Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

S&C Power Fuses

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

S&C Power Fuses For use with SM Refill Units

Types SM- 4, SM-5, SMD-20, and SMD-40d or SMU Fuse Units


Outdoor Distribution (4.16 kV through 34.5 kV)

Specifications
Station style mountings (except station—right-angle
Conditions of Sale style) of a given voltage rating can be provided with
STANDARD: Seller’s standard conditions of sale set insu­lators of the next lower voltage rating—add suffix
“-Z2” to the catalog number, or the next higher voltage
forth in Price Sheet 150 apply, except as modified under
“WARRANTY QUALIFICATIONS” on page 2. rating—add suffix “-Z3” to the catalog number.f
Station style mountings cannot be supplied less bases.
SPECIAL TO THIS PRODUCT: Station style mountings (except station—right-angle
style) can be supplied with tin-plated terminal pads. To
INCLUSIONS:
specify, add suffix “-Z5” to the catalog number.
SMD-20 and SMD-40 Mountings
Complete mountings include fuse-unit end fittings. Fuse-unit Overhead—pole-top style SMD-20 Mountings cannot be
end fittings for SMD-40 Power Fuses include Silencer. supplied less insulators.

A choice of connector arrangements is available with SM-4 and SM-5 Mountings


complete mountings as listed in the table on page 13. SM-4 and SM-5 Mountings are offered with a choice of
Specify the connector arrangement desired by adding Cypoxy or porcelain station post insulators.
the appropriate suffix letter to the catalog number of the
The standard insulator color is gray. When mountings are
selected mounting.
to be provided with special insulators, consult your nearest
Each overhead—pole-top style SMD-20 Mounting S&C Sales Office for availability.
includes mounting bracket and hardware.
Mountings can be supplied less insulators; add suffix
EXCLUSIONS: “‑Z1” to the catalog number.
SMD-20 and SMD-40 Mountings Mountings of a given voltage rating can be provided
Mountings do not include fuse units. with insulators of the next lower voltage rating—add suf­fix
“-Z2” to the catalog number, or the next higher voltage
SM-4® and SM-5® Mountings
rating—add suffix “-Z3” to the catalog number.f
Complete mountings and live parts do not include holders
or refill units. Mountings can be supplied less bases but including
insulators, add suffix “-Z4” to the catalog number.
Complete mountings and live parts do not include
con­nectors. Various connectors are available as listed in Mountings can be supplied with tin-plated terminal
the table on page 14. Specify quantity and catalog number pads. To specify, add suffix “-Z5” to the catalog number.
of connectors desired. Disconnect style parallel SM-5 Power Fuses are furnished
with aluminum terminal pads as a standard feature.
SPECIFICATION DEVIATIONS:
SMD-20 and SMD-40 Mountings
Live parts are not available separately for SMD-20 and
SMD-40 Power Fuses.
Station style SMD-20 and SMD-40 Mountings are offered a Cypoxy is the S&C trademark for S&C’s cycloaliphatic epoxy resin
with a choice of Cypoxy® a or porcelain station post system. Cypoxy is nontracking, self-scouring, nonweathering . . .
insulators. there’s never a compromise of insulation integrity. S&C Cypoxy station
post insu­lators meet or exceed the electrical and mechanical-strength
The standard insulator color is gray. When mountings are require­ments established in ANSI Standard C29.9 (1983) for porcelain
to be provided with special insulators, consult your nearest standard-strength station post insulators.
S&C Sales Office for availability. f Mountings rated 4.8 kV or 7.2 kV cannot be provided with lower rated
insulators. Fuse mountings rated 14.4 kV provided with insulators of the
Station style mountings (except station—right-angle next lower voltage rating will be furnished with porcelain station post
insulators rated 7.2 kV, T.R. No. 202. Fuse mountings rated 34.5 kV pro­
style) can be supplied less insulators; add suffix “-Z1” to vided with insulators of the next higher voltage rating will be furnished
the catalog number. with porcelain station post insulators rated 46 kV, T.R. No. 214.

d S&C Power Fuses—Types SM and SMD are manufactured in accordance with a quality system certified to ISO 9001:2000, and they are Rural Utilities
Service (RUS) accepted.

October 4, 2010© S&C Electric Company Specification Bulletin  242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM-4 and SM-5 Mountings


Conditions of Sale—Continued
For the standard warranty contained in seller’s standard
conditions of sale (as set forth in Price Sheet 150) to apply
WARRANTY QUALIFICATIONS:
to live parts when ordered separately, the live parts must
SMD-20 and SMD-40 Mountings be assembled on mountings in accordance with S&C
The standard warranty contained in seller’s standard Instruction Sheet 252-505.
con­ditions of sale (as set forth in Price Sheet 150) does not
The standard warranty contained in seller’s standard
apply to S&C SMD-20 or SMD-40 Mountings when installed
conditions of sale (as set forth in Price Sheet 150) does not
in conjunction with fuse units or end fittings of other than
apply to S&C SM Mountings when installed in con­junction
S&C manufacture, nor does it apply to S&C fuse units
with fuses of other than S&C manufacture.
or end fittings installed in mountings of other than S&C
manufacture.

2  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

Types SM-4 and SM-5


How to Order a Complete Power Fuse
1. Obtain the catalog number of the desired mounting from
the column entitled, “Mounting” on page 6. If only live
Types SMD-20 and SMD-40 parts are desired, refer to the “LIVE PARTS” table on
1. Obtain the catalog number of the desired mounting page 16.
from the column entitled, “Mounting” on pages 4 and 5.
Note: Live parts for SMD-20 or SMD-40 Power Fuses 2. Obtain the catalog number of the applicable holder from
cannot be ordered separately. the “Holder” column on page 6, reading from the same
line in which the selected mounting is listed.
2. Obtain the catalog number of the applicable SMU-20 or
SMU-40 fuse unit from the tables on pages 7 through 9, 3. Obtain the catalog number of the applicable refill unit
taking care to match the voltage rating of the fuse unit from the tables on pages 10 through 12, taking care to
to that of the mounting. match the voltage rating of the refill unit to that of the
mounting. Note: For each mounting rated 720E amperes,
3. Select the desired connector arrangement from the table order two holders and two refill units.
on page 13. Add the indicated suffix letter to the catalog
number of the mounting selected in Step 1, above. 4. Obtain the catalog number of the desired connector from
the table on page 14. Order two connectors for each
4. Obtain the catalog number of desired conversion kits, mounting or set of live parts.
parts, and maintenance supplies from the tables listed
on page 15. 5. Obtain the catalog number of desired parts from the table
listed on page 16.
How to Order Handling Tools
Obtain the catalog number(s) of recommended handling How to Order Handling Tools
tool(s) from the table on page 15. Refer to Specification Obtain the catalog number(s) of recommended handling
Bulletin 851-31. tools(s) from the table on page 16. Refer to Specification
Bulletin 851-31.

