Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

3-Fault Analysis

Download as pdf or txt
Download as pdf or txt
You are on page 1of 104

3.1 Fault Analysis 3.

1 Fault Analysis
Fault Analysis Fault Analysis

Ref : APP12 – APP14 Ref : APP12 – APP14

Issue C Issue C
Last Release : June 2011 Last Release : June 2011

Fault analysis
y Fault analysis
y

● Short-circuit calculation need for various power system studies ● Short-circuit calculation need for various power system studies

● To
T determine
d t i the
th capacity
it or rating
ti off electrical
l t i l equipment
i t ● To
T determine
d t i the
th capacity
it or rating
ti off electrical
l t i l equipment
i t

● To set protective relays ● To set protective relays

● To specify current transformer ● To specify current transformer

Schneider Electric - Energy Automation – Technical Institute 2 Schneider Electric - Energy Automation – Technical Institute 2
Summaryy Summaryy

Types of fault Types of fault


Symmetrical components Symmetrical components
Impedance transformation Impedance transformation
2 windings transformer 2 windings transformer
g transformer
3 windings g transformer
3 windings
Overhead line and cable Overhead line and cable
Synchronous machine Synchronous machine
Induction machine Induction machine

Schneider Electric - Energy Automation – Technical Institute 3 Schneider Electric - Energy Automation – Technical Institute 3

Types of fault Types of fault


Symmetrical components Symmetrical components
Impedance transformation Impedance transformation
2 windings transformer 2 windings transformer
3 windings transformer 3 windings transformer
Overhead line and cable Overhead line and cable
Synchronous machine Synchronous machine
Induction machine Induction machine

Schneider Electric - Energy Automation – Technical Institute 4 Schneider Electric - Energy Automation – Technical Institute 4
Generalityy Generality
y

● Faults are the main causes of loss of electricity supply ● Faults are the main causes of loss of electricity supply

● IIn most cases, faults l d to short-circuit


f l lead h i i ● IIn most cases, faults l d to short-circuit
f l lead h i i
● Between conductors ● Between conductors
● Between conductor and earth ● Between conductor and earth

● Short-circuit must be cleared by isolating the faulty equipement ● Short-circuit must be cleared by isolating the faulty equipement

Schneider Electric - Energy Automation – Technical Institute 5 Schneider Electric - Energy Automation – Technical Institute 5

Fault causes Fault causes


EXTERNAL INTERNAL EXTERNAL INTERNAL

● Weather : ● definition : ● Weather : ● definition :

● Storm, snow wind,


Storm snow, frost…
wind frost Those faults are not initiated by ● Storm, snow wind,
Storm snow, frost…
wind frost Those faults are not initiated by
external causes external causes
● First cause of fault on overhead line ● First cause of fault on overhead line
(lightning strike scause 50% to 80% (lightning strike scause 50% to 80%
off fault
f lt on OHL) ● example : off fault
f lt on OHL) ● example :

Overvoltage due to : Overvoltage due to :


● Mecanical ● Mecanical
● resonance ● resonance
● OHL : branchs, birds, … ● Wrong operation ● OHL : branchs, birds, … ● Wrong operation
● UGC : excavation machine ● UGC : excavation machine

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 6 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 6
Fault classification Fault classification

● Permanent fault ● Permanent fault


is a fault which affects a device and prevents its restoration into service until is a fault which affects a device and prevents its restoration into service until
action has been taken at the point of the fault
fault. action has been taken at the point of the fault
fault.

● Transient fault ● Transient fault


is an insulation fault which only temporarily affects a device's dielectric is an insulation fault which only temporarily affects a device's dielectric
properties which are restored after a short time properties which are restored after a short time

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 7 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 7

Fault classification Fault classification

● Developing fault ● Developing fault


is an insulation fault which begins as a phase-to-earth (or phase-to-phase) is an insulation fault which begins as a phase-to-earth (or phase-to-phase)
fault and develops into a two-phase or three-phase fault
fault. fault and develops into a two-phase or three-phase fault
fault.

● Intermittent fault ● Intermittent fault


is a transient fault which recurs repeatedly in the same place and due to the is a transient fault which recurs repeatedly in the same place and due to the
same cause same cause

● Self extinguishing fault ● Self extinguishing fault


is an insulation fault where the arc extinguishes without it being necessary to is an insulation fault where the arc extinguishes without it being necessary to
disconnect the device from the system for its essential dielectric properties disconnect the device from the system for its essential dielectric properties
to be restored. to be restored.

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 8 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 8
Statistics Statistics

Transmission 15.2 fault per 100 km per year Transmission 15.2 fault per 100 km per year
mono 83 % mono 83 %
poly 17 % poly 17 %

Sub-transmission 37.5 fault per 100 km per year Sub-transmission 37.5 fault per 100 km per year
mono 68 % mono 68 %
poly 32 % poly 32 %

Distribution 150 fault per 100 km per year Distribution 150 fault per 100 km per year
mono 64 % mono 64 %
poly 36 % poly 36 %

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 9 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 9

Consequences
q Consequences
q

● Short-circuit leads to two effects ● Short-circuit leads to two effects


● Drop of voltage ● Drop of voltage
● Overcurrent ● Overcurrent

● Overcurrent has effect on ● Overcurrent has effect on


● Thermal withstand because of RMS value ● Thermal withstand because of RMS value
● Breaking capacity because of decaying aperiodic component ● Breaking capacity because of decaying aperiodic component
● Mechanical withstand because of peak value ● Mechanical withstand because of peak value

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 10 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 10
Types of fault Types of fault

S mmetrical components
Symmetrical S mmetrical components
Symmetrical
Impedance transformation Impedance transformation
2 windings transformer 2 windings transformer
3 windings transformer 3 windings transformer
Overhead line and cable Overhead line and cable
Synchronous machine Synchronous machine
Induction machine Induction machine

Schneider Electric - Energy Automation – Technical Institute 11 Schneider Electric - Energy Automation – Technical Institute 11

Generality Generality

● During rated operation, three phase system is symmetrical. ● During rated operation, three phase system is symmetrical.

