Condensate Drain Calculation - Split Units PDF
Condensate Drain Calculation - Split Units PDF
Condensate Drain Calculation - Split Units PDF
Cooling Coil
6. Volumetric Air Flow through Coil : 1,440 m3 / hr
7. Air Velocity through Coil : 1.00 m/s < 2.0 m/s ( w/o Mist Eliminator )
o
8. Inlet Air Properties : 40.00 C 33.43 g / ( kg-dry air )
o
9. Outlet Air Properties : 14.00 C 9.67 g / ( kg-dry air )
10. Condensate Drain Amount : 41.60 kg / hr ( Dehumidifying Capacity )
11. Condensate Drain Amount : 42.00 kg / hr ( From Coil Manufacturer )
3
12. Density of Water : 1,000 kg / m
Fig. 1 - Trap for Draw Through Unit Fig. 2 - Trap for Blow Through Unit
( During Fan Off Cycle ) ( During Fan Off Cycle )