S&C Specification Bulletin 242-31  3


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMD-20 AND SMD-40 MOUNTINGS—Less Connectors12


Mounting (including Live Parts
Rating Leakage and End Fittings,
Distance less Connectors5) Page Reference
Style Type Amperes, RMS, to Ground, Polymer Porcelain for Dimensional
kV
Sym.3 Minimum, Insulators Insulators Information
Inter- Inches (mm) Catalog Catalog
Nom. Max BIL Max4
rupting Number Number
Overhead—
14.4 17.0 125 200 14 000 11 (279) — 92122R3a 17
Pole-Top67
14.4 17.0 150 200 14 000 17 (432) 92142R3-Pa 92142R3a 17
SMD-20
25d 27 150 200 12 500 17 (432) — 92123R3a 17
25d 27 150 200 12 500 26 (660)k 92123R3-Pa 92143R3ah 17
Overhead—
Pole-Top67
SMD-20 34.5 38 200 200 10 000 25Z\x (648) — 92544R3a 18

1 For available connector arrangements, refer to the table on page 13. 6 All SMD-20 Mountings are equipped with attachment hook to accom­
2 SMD-20 and SMD-40 Live Parts are not available separately. modate Loadbuster.
3 Symmetrical ratings assigned are based on available short-circuit 7 Connectors must be specified for Overhead—Pole-Top Style and
cur­rent at locations where the X/R ratio is 15. The interrupting ratings Right-Angle Style SMD-20 Mountings, refer to the table on page 13.
expressed in amperes, RMS asymmetrical are 1.6 times the symmetrical d Also suitable for protection of single-phase-to-neutral circuits (lines or
ratings listed. Higher symmetrical ratings have been determined for transformers) on 20/34.5 GrY-kV systems.
SMD‑20 Power Fuses where X/R = 10 and X/R = 5. These higher ratings k Leakage distance to ground is 26 inches (660 mm) for Catalog
as well as asymmetrical ratings are given in S&C Descriptive Bulletin Number 92143R3, 30 inches (762 mm) for Catalog Number 92123R3-P.
242-32.
a For provisions only for NEMA pad-terminal connectors or two-hole
4 SMU-20 Fuse Units for use in SMD-20 Mountings are available in compression connectors, add suffix “-G” to catalog number.
ratings through 200K amperes, as well as 200E amperes, and 20 DR.
h Meets 170 kV BIL rating requirement of IEC Publication 282-2.
5 Specify connectors, if desired, by adding the appropriate suffix let-
ter to catalog number. For example, “SMD-20 Outdoor Distribution
Power Fuse Mounting, Station—Vertical-Offset Style, Catalog Number
192222R2-L.” (See table, page 13.)

4  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMD-20 AND SMD-40 MOUNTINGS—Less Connectors12


Rating Catalog Number of Mounting
Leakage
(Including Live Parts and End
Distance Page Reference
kV Amperes, RMS, Sym.3 Fittings, less Connectors5)
Style Type to Ground, for Dimensional
Minimum, Cypoxy Station Porcelain Information
Inter-
Nom. Max BIL Max4 Inches (mm) Post Insulators Station Post
rupting
Insulators
Station—
Vertical-Offset6
14.4 17.0 110 200 14 000 15Z\x (394) 192222R2-E 192222R2 19
SMD-20 25 27 150 200 12 500 24 (610) 192223R2-E 192223R2 19
34.5 38 200 200 10 000 37 (940) 192504-E 192504 19

Station—
Inverted6
14.4 17.0 110 200 14 000 15Z\x (394) 192292-E 192292 20
SMD-20 25 27 150 200 12 500 24 (610) 192293-E 192293 20
34.5 38 200 200 10 000 37 (940) 192294-E 192294 20

Station—
Right-Angle67
14.4 17.0 110 200 14 000 15Z\x (394) 192232R3-Ea 192232R3a 21
SMD-20 25 27 150 200 12 500 24 (610) 192233R3-Ea 192233R3a 21
34.5 38 200 200 10 000 37 (940) 192234R3-Ea 192234R3a 21

Station—Vertical8
 4.8  5.5  95 400E 25 000 15Z\x (394)f 192320 192320-SP 22
SMD-40 14.4 17.0 110 400E 25 000 15Z\x (394) 192322 192322-SP 22
25 29 150 400E 20 000 24 (610) 192323 192323-SP 22

1 For available connector arrangements, refer to the table on page 13. 6 All SMD-20 Mountings are equipped with attachment hook to accom­
2 SMD-20 and SMD-40 Live Parts are not available separately. modate Loadbuster.
3 Symmetrical ratings assigned are based on available short-circuit 7 Connectors must be specified for Overhead—Pole-Top Style and
cur­rent at locations where the X/R ratio is 15. The interrupting ratings Right-Angle Style SMD-20 Mountings, refer to page 13.
expressed in amperes, RMS asymmetrical are 1.6 times the symmetri- 8 SMD-40 Mountings can be equipped with an optional attachment
cal ratings listed. Higher symmetrical ratings have been determined for hook to accommodate Loadbuster®. Specify by adding suffix “-LB” to the
SMD‑20 Power Fuses where X/R = 10 and X/R = 5. These higher ratings catalog number of the SMD-40 Mounting.
as well as asymmetrical ratings are given in S&C Descriptive Bulletin a For provisions only for NEMA pad-terminal connectors or two-hole
242-32. compression connectors, add suffix “-G” to catalog number.
4 SMU-20 Fuse Units for use in SMD-20 Mountings are available in f Mounting includes 14.4-kV 110-kV BIL Cypoxy station post insula-
ratings through 200K amperes, as well as 200E amperes, and 20 DR. tors. Leakage distance to ground is 10Z\x inches (267 mm) for mountings
5 Specify connectors, if desired, by adding the appropriate suffix let- with 95-kV BIL porcelain station post insulators; i.e., Catalog Number
ter to catalog number. For example, “SMD-20 Outdoor Distribution 192320-SP.
Power Fuse Mounting, Station—Vertical-Offset Style, Catalog Number
192222R2-L.” (See table, page 13.)

S&C Specification Bulletin 242-31  5


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM MOUNTINGS AND HOLDERS—Less Refill Units


Rating Catalog Number
Page
kV
Amperes, RMS, Mounting2 (Including Live Parts, less Reference for
Style Type Sym.1 Connectors3 less Holder) Dimensional
Holder4
Inter- Cypoxy Station Porcelain Station Information
Nom. Max BIL Max
rupting Post Insulators Post Insulators
Disconnect  7.2  8.3  95 200E 15 600 190501R1-Ef 190501R1 86051 23
180° Opening
14.4 17.0 110 200E 12 500 190502R1-E 190502R1 86052 23
Vertical5
SM-4 25 27 150 200E   9 400 190503R1-E 190503R1 86053 23
34.5 38 150 200E   6 250 — 190054 86054 23
34.5 38 200 200E   6 250 190504R1-E 190504R1 86054 23
 7.2  8.3  95 400E 26 000 190601R2-Ef 190601R2 86151R2 24
 7.2  8.3  95 720E 26 000 190561R3-Ef 190561R3 86151R2l 25
14.4 17.0 110 400E 34 000d 190602R2-E 190602R2 86152R2 24
SM-5 14.4 17.0 110 720E 25 000k 190562R3-E 190562R3 86152R2l 25
25 27 150 300E 20 000 190603R2-E 190603R2 86153R2 24
34.5 38 150 300E 17 500 — 190064 86154R2 24
34.5 38 200 300E 17 500 190604R2-E 190604R2 86154R2 24
Disconnect
90° Opening  7.2  8.3  95 400E 26 000 190801R2-Ef 190801R2 86191R2 26
Inverted
14.4 17.0 110 400E 34 000d 190802R2-E 190802R2 86192R2 26
SM-5 25 27 150 300E 20 000 190803R2-E 190803R2 86193R2 26
34.5 38 150 300E 17 500 — 190084 86194R2 26
34.5 38 200 300E 17 500 190804R2-E 190804R2 86194R2 26