● Therefore,
Th f the
th three
th phase
h systems
t can be
b come d
down tto a single
i l ● Therefore,
Th f the
th three
th phase
h systems
t can be
b come d
down tto a single
i l
phase system. phase system.

● This single phase representation cannot be used when symmetry is ● This single phase representation cannot be used when symmetry is
broken (during fault for example) broken (during fault for example)

● Calculation on unbalanced system become complex. ● Calculation on unbalanced system become complex.
Kirchhoff laws must be applied on each phase. Kirchhoff laws must be applied on each phase.

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 16 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 16
Generalityy Generality
y

● Symmetrical component simplified calculation for unbalanced system. ● Symmetrical component simplified calculation for unbalanced system.

● This
Thi method
h d relies
li on the
h ffollowing
ll i theorem:
h ● This
Thi method
h d relies
li on the
h ffollowing
ll i theorem:
h
Any unbalanced three phase system can be split into three symmetrical three Any unbalanced three phase system can be split into three symmetrical three
phase systems: the symmetrical components phase systems: the symmetrical components

● The three symmetrical components are : ● The three symmetrical components are :
●Positive
P iti sequence (I1) ●Positive
P iti sequence (I1)
●Negative sequence (I2) ●Negative sequence (I2)
●Zero sequence. (I0) ●Zero sequence. (I0)

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 17 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 17

Mathematical representation
p Mathematical representation
p

● Current : ● Current :
IA 1 1 1 I1 I1 1 a a² IA IA 1 1 1 I1 I1 1 a a² IA
IB = a² a 1
a I2 I2 = 1/3 1 a²
a a IB IB = a² a 1
a I2 I2 = 1/3 1 a²
a a IB
IC a a² 1 I0 I0 1 1 1 IC IC a a² 1 I0 I0 1 1 1 IC
● Voltage: ● Voltage:
VA 1 1 1 V1 V1 1 a a² VA VA 1 1 1 V1 V1 1 a a² VA
VB = a² a 1 V2 V2 = 1/3 1 a² a VB VB = a² a 1 V2 V2 = 1/3 1 a² a VB
VC a a² 1 V0 V0 1 1 1 VC VC a a² 1 V0 V0 1 1 1 VC
● Ohm
O law : ● Ohm
O law :
V1 Vn Z1 0 0 I1 V1 Vn Z1 0 0 I1
V2 = 0 – 0 Z2 0 · I2 V2 = 0 – 0 Z2 0 · I2
V0 0 0 0 Z0 I0 V0 0 0 0 Z0 I0
● Other relations : ● Other relations :
1+a+a
a² = 0 ; a³ = 1
a 1+a+a
a² = 0 ; a³ = 1
a

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 18 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 18
Kirchhoff law with classical method Kirchhoff law with classical method
Ia ZS Ia ZS
Vn Va Vn Va

Ib ZS Zm Zm Ib ZS Zm Zm
Vb Vb

Ic ZS Zm Ic ZS Zm
Vc Vc

∆VA = IAZS + IBZM + ICZM ∆VA = IAZS + IBZM + ICZM


∆VB = IAZM + IBZS + ICZM ∆VB = IAZM + IBZS + ICZM
∆VC = IAZM + IBZM + ICZS ∆VC = IAZM + IBZM + ICZS

Matrix notation : Matrix notation :


∆VA ZS ZM ZM IA ∆VA ZS ZM ZM IA
∆VB = ZM ZS ZM IB ∆VB = ZM ZS ZM IB
∆VC ZM ZM ZS IC ∆VC ZM ZM ZS IC

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 19 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 19

Kirchhoff law with symmetrical


y component
p Kirchhoff law with symmetrical
y component
p
1 1 1 ∆V1 ZS ZM ZM 1 1 1 I1 1 1 1 ∆V1 ZS ZM ZM 1 1 1 I1
a² a 1
a ∆V2 = ZM ZS ZM a² a 1
a I2 Multiply by [A]-1 a² a 1
a ∆V2 = ZM ZS ZM a² a 1
a I2 Multiply by [A]-1
a a² 1 ∆V0 ZM ZM ZS a a² 1 I0 a a² 1 ∆V0 ZM ZM ZS a a² 1 I0

-1 -1
∆V1 1 1 1 ZS ZM ZM 1 1 1 I1 ∆V1 1 1 1 ZS ZM ZM 1 1 1 I1
∆V2 = a² a 1 ZM ZS ZM a² a 1 I2 ∆V2 = a² a 1 ZM ZS ZM a² a 1 I2
∆V0 a a² 1 ZM ZM ZS a a² 1 I0 ∆V0 a a² 1 ZM ZM ZS a a² 1 I0

