MGCB
circuit breaker even if the warning has not been acknowledged.

The parameter P.0897 is a bit-field parameter, allowing the operator to select in which
conditions MCB opening as to be allowed at the end of configured time:

• Bit 0: in MAN mode.

• Bit 1: in AUTO mode.

• Bit 2: in TEST mode.

• Bit 3: in REMOTE START mode.

• Bit 7: in case of failure in opening MGCB.

Type: Warning
Parameters connected: P.0141 P.0142 P.0143 P.0144
To disable: P.0141=0 and P.0142=0 and P.0143=0 and P.0144=0
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is enabled if the CAN bus is activated (P.0141 or P.0142 or P.0143 or P.0144
different from zero).

It will be activated when one or more boards configured with the previous parameters isn't
communicating on the CAN bus. On page S.02, by selecting this early warning, the board
shows which module isn't communicating.

Type: Warning
Parameters connected: P.0141 P.0142 P.0143 P.0144
To disable: P.0142=0 and P.0143=0
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is enabled if the CAN bus for the expansion modules is activated (P.0141 or
P.0142 or P.0143 or P.0144 different from zero).

It will be activated when the controller doesn’t receive an analogue measure from the CAN
bus. The board verifies the sole presence of the utilized analogue measures (those that have
a function different from zero in P.4001 parameter or equivalent ones for the other analogue

198 MC200 Technical Manual EAAM0578EN


inputs). On S.02 page, by selecting this early warning, the board indicates which channel of
which module isn't carrying out the measurement.

Type: Warning
Parameters connected: P.0141 P.0142 P.0143 P.0144
To disable: P.0141=0 e P.0142=0 e P.0143=0 e P.0144=0
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is enabled if the CAN bus for the expansion modules is activated (P.0141 or
P.0142 or P.0143 or P.0144 different from zero).

It will be activated if two or more expansion modules are configured with the same address.
On S.02 page, by selecting this early warning, the board indicates which module has the
duplicated address.

Type: Warning
Parameters connected: P.0142 P.0143
To disable: P.0142=0 and P.0143=0
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is enabled if the CAN bus for the expansion modules is activated (P.0141 or
P.0142 or P.0143 or P.0144 different from zero).

It will be activated when a DIGRIN, DITHERM or DIVIT module reports the status of
“disconnected sector”. On S.02 page, by selecting this early warning, the board indicates
which channel of which module has a disconnected sensor.

Typology: Warning / alarm


Related parameters: P.0852
To disable: P.0852 = 0
Enabled if: AUTO, TEST, REMOTE START.

This anomaly is activated only during automatic synchronization, for MGCB closure. If the
circuit breaker is not closed after the P.0852 delay, MC200 activates the anomaly: it’s a
warning in MAN mode, an alarm in all other modes.

Typology: Warning
Related parameters: P.0853
To disable: P.0853 = 0
Enabled if: AUTO, TEST, REMOTE START.

This anomaly is activated only during automatic synchronization, for MCB closure. If the circuit
breaker is not closed after the P.0852 delay, MC200 activates the anomaly.

Typology: Warning / alarm


Related parameters: -
To disable: -
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 Technical Manual EAAM0578EN 199


MC200 activates this anomaly to signal a “wrong configuration” of parameters. In the “S.02”
display page, a detailed description shows the real cause of the anomaly. Possible causes
are:

• The parameters which require the “SICES” password are never been set after the first
factory configuration. It’s an alarm.

• Selected plant type (P.0802) is different from “MPM”, and the MCB circuit breaker is
configured as “not managed” (P.0855). It’s an alarm.

• MCB circuit breaker is configured as “external” (P.0855) and no digital input is


configured to acquire its status (function DIF.3002). It’s an alarm.

• MCB circuit breaker is managed by MC200 without static commands, and no digital
input is configured to acquire its status (function DIF.3002). It’s an alarm.

• MCB circuit breaker is configured as “external synchronizable” (P.0855), and no digital


input is configured to acquire external synchronization requests (function DIF.1034).
It’s an alarm.