Non-Disconnect  7.2  8.3  95 200E 15 600 190301R1-Efh 190301R1h 86041


Vertical
14.4 17.0 110 200E 12 500 190302R1-Eh 190302R1h 86042
SM-4 25 27 150 200E   9 400 190303R1-Eh 190303R1h 86043
34.5 38 150 200E   6 250  — 190034h 86044
34.5 38 200 200E 6 250 190304R1-Eh 190304R1h 86044
 7.2  8.3  95 400E 26 000 190401R2-Efh 190401R2h 86141R2
14.4 17.0 110 400E 34 000d 190402R2-Eh 190402R2h 86142R2
SM-5 25 27 150 300E 20 000 190403R2-Eh 190403R2h 86143R2
34.5 38 150 300E 17 500 — 190044h 86144R2
34.5 38 200 300E 17 500 190404R2-Eh 190404R2h 86144R2
Non-Disconnect  7.2  8.3  95 200E 15 600 190301R1-Efh 190301R1h 86281h
Upright
14.4 17.0 110 200E 12 500 190302R1-Eh 190302R1h 86282
SM-4 25 27 150 200E   9 400 190303R1-Eh 190303R1h 86283
34.5 38 150 200E   6 250 — 190034h 86284h
34.5 38 200 200E   6 250 190304R1-Eh 190304R1h 86284h
 7.2  8.3  95 400E 26 000 190401R2-Efh 190401R2h 86381R2
14.4 17.0 110 400E 34 000d 190402R2-Eh 190402R2h 86382R2
SM-5 25 27 150 300E 20 000 190403R2-Eh 190403R2h 86383R2
34.5 38 150 300E 17 500 — 190044h 86384R2
34.5 38 200 300E 17 500 190404R2-Eh 190404R2h 86384R2

1 Symmetrical ratings assigned are based on available short-circuit 5 All SM-4 Mountings in the Disconnect 180° Opening Vertical Style can
cur­rent at locations where the X/R ratio is 15. The interrupting ratings be equipped with attachment hook to accommodate Loadbuster. Specify
expressed in amperes, RMS asymmetrical are 1.6 times the symmetri- by adding suffix “-LB” to catalog number of the mounting.
cal ratings listed. Higher symmetrical ratings have been determined for d 60-hertz rating. For systems rated above 15.5 kV through 17.0 kV,
these fuses applied at lower system voltages and in locations where interrupting rating is 25,000 amperes, RMS symmetrical, 50/60 hertz.
X/R = 10 and X/R = 5. These higher ratings as well as asymmetrical
ratings are given in S&C Descriptive Bulletin 242-30. k 60-hertz rating.
f Mounting includes 14.4-kV 110-kV BIL Cypoxy station post insulators.
2 For live parts furnished separately, refer to the table on page 16.
h Product discontinued.
3 For available connectors, refer to the table on page 14.
l Two holders required with each mounting.
4 Holder does not carry Snuffler or Silencer.

6  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SWITCH BLADES
Rating
Catalog
Item kV
Amperes, Number
Cont.
Nom. Max

7.2 7.2 200 3231

Switch Blades, for use instead of SM-4 Holders in Disconnect 14.4 17 200 3232
180° Opening Vertical Style SM-4 Mountings 25 27 200 3233

34.5 38 200 3234

7.2 7.2 400 3241

Switch Blades, for use instead of SM-5 Holders in Disconnect 14.4 17 400 3242
180° Opening Vertical Style SM-5 Mountings 25 27 300 3243

34.5 38 300 3244

14.4 17 200 3252


Switch Blades, for use instead of SMU-20 Fuse Units in all
25 27 200 3253
styles except Station—Inverted SMD-20 Mountings
34.5 38 200 3254

SMU-20® FUSE UNITS (For use in SMD-20 Mountings)


14.4 kV Nominal, 17.0 kV Max
“K” Ratings “E” Ratings “DR” Ratings

Rating, Catalog Rating, Rating, Catalog


Catalog Number
Amperes Number Amperes Amperes Number

S&C “K” S&C Std. S&C “DR”


Speed Speed Speed
TCC 165-2 TCC 115-2 TCC 175-2

1 702001

S&C Std. S&C Slow S&C Very Slow


Speed
TCC 153-2 TCC 119-2 TCC 176-2

3K 702003 3DR 622003


6K 702006 5E 612005 4DR 622004
8K 702008 7E 612007 5DR 622005
10K 702010 10E 612010 7DR 622007
12K 702012 13E 612013 10DR 622010
15K 702015 15E 612015 712015 15DR 622015
20K 702020 20E 612020 712020 20DR 622020
25K 702025 25E 612025 712025
30K 702030 30E 612030 712030
40K 702040 40E 612040 712040
50K 702050 50E 612050 712050 602050
65K 702065 65E 612065 712065 602065
80K 702080 80E 612080 712080 602080
100K 702100 100E 612100 712100 602100
140K 702140 125E 612125 712125 602125
200K 702200 150E 612150 712150 602150
175E 612175 712175 602175
200E 612200 712200 602200

S&C Specification Bulletin 242-31  7


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMU-20® FUSE UNITS (For use in SMD-20 Mountings)—Continued


25 kV Nominal, 27 kV Max1
“K” Ratings “E” Ratings “DR” Ratings

Rating, Catalog Rating, Rating, Catalog


Catalog Number
Amperes Number Amperes Amperes Number
S&C “K” S&C Std. S&C “DR”
Speed Speed Speed
TCC 165-2 TCC 115-2 TCC 175-2

1 703001

S&C Std. S&C Slow S&C Very Slow


Speed
TCC 153-2 TCC 119-2 TCC 176-2

3K 703003 3DR 623003


6K 703006 5E 613005 4DR 623004
8K 703008 7E 613007 5DR 623005
10K 703010 10E 613010 7DR 623007
12K 703012 13E 613013 10DR 623010
15K 703015 15E 613015 713015 15DR 623015
20K 703020 20E 613020 713020 20DR 623020
25K 703025 25E 613025 713025
30K 703030 30E 613030 713030
40K 703040 40E 613040 713040
50K 703050 50E 613050 713050 603050
65K 703065 65E 613065 713065 603065
80K 703080 80E 613080 713080 603080
100K 703100 100E 613100 713100 603100
140K 703140 125E 613125 713125 603125
200K 703200 150E 613150 713150 603150
175E 613175 713175 603175
200E 613200 713200 603200

34.5 kV Nominal, 38 kV Max


“K” Ratings “E” Ratings “DR” Ratings

Rating, Catalog Rating, Rating, Catalog


Catalog Number
Amperes Number Amperes Amperes Number
S&C “K” S&C Std. S&C “DR”
Speed Speed Speed
TCC 165-2 TCC 115-2 TCC 175-2

1 704001

S&C Std. S&C Slow S&C Very Slow


Speed
TCC 153-2 TCC 119-2 TCC 176-2

3K 704003 3DR 624003


6K 704006 5E 614005 4DR 624004
8K 704008 7E 614007 5DR 624005
10K 704010 10E 614010 7DR 624007
12K 704012 13E 614013 10DR 624010
15K 704015 15E 614015 714015 15DR 624015
20K 704020 20E 614020 714020 20DR 624020
25K 704025 25E 614025 714025
30K 704030 30E 614030 714030
40K 704040 40E 614040 714040
50K 704050 50E 614050 714050
65K 704065 65E 614065 714065 604050
80K 704080 80E 614080 714080 604065
100K 704100 100E 614100 714100 604080
140K 704140 125E 614125 714125 604100
200K 704200 150E 614150 714150 604125
175E 614175 714175 604150
200E 614200 714200 604175
604200

1 Also suitable for protection of single-phase-to-neutral circuits (lines


or transformers) on 20/34.5 GrY-kV systems.