∆V1 1 a a² ZS ZM ZM 1 1 1 I1 ∆V1 1 a a² ZS ZM ZM 1 1 1 I1
∆V2 = 1/3 1 a² a ZM ZS ZM a² a 1 I2 ∆V2 = 1/3 1 a² a ZM ZS ZM a² a 1 I2
∆V0 1 1 1 ZM ZM ZS a a² 1 I0 ∆V0 1 1 1 ZM ZM ZS a a² 1 I0

∆V1 ZS- ZM ZM + a ZS + a² ZM ZM + a ZM + a² ZS 1 1 1 I1 ∆V1 ZS- ZM ZM + a ZS + a² ZM ZM + a ZM + a² ZS 1 1 1 I1


∆V2 = 1/3 ZS- ZM ZM + a²ZS + a ZM ZM + a² ZM + a ZS a² a 1 I2 ∆V2 = 1/3 ZS- ZM ZM + a²ZS + a ZM ZM + a² ZM + a ZS a² a 1 I2
∆V0 ZS + 2 ZM ZS + 2 ZM ZS + 2 ZM a a²
a 1 I0 ∆V0 ZS + 2 ZM ZS + 2 ZM ZS + 2 ZM a a²
a 1 I0

∆V1 ZS - ZM 0 0 I1 Zd 0 0 I1 ∆V1 ZS - ZM 0 0 I1 Zd 0 0 I1
∆V2 = 0 ZS - ZM 0 I2 = 0 Zi 0 I2 ∆V2 = 0 ZS - ZM 0 I2 = 0 Zi 0 I2
∆V0 0 0 ZS + 2 ZM I0 0 0 Z0 I0 ∆V0 0 0 ZS + 2 ZM I0 0 0 Z0 I0
Schneider Electric - Energy Automation – Technical institut – 19/11/2010 20 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 20
Kirchhoff law with symmetrical Kirchhoff law with symmetrical
component component
Ia ZS Ia ZS
Vn Va Vn Va

Ib ZS Zm Zm Ib ZS Zm Zm
Vb Vb

Ic ZS Zm Ic ZS Zm
Vc Vc

● Ohm law is simplified: ● Ohm law is simplified:


V1 Vn ∆V1 V1 Vn ∆V1
V2 = 0 – ∆V2 V2 = 0 – ∆V2
V0 0 ∆V0 V0 0 ∆V0

V1 Vn Z1 0 0 I1 V1 Vn Z1 0 0 I1
V2 = 0 – 0 Z2 0 · I2 V2 = 0 – 0 Z2 0 · I2
V0 0 0 0 Z0 I0 V0 0 0 0 Z0 I0

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 21 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 21

Balanced system Balanced system


G G

I1 I1

P iti
Positive G P iti
Positive G

I2 = 0 I2 = 0
Negative Negative

I0 = 0 I0 = 0
Zero Zero

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 22 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 22
Unbalanced system Unbalanced system
G G

Fault Fault

E, ZG,1 ZT,1 I1 ZC,1, CC,1 E, ZG,1 ZT,1 I1 ZC,1, CC,1


P iti
Positive G ZL,1
L1 P iti
Positive G ZL,1
L1

ZG,2
G2 ZT,2
T2 I2 ZC,2
C 2 , CC,2
C2 ZG,2
G2 ZT,2
T2 I2 ZC,2
C 2 , CC,2
C2

Negative ZL,2 Negative ZL,2

ZT,0 I0 ZC,0 , CC,0 ZT,0 I0 ZC,0 , CC,0


Zero ZL,0 Zero ZL,0
3 ZN 3 ZN

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 23 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 23

Three p
phase fault Three p
phase fault

Phase A Phase A

Phase B Phase B
IA IA
Phase C Phase C
IB IB

F IC F IC

IA + IB + IC = 0 VA VB VC VA = VB = VC IA + IB + IC = 0 VA VB VC VA = VB = VC

Balanced short circuit : Balanced short circuit :


I0 = 0 ; I2 =0 I0 = 0 ; I2 =0

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 24 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 24
Three p
phase fault Three p
phase fault

Z1 Z1
I1 F I1 F

Vn Vn

N1 N1

Only positive sequence plays a Only positive sequence plays a


part in equivalent scheme part in equivalent scheme

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 25 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 25

Phase to p
phase fault Phase to p
phase fault

Phase A Phase A

Phase B Phase B
IA = 0 IA = 0
Phase C Phase C
IB IB

F IC F IC

IB = -IC VA VB VC VB = VC IB = -IC VA VB VC VB = VC

I0 = 0 I0 = 0
IA= 0  I1 = - I2 IA= 0  I1 = - I2

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 26 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 26
Phase to p
phase fault Phase to p
phase fault

Z1 F Z1 F
I1 I1

Vn Vn

N1 N1

Z2 F Z2 F
I2 I2
Both positive and negative Both positive and negative
sequences play a part in sequences play a part in
equivalent scheme equivalent scheme

N2 N2

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 27 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 27

Phase to earth fault Phase to earth fault

Phase A Phase A

Phase B Phase B
IA IA
Phase C IB Phase C IB
IC IC
F F

IB = IC = 0 VA VB VC VA = 0 IB = IC = 0 VA VB VC VA = 0

IB = IC = 0  I1 = I2 = I0 IB = IC = 0  I1 = I2 = I0

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 28 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 28
Phase to earth fault Phase to earth fault
Z1 F Z1 F
I1 I1