• MGCB circuit breaker is configured as “external” (P.0854) and no digital input is


configured to acquire its status (function DIF.3003). It’s an alarm.

• MGCB circuit breaker is managed by MC200 without static commands, and no digital
input is configured to acquire its status (function DIF.3003). It’s an alarm.

• MGCB circuit breaker is configured as “external synchronizable” (P.0854), and no


digital input is configured to acquire external synchronization requests (function
DIF.1004). It’s an alarm.

• The parameter P.9506 is programmed to zero, but in the plant is present at least one
controller that does not support MC200 mode. Function available by DST4602 starting
from version 00.87 and GC600 from version 1.04; but not by the MC100. It’s a warning.

Typology: Alarm
Related parameters: P.2001 (or equivalent for other inputs)
To disable: P.2001 <> DIF.4261
Enabled if: MAN, AUTO, TEST, REMOTE START.

MC200 activates this anomaly if the digital input configured with the function DIF.4261
(“production line open”) is activated (even for a very small time). Note: this alarm forces the
opening of all generator circuit breakers GCB; this function is directly managed by the
genset controllers after receiving a proper message over the PMCB bus.

Typology: Alarm
Related parameters: P.0900
To disable: P.0900 = 0
Enabled if: MAN, AUTO, TEST, REMOTE START.

This anomaly is used only for parallel to mains operations. MC200 activates it when the circuit
breaker configured as “interface device” (P.0900) does not open in 0.5 seconds from the “loss
of mains”. Set P.0900 to zero do disable this control: ensure some external logic can
disconnect generators from mains in case of loss of mains.

Type: Warning/Alarm
Parameters connected: -
To disable: -

200 MC200 Technical Manual EAAM0578EN


Enabled in: MAN, AUTO, TEST, REMOTE START

The board will activate this warning before closing MGCB, if it notices a divergence between
the effective presence of voltage on parallel bars and what it expects per the statuses of the
switches, mains and any other generator control boards connected on PMCB. The anomaly is
activated only if there isn’t voltage on bars when, on the contrary, it should be present. For
example, if at least a generator has closed GCB, there should be voltage on parallel bars: if
the board doesn't detect it (through the three-phase sensor or through a contact), after two
seconds the signalling is activated. Usually the signal is a warning, it becomes an alarm (only
in case of automatic procedures) after 60 seconds if the board needs to close the MGCB.

Typology: Warning / alarm


Related parameters: P.0384, P.0385, P.0386
To disable: P.0385 = 0
Enabled if: MAN, AUTO, TEST, REMOTE START.

This anomaly is activated when the active power measured on the mains is negative
(exported) and is greater (absolute value) than the threshold P.0384 continuously for the time
P.0385. The action related to the protection can be configured by P.0386:

• 1 – Warning. The controller activates the warning but keeps the generators in parallel
to the mains,

• 4 – Alarm. The controller activates the alarm, opens MGCB (when present), forces the
genset controllers to open their GCB and to stop the engines with the standard
procedure (with the cool down cycle).

• 9 – Warning (MCB). If this value is selected, when the protection trips the controller
opens MCB and keeps the gensets running for supply the load in island mode. The
controller will try to close MCB only after the warning has been acknowledged. Note:
using this value, the protection works in OFF/RESET mode also (it opens MCB). In
this way, the mains is protected against manual parallel performed on the genset
controllers when MC200 is in OFF/RESET mode.

See 8.6.

See 8.7.

Type: Warning
Parameters connected: -
To disable: -
Enabled in: MAN, AUTO, TEST, REMOTE START

The protection is enabled only when a valid PLC program has been transferred to the board.
It reports possible problems during the running of the PLC:

• The PLC program uses more FLASH memory than available.

• The PLC program uses more RAM memory than available.

• The PLC program has an invalid control check-sum.

• The PLC program is developed with a version not supported by this board.