8  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMU-40® FUSE UNITS (For use in SMD-40 Mountings)

Rating, 4.8 kV Nominal, 5.5 kV Max 14.4 kV Nominal, 17.0 kV Max 25 kV Nominal, 29 kV Max
Amperes Catalog Number Catalog Number Catalog Number
S&C Std. S&C Std. S&C Std.
Speed
TCC 115-2 TCC 115-2 TCC 115-2
1 820001 822001 823001
2 820002 822002 823002
S&C Std. S&C Slow S&C Std. S&C Slow S&C Std. S&C Slow
Speed
TCC 153-2 TCC 119-2 TCC 153-2 TCC 119-2 TCC 153-2 TCC 119-2
3E 820003 822003 823003
5E 820005 822005 823005
7E 820007 822007 823007
10E 820010 822010 823010
13E 820013 822013 823013
15E 820015 830015 822015 832015 823015 833015
20E 820020 830020 822020 832020 823020 833020
25E 820025 830025 822025 832025 823025 833025
30E 820030 830030 822030 832030 823030 833030
40E 820040 830040 822040 832040 823040 833040
50E 820050 830050 822050 832050 823050 833050
65E 820065 830065 822065 832065 823065 833065
80E 820080 830080 822080 832080 823080 833080
100E 820100 830100 822100 832100 823100 833100
125E 820125 830125 822125 832125 823125 833125
150E 820150 830150 822150 832150 823150 833150
175E 820175 830175 822175 832175 823175 833175
200E 820200 830200 822200 832200 823200 833200
250E 820250 830250 822250 832250 823250 833250
300E 820300 830300 822300 832300 823300 833300
400E 820400 830400 822400 832400 823400 833400

S&C Specification Bulletin 242-31  9


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM-4® REFILL UNITS (For use in SM-4 Holders)

Rating, 7.2 kV Nominal, 8.3 kV Max1 14.4 kV Nominal, 17.0 kV Max


Amperes Catalog Number Catalog Number
S&C Std. S&C Std.
Speed
TCC 115-4 TCC 115-4
1 121001R4 122001R4
2 121002R4 122002R4
S&C Std. S&C Slow S&C Std. S&C Slow S&C Coord.
Speed
TCC 153-4 TCC 119-4 TCC 153-4 TCC 119-4 TCC 179-4
3E 121005R4 122005R4
5E 121007R4 122007R4
7E 121010R4 122010R4
10E 121015R4 122015R4
13E 121020R4 122020R4
15E 121025R4 251025R4 122025R4 252025R4
20E 121030R4 251030R4 122030R4 252030R4
25E 121040R4 251040R4 122040R4 252040R4
30E 121050R4 251050R4 122050R4 252050R4
40E 121060R4 251060R4 122060R4 252060R4
50E 121075R4 251075R4 122075R4 252075R4
65E 121100R4 251100R4 122100R4 252100R4
80E 121125R4 251125R4 122125R4 252125R4
100E 121150R4 251150R4 122150R4 252150R4
125E 121200R4 251200R4 122200R4 252200R4
150E 121250R4 251250R4 122250R4 252250R4
175E 121275R4 251275R4 122275R4 252275R4
200E 121300R4 251300R4 122300R4 252300R4
210  382210R4f

Rating, 25 kV Nominal, 27 kV Max 34.5 kV Nominal, 38 kV Max


Amperes Catalog Number Catalog Number
S&C Std. S&C Std.
Speed
TCC 115-4 TCC 115-4
1 123001R4 124001R4
2 123002R4 124002R4
S&C Std. S&C Slow S&C Std. S&C Slow
Speed
TCC 153-4 TCC 119-4 TCC 153-4 TCC 119-4
123005R4 124005R4
3E
123007R4 124007R4
5E
123010R4 124010R4
7E
123015R4 124015R4
10E
123020R4 124020R4
13E
123025R4 124025R4
15E
123030R4 253025R4 124030R4 254025R4
20E
123040R4 253030R4 124040R4 254030R4
25E
123050R4 253040R4 124050R4 254040R4
30E
123060R4 253050R4 124060R4 254050R4
40E
123075R4 253060R4 124075R4 254060R4
50E
123100R4 253075R4 124100R4 254075R4
65E
123125R4 253100R4 124125R4 254100R4
80E
123150R4 253125R4 124150R4 254125R4
100E
123200R4 253150R4 124200R4 254150R4
125E
123250R4 253200R4 124250R4 254200R4
150E
123275R4 253250R4 124275R4 254250R4
175E
123300R4 253275R4 124300R4 254275R4
200E
253300R4 254300R4
1 Rated 7.2 kV nominal for use in SM-4 Holders rated 7.2 kV.
f This S&C Coordinating Speed refill unit should be applied where the
maximum continuous load current does not exceed 200 amperes and
where all fault currents below 1000 amperes will be cleared by another
fuse.

10  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM-5® REFILL UNITS (For use in SM-5 Holders)


Rating, 4.16 kV Nominal, 4.76 kV Max1 7.2 kV Nominal, 8.3 kV Max2
Amperes Catalog Number Catalog Number
S&C Std. S&C Std.
Speed
TCC 115-4 TCC 115-4
1 130001R4 131001R4
2 130002R4 131002R4
S&C Std. S&C Slow S&C Coord. S&C Std. S&C Slow S&C Coord.
Speed
TCC 153-4 TCC 119-4 TCC 173-4 TCC 153-4 TCC 119-4 TCC 173-4
3E 130005R4 131005R4
5E 130007R4 131007R4
7E 130010R4 131010R4
10E 130015R4 131015R4
13E 130020R4 131020R4
15E 130025R4 260025R4 131025R4
20E 130030R4 260030R4 131030R4
25E 130040R4 260040R4 131040R4
30E 130050R4 260050R4 131050R4
40E 130060R4 260060R4 131060R4
50E 130075R4 260075R4 131075R4
65E 130100R4 260100R4 131100R4
80E 130125R4 260125R4 131125R4
100E 130150R4 260150R4 131150R4
125E 130200R4 260200R4 131200R4
150E 130250R4 260250R4 131250R4
175E 130275R4 260275R4 131275R4
200E 130300R4 260300R4 131300R4
250E 130400R4 260400R4 131400R4 261400R4
300E 130500R4 260500R4 131500R4 261500R4
400E 130600R4 260600R4 131600R4 261600R4
410 381410R4df 381410R4f
420 381420R4df 381420R4f

Rating, 14.4 kV Nominal, 17.0 kV Max 25 kV Nominal, 27 kV Max


Amperes
Catalog Number Catalog Number
S&C Std. S&C Std.
Speed
TCC 115-4 TCC 115-4
1 132001R4 133001R4
2 132002R4 133002R4
S&C Std. S&C Slow S&C Coord. S&C Std. S&C Slow
Speed
TCC 153-4 TCC 119-4 TCC 173-4 TCC 153-4 TCC 119-4
3E 132005R4 133005R4
5E 132007R4 133007R4
7E 132010R4 133010R4
10E 132015R4 133015R4
13E 132020R4 133020R4
15E 132025R4 262025R4 133025R4 263025R4
20E 132030R4 262030R4 133030R4 263030R4
25E 132040R4 262040R4 133040R4 263040R4
30E 132050R4 262050R4 133050R4 263050R4
40E 132060R4 262060R4 133060R4 263060R4
50E 132075R4 262075R4 133075R4 263075R4
65E 132100R4 262100R4 133100R4 263100R4
80E 132125R4 262125R4 133125R4 263125R4
100E 132150R4 262150R4 133150R4 263150R4
125E 132200R4 262200R4 133200R4 263200R4
150E 132250R4 262250R4 133250R4 263250R4
175E 132275R4 262275R4 133275R4 263275R4
200E 132300R4 262300R4 133300R4 263300R4
250E 132400R4 262400R4 133400R4 263400R4
300E 132500R4 262500R4 133500R4 263500R4
400E 132600R4 262600R4
410 382410R4f
420 382420R4f
1 Rated 4.16 kV nominal, for use in SM-5 Holders rated 7.2 kV when Interrupting ratings are those listed in S&C Descriptive Bulletin 242-30
applied in listed mountings rated 7.2 kV for system voltages through for 7.2-kV SM-5 Power Fuses applied to systems rated 2.4/4.16 Y kV.
4.16 kV. f These S&C Coordinating Speed refill units should be applied where
2 Rated 7.2 kV nominal, for use in SM-5 Holders rated 7.2 kV when the maximum continuous load current does not exceed 400 amperes
applied in listed mountings rated 7.2 kV for system voltages through and where all fault currents below 3000 amperes for Catalog Numbers
4.8 kV through 7.2 kV. 381410R4 and 382410R4 and 4000 amperes for Catalog Numbers
381420R4 and 382420R4 will be cleared by another fuse.
d Catalog numbers are in italics because these are 7.2-kV refill units.