Vn Vn
N1 N1

Z2 Z2
I2 I2
F F

All sequences play a part in All sequences play a part in


N2 N2
equivalent scheme equivalent scheme

Z0 Z0
I0 I0
F F

N0 N0

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 29 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 29

y
Synthesis y
Synthesis

G G

3 Ph Ph-E Ph-Ph Ph-Ph-E 3 Ph Ph-E Ph-Ph Ph-Ph-E


ZG,1 ZT,1 ZL,1 ZG,1 ZT,1 ZL,1

~ E Positive sequence ~ E Positive sequence

ZG,2 ZT,2 ZL,2 ZG,2 ZT,2 ZL,2

Negative sequence Negative sequence

ZT,0 ZL,0 ZT,0 ZL,0

3 ZN Zero sequence
q 3 ZN Zero sequence
q

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 30 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 30
Resistive fault Resistive fault
a a
b b
c c
ZF ZF ZF ZF ZF ZF ZF ZF ZF ZF

ZF ZF
E E
ZF ZF

Positive Positive
ZF ZF

ZF ZF

Negative 3 ZF ZF Negative 3 ZF ZF

ZF ZF

Zero ZF Zero ZF
E E

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 31 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 31

Earthing
g impedance
p Earthing
g impedance
p

N IA0 N IA0

IB0 IB0

IC0 IC0

3IA0 IA0 + IB0 + IC0 = 3IA0 3IA0 IA0 + IB0 + IC0 = 3IA0

Zero sequence voltage between N and E: Zero sequence voltage between N and E:
R V0 = 3IA0.R R V0 = 3IA0.R
Zero sequence impedance of earthing impedance: Zero sequence impedance of earthing impedance:
E Z0 = V0 / IA0= 3R E Z0 = V0 / IA0= 3R

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 32 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 32
Zero sequence
q equivalent
q network Zero sequence
q equivalent
q network
Generator Transformer Generator Transformer
Line F Line F
N N
RT RT
R R
Single line diagram Single line diagram
E E

N0 ZG0 ZT0 ZL0 I0 F0 N0 ZG0 ZT0 ZL0 I0 F0

3R 3RT V0 3R 3RT V0

E0 (N0) E0 (N0)
Zero sequence equivalent network Zero sequence equivalent network

V0 = Zero sequence voltage V0 = Zero sequence voltage


I0 = Zero sequence current I0 = Zero sequence current
V0 = -II0 (ZT0 + ZL0) V0 = -II0 (ZT0 + ZL0)

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 33 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 33

Example
p 1 Example
p 1

Cable L2 Cable L2

T2 T2
Load
L d Load
L d

Zsource Zsource

Cable L1 Cable L1

T1 T1

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 34 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 34
Example
p 1: three p
phase fault Example
p 1: three p
phase fault
Z1T2 Z1L2 Z1T2 Z1L2

Z1s Z1s
I1 I1
Z1T1 F Z1L1 Z1T1 F Z1L1
Vn Vn

N1 N1

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 35 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 35

Example phase to p
p 1: p phase fault Example phase to p
p 1: p phase fault

Z1T2 Z1L2 Z1T2 Z1L2

Z1s Z1s
I1 I1
Z1T1 F Z1L1 Z1T1 F Z1L1
Vn Vn

N1 N1
Z2T2 Z2L2 Z2T2 Z2L2

Z2s Z2s
I2 I2
Z2T1 F Z2L1 Z2T1 F Z2L1

N2 N2

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 36 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 36
Example
p 2 Example
p 2

Cable L2 Cable L2

T2 T2
Load Load

Zsource Zsource

Cable L1 Cable L1

T1 T1

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 37 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 37

p 2: Phase to earth fault


Example p 2: Phase to earth fault
Example
Z1T2 Z1L2 Z1T2 Z1L2

Z1s F Z1s F
I1 I1
Z1T1 Z1L1 Z1T1 Z1L1
Vn Vn

N1 N1
Z2T2 Z2L2 Z2T2 Z2L2

Z2
Z2s F Z2
Z2s F
I2 I2
Z2T1 Z2L1 3*Rf Z2T1 Z2L1 3*Rf

N2 N2
Z0T2 Z0L2 Z0T2 Z0L2

Zos F Zos F

Z0T1 Z0L1 Z0T1 Z0L1


Io Io

No No
Schneider Electric - Energy Automation – Technical institut – 19/11/2010 38 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 38
To summarize To summarize

● Equivalent circuits are used to calculate symmetrical components. ● Equivalent circuits are used to calculate symmetrical components.

● Current on each phase are calculated from symmetrical components by ● Current on each phase are calculated from symmetrical components by
using transformation formula. using transformation formula.

● Finally,
Fi ll usuall ffaults
lt can b
be calculated
l l t d thi
this way: ● Finally,
Fi ll usuall ffaults
lt can b
be calculated
l l t d thi
this way:
● 3 phases fault : ● 3 phases fault :
Ik3 = Vn / Z1 with Vn = Un/ √3 Ik3 = Vn / Z1 with Vn = Un/ √3

● Phase to phase fault : ● Phase to phase fault :


Ik2 = √3 Vn / ((Z1 + Z2)) Ik2 = √3 Vn / ((Z1 + Z2))

● Phase to earth fault : ● Phase to earth fault :


Ik1 = 3 Vn / (Z1 + Z2 + Z0) Ik1 = 3 Vn / (Z1 + Z2 + Z0)

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 39 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 39

Types of fault Types of fault


Symmetrical components Symmetrical components

Impedance transformation Impedance transformation


2 windings transformer 2 windings transformer
3 windings transformer 3 windings transformer
Overhead line and cable Overhead line and cable
Synchronous machine Synchronous machine
Induction machine Induction machine

