Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Rpf2Ap7: Product Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Product datasheet RPF2AP7

Characteristics power relay plug-in - Zelio RPF - 2 NO - 230 V AC -


30 A

Main
Range of product Zelio Relay
Series name Power
Product or component type Plug-in relay
Device short name RPF
Contacts type and composition 2 NO
Control circuit voltage 230 V AC
Control type Without lockable test button
Shape of pin Flat
Contacts material Silver tin oxide
[Ithe] conventional enclosed 25 A at -40...55 °C for relays side by side without a
thermal current gap
30 A at -40...55 °C for 13 mm gap between two

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
relays
Load current 25 A at 28 V DC
30 A at 250 V AC
Utilisation coefficient 10 %

Complementary
Mounting support DIN rail

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Panel

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Control circuit voltage limits 184...253 V
[Ie] rated operational current 30 A at 250 V AC (for NO) conforming to IEC
30 A at 277 V AC (for NO) conforming to UL
20 A at 28 V DC (for NO) conforming to UL
25 A at 28 V DC (for NO) conforming to IEC
[Ui] rated insulation voltage 250 V conforming to IEC
300 V conforming to UL
[Uimp] rated impulse withstand voltage 4 kV 1.2/50 µs
Maximum switching voltage 250 V conforming to IEC
Maximum switching capacity 7500 VA/700 W
Minimum switching capacity 6000 mW (500 mA / 12 V) for NO
Operating rate <= 18000 cycles/hour no-load
<= 1200 cycles/hour under load
Mechanical durability 5000000 cycles
Electrical durability 100000 cycles for resistive load
Average consumption 4 VA at 60 Hz
Drop-out voltage threshold >= 0.15 Uc
Operating time 25 ms
Reset time 25 ms
Average resistance 15600 Ohm (tolerance +/- 15 %) at 20 °C
Safety reliability data B10d = 100000
Protection category RT II
Operating position Any position
Product weight 0.082 kg
Device presentation Complete product

Environment
dielectric strength 2000 V AC between poles with basic insulation
1500 V AC between contacts with micro disconnection insulation
4000 V AC between coil and contact with reinforced insulation

1/3
standards EN/IEC 61810-1
UL 508
CSA C22.2 No 14
product certifications CE
CSA
GOST
UL
ambient air temperature for storage -40...85 °C
ambient air temperature for operation -40...55 °C
vibration resistance 3 gn (+/- 1 mm, f = 10...150 Hz) 5 cycles in operation
10 gn (+/- 1 mm, f = 10...150 Hz) 5 cycles not operating
IP degree of protection IP40 conforming to EN/IEC 60529
shock resistance 10 gn in operation
30 gn not operating
pollution degree 3

Contractual warranty
Warranty period 18 months

Dimensions

Wiring Diagram

Symbols shown in blue correspond to Nema marking.

Electrical Durability of Contacts

AC Resistive load

2/3
X Switching capacity (kVA)
Y Durability (number of operating cycles)
AC Reduction coefficient for inductive load (depending on power factor cos ϕ)

Durability (inductive load) = durability (resistive load) x reduction coefficient.

Y reduction coefficient
Maximum switching capacity on DC resistive load

A 30 A
B 25 A
Note : These are typical curves, actual durability depends on load, environment, duty cycle, etc.

3/3