S&C Specification Bulletin 242-31  11


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM-5® REFILL UNITS (For use in SM-5 Holders)


Rating, 34.5 kV Nominal, 38 kV Max
Amperes Catalog Number
S&C Std.
Speed
TCC 115-4
1 134001R4
2 134002R4
S&C Std. S&C Slow
Speed
TCC 153-4 TCC 119-4

3E 134005R4
5E 134007R4
7E 134010R4
10E 134015R4
13E 134020R4
15E 134025R4 264025R4
20E 134030R4 264030R4
25E 134040R4 264040R4
30E 134050R4 264050R4
40E 134060R4 264060R4
50E 134075R4 264075R4
65E 134100R4 264100R4
80E 134125R4 264125R4
100E 134150R4 264150R4
125E 134200R4 264200R4
150E 134250R4 264250R4
175E 134275R4 264275R4
200E 134300R4 264300R4
250E 134400R4 264400R4
300E 134500R4 264500R4

12  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

CONNECTORS—Two Provided per Mounting—For use with SMD-20 and SMD-40 Mountings
To Specify Connector Arrangement
Add Catalog
Accommodating Conductors Number Suffix
Illustration Description
Size and Material

Two No. 6 solid (13.3 mm2) through No. 2 stranded


(44.4 mm2) copper or aluminum in one groove, No. 2
Parallel-Groove Connectors solid (33.6 mm2) through 250 kc mil (168 mm2) stranded -Dd
copper or aluminum, or 4/0 ACSR (161 mm2) in the other
groove

Bronze Body, Tin Plated, Single No. 2 solid (33.6 mm2) through 500 kc mil (335 mm2)
Z\x –13 3 2Z\x Galvanized Steel Bolt. Same stranded copper or aluminum, or 397.5 kc mil ACSR -K
as Catalog Number 4740R1 (329 mm2)

Aluminum-Alloy Body, Tin Plated, Two No. 2 solid (33.6 mm2) through 500 kc mil (335 mm2)
Z\x –13 3 2Z\x Galvanized Steel Bolts. Same stranded copper or aluminum, or 397.5 kc mil ACSR -L
as Catalog Number 4744 (329 mm2)

Provision only for NEMA pad-terminal


connectors or two-hole compression
-Gd
connectors. Includes tin plated terminal
adapters but does not include hardware

No. 8 solid (8.4 mm2) through 250 kc mil (168 mm2)


Eye-Bolt Connectors -Md
stranded copper or aluminum, or 4/0 ACSR (161 mm2)

d Applies only to station—right-angle and overhead—pole-top style


SMD-20 Mountings.

S&C Specification Bulletin 242-31  13


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

CONNECTORS—For use with SM-4® and SM-5® Mountings


Catalog Number
Illustration and Description Accommodating Conductor
Upper Lower
Terminal Pad Terminal Pad

No. 2 solid (33.6 mm2) through 500 kc mil (335 mm2) stranded
4741R2 —
copper or aluminum
Aluminum Alloy Body, Tin Plated, Two
Z\x –13 3 2C\v Galvanized Steel Bolts

No. 2 solid (33.6 mm2) through 500 kc mil (335 mm2) stranded
— 4746
copper or aluminum
Aluminum Alloy Body, Tin Plated, Two
Z\x –13 3 2Z\v Galvanized Steel Bolts

— 4564R1-A
No. 6 solid (13.3 mm2) through 250 kc mil (168 mm2) copper or
aluminum
4564R1-B —

— 4565R1-A
1/0 solid (53.5 mm2) through 500 kc mil (335 mm2) copper or
aluminum
4565R1-B —
Standard Bronze-Pad Terminal,
Tin Plated, Four-Bolt. Includes Z\x-inch — 4567R1-A
galvanized steel hardware for attachment 2/0 stranded (89 mm2) through 800 kc mil (539 mm2) copper
to terminal pads of fuses or aluminum
4567R1-B —

14  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

CONVERSION KITS—For use with SMD-20 Power Fuses


Item Catalog Number

Conversion Kit, adapts superseded 34.5-kV station—vertical-offset style mountings1 to accept shorter, 28Z\x-inch (724 mm) 5256
34.5-kV SMU-20 Fuse Units listed on page 8 [superseded length was 34Z\v inches (870 mm)]

1 Identified by the following catalog numbers:


 92224R2  92224R1  92224
192224R2 192224R1 192224
192224R2-HF 192224R1-HF 192224-HF

PARTS—For use with SMD-20 and SMD-40 Power Fuses


For Fuse Unit Rated,
Item kV, Nominal Catalog Number
From To
Spare Fuse-Unit End Fittings—for use in SMD-20 Mountings, all styles except
7.2 34.5 3095
Station—Inverted
Spare Fuse-Unit End Fittings—for use in SMD-20 Mountings, Station—Inverted Style 14.4 34.5 3096
Spare Fuse-Unit End Fittings—for use in SMD-40 Mountings, Station—Vertical Style 4.8 25 3085d
Replacement Silencers—for use in SMD-40 Mountings, Station—Vertical Style 4.8 25 FDA-1064

d Includes Silencer.

MAINTENANCE SUPPLIES—For use with SMD-20 and SMD-40 Power Fuses


Item For Fuse Unit Catalog Number

Fuse-Unit Recoating Kit—one-half pint Light Gray Epoxy Polyester Gloss Enamel 13-E-1
All 9900-027
and one-half pint Catalyst 13-C-0 (two coats for ten fuse units).1 Requires thinner listed below
Thinner for above—one pint All FA-104643

1 Shelf life is one year from date of manufacture.

RECOMMENDED HANDLING TOOLS—For use with SMD-20 and SMD-40 Power Fuses
Item Catalog Number

Large Clampf 4410R3

Station Prong 4402R2

Distribution Prong 4416

Talon™ 4440

Universal Pole l
f For installing and removing fuse units in SMD-40 Power Fuse
Mount­ings.
l Select to match height of installation. Refer to Specification Bulletin
851-31.

S&C Specification Bulletin 242-31  15


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

LIVE PARTS—For SM-4 and SM-5 Power Fuses


Item For Fuse Type Catalog Number

SM-4 87119

Disconnect, 180° Opening Vertical SM-5 87519R2

SM-5 (Parallel) 87169R3

Disconnect, 90° Opening Inverted SM-5 87199R2

PARTS—For use with SM-4 and SM-5 Power Fuses


For Holder
Item Catalog Number
Rated (kV, Nominal) Type

7.2 SM-4 FA-972


7.2 SM-5 FA-2341d
14.4 SM-4 FA-973
14.4 SM-5 FA-2342d
Spare Spring-and-Cable Assembly
23 or 25 SM-4 FA-974
23 or 25 SM-5 FA-2343d
34.5 SM-4 FA-975
34.5 SM-5 FA-2344d
Pull-Ring Assembly for Holder, Disconnect, 7.2 through 34.5 SM-4 FDA-1025
180° Opening Vertical 7.2 through 34.5 SM-5 FDA-1027

Pivot/Rain Shield Assembly for Holder, 7.2 through 34.5 SM-4 FDA-1028
Disconnect, 180° Opening Vertical 7.2 through 34.5 SM-5 FDA-1029
d For use only in holders carrying an arrow-shaped nameplate. Spring-
and-cable assemblies for holders which do not carry an arrow-shaped
nameplate are no longer available—so a new holder with the appropriate
voltage rating must be ordered.