Schneider Electric - Energy Automation – Technical Institute 40 Schneider Electric - Energy Automation – Technical Institute 40
Generality Generality

● On network with several voltage level, it may be useful to convert ● On network with several voltage level, it may be useful to convert
impedance in order to performed calculation on only one voltage level impedance in order to performed calculation on only one voltage level

● Two methods are possible ● Two methods are possible


● Introduction of a base voltage:
g ● Introduction of a base voltage:
g
Current and impedance are still expressed in amp and ohm Current and impedance are still expressed in amp and ohm
● Introduction of a base power and a base voltage: ● Introduction of a base power and a base voltage:
Current and impedance are expressed in per unit Current and impedance are expressed in per unit

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 41 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 41

Ohm method Ohm method

● Principle ● Principle
Calculation are performed considering only one voltage level Calculation are performed considering only one voltage level

● Base quantity : ● Base quantity :


Base voltage : Ub Base voltage : Ub

● Impedance conversion: ● Impedance conversion:

New Z (ohm) = Z(ohm) * (Ub / Un)² New Z (ohm) = Z(ohm) * (Ub / Un)²

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 42 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 42
Ohm method (example) Ohm method (example)

● Conversion under 20 kV ● Conversion under 20 kV


225 kV 20 kV 225 kV 20 kV

1500 MVA R : 0,3 ohm 36 MVA R : 0,2 ohm 1500 MVA R : 0,3 ohm 36 MVA R : 0,2 ohm
X : 10 ohm 225 kV/20kV X : 2 ohm X : 10 ohm 225 kV/20kV X : 2 ohm
Ucc : 16% Ucc : 16%

j Ub² / Scc (R+jX)* (Ub / Un)² Ucc * (Ub² / Sn) (R+jX)* (Ub / Un)² j Ub² / Scc (R+jX)* (Ub / Un)² Ucc * (Ub² / Sn) (R+jX)* (Ub / Un)²
Z Z
j20² / 1500 (0,3+j10)*(20/225)² j0,16*(20²/36) 0,2+j2*(20/20)² j20² / 1500 (0,3+j10)*(20/225)² j0,16*(20²/36) 0,2+j2*(20/20)²
j0.0133 ohm 0.0024+j0.08 ohm j1,77 ohm 0,2 + j2 j0.0133 ohm 0.0024+j0.08 ohm j1,77 ohm 0,2 + j2

0,2 + j4,05
0, j ,05 o
ohm 0,2 + j4,05
0, j ,05 o
ohm

V 20 kV IF = 2,8 kA V 20 kV IF = 2,8 kA

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 43 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 43

Per unit method Per unit method

● Principle ● Principle
● Values (voltage, current, impedance) are converted into relative values. ● Values (voltage, current, impedance) are converted into relative values.
● Calculation with per unit values are non longer voltage dependant ● Calculation with per unit values are non longer voltage dependant

● Base quantities : ● Base quantities :


● Base power : Sb ● Base power : Sb
● Base voltage : Ub ● Base voltage : Ub

● Resulting quantities : ● Resulting quantities :


● Base current : Ib = Sb / (√3*Ub) ● Base current : Ib = Sb / (√3*Ub)
● Base impedance : Zb = Ub² / Sb = Ub / (√3*Ib) ● Base impedance : Zb = Ub² / Sb = Ub / (√3*Ib)
● Impedance conversion: ● Impedance conversion:
z (%) = (Z / Zb) * (Ub / Un)² z (%) = (Z / Zb) * (Ub / Un)²

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 45 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 45
Per unit method (example) Per unit method (example)

● Base quantities : 1 kV et 30 MVA ● Base quantities : 1 kV et 30 MVA


● Zb = (1kV)² / (30MVA) = 0.0333 ohm Ib = (30 MVA)/(√3*1kV) = 17320 A ● Zb = (1kV)² / (30MVA) = 0.0333 ohm Ib = (30 MVA)/(√3*1kV) = 17320 A
225 kV 20 kV 225 kV 20 kV

1500 MVA R : 0,3 ohm 36 MVA R : 0,2 ohm 1500 MVA R : 0,3 ohm 36 MVA R : 0,2 ohm
X : 10 ohm 225 kV/20kV X : 2 ohm X : 10 ohm 225 kV/20kV X : 2 ohm
Ucc : 16% Ucc : 16%

jSb / Scc (R+jX) / Zb)* (Ub / Un)² Ucc * (Sb / Sn) ((R+jX) / Zb)* (Ub / Un)² jSb / Scc (R+jX) / Zb)* (Ub / Un)² Ucc * (Sb / Sn) ((R+jX) / Zb)* (Ub / Un)²
Zpu Zpu
j30 / 1500 (0,3+j10)/0.0333*(1/225)² j0,16*(30/36) (0,2+j2)/0.0333*(1/20)² j30 / 1500 (0,3+j10)/0.0333*(1/225)² j0,16*(30/36) (0,2+j2)/0.0333*(1/20)²
J0,02 0.00018+j0,0059 j0,1333 0,015+j0,15 J0,02 0.00018+j0,0059 j0,1333 0,015+j0,15

0,015+j0,309p.u. 0,015+j0,309p.u.

