Sizing, Selection, Installation & Maintenance Instructions For Piston Type Water Hammer Arrestor
Sizing, Selection, Installation & Maintenance Instructions For Piston Type Water Hammer Arrestor
Sizing, Selection, Installation & Maintenance Instructions For Piston Type Water Hammer Arrestor
5. Threading the Model Z1705 into the determined location should be LONG RUN OF PIPING
engineers to size water distribution systems and are also used to size wa-
ter hammer arresters. Match total fixture units to correct model of water
TABLE II FIXTURE UNITS SIZING INFORMATION
hammer arresters required from Table I. All sizing data is based on flow
TYPES OF FIXTURE-UNITS
velocities of 10 F.P.S. or less. The sizing method was designed with a FIXTURE SUPPLY PUBLIC PRIVATE
maximum velocity of 10 F.P.S. to insure that the Water Hammer Arrester is CONTROL Total C.W. H.W. Total C.W. H.W.
capable of handling the shocks of maximum intensity that may be encoun- Water Closet Flush Valve 10 10 N/A 6 6 N/A
tered. Water Closet Flush Tank 5 5 N/A 3 3 N/A
Pedestal Urinal Flush Valve 10 10 N/A N/A N/A N/A
EXAMPLE - Fig 1 Stall or Wall Urinal Flush Valve 5 5 N/A N/A N/A N/A
C.W. =26 Fixture Units Fig 1 Stall or Wall Urinal Flush Tank 3 3 N/A N/A N/A N/A
Needs - 1705-B "A"
"B" Lavoratory Faucet 2 1 1/2 1 1/2 1 1 1
Bathtub Faucet 4 2 3 2 1 1/2 1 1/2
Shower Head Mixing Valve 4 2 3 2 1 2
H.W. =6 Fixture Units Flush Valve
Needs - 1705-A Bathroom Group
Closet
N/A N/A N/A 8 8 3
Flush Tank
Bathroom Group N/A N/A N/A 6 6 3
Closet
LONG RUNS OF PIPING TO REMOTE EQUIPMENT Separate Shower
Service Sink
Mixing Valve
Faucet
N/A
3
N/A
3
N/A
3
2
N/A
1
N/A
2
N/A
When long runs of piping are employed to serve a remote item of equip- Laundry Tubs (1-3) Faucet N/A N/A N/A 3 3 3
ment, the Water Hammer Arrester should be located as close to the quick Combination Fixture Faucet N/A N/A N/A 3 3 3
closure valve as possible. (see Fig. 4).
The size and quantity of Water Hammer Arrester to be installed in branch MULTI-FIXTURE BRANCH LINES
lines is shown in Table III. Ideally, the flow pressure in branch lines serving
fixtures should never exceed 55 PSIG. Pressure reducing valves should be Rule 1 - Branch lines of 20 feet or less.
installed to maintain proper pressure. When, however, flow pressures of Water Hammer Arrester should be placed at the end of the branch
65 to 85 PSIG are used, the next larger size Water Hammer Arrester should line between the last two fixtures served (see fig. 2). Select required
be selected (see Table III). model using fixture unit sizing.
TABLE III
Rule 2 - Branch lines exceeding 20 feet.
FOR FLOW
FOR FLOW PRESSURES
PRESSURESUP UPTO85 85 PSIG
PSIG An additional Water Hammer Arrester should be placed as shown
Nominal Pipe Diameter (see fig. 3). Select required models using fixture unit sizing. The
LENGTH
1/2" 3/4" 1" 1 1/4" 1 1/2" 2" sum of the fixture unit ratings of units X and Y shall be equal to or
OF PIPE
* ** * ** * ** * ** * ** * **
greater than the demand of the branches.
25’ A B A B B C C D D E E F
Fig. 2
50’ A B B C C D D E E F F CF RISER WATER HAMMER ARRESTER
Fig. 3
OVER 20'
75’ B C C D D E AE F F CF EF FF TYPICAL BRANCH LINE
Y X
100’ C D D E E F F CF CF EF FF EFF
125’ C D D E E CF AF DF EF FF EFF BFFF UP TO 20'
WARRANTY: ZURN Water Hammer Arrestors are guaranteed against defects of material or workmanship when used for the
services recommended. If in any recommended service, a defect develops due to material or workmanship, and the arrestor is
returned, freight prepaid, to ZURN within 12 months from date of purchase, it will be repaired or replaced free of charge. ZURNS'
liability shall be limited to our agreement to repair or replace the arrestor only.