RECOMMENDED HANDLING TOOLS—For use with SM-4 and SM-5 Power Fuses
For Fuse Mounting
Item Catalog Number
Style Type

Locking Prong Disconnect 90° Opening Inverted SM-5 4404

Disconnect 180° Opening Vertical


Station Prong SM-4 or SM-5 4402R2
and Disconnect 90° Opening Inverted

Universal Pole l

l Select to match height of installation. Refer to Specification Bulletin


851-31.

16  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMD-20 Power Fuse


Overhead—Pole-Top Style

Dimensions in inches (mm)

Rating Catalog Number12 Dimensions in Inches (mm)


Leakage (Complete Mounting Incl.
Distance Net Wt.,
Live Parts
to Ground Lbs. (Kg.)
kV and End Fittings,
Amps, Minimum, less Connectors) A1 A2 M1 M2 P R1 R2 S3
Max Inches
Polymer Porcelain Polymer Porcelain
Nom. Max BIL (mm)
Insulators Insulators Insulators Insulators

14.4 17.0 125 200 11 — 12M\,


92122R3d (327) 6B\, 28B\, 30 5Z\x 21Z\x 14 6M\, — 23
(279) (168) (727) (762) (140) (546) (356) (175) (10)

14.4 17.0 150 200 17 12M\,


92142R3-Pd 92142R3d (327) 6B\, 28B\, 30 5Z\x 21Z\x 14 6M\, 17 27
(432) (168) (727) (762) (140) (546) (356) (175) (8) (12)

25a 27 150 200 17 — 13C\,


92123R3d (340) 5C\, 31Z\x 35Z\, 4M\, 22Z\zn 15B\, 8Z\v — 25
(432) (137) (800) (892) (124) (560) (397) (210) (11)

25a 27 150 200 26j 13C\,


92123R3-Pd 92143R3d (340) 5C\, 31Z\x 35Z\, 4M\, 22Z\zn 15B\, 8Z\v 19 30
(660) (137) (800) (892) (124) (560) (397) (210) (9) (14)

1 All SMD-20 Mountings are equipped with attachment hook to accom­ a Also suitable for protection of single-phase-to-neutral circuits (lines
modate Loadbuster. or transformers) on 20/34.5 GrY-kV systems.
2 Connectors must be specified, refer to the table on page 13. d For provisions only for NEMA pad-terminal connectors or two-hole
compression connectors, add suffix “-G” to catalog number.
3 Dimension applies to mounting furnished with optional parallel-groove
connectors (mounting catalog number suffix “-D”). Dimension varies for j Leakage distance to ground is 26 inches for Catalog Number
mountings furnished with other connector arrangements. 92143R3, 30 inches for Catalog Number 92123R3-P.

S&C Specification Bulletin 242-31  17


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMD-20 Power Fuse


Overhead—Pole-Top Style

Dimensions in inches (mm)

37
(940)
23Z\,
(587)
14C\v
(375)

10Z\v
(260)

19
(483)

3B\,
(92)

45Z\,
(1146)

Rating Leakage
Distance to Catalog Number12 (Complete
Net Wt.,
kV Ground Mounting Incl. Live Parts and
Lbs. (Kg.)
Amps, Max Minimum, Inches End Fittings, less Connectors)
Nom. Max BIL (mm)

34.5 38 200 200 25Z\x (648) 92544R3d 33 (15)


1 All SMD-20 Mountings are equipped with attachment hook to accom­ d For provisions only for NEMA pad-terminal connectors or two-hole
modate Loadbuster. compression connectors, add suffix “-G” to catalog number.
2 Connectors must be specified, refer to the table on page 13.

18  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMD-20 Power Fuse


Station—Vertical-Offset Style

Dimensions in inches (mm)

1Z\x 8M\,
(38) (225)
7
(178)
>\zn (14) DIA. HOLES
ON 10 (25) CENTERS
(18 per side) Z\,
(3)

>\zn (14) DIA. HOLES


ON 1C\v0 (44)
CENTERS
SEE NOTE

B\zn
(8)

2
(51)
>\zn 3 1>\zn (14 3 40) SLOTS
ON 20 (51) CENTERS

NOTE: Terminal pads provided on both sides of fuse mounting.

Catalog Number (Complete


Leakage Mounting Incl. Live Parts
Rating Dimensions in Inches (mm) Net Wt., Lbs. (Kg.)
Distance and End Fittings, less
to Connectors)12 Number
Ground of slots
kV Minimum, per side
Cypoxy Porcelain Cypoxy Porcelain
Amps, Inches
Max (mm)
Station Post Station Post A1 A2 B C F L M1 M2 N R Station Post Station Post
Nom. Max BIL Insulators Insulators Insulators Insulators

14.4 17.0 110 200 15Z\x 192222R2-E 192222R2 19M\, 14Z\x 10 27 18ZC\zn 25 36C\, 18C\, 4Z\zn 27B\, 3 60 74
(394) (505) (368) (254) (686) (478) (635) (924) (467) (103) (702) (27) (34)
24 24C\v 18Z\x 14 31 22Z\v 29 43M\, 21M\, 4C\, 32B\, 77 104
25 27 150 200 192223R2-E 192223R2 5
(610) (629) (470) (356) (787) (565) (737) (1114) (556) (111) (829) (35) (47)
37 30C\, 22Z\x 18 39 28 37 53M\, 27M\, 5Z\x 38Z\, 98 136
34.5 38 200 200 192504-E 192504 9
(940) (772) (572) (457) (991) (711) (940) (1368) (708) (140) (968) (44) (62)

1 All SMD-20 Mountings are equipped with attachment hook to accom­ 2 For available connector arrangements, refer to the table on page 13.
modate Loadbuster.

S&C Specification Bulletin 242-31  19


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMD-20 Power Fuse


Station—Inverted Style

Dimensions in inches (mm)

8M\,
(225) >\zn (14) DIA. HOLES
1Z\x 7 2
ON 10 (25) CENTERS (51)
(38) (178)

3Z\x (89)

C\v (19)

>\zn (14) DIA. HOLES


ON 1C\v0 (44)
CENTERS

>\zn 3 1>\zn SLOTS


(14 3 40)

Catalog Number
Leakage (Complete Mounting
Rating Distance Incl. Live Parts and Dimensions in Inches (mm) Net Wt., Lbs. (Kg.)
to End Fittings, less
Ground Connectors)12
kV Minimum, Cypoxy Porcelain Cypoxy Porcelain
Amps, Inches Station Station Station Station
(mm) A1 A2 B C D F L M1 M2 N R
Max Post Post Post Post
Nom. Max BIL
Insulators Insulators Insulators Insulators
15Z\x 14C\, 14Z\, 10 25 17M\, 17Z\v 22 35B\, 18C\, 4 22Z\, 53 67
14.4 17.0 110 200 192292-E 192292
(394) (365) (359) (254) (635) (454) (438) (559) (905) (467) (102) (562) (24) (30)
24 18C\, 18Z\, 14 29 21M\, 20C\v 26 43Z\, 21M\, 4Z\v 26Z\, 70 97
25 27 150 200 192293-E 192293
(610) (467) (460) (356) (737) (556) (527) (660) (1095) (556) (108) (664) (32) (44)
37 22C\, 22Z\, 18 35 25M\, 26C\v 32 53Z\, 27M\, 4Z\v 30Z\, 90 128
34.5 38 200 200 192294-E 192294
(940) (568) (562) (457) (889) (657) (679) (813) (1349) (708) (108) (765) (41) (58)
1 All SMD-20 Mountings are equipped with attachment hook to accom­ 2 For available connector arrangements, refer to the table on page 13.
modate Loadbuster.