V 1p.u. IF = 3,2 pu IF 20kV = 3,2


3 2 * 17320 A *(1kV/20kV)
(1kV/20kV) V 1p.u. IF = 3,2 pu IF 20kV = 3,2
3 2 * 17320 A *(1kV/20kV)
(1kV/20kV)
= 2,8 kA = 2,8 kA

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 47 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 47

Types of fault Types of fault


Symmetrical components Symmetrical components
p
Impedance transformation p
Impedance transformation

2 windings transformer 2 windings transformer


3 windings transformer 3 windings transformer
Overhead line and cable Overhead line and cable
Synchronous machine Synchronous machine
I d i machine
Induction hi I d i machine
Induction hi

Schneider Electric - Energy Automation – Technical Institute 49 Schneider Electric - Energy Automation – Technical Institute 49
Positive and negative
g sequences
q Positive and negative
g sequences
q

Z1 ≈ X1 = zpu * (Ub2 / Sn) Z1 ≈ X1 = zpu * (Ub2 / Sn)


Z2 ≈ X2 = zpu * (Ub2 / Sn) Z2 ≈ X2 = zpu * (Ub2 / Sn)

90kV / 20kV 90kV / 20kV


Ucc = 15% Ucc = 15%
50MVA 50MVA

Z1 = Z2 = 0.15
0 15 * (20kV2 / 50MVA) Z1 = Z2 = 0.15
0 15 * (20kV2 / 50MVA)
= 1.2 ohm under 20kV = 1.2 ohm under 20kV

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 50 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 50

Transformer zero sequence impedance Transformer zero sequence impedance


(1/4) (1/4)

● Zero sequence impedance of transformer vary with the winding ● Zero sequence impedance of transformer vary with the winding
coupling coupling

P Q P Q

ZT0 ZT0
a a a a
P Q P Q

b b b b

N0 N0

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 51 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 51
Transformer zero sequence impedance Transformer zero sequence impedance
(2/4) (2/4)
P S P S

P0 ZT0 S0 P0 ZT0 S0
a a a a

b b b b

N0 N0

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 52 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 52

Transformer zero sequence impedance Transformer zero sequence impedance


(3/4) (3/4)
P S P S

P0 ZT0 P0 ZT0
a a S0 a a S0

b b b b

N0 N0

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 53 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 53
Transformer zero sequence impedance Transformer zero sequence impedance
(4/4) (4/4)
P S P S

P0 ZT0 P0 ZT0
a a S0 a a S0

b b b b

N0 N0

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 54 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 54

Types of fault Types of fault


Symmetrical components Symmetrical components
Impedance transformation Impedance transformation
Impédances des transformateurs 2 enroulements Impédances des transformateurs 2 enroulements

3 windings transformer 3 windings transformer


Overhead line and cable Overhead line and cable
Synchronous machine Synchronous machine
duc o machine
Induction ac e duc o machine
Induction ac e

Schneider Electric - Energy Automation – Technical Institute 55 Schneider Electric - Energy Automation – Technical Institute 55
Positive and negative
g sequences
q Positive and negative
g sequences
q
1 Z2 1 Z2
13.8kV
161kV / 115kV / 13 8kV Z1 2 13.8kV
161kV / 115kV / 13 8kV Z1 2
Sn12=10% sur 30MVA Sn12=10% sur 30MVA
Sn13=6% sur 10MVA 1 Sn13=6% sur 10MVA 1
Sn23=14% sur 15MVA Z3 Sn23=14% sur 15MVA Z3

3 3

Z1 = 1/2 * (Z12 + Z13 - Z23) Z1 = 1/2 * (Z12 + Z13 - Z23)


Z2 = 1/2 * (Z12 + Z23 - Z13) Z2 = 1/2 * (Z12 + Z23 - Z13)
Z3 = 1/2 * (Z13 + Z23 - Z12) Z3 = 1/2 * (Z13 + Z23 - Z12)
2 3 2 3

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 56 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 56

Positive and negative sequences Positive and negative sequences


e ample
example Calculation under Sb = 100MVA :
e ample
example Calculation under Sb = 100MVA :
1 1
Z12 = (100MVA/30MVA) * 10% = 33.33% Z12 = (100MVA/30MVA) * 10% = 33.33%
161kV / 115kV / 13.8kV
13 8kV Z13 = (100MVA/10MVA) * 6% = 60% 161kV / 115kV / 13.8kV
13 8kV Z13 = (100MVA/10MVA) * 6% = 60%
Z12=10% under 30MVA Z23 = (100MVA/15MVA) * 14% = 93.33% Z12=10% under 30MVA Z23 = (100MVA/15MVA) * 14% = 93.33%
Z13= 6% under 10MVA Z13= 6% under 10MVA
Z23=14% under 15MVA Z23=14% under 15MVA

Z1 = 1/2 * (Z12 + Z13 - Z23) Z1 = 1/2 * (Z12 + Z13 - Z23)


= 1/2 * (33.33 + 60 - 93.33) = 0% = 1/2 * (33.33 + 60 - 93.33) = 0%
Z2 = 1/2 * (Z12 + Z23 - Z13) Z2 = 1/2 * (Z12 + Z23 - Z13)
= 1/2 * (33.33 + 93.33 - 60) = 33.33% = 1/2 * (33.33 + 93.33 - 60) = 33.33%
Z3 = 1/2 * (Z13 + Z23 - Z12) Z3 = 1/2 * (Z13 + Z23 - Z12)
= 1/2 * (60 + 93.33 - 33.33) = 60% = 1/2 * (60 + 93.33 - 33.33) = 60%