MC200 Technical Manual EAAM0578EN 201


• A digital or analogue output controlled by the PLC is not configured with DOF.0101 or
AOF.0101 function (“used by the PLC”).

• The PLC program uses a resource (of any kind) not available on this board (for
example, a digital input of a non-connected expansion module).

• An invalid parameter has been specified for one of PLC blocks.

• An invalid type of block has been specified.

• Calculation error during the running of the program.

On S.02 page, by selecting this early warning, the board shows additional information to help
solving the problem.

The PLC program, through one of its blocks, can activate anomalies. Codes 901 through 964
are connected to such anomalies. Anomalies triggered by the PLC can be alarms, unloads or
warnings.

202 MC200 Technical Manual EAAM0578EN


9
9.1
The MC200 controller is equipped with a PLC environment (acronym for “Programmable Logic
Controller”) that carries out a sequence of functions previously stored in a proper Flash
memory.

Use “SicesPlcEditor” software to create and fulfil the PLC program. Use the “BoardPrg3”
software to transfer the compiled PLC program to MC200 or to read it again from the board
[2].

The PLC program is run every 100ms. This time span could not be adequate to manage
protections that should intervene very quickly.

9.2
This function is used for “emergency” plants (MSB or MSB+MSTP). Normally, in case of mains
live, the controller connects the load to the mains. For stand-by application, MCB must be
usually closed to connect the loads to the mains. Using this function is possible to automatically
start the gensets and supply the loads in case of MCB failure.

To use this function, carry out following configuration:

• MCB feedback must be connected to a digital input of the controller.

• Set parameter P.9514 to 1.

With such configuration, MCB status is continuously monitored. When MCB is commanded
closed but remains opened for more than the programmed time (mains should be present if
MCB is supplied by mains – P.0847), the following actions are carried out:

• It tries to close the MCB circuit breaker.

• In case if failure, warning W013 is issued.

• All available engines are started.

• Loads are connected to generators.

Now, the loads won’t be switched automatically on the mains until the operator “acknowledges”
the warning W013. After this operation, the controller will try again to close MCB: if it does not
close, the warning will be issued again and the load will stay switched on gensets.

In MAN mode (or with start inhibitions activated) the function is disabled; it is also disabled if
a “inhibition to start” is activated,

The controller starts the generators (if P.9514 is set to 1) even when is activated the generic
warning related to a digital input configured with the functions DIF.4021, DIF.4022, DIF.4024
(these anomalies force the opening of MCB). Even in this case, the controller will try to close
MCB (and then will stop the generators) only when the operator will acknowledge and reset
that warning.

9.3
The board is provided with a hardware clock. It is shown in details on page S.03. It is possible
to set the clock through 4.7.1 menu or serial ports. It is used for several functions:

 History logs recordings.

 TEST weekly planning.

 Weekly planning of time intervals in which the gensets can start automatically.

 Weekly plan of periods in which the gensets automatic activation must be forced

MC200 Technical Manual EAAM0578EN 203


The clock is equipped with a rechargeable battery and can work for some months even if the
controller is not supplied. After a long time in which the controller is not used (no supply), even
if the clock reactivates immediately when the supply comes back, a few hours are necessary
to guarantee to full recharge of the internal battery.
9.3.1 Clock automatic update
In case the controller has an Ethernet connection, the clock can be automatically updated
through the connection towards a NTP server (see par. 5.11.4). The controller registers the
event “EVT.1076 - Date and hour modified” in the history log, but only if the difference between
the new time received and the current one is higher than one minute.

The server TNP (questioned by the controller every 5 minutes) gives the date and hour of the
reference time zone (that is UCT “Universal Coordinated Time”) from which the controller can
calculate and update the internal calendar considering its own time zone and eventual daylight
saving time. To this purpose, the follow parameters are available:

 P.0408: Daylight saving offset (1=15 min.; 4=1 hour). The setting limits are from 0 to 48
and allow to manage the offset to be added/subtracted for the daylight saving time.

 P.0409: Daylight saving time.

