Four-Wire Feeder Schedule Feeder Wire Ground Conduit 208V Max. 480V Max. Name Size Wire Size Size Length Length

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 4

FOUR-WIRE FEEDER SCHEDULE

FEEDER WIRE GROUND CONDUIT 208V MAX. 480V MAX.


NAME SIZE WIRE SIZE SIZE LENGTH LENGTH
20-4 #12 #12 3/4" 98' 227'
30-4 #10 #10 3/4" 109' 250'
40-4 #8 #10 1" 123' 285'
60-4 #6 #10 1 1/4" 128' 295'
70-4 #4 #8 1 1/4" 169' 390'
100-4 #2 #8 1 1/4" 176' 406'
125-4 #1 #6 1 1/2" 171' 394'
150-4 #1/0 #6 2" 182' 420'
175-4 #2/0 #6 2" 182' 418'
200-4 #3/0 #6 2" 192' 443'
225-4 #4/0 #4 2 1/2" 203' 468'
250-4 #250 MCM #4 2 1/2" 202' 466'
300-4 #350 MCM #4 3" 211' 487'
350-4 #400 MCM #2 3" 194' 450'
400-4 #500 MCM #2 3 1/2" 191' 442'
450-4 (2) #4/0 (2) #1 (2) 2 1/2" 203' 468'
500-4 (2) #250 MCM (2) #1 (2) 2 1/2" 202' 466'
600-4 (2) #350 MCM (2) #1 (2) 3" 210' 487'
700-4 (2) #500 MCM (2) #1/0 (2) 3 1/2" 219' 505'
800-4 (2) #600 MCM (2) #1/0 (2) 3 1/2" 207' 478'
1000-4 (3) #400 MCM (3) #2/0 (3) 3 1/2" 205' 474'
1200-4 (3) #600 MCM (3) #3/0 (3) 3 1/2" 207' 478'
1600-4 (4) #600 MCM (4) #4/0 (4) 3 1/2" 207' 478'
2000-4 (5) #600 MCM (5) #250 MCM (5) 3 1/2" 207' 478'
2500-4 (6) #600 MCM (6) #350 MCM (6) 3 1/2" 199' 459'
THREE-WIRE FEEDER SCHEDULE
FEEDER WIRE GROUND CONDUIT 208V MAX. 480V MAX.
NAME SIZE WIRE SIZE SIZE LENGTH LENGTH
20-3 #12 #12 3/4" 98' 227'
30-3 #10 #10 3/4" 109' 250'
40-3 #8 #10 3/4" 123' 285'
60-3 #6 #10 1" 128' 295'
70-3 #4 #8 1 1/4" 169' 390'
100-3 #2 #8 1 1/4" 176' 406'
125-3 #1 #6 1 1/2" 171' 394'
150-3 #1/0 #6 2" 182' 420'
175-3 #2/0 #6 2" 182' 418'
200-3 #3/0 #6 2" 192' 443'
225-3 #4/0 #4 2 1/2" 203' 468'
250-3 #250 MCM #4 2 1/2" 202' 466'
300-3 #350 MCM #4 2 1/2" 211' 487'
350-3 #400 MCM #2 3" 194' 450'
400-3 #500 MCM #2 3 1/2" 191' 442'
450-3 (2) #4/0 (2) #1 (2) 2 1/2" 203' 468'
500-3 (2) #250 MCM (2) #1 (2) 2 1/2" 202' 466'
600-3 (2) #350 MCM (2) #1 (2) 2 1/2" 210' 487'
700-3 (2) #500 MCM (2) #1/0 (2) 3 1/2" 219' 505'
800-3 (2) #600 MCM (2) #1/0 (2) 3 1/2" 207' 478'
1000-3 (3) #400 MCM (3) #2/0 (3) 3" 205' 474'
1200-3 (3) #600 MCM (3) #3/0 (3) 3 1/2" 207' 478'
1600-3 (4) #600 MCM (4) #4/0 (4) 3 1/2" 207' 478'
2000-3 (5) #600 MCM (5) #250 MCM (5) 3 1/2" 207' 478'
2500-3 (6) #600 MCM (6) #350 MCM (6) 3 1/2" 199' 459'
TWO-WIRE FEEDER SCHEDULE
FEEDER WIRE GROUND CONDUIT 208V MAX. 480V MAX.
NAME SIZE WIRE SIZE SIZE LENGTH LENGTH
20-2 #12 #12 3/4" 98' 227'
30-2 #10 #10 3/4" 109' 250'
40-2 #8 #10 3/4" 123' 285'
60-2 #6 #10 3/4" 128' 295'
70-2 #4 #8 1" 169' 390'
100-2 #2 #8 1 1/4" 176' 406'
125-2 #1 #6 1 1/4" 171' 394'
150-2 #1/0 #6 1 1/2" 182' 420'
175-2 #1/0 #6 1 1/2" 182' 418'
200-2 #2/0 #6 1 1/2" 192' 443'
225-2 #4/0 #4 2" 203' 468'
250-2 250 MCM #4 2" 202' 466'
300-2 350 MCM #4 2 1/2" 211' 487'
350-2 #400 MCM #2 2 1/2" 194' 450'
400-2 #500 MCM #2 2 1/2" 191' 442'
450-2 (2) #4/0 (2) #1 (2) 2" 203' 468'
500-2 (2) #250 MCM (2) #1 (2) 2" 202' 466'
600-2 (2) #350 MCM (2) #1 (2) 2 1/2" 210' 487'
700-2 (2) #500 MCM (2) #1/0 (2) 2 1/2" 219' 505'
800-2 (2) #600 MCM (2) #1/0 (2) 3" 207' 478'
1000-2 (3) #400 MCM (3) #2/0 (3) 2 1/2" 205' 474'
1200-2 (3) #600 MCM (3) #3/0 (3) 3" 207' 478'
1600-2 (4) #600 MCM (4) #4/0 (4) 3" 207' 478'
2000-2 (5) #600 MCM (5) #250 MCM (5) 3" 207' 478'
2500-2 (6) #600 MCM (6) #350 MCM (6) 3" 199' 459'
NOTES:
1. Conduits smaller than 3" may be upgraded to the next larger size when
used for underground installations or long runs.
2. Conduit sizes indicated are minimum recommended sizes, and may be
increased for long circuits, or where multiple bends are necessary.
3. The feeder name represents its base ampacity and the number of wires
(not including ground).
4. The base ampacity indicated in the feeder name does not account for
voltage drop, fault current or temperature
5. All feeders for 120/208V panelboards with isolated ground (IG) bus shall
include a separate IG conductor tied to the IG bus.
6. The rating of the overcurrent protection device may be lower, but not
higher, than the rating of the feeder that it protects.
7. Maximum limits on the number of turns and conduit length should be
verified for all underground installations.
8. Maximum feeder length is the length that produces a 3% voltage drop
at the specified voltage, when the load is at the full ampacity of the
feeder, and has a power factor of 90%.
9. Maximum feeder length does not apply if the feeder is sized for voltage
drop rather than ampacity.