2 3 2 3

Calculation in ohm under 161kV : Calculation in ohm under 161kV :


Z1 = 10% * 161kV2
/ 30MVA = 86.4 ohm under 161kV Z1 = 10% * 161kV2 / 30MVA = 86.4 ohm under 161kV
Z2 = 6% * 161kV2 / 10MVA = 155.5 ohm under 161kV Z2 = 6% * 161kV2 / 10MVA = 155.5 ohm under 161kV
Z3 = 14% * 161kV2 / 15MVA = 241.9 ohm under 161kV Z3 = 14% * 161kV2 / 15MVA = 241.9 ohm under 161kV

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 57 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 57
Zero sequence
q Zero sequence
q

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 58 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 58

Types of fault Types of fault


Symmetrical components Symmetrical components
Impedance transformation Impedance transformation
2 windings transformer 2 windings transformer
g transformer
3 windings g transformer
3 windings

Overhead line and cable Overhead line and cable


Synchronous machine Synchronous machine
Induction machine Induction machine

Schneider Electric - Energy Automation – Technical Institute 59 Schneider Electric - Energy Automation – Technical Institute 59
Overhead line : Overhead line :
Positive sequence impedance (reactance) Positive sequence impedance (reactance)

● Resistance (R) : ● Resistance (R) :


● Resistance is given by: ● Resistance is given by:
●resistivity (ρ) ●resistivity (ρ)
●length (l) ●length (l)
●section (s)
R = ρ * l / (s * n) ●section (s)
R = ρ * l / (s * n)
●Number of conductors in parallel (n) ●Number of conductors in parallel (n)

● Example : ● Example :
● Almelec (ρ =0.032 en 10-6 ohm*m) ● Almelec (ρ =0.032 en 10-6 ohm*m)
● length: 2500 m ● length: 2500 m
● section: 228mm2 ● section: 228mm2
● 1 conductor ● 1 conductor

Rd = 0.032 * 2500m / (228mm2 * 1) = 0.35 ohm Rd = 0.032 * 2500m / (228mm2 * 1) = 0.35 ohm

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 60 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 60

Overhead line : Overhead line :


Positive sequence impedance (reactance) Positive sequence impedance (reactance)

● Reactance (X) : ● Reactance (X) :


● Reactance value is almost not dependent from the rated voltage or section. ● Reactance value is almost not dependent from the rated voltage or section.
But it is affected by the number of conductors per phase.
phase But it is affected by the number of conductors per phase.
phase

● On line with one conductor per phase (up to 220kV) ● On line with one conductor per phase (up to 220kV)
X ≈ 0.4ohm/km X ≈ 0.4ohm/km

● On line with two conductors per phase (typically 400kV): ● On line with two conductors per phase (typically 400kV):
X ≈ 0.32ohm/km X ≈ 0.32ohm/km

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 61 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 61
Overhead line : Overhead line :
Negati e seq
Negative sequence
ence impedance Negati e seq
Negative sequence
ence impedance

● When transposed, positive et negative sequences are equal ● When transposed, positive et negative sequences are equal

● It is assumed to be always the case even if the line is not transposed ● It is assumed to be always the case even if the line is not transposed

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 62 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 62

Overhead line : Overhead line :


Zero seq
sequence
ence impedance Zero seq
sequence
ence impedance

● IZero sequence impedance is about three times the positive sequence ● IZero sequence impedance is about three times the positive sequence
when there is no earth wire when there is no earth wire

Z0 ≈ 3 Z1 Z0 ≈ 3 Z1

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 63 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 63
Underground cable : Underground cable :
Positive sequence impedance(resistance) Positive sequence impedance(resistance)

● Resistance (R) : ● Resistance (R) :


● Resistance is given by: ● Resistance is given by:
●resistivity (ρ) ●resistivity (ρ)
●length (l) ●length (l)
●section (s)
R = ρ * l / (s * n) ●section (s)
R = ρ * l / (s * n)
●Number of conductors in parallel (n) ●Number of conductors in parallel (n)

● Example : ● Example :
● Copper (ρ =0.018 en 10-6 ohm*m) ● Copper (ρ =0.018 en 10-6 ohm*m)
● length : 700m ● length : 700m
● section: 95mm2 ● section: 95mm2

Rd = 0.018 * 700m / 95mm2 = 0.13 ohm Rd = 0.018 * 700m / 95mm2 = 0.13 ohm

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 64 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 64

Underground cable : Underground cable :


Positive sequence impedance(reactance) Positive sequence impedance(reactance)

● Réactance (X) ● Réactance (X)


● Reactance value is almost not dependent from the rated voltage or section. ● Reactance value is almost not dependent from the rated voltage or section.
But it is affected by the number of conductors per phase.
phase But it is affected by the number of conductors per phase.
phase

0.1 ohm/km < X < 0.15 ohm/km 0.1 ohm/km < X < 0.15 ohm/km

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 65 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 65
Underground cable : Underground cable :
Negati e and zero
Negative ero seq
sequence
ence impedance Negati e and zero
Negative ero seq
sequence
ence impedance

● Negative sequence impedance (Z2) : ● Negative sequence impedance (Z2) :


When symetrical wiring, positive et negative sequences are equal When symetrical wiring, positive et negative sequences are equal

Zi = Zd Zi = Zd

● Zero sequence impedance (Z0) : ● Zero sequence impedance (Z0) :