 “0-No” daylight saving time not in use

 “1-Yes” daylight saving time in use (it adds P.0408 to the one received).

 “2-Automatic (only Europe)”: It is only valid for Europe, as since 2002 has been unified
(it activates ate 01.00 of the last Sunday of March and deactivates at 01.00 of the last
Sunday of October).

 P.0410: Time zone (1=15 min.; 4=1 hour). The setting limits are from -47 to + 48 and
allow to manage all time zones of the Earth by hour quarts.
9.3.2 Weekly planning for TEST.
The starting test plans is made on weekly base. That is, it is possible to indicate in which days
of the week the generators must be started in test and in which not.

The parameters related to this function are the following:

 P.0418: allows to specify in which days of week the TEST will be performed. It is a bit-
configurable parameter; each bit of the parameter corresponds to a day of the week.
The value you must set for the parameter is the sum of the value field of the following
table for the days needed.
Bit Hexadecimal value Day
0 01 Sunday
1 02 Monday
2 04 Tuesday
3 08 Wednesday
4 10 Thursday
5 20 Friday
6 40 Saturday

For example, if you want to perform the TEST only on Monday and Thursday, you
must set 12 (10+02).

 P.0419: allows to set start time for the TEST (Hours and minutes).

 P.0420: allows to configure the TEST duration (in minutes).

P.0420 allows to configure the TEST duration (in minutes). This is because the same
parameter is used also for the TEST activated by an SMS command.

204 MC200 Technical Manual EAAM0578EN


9.3.3 Weekly planning for working days.
In some applications, it is useful to inhibit the automatic intervention of the gensets for mains
failure in hours or days where the mains is not used. For example, if a factory is closed on
Sunday, the gensets should never start in this day for mains failure (because it consumes
unnecessary fuel). With this function, you can select in which days and in which time intervals
the gensets can start automatically. The planning is made on a weekly basis: therefore, it is
possible to plan in which days the generator must operate. Besides days, it is possible to set
a single auto operation enable time slot common to all selected days.

The parameters related to this function are the following:

 P.0421: allows to specify in which days of week the gensets can start automatically.
It is a bit-configurable parameter; each bit of the parameter corresponds to a day of
the week. The value you must set for the parameter is the sum of the value field of the
following table for the days needed.


Bit Hexadecimal value Day
0 01 Sunday
1 02 Monday
2 04 Tuesday
3 08 Wednesday
4 10 Thursday
5 20 Friday
6 40 Saturday

 P.0422: allows to configure the start of the time interval during which the gensets can
start automatically (in hours and minutes).

 P.0423: allows to configure the end of the time interval during which the gensets can
start automatically (in hours and minutes).

Usually P.0422 will be set to a value lower than P.0423. On the contrary, if it contains a higher
value, the controller infers that the time interval is set across midnight: in this case, the time
set with P.0422 refers to the days selected with P.0421, while the time set with P.0423 refers
to the following days.

For example, in case an automatic gensets start is required only Monday through Friday,
between 08:00 and 18:00, you must set:

P.0421 = 3E (02+04+08+10+20)

P.0422 = 08:00

P.0423 = 18:00
9.3.4 Weekly planning of intervention forcing.
The planning of intervention forcing is performed weekly. That is, it is possible to indicate on
which days of the week the generators must intervene, even if the status of the system doesn't
require the intervention. Besides the days, it is possible to specify from what time to what time
the intervention should be forced. This time interval is common to all the days selected.

The parameters related to this function are the following:

• P.0426: it allows specifying on which days of the week the intervention of the
generators must be forced. It is a bit-configurable parameter; each bit of the parameter
corresponds to a day of the week. The value to be set for the parameter is the sum of
the value fields in the following table related to the days needed.
Bit Hexadecimal value Day
0 01 Sunday

MC200 Technical Manual EAAM0578EN 205


1 02 Monday
2 04 Tuesday
3 08 Wednesday
4 10 Thursday
5 20 Friday
6 40 Saturday

For example, to configure the forcing of the intervention only on Monday and
Thursday, it is necessary to set 12 (10+02).