20  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMD-20 Power Fuse


Station—Right-Angle Style

Dimensions in inches (mm)


1
2Z\x (25)
(64) ZZ\zn (17) DIA. HOLES

5 (127) 3 (76)

1Z\x 3 1 (25)
(38) (76)

1 (25)
3
(76)
2Z\x
(64)
3Z\x
3 (89)
(76)
1 (25)
ZZ\zn (17) DIA. HOLES (4)

Catalog Number (Complete


Leakage Mounting Incl. Live Parts
Rating Dimensions in Inches (mm) Net Wt., Lbs. (Kg.)
Distance and End Fittings, less
to Ground Connectors)12
kV Minimum, Cypoxy Porcelain
Cypoxy Porcelain
Amps, Inches Station Station
Station Post Station Post A1 A2 B M1 M2 R1 R2
Max (mm) Post Post
Nom. Max BIL Insulators Insulators
Insulators Insulators
15Z\x 21B\, 17 10 39Z\x 35Z\v 30B\, 17B\, 50 64
14.4 17.0 110 200 192232R3-Ed 192232R3d
(394) (549) (432) (254) (1003) (895) (778) (448) (23) (29)
24 25C\v 20C\, 14 46C\, 41Z\x 34C\v 20C\, 60 87
25 27 150 200 192233R3-Ed 192233R3d
(610) (654) (518) (356) (1178) (1054) (883) (518) (27) (39)
37 29Z\, 22Z\, 18 54Z\, 51Z\, 38Z\, 24 72 110
34.5 38 200 200 192234R3-Ed 192234R3d
(940) (740) (562) (457) (1375) (1299) (968) (610) (33) (50)
1 All SMD-20 Mountings are equipped with attachment hook to accom­ d For provisions only for NEMA pad-terminal connectors or two-hole
modate Loadbuster. compression connectors, add suffix “-G” to catalog number.
2 Connectors must be specified, refer to the table on page 13.

S&C Specification Bulletin 242-31  21


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SMD-40 Power Fuse


Station—Vertical Style

Dimensions in inches (mm)

8M\,
(225)
7 Optional attachment hook
(178) for use with Loadbuster®
1Z\x 2 (catalog number suffix “-LB”)
7C\zn
(38) (51) (183)

3Z\, (79)

>\zn (14) DIA. HOLES


ON 10 (25) CENTERS
(18 per side)

>\zn (14) 3 1>\zn (40) SLOTS


ON 20 (51) CENTERS
1M\, (48)

6Z\x
(165)
2
(51)

Z\x 
(13)
1C\v (44)
>\zn (14)
5Z\v DIA. HOLES 4C\,
(133) (111)
BASE DETAIL TERMINAL PAD DETAIL HINGE DETAIL
(TOP AND BOTTOM)

Rating Catalog Number Dimensions in Inches (mm) Net Weight, Lbs. (Kg.)
Leakage (Complete Mounting
Distance incl. Live Parts and
kV to End Fittings, less Number
Connectors)123 Cypoxy Porcelain
Amps, Ground, of Slots Station Station
A1 A2 B C F L M R
Max Minimum, Cypoxy Porcelain per Side Post Post
Inches Station Station Insulators Insulators
Nom. Max BIL (mm) Post Post
Insulators Insulators
15Z\x f 13B\,f 10f 27 19Z\v 25 36C\,f 21C\,f 65 73
 4.8  5.5  95 400E (394) 192320d 192320-SP 12B\,
(321) (346) (254) (686) (489) (635) (924) (543) 3 (29) (33)

14.4 17.0 110 400E 15Z\x 192322 12B\, 13B\,


192322-SP (321) 10 29 22C\v 27 38C\v 21C\, 4 70 85
(394) (346) (254) (737) (578) (686) (984) (543) (32) (39)

25 29 150 400E 24 192323 16B\, 17B\,


192323-SP (422) 14 33 26Z\v 31 45Z\, 25C\, 6 85 110
(610) (448) (356) (838) (667) (787) (1146) (645) (39) (50)

1 For available connector arrangements, refer to the table on page 13. f These dimensions are for mountings with 110-kV BIL Cypoxy station
post insulators. Deduct 2Z\x inches (64 mm) for mountings furnished
2 SMD-40 Live Parts are not available separately. with 95-kV BIL porcelain station post insulators; i.e., Catalog Number
3 To specify optional Loadbuster Tool attachment hook, add suffix “‑LB” 192320-SP. Leakage distance to ground is 10Z\x inches (267 mm) for
to catalog number; e.g., Catalog Number 192320-LB. mounting with porcelain station post insulators.
d Mounting includes 14.4-kV 110-kV BIL Cypoxy station post
insulators.

22  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM-4h Power Fuse


Disconnect, 180° Opening, Vertical Style

Dimensions in inches (mm)

8M\,
(225) 2
1Z\x >\zn (14)
(38) 7 2 (51) >\zn (14) DIA.
(178) (51) HOLES

5Z\, (130)
>\zn (14) DIA.
HOLES ON 10 1C\v
(44)
(25) CENTERS

>\zn (14) 3 1>\zn


(40) SLOTS
3Z\x (89)
1C\v (44)

1Z\x (38) 1Z\v (32) DIA. Z\x (13)—13 TAPPED HOLES


(TWO EACH SIDE) 3M\, (98)

BASE DETAIL TO END OF HOLDER IN 180° OPEN POSITION

h SM-4 Mountings in the Disconnect 180° Opening Vertical Style can be equipped with attachment hook to accommodate Loadbuster. Specify by add­ing
suffix “-LB” to catalog number of mounting.

Rating Catalog Number Dimensions in Inches (mm) Net Weight, Lbs. (Kg.)
kV Mounting12
Cypoxy Porcelain
Amps, Porcelain Station Station
Cypoxy
Station Holder3 A1 A2 B C F M1 M2 R X Holder
Nom. Max BIL Max Station Post Post Post
Post Insulators Insulators
Insulators
Insulators

7.2 8.3 95 200E 190501R1-Ej 190501R1 86051 12C\,† 13Z\x† 10‡ 24 12Z\x 30C\,† 15Z\x 20C\v† 5C\v 50 57 8.0
(314) (343) (254) (610) (318) (772) (394) (527) (146) (23) (26) (3.6)

14.4 17.0 110 200E 190502R1-E 190502R1 86052 12C\,§ 13Z\x 10 28 16Z\x 34C\, 19Z\x 20C\v§ 5C\v 56 70 9.0
(314) (343) (254) (711) (419) (873) (495) (527) (146) (25) (32) (4.1)

25 27 150 200E 190503R1-E 190503R1 86053 16C\,§ 17Z\x 14 32 20C\v 42B\, 23C\v 24C\v§ 5B\, 72 99 10.3
(416) (445) (356) (813) (527) (1083) (603) (629) (143) (33) (45) (4.6)

34.5 38 150 200E — 190054 86054 16C\,§ 17Z\x 14 40 28 49M\, 31 24C\v§ 6 — 105 14.3
(416) (445) (356) (1016) (711) (1267) (787) (629) (152) (48) (6.5)

34.5 38 200 200E 190504R1-E 190504R1 86054 20C\,§ 21Z\x 18 40 28 53M\, 31 28C\v§ 6 90 128 14.3
(518) (546) (458) (1016) (711) (1368) (787) (730) (152) (41) (58) (6.5)
1 Mounting includes live parts, less holder. For live parts furnished sep­ † Mounting includes 14.4-kV BIL Cypoxy station post insulators.
arately, refer to the table on page 16. ‡ Deduct 2 inches (51 mm) from dimension of mountings equipped with
2 For available connectors, refer to the table on page 14. porcelain station post insulators.
§ Add Z\x inch (13 mm) to dimension of mountings equipped with porce­
3 Holder does not carry snuffler or silencer. lain station post insulators.
f Mounting includes 14.4-kV, 110-kV BIL Cypoxy station post
insulators.

