Online Two-Section PV Array Fault Diagnosis With Optimized Voltage Sensor Locations
Online Two-Section PV Array Fault Diagnosis With Optimized Voltage Sensor Locations
Online Two-Section PV Array Fault Diagnosis With Optimized Voltage Sensor Locations
Manuscript received October 30, 2014; revised January 24, 2015; April 18, W. Cao and J. L. Kirtley are with the Department of Electrical Engineering
2015 and May 23, 2015; accepted June 7, 2015. and Computer Science, Massachusetts Institute of Technology, Cambridge,