• P.0427: it allows setting the starting time of the forcing (in hours and minutes).

• P.0428: it allows setting the ending time of the forcing (in hours and minutes).
9.3.5 Configurable calendars
The controller provides 16 calendars fully configurable. They allow to select days and time-
slots, inside which the controller activates an internal bit. This bit could then be used by
AND/OR logics to activate a digital output or to create more complex logics. All calendars are
identical: calendars 15 and 16, however, can be used for the activation/deactivation of the
daylight save time (if parameter P.0409 is set to “3”).

Each calendar can be individually selected as “monthly” or “weekly”:

206 MC200 Technical Manual EAAM0578EN


Using BoardPrg3 software, it is very easy to select whether a calendar is “weekly” or “monthly”.
If you want to use the parameters of the controller, you must act on the parameter P.1900. It
is a bit-field parameter; one bit is provided for each calendar:
BIT Value Hexadecimal Calendar
0 1 0001 Calendar 1
1 2 0002 Calendar 2
2 4 0004 Calendar 3
3 8 0008 Calendar 4
4 16 0010 Calendar 5
5 32 0020 Calendar 6
6 64 0040 Calendar 7
7 128 0080 Calendar 8
8 256 0100 Calendar 9
9 512 0200 Calendar 10
10 1024 0400 Calendar 11
11 2048 0800 Calendar 12
12 4096 1000 Calendar 13
13 8192 2000 Calendar 14
14 16384 4000 Calendar 15
15 32768 8000 Calendar 16

The parameter must be set with the sum of the values for all the calendars that must be
selected as “weekly” (in hexadecimal notation). In fact, a bit set to “1” selects the “weekly”
mode.

Both calendar types allow to select in which months the controller activates the internal bit (at
least one month must be selected, it is even possible to select all months). Using the
parameters of the controller, this selection is done by means parameter P.1901 (for the
calendar 1 or equivalent for other calendars). This is also a bit-field parameter:
BIT Value Hexadecimal Month
0 1 0001 January
1 2 0002 February
2 4 0004 March
3 8 0008 April
4 16 0010 May
5 32 0020 June
6 64 0040 July
7 128 0080 August
8 256 0100 September
9 512 0200 October
10 1024 0400 November
11 2048 0800 December

The parameter must be set with the sum of the values of the required months (in hexadecimal
notation).

For “monthly” calendars, is then possible to select the days of the month for the activation of
the internal bit (at least one day must be selected, it is even possible to select all days). Using
the parameters of the controller, this selection is done by means parameter P.1902 (for the
calendar 1 or equivalent for other calendars). This is also a bit-field parameter:
BIT Value Hexadecimal Day of month
0 1 00000001 1
1 2 00000002 2
2 4 00000004 3
3 8 00000008 4

MC200 Technical Manual EAAM0578EN 207


4 16 00000010 5
5 32 00000020 6
6 64 00000040 7
7 128 00000080 8
8 256 00000100 9
9 512 00000200 10
10 1024 00000400 11
11 2048 00000800 12
12 4096 00001000 13
13 8192 00002000 14
14 16384 00004000 15
15 32768 00008000 16
16 65536 000100000 17
17 131072 00020000 18
18 262144 00040000 19
19 524288 00080000 20
20 1048576 00100000 21
21 2097152 00200000 22
22 4194304 00400000 23
23 8388608 00800000 24
24 16777216 01000000 25
25 33554432 02000000 26
26 67108864 04000000 27
27 134217728 08000000 28
28 268435456 10000000 29
29 536870912 20000000 30
30 1073741824 40000000 31

The parameter must be set with the sum of the values of the required days (in hexadecimal
notation).