No general rule No general rule
Zero sequence impedance is influenced by: Zero sequence impedance is influenced by:
●Soil
Soil resistivity ●Soil
Soil resistivity
●Surrounding conductors ●Surrounding conductors
●Earthing of the sheath ●Earthing of the sheath

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 66 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 66

Types of fault Types of fault


Symmetrical components Symmetrical components
Impedance transformation Impedance transformation
2 windings transformer 2 windings transformer
g transformer
3 windings g transformer
3 windings
Overhead line and cable Overhead line and cable

Synchronous machine Synchronous machine


Induction machine Induction machine

Schneider Electric - Energy Automation – Technical Institute 67 Schneider Electric - Energy Automation – Technical Institute 67
Positive sequence
q impedance
p Positive sequence
q impedance
p
Short circuit decrement curve Short circuit phase-earth Short circuit decrement curve Short circuit phase-earth

I
Isc (per
( unit
it - rms)) Short circuit phase-phase
phase phase I
Isc (per
( unit
it - rms)) Short circuit phase-phase
phase phase

9 3 phase short-circuit 9 3 phase short-circuit

8 8
Mise enStart
routeofdeAVR
l’AVR Mise enStart
routeofdeAVR
l’AVR
7 7

6 6

5 5

4 4

3 3

2 2

1 Zdg ≈ Xdg = f(t) 1 Zdg ≈ Xdg = f(t)


0 0
0,001 0,01 0,1 1 10 0,001 0,01 0,1 1 10
Time (sec) Time (sec)
Schneider Electric - Energy Automation – Technical institut – 19/11/2010 68 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 68

Positive sequence
q impedance
p Positive sequence
q impedance
p
● Positive sequence impedance is not constant ● Positive sequence impedance is not constant
● Several reactances must be defined ● Several reactances must be defined
● Short circuit current behave like this: ● Short circuit current behave like this:

     
t

t
 
    
 
    
'd

'd

'd

'd
1

1
         
Τ

Τ
 
a

a
                 
Ι
t

Ι
n

c
o
s

ω
t

Ι
t

Ι
n

c
o
s

ω
t

e
'
' d

' d

' d

' d
'

'
' d

' d

' d

' d
'
 
x

x
             
d

d
● With ● With
In = rated current (Amp) In = rated current (Amp)
X’’d = subtransient reactance (p.u.) X’’d = subtransient reactance (p.u.)
X’d = transient reactance(p.u.) X’d = transient reactance(p.u.)
Xd = synchronous reactance (p.u.) Xd = synchronous reactance (p.u.)
T’’d = subtransient time constant (s) T’’d = subtransient time constant (s)
T’d = transient time constant (s) T’d = transient time constant (s)
T =
Ta DC titime constant
t t (s)
( ) T =
Ta DC titime constant
t t (s)
( )

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 69 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 69
Schneider Electric - Energy Automation – Technical institut – 19/11/2010 70 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 70

Negative
g and zero sequence
q impedance
p Negative
g and zero sequence
q impedance
p

● Negative sequence impedance (Z2) : ● Negative sequence impedance (Z2) :


Negative sequence impedance is about the transient reactance Negative sequence impedance is about the transient reactance

Z2 ≈ X’d Z2 ≈ X’d

● Zero sequence impedance(Z0) : ● Zero sequence impedance(Z0) :


This impedance is very low and in practice is not used because of: This impedance is very low and in practice is not used because of:
●Zero sequence filtering by transformer ●Zero sequence filtering by transformer
●Neutral
Neutral point grounding throught an high resistance ●Neutral
Neutral point grounding throught an high resistance

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 71 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 71
Types of fault Types of fault
Symmetrical components Symmetrical components
Impedance transformation Impedance transformation
2 windings transformer 2 windings transformer
g transformer
3 windings g transformer
3 windings
Overhead line and cable Overhead line and cable
Synchronous machine Synchronous machine

Induction machine Induction machine


Schneider Electric - Energy Automation – Technical Institute 73 Schneider Electric - Energy Automation – Technical Institute 73

Positive,, negative,
g , zero sequence
q Positive,, negative,
g , zero sequence
q

● Positive sequence impedance (Z1) : ● Positive sequence impedance (Z1) :


During three phase fault, short-circuit current appears only during the first milliseconds During three phase fault, short-circuit current appears only during the first milliseconds
●I(t)
I(t) = Istarting * exp(
exp(-t/T),
t/T), ●I(t)
I(t) = Istarting * exp(
exp(-t/T),
t/T),
2 2
T ≈ 50 ms Un T ≈ 50 ms Un
Zinit  Zinit 
Istart Istart
Sn  Sn 
In In
Z permanent   Z permanent  

● Negative sequence impedance (Zi) : ● Negative sequence impedance (Zi) :


Negative sequence is equal to the positive sequence Negative sequence is equal to the positive sequence
Z2 ≈ X2 = X1 Z2 ≈ X2 = X1

● Zero sequence impedance (Z0) : ● Zero sequence impedance (Z0) :


Neutral point usually not grounded Neutral point usually not grounded

Schneider Electric - Energy Automation – Technical institut – 19/11/2010 74 Schneider Electric - Energy Automation – Technical institut – 19/11/2010 74
3.2 Annex 1 -CT18_Analysis of three-phase 3.2 Annex 1 -CT18_Analysis of three-phase
networks networks
3.3 Annex 2 CT158_Calculation of short-circuit 3.3 Annex 2 CT158_Calculation of short-circuit
currents currents

You might also like