Sizing, Selection, Installation & Maintenance Instructions For Piston Type Water Hammer Arrestor

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Z1705

® Sizing, Selection, Installation & Maintenance Instructions for


Piston Type Water Hammer Arrestor

SIZING AND SELECTION


1. Determine number of fixture units from Table l.
2. Determine shock arrester size from Table II.
INSTALLATION 3. Finally, match arrester to size and length of pipe run from Table lll.
1. Flush lines thoroughly prior to installation of Model Z1705.
2. Determine size of Water Hammer Arrester based on fixture units then TABLE I
refer to charts for proper devices. 1705
MODEL 1250
A B C D E F
3. The Model Z1705 should be located as close to the source of shock (SIZES)
as possible; one each on the hot and cold water lines. Use only teflon FIXTURE UNITS 1 TO 11 12 TO 32 22 TO 60 61 TO 113 114 TO 154 155 TO 330
tape to seal pipe threads.
4. To insure proper performance, the Model Z1705 should be installed
so that there is an unobstructed path to the arrester. WATER HAMMER ARRESTER QUICK CLOSURE VALVE

5. Threading the Model Z1705 into the determined location should be LONG RUN OF PIPING

done with an appropriate sized wrench on the hex only.


SHOCK
The fixture units shown in Table II represent the standard ratings used by Fig. 4
OUTLET

engineers to size water distribution systems and are also used to size wa-
ter hammer arresters. Match total fixture units to correct model of water
TABLE II FIXTURE UNITS SIZING INFORMATION
hammer arresters required from Table I. All sizing data is based on flow
TYPES OF FIXTURE-UNITS
velocities of 10 F.P.S. or less. The sizing method was designed with a FIXTURE SUPPLY PUBLIC PRIVATE
maximum velocity of 10 F.P.S. to insure that the Water Hammer Arrester is CONTROL Total C.W. H.W. Total C.W. H.W.
capable of handling the shocks of maximum intensity that may be encoun- Water Closet Flush Valve 10 10 N/A 6 6 N/A
tered. Water Closet Flush Tank 5 5 N/A 3 3 N/A
Pedestal Urinal Flush Valve 10 10 N/A N/A N/A N/A
EXAMPLE - Fig 1 Stall or Wall Urinal Flush Valve 5 5 N/A N/A N/A N/A
C.W. =26 Fixture Units Fig 1 Stall or Wall Urinal Flush Tank 3 3 N/A N/A N/A N/A
Needs - 1705-B "A"
"B" Lavoratory Faucet 2 1 1/2 1 1/2 1 1 1
Bathtub Faucet 4 2 3 2 1 1/2 1 1/2
Shower Head Mixing Valve 4 2 3 2 1 2
H.W. =6 Fixture Units Flush Valve
Needs - 1705-A Bathroom Group
Closet
N/A N/A N/A 8 8 3

Flush Tank
Bathroom Group N/A N/A N/A 6 6 3
Closet
LONG RUNS OF PIPING TO REMOTE EQUIPMENT Separate Shower
Service Sink
Mixing Valve
Faucet
N/A
3
N/A
3
N/A
3
2
N/A
1
N/A
2
N/A
When long runs of piping are employed to serve a remote item of equip- Laundry Tubs (1-3) Faucet N/A N/A N/A 3 3 3
ment, the Water Hammer Arrester should be located as close to the quick Combination Fixture Faucet N/A N/A N/A 3 3 3
closure valve as possible. (see Fig. 4).
The size and quantity of Water Hammer Arrester to be installed in branch MULTI-FIXTURE BRANCH LINES
lines is shown in Table III. Ideally, the flow pressure in branch lines serving
fixtures should never exceed 55 PSIG. Pressure reducing valves should be Rule 1 - Branch lines of 20 feet or less.
installed to maintain proper pressure. When, however, flow pressures of Water Hammer Arrester should be placed at the end of the branch
65 to 85 PSIG are used, the next larger size Water Hammer Arrester should line between the last two fixtures served (see fig. 2). Select required
be selected (see Table III). model using fixture unit sizing.
TABLE III
Rule 2 - Branch lines exceeding 20 feet.
FOR FLOW
FOR FLOW PRESSURES
PRESSURESUP UPTO85 85 PSIG
PSIG An additional Water Hammer Arrester should be placed as shown
Nominal Pipe Diameter (see fig. 3). Select required models using fixture unit sizing. The
LENGTH
1/2" 3/4" 1" 1 1/4" 1 1/2" 2" sum of the fixture unit ratings of units X and Y shall be equal to or
OF PIPE
* ** * ** * ** * ** * ** * **
greater than the demand of the branches.
25’ A B A B B C C D D E E F
Fig. 2
50’ A B B C C D D E E F F CF RISER WATER HAMMER ARRESTER
Fig. 3
OVER 20'
75’ B C C D D E AE F F CF EF FF TYPICAL BRANCH LINE

Y X
100’ C D D E E F F CF CF EF FF EFF
125’ C D D E E CF AF DF EF FF EFF BFFF UP TO 20'

150’ D E E F F CF DF FF FF DFF FFF FFFF


* Flow Pressures up to 65 psig
** Flow Pressures over 65 psig and up to 85 psig

WARRANTY: ZURN Water Hammer Arrestors are guaranteed against defects of material or workmanship when used for the
services recommended. If in any recommended service, a defect develops due to material or workmanship, and the arrestor is
returned, freight prepaid, to ZURN within 12 months from date of purchase, it will be repaired or replaced free of charge. ZURNS'
liability shall be limited to our agreement to repair or replace the arrestor only.

Mandatory Notice for California Use


Proposition 65 Warning This product contains chemicals known to the state of California to cause cancer and birth defects
or other reproductive harm.
ZURN INDUSTRIES LIMITED ¨ 3544 Nashua Drive ¨ Mississauga, Ontario L4V1L2 ¨ Phone: 905\405-8272 Fax: 905\405-1292
In the U.S.: ZURN INDUSTRIES, INC. ¨ SPECIFICATION DRAINAGE OPERATION ¨ 1801 Pittsburgh Ave. ¨ Erie, PA 16514
Phone: 814\455-0921 ¨ Fax: 814\454-7929 ¨ World Wide Web: www.zurn.com

Form # WH4 Date: 10/6/03 C.N. No. 91351 Rev. A

You might also like