For “weekly” calendars, is then possible to select the days of the week for the activation of the
internal bit (at least one day must be selected, it is even possible to select all days). Using the
parameters of the controller, this selection is done by means parameter P.1902 (for the
calendar 1 or equivalent for other calendars). This is also a bit-field parameter:
BIT Value Hexadecimal Day of week
16 65536 00010000 Sunday
17 131072 00020000 Monday
18 262144 00040000 Tuesday
19 524288 00080000 Wednesday
20 1048576 00100000 Thursday
21 2097152 00200000 Friday
22 4194304 00400000 Saturday

The parameter must be set with the sum of the values of the required days (in hexadecimal
notation).

Selecting a day of the week (Sunday for example), it is then possible to select if all “Sundays”
in the month must be used or only some of them. Using the parameters of the controller, this
selection is done by means parameter P.1902 (for the calendar 1 or equivalent for other
calendars). This is also a bit-field parameter:
BIT Value Hexadecimal Occurrence
0 1 00000001 First occurrence
1 2 00000002 Second occurrence
2 4 00000004 Third occurrence

208 MC200 Technical Manual EAAM0578EN


3 8 00000008 Forth occurrence
4 16 00000010 Last occurrence

The parameter must be set with the sum of the values of the required occurrences (in
hexadecimal notation). Note: for “weekly” calendars, the days of week and their
occurrences in the month are selected by the same parameter, using different bits.

If the “occurrence” bits are all “0”, then the selected days of week will be managed in any week
of the month; otherwise they will be managed for the selected occurrences only. The “last”
option is useful because, depending on the month and on the year, a certain day of the week
can be present 4 or 5 times in a month: using the “last” option you can do an action exactly in
the last occurrence in the month. A typical example is the management of the daylight save
time; in Italy, it is activated on the last Sunday of October, and deactivated on the last Sunday
of March. Those Sundays can be the 4° or the 5° occurrence in the month, depending on the
first day of the month. Using the “last” option, the problem is solved.

Finally, for both “weekly” and “monthly” calendars, it is possible to select a time-slot (valid for
all selected days). The controller will activate the internal bit only inside the selected time-slot.
Using the parameters of the controller, the time-slot can be selected by means P.1903 and
P.1904 (for the calendar 1 or equivalent for other calendars). If those parameters are set with
the same values, the full day is selected. If the start time is lower than the end time, the time-
slot is not across midnight; otherwise, the internal bit is activated after the start time of the
selected days, and it is deactivated after the end time of the day after the selected one.

Using the AND/OR logics, it is possible to activate a digital output into selected days and time-
slot (selected using a calendar):

This is an example for the configuration of the daylight save time for Italy, using calendars 15
and 16:

• Calendar 15.

o Select “weekly” (bit 14 of P.1900 = “1”).

o Last Sunday of October:

▪ Select “October” (P.1957 = “0200”).

▪ Select “Sunday”, “Last” (P.1958 = “00010010”).

o The activation should happen at 02:00:

▪ Select “2:00” as start time (P.1959).

▪ Select “2:01” as end time (P.1960).

• Calendar 16.

o Select “weekly” (bit 15 of P.1900 = “1”).

o Last Sunday of March:

MC200 Technical Manual EAAM0578EN 209


▪ Select “March” (P.1961 = “0004”).

▪ Select “Sunday”, “Last” (P.1962 = “00010010”).

o The activation should happen at 03:00:

▪ Select “3:00” as start time (P.1963).

▪ Select “3:01” as end time (P.1964).

9.4
The controller is provided with a hardware thermometer, for measuring its internal
temperature. The temperature is shown at page S.03, multifunction display. It is used for many
functions:

• At very low temperatures information display slows down. By utilizing the


thermometer, when the temperature falls under a very low threshold, the board keeps
always the backlighting lamp on, that contributes to heat the display and therefore to
increase its efficiency.

• The electronic components inside the controller have an extended working


temperature range. Despite this, it is possible in critical ambient conditions that
temperature goes out of this range. The controller uses the thermometer to activate a
warning if the ambient temperature goes over a threshold configurable with parameter
P.0366. This serves to alert the operator, but it is also possible, by using AND/OR
logics, to ensure that, when the early warning is active, also an output is activated,
output that therefore can be used to start cooling the mechanisms.

9.5
The controller manages internally the following counters:

• Working time with MGCB closed (hours) counter (resettable to zero)

• Working time with MGCB closed (hours) counter (total)

• Active energy counter (kWh) exported by the generators (resettable to zero).

• Active energy counter (kWh) exported by the generators (total).

• Reactive energy counter (kvarh) exported by the generators (resettable to zero).

• Reactive energy counter (kvarh) exported by the generators (total).

• Active energy counter (kWh) imported by the generators (resettable to zero).

• Active energy counter (kWh) imported by the generators (total).

• Reactive energy counter (kvarh) imported by the generators (resettable to zero).

• Reactive energy counter (kvarh) imported by the generators (total).

• Active energy counter (kWh) exported on the mains (resettable to zero).

• Active energy counter (kWh) exported on the mains (total).

• Reactive energy counter (kvarh) exported on the mains (resettable to zero).

• Reactive energy counter (kvarh) exported on the mains (total).

210 MC200 Technical Manual EAAM0578EN


• Active energy counter (kWh) imported from the mains (resettable to zero).

• Active energy counter (kWh) imported from the mains (total).

• Reactive energy counter (kvarh) imported from the mains (resettable to zero).

• Reactive energy counter (kvarh) imported from the mains (total).

• Controller total power supply time (hours) counter

Almost all these counters and meters are displayed on the controller's front panel. However,
all can be read via the serial port (with the ModBus protocol). Some of these counters can be
reset by the operator following a proper procedure, or via the serial port (they are marked in
the list with “resettable to zero”). All these counters are saved in a non-volatile memory;
therefore, they store their values also when the controller is powered off. Since non-volatile
memories “consume” themselves writing in them, it is necessary to reduce at the minimum the
number of writings. For this reason, a counter is not immediately saved as its value changes,
and it is then important to know when values are saved and how to be sure that they are saved
before removing supply from the board.

Counters are saved (all together and in the same time) in the following conditions:

 Each time the working hours counter (with MGCB closed) is increased (both total and
partial, also if the gensets have been started for instance six times for ten minutes
each time).

 Each time the operating mode is switched to OFF_RESET.

 Each time a “parallel to the pains” protection trips.

 For each hour of working of the controller.

Furthermore, counters are saved when they are reset to zero (individually or globally) via front
panel or serial port. Note that some counters have a decimal part (for example the minutes-
counters associated to hours-counters), which is also saved in a non-volatile memory.
Powering off the controller in an uncontrolled way can cause the loss of the decimal part. You
will need to switch the key to OFF-RESET to force the controller to save data, before switching
off the power.
9.5.1 Counters reset
The reset procedure is common to all counters, but it works only on some of them based on
the page shown on the multifunctional viewer. See in par. Errore. L'origine riferimento non è
stata trovata. the description of the displayed page containing the counter to be reset

MC200 Technical Manual EAAM0578EN 211


9.6
You can use certain properly configured digital inputs to change the configuration of the
system without changing the programming parameters. In fact, the controller manages
internally four groups of alternative parameters that can be “copied” in the operating
parameters on request (through a dedicated digital input).

Alternative configurations can be programmed only using the BoardPrg3xx.

You cannot program or modify the configurations from the controller.

The parameters present in each alternative group are the following:

 P.0101: Generators bus number of phases.

 P.0102: Generators bus nominal voltage

 P.0103: Primary of generators bus voltmeter transformers.

 P.0104: Secondary generators bus voltmeter transformers.

 P.0128: Is the neutral of the generators bus connected to the controller?

 P.0119: Mains phases number.

 P.0116: P.0116: nominal voltage.

 P.0117: Primary of mains voltmeter transformers.

 P.0118: Secondary of mains voltmeter transformers.

 P.0129: Is the neutral of the generator connected to the controller?

 P.0105: Generator nominal frequency.

 P.0124: Connection of current transformers

 P.0107: Primary of the current transformer.

 P.0139: Secondary of current transformer.

 P.0109: Transformer type for auxiliary current.

 P.0130: Auxiliary current connection.

 P.0108: Primary of the current transformer or toroid ratio for auxiliary power.

 P.0135: Secondary of current transformer or toroid ratio for auxiliary current

 P.0131: Auxiliary current use.

It is possible to change the configuration by means the following input digital functions:

 DIF.2151 – “Select configuration 1”. When the input becomes "active", parameters of
alternative configuration set 1 are copied in the working configuration.

 DIF.2152 – “Select configuration 2”. When the input becomes "active", parameters of
alternative configuration set 2 are copied in the working configuration.

212 MC200 Technical Manual EAAM0578EN


 DIF.2153 – “Select configuration 3”. When the input becomes "active", parameters of
alternative configuration set 3 are copied in the working configuration.

 DIF.2154 – “Select configuration 4”. When the input becomes "active", parameters of
alternative configuration set 4 are copied in the working configuration.

Remark: copying an alternative set in working configuration causes the loss of the
previous loaded parameters. The only way to restore them is to save them in another
alternative configuration and recall it.

This function is usually used with multi-voltage and/or multi-frequency panel: cabling the cams
in a panel selector on the inputs of the controller it is possible to switch manually voltages and
frequency without using the parameter of the controller.

NB. The change of parameters happens only with the controller in OFF_RESET.

9.7
The controller has a non-volatile memory inside (with no need to be supplied), used to store
different information as parameters, counters or other. The memory is divided into different
zones. When the controller is powered, it performs a check on the data stored in each area: if
even just one area is incorrect, it displays an error message. This message contains a numeric
code (hexadecimal note); each bit if this code corresponds to a non-valid memory zone. A
chart follows with the zones and relative bits.
Area Versi Bit Value Description
on
1 1.00 1 0001 Coefficients for the calibration of the measuring inputs of the
controller.
2 1.00 2 0002 Different information (selected languages, lcd display contrast,
maintenance request).
3 1.00 3 0004 Counters
4 1.00 4 0008 History log of the maximum peaks.
5 1.00 5 0010 Parameters alternative configurations.
6 1.00 6 0020 Setpoint for the PLC
7 1.00 7 0040 Parameter:
8 1.00 8 0080 Parameters in text form (E.g. Configurable messages connected
to inputs)

If for example the value between brackets was “0004”, this means that the only counter zone
is not valid. If the value was “0041”, this means that the parameters zones (0040) and the
calibration zones (0001) are not valid.

If a zone is not valid, the normal operation sequences are not performed until when the
operator does not press ACK/ENTER + ESC/SHIFT: it is, in effect, necessary that the situation
is clear also because it might cause malfunctions (e.g. If the non-valid zone was the one of
the parameters). Only when the operator presses ACK/ENTER + ESC/SHIFT, the controller
recharges the default data for the data stored in non-valid zones: this means that if you turn
off the controller without pressing ACK/ENTER + ESC/SHIFT, in a subsequent start there will
be a signalling of not valid memory.

MC200 Technical Manual EAAM0578EN 213


This document is owned by SICES s.r.l..
All rights reserved. SICES s.r.l. reserves the right to modify this document without prior notice.
SICES has made any effort to ensure that the information herein provide are correct; in any case
SICES does not assume any liability for the use these information.
The disclosure by any means of this document to third parties is not allowed.

S.I.C.E.S. SRL
Società Italiana Costruzioni Elettriche Sumirago

Via Molinello 8B
21040 - Jerago con Orago (VA) ITALY

T +39 0331 212941


F +39 0331 216102

www.sices.eu
sales@sices.eu

SICES BRASIL LTDA

Avenida Portugal, 1174


Condomínio Empresarial ONIX
06696-060 / ITAPEVI (SP)
CNPJ 17.774.501/0001-28

+55 (11) 4193 2008

www.sicesbrasil.com.br
comercial@sicesbrasil.com.br