S&C Specification Bulletin 242-31  23


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM-5 Power Fuse


Disconnect, 180° Opening, Vertical Style

Dimensions in inches (mm)

8M\,
(225) 2
1Z\x >\zn (14)
(38) 7 2 (51) >\zn (14) DIA.
(178) (51) HOLES

5Z\x (140)
>\zn (14) DIA.
HOLES ON 10 1C\v
(44)
(25) CENTERS

>\zn (14) 3 1>\zn


(40) SLOTS
5ZC\zn (148)
1C\v (44)

1Z\x (38) 1Z\v (32) DIA. Z\x (13)—13 TAPPED HOLES


(TWO EACH SIDE)
4M\, (124)

BASE DETAIL TO END OF HOLDER IN 180° OPEN POSITION

Rating Catalog Number Dimensions in Inches (mm) Net Weight, Lbs. (Kg.)
kV Mounting12
Cypoxy Porcelain
Amps, Porcelain Station Station
Cypoxy
Station Holder3 A1 A2 B C F M1 M2 R X Holder
Nom. Max BIL Max Station Post Post Post
Post Insulators Insulators
Insulators
Insulators

7.2 8.3 95 400E 190601R2-Ej 190601R2 86151R2 12C\,‡ 13Z\x‡ 10‡ 24 12Z\x 33B\,‡ 19B\, 21C\v‡ 5C\v 54 61 21.0
(314) (343) (254) (610) (318) (854) (498) (552) (146) (24) (28) (9.5)

14.4 17.0 110 400E 190602R2-E 12C\, 13Z\x 10


190602R2 86152R2 (314) 28 16Z\x 37B\, 23B\, 21C\v 5C\v 60 74 23.3
(343) (254) (711) (419) (956) (600) (552) (146) (27) (34) (10.5)

25 27 150 300E 190603R2-E 16C\, 17Z\x 14


190603R2 86153R2 (416) 32 20C\v 45M\, 27M\, 25C\v 5B\, 76 103 25.8
(445) (356) (813) (527) (1165) (708) (654) (143) (34) (47) (11.7)

34.5 38 150 300E — 190064 16C\, 17Z\x 14


86154R2 (416) 40 28 53Z\, 35Z\, 25C\v 6 — 109 31.8
(445) (356) (1016) (711) (1349) (892) (654) (152) (49) (14.4)

34.5 38 200 300E 190604R2-E 20C\, 21Z\x 18


190604R2 86154R2 (518) 40 28 57Z\, 35Z\, 29C\v 6 94 132 31.8
(546) (458) (1016) (711) (1451) (892) (756) (152) (43) (60) (14.4)
1 Mounting includes live parts, less holder. For live parts furnished sep­ f Mounting includes 14.4-kV, 110-kV BIL Cypoxy station post
arately, refer to the table on page 16. insulators.
2 For available connectors, refer to the table on page 14. ‡ Deduct 2 inches (51 mm) from dimension of mountings equipped with
porcelain station post insulators.
3 Holder does not carry snuffler or silencer.

24  S&C Specification Bulletin 242-31


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM-5 Power Fuse


Disconnect, 180° Opening—Vertical Style

Dimensions in inches (mm)

>\zn (14) DIA. HOLES 3 (76)


1Z\x 8M\,
(38) (225) B\, (16) 2
7 (51)
(178)
1C\v (44)
6 (152)
>\zn (14) DIA. 5C\v (146)
HOLES ON
10 (25)
CEN­TERS

>\zn (14) 3 1>\zn


(40) SLOTS

10 (254) 10
1Z\v (32) DIA. (254)
1Z\x
(38)

3
(76) B\,
11Z\, (16)
(283)
>\zn (14) DIA.
HOLES

Rating Catalog Number Dimensions in Inches (mm) Net Weight, Lbs. (Kg.)
kV Mounting12
Cypoxy Porcelain
Amps, Porcelain Station Station
Cypoxy Holder3 A B C F M1 M2 R Holder
Station
Nom. Max BIL Max Station Post Post Post
Post Insulators Insulators
Insulators
Insulators
12Z\x‡ 10‡ 24 12Z\x 34‡ 20Z\v 22C\,‡ 84 91 21.0
 7.2  8.3  95 720E 190561R3-Ef 190561R3 86151R2a
(318) (254) (610) (318) (864) (514) (568) (38) (41) (9.5)
12Z\x 10 28 16Z\x 38 24Z\v 22C\, 90 104 23.3
14.4 17.0 110 720E 190562R3-E 190562R3 86152R2a
(318) (254) (711) (419) (965) (616) (568) (41) (47) (10.5)
1 Mounting includes live parts, less holder. For live parts furnished f Mounting includes 14.4-kV, 110-kV BIL Cypoxy station post
separately, refer to the table on page 16. insulators.
2 For available connectors, refer to the table on page 14. a Two holders required with each mounting.
‡ Deduct 2Z\x inches (64 mm) from dimension of mountings equipped
3 Holder does not carry snuffler or silencer. with porcelain station post insulators.

S&C Specification Bulletin 242-31  25


S&C Power Fuses — Types SM-4, SM-5, SMD-20, and SMD-40

SM-5 Power Fuse


Disconnect, 90° Opening, Inverted Style

Dimensions in inches (mm)

1Z\x (38) 1Z\x (38)

7 8M\, (225)
(178)

>\zn (14) 3 1>\zn (40) SLOTS >\zn (14) DIA. HOLES ON


1Z\v (32) DIA. 10 (25) CENTERS

1C\v (44)
>\zn (14)
1C\v
(44) 2 (51)

>\zn (14) DIA. HOLES


Z\x (13)–13
TAPPED HOLES
3C\v (95) (TWO EACH 5Z\,
SIDE) (130)
3Z\v
(83)

Rating Catalog Number Dimensions in Inches (mm) Net Weight, Lbs. (Kg.)
kV Mounting12
Cypoxy Porcelain
Amps, Porcelain Station Station
Cypoxy
Station Holder3 A1 A2 B C F M R X Holder
Nom. Max BIL Max Station Post Post Post
Post Insulators Insulators
Insulators
Insulators

7.2  8.3 95 400E 190801R2-Ef 190801R2 86191R2 12C\,‡ 13Z\x‡ 10‡ 24 12Z\x 39C\,‡ 20M\,‡ 5C\v 53 60 23.5
(314) (343) (254) (610) (318) (1000) (530) (146) (24) (27) (10.7)

14.4 17.0 110 400E 190802R2-E 12C\, 13Z\x


190802R2 86192R2 (314) 10 28 16Z\x 43C\, 20M\, 5C\v 59 73 25.8
(343) (254) (711) (419) (1102) (530) (146) (27) (33) (11.7)

25 27 150 300E 190803R2-E 16C\, 17Z\x


190803R2 86193R2 (416) 14 32 20C\v 51B\, 24M\, 5B\, 75 102 28.3
(445) (356) (813) (527) (1311) (632) (143) (34) (46) (12.8)

34.5 38 150 300E — 190084 16C\, 17Z\x


86194R2 (416) 14 40 28 62M\, 24M\, 6 — 108 34.3
(445) (356) (1016) (711) (1597) (632) (152) (49) (15.5)

34.5 38 200 300E 190804R2-E 20C\, 21Z\x


190804R2 86194R2 (518) 18 40 28 62M\, 28M\, 6 93 131 34.3
(546) (458) (1016) (711) (1597) (733) (152) (42) (59) (15.5)
1 Mounting includes live parts, less holder. For live parts furnished sep­ f Mounting includes 14.4-kV, 110-kV BIL Cypoxy station post
arately, refer to the table on page 16. insulators.
2 For available connectors, refer to the table on page 14. ‡ Deduct 2 inches (51 mm) from dimension of mountings equipped with
porcelain station post insulators.
3 Holder does not carry snuffler or silencer.

26  S&C Specification Bulletin 242-31


Printed in U.S.A.

You might also like