R4850G1 Rectifier User Manual V1.3: Environmental Specifications
R4850G1 Rectifier User Manual V1.3: Environmental Specifications
R4850G1 Rectifier User Manual V1.3: Environmental Specifications
3
Environmental Specifications
Item Specification
Operating temperature -40 °C to +75 °C (referring
to Figure 3)
(-40°F to +167°F)
Storage temperature -40 °C to +75 °C (not
packaged)
(-40°F to +167°F)
Efficiency The peak point is≥ 96%;
Relative humidity 5%-95% (non-condensing)
≥ 95%(230V AC,20%–90%
load) Altitude range ≤ 4000 m (13,123.2 ft)
Height x Width x 88.9 mm x 103 mm x 243 Note: If the altitude is between 3000 m (9842.4 ft) and 4000 m (13,123.2 ft), the
Depth mm temperature derates by 1 °C (1.8°F ) for each additional 200 m (656.2 ft).
Output short circuit A long term short circuit is allowed. Figure 2 efficiency(Vin = 230 VAC,Ta:25 °C / 77
protection After the fault is rectified, the rectifier is °F)
restored to a healthy state
automatically.
The rear panel of the rectifier provides an AC input Pin Definition Function
socket and a DC output socket. PIN1–PIN16 on the
DC output socket function as a signal interface. For AC input pins
the location of the pins, see Figure 4. For the L Live Live line
definitions of the pins, see Table 1.
PE PE Protect earth
N N Neutral line
Figure 4 Pins on the rear panel
Signal pins
PIN1 ADDRESS0 Address
PIN2 ADDRESS1 Address
PIN3 LOADSHARE+ Share bus
PIN4 NC NC
PIN5 CURRENT Output current
LIMIT+ limiting
PIN6 SEC_GND Secondary GND
PIN7 ADDRESS2 Address
PIN8 ADDRESS3 Address
PIN9 NC NC
PIN10 NC NC
PIN11 NC NC
PIN12 RS485- RS485-
PIN13 ADDRESS4 Address
PIN14 NC NC
PIN15 RS485+ RS485+
PIN16 DC- Output 48V-
Pre- Pre-charge Pre-charge
charge
DC output pins
DC+ DC+ Output:48V+
DC- DC- Output:48V-
Transport
CAUTION The product must be packed with firmly packing
Only trained and qualified personnel can be allowed box when transport. Out of the box the mark
to install or service the rectifier. To avoid electric
“prevent moisture ”,”lay down carefully” and
shock or burning, wear antistatic clothes, antistatic
gloves, and ESD wrist straps before operating the other required mark must have. Any transport
rectifier. tools are permitted if the product in the packing
Each rectifier input is protected by two fuses, one box .When transport must avoid rain and snow
for the live wire and the other for the neutral wire. attack directly and mechanical shock.
Storage
Installing the Rectifier
Product should be packaged in the packing box
Figure 5 Procedure for installing the before use .The store room should be meet :-40
rectifier °C (-40°F) to +70 °C(158°F) ambient
temperature ,related humidity less than
80%,dry ,ventilation and hasn’t any corrosive
gas.
DANGER
• The high -voltage power supply energize equipment. Contacting the high-voltage power supply directly or through a dampened
object may cause you to death.
• Improper operations on the high-voltage power supply may cause accidents such as fire or electric shock.
Run Green Steady on The rectifier output is normal. The rectifier runs properly, and no measure is
indicator required.
Off The rectifier has no output. Replace the rectifier if the AC input is normal.
The rectifier generates an Check that the electrical grid voltage is within
alarm due to AC input a normal range.
overvoltage or undervoltage
protection.
The rectifier is hibernated. No measure is required.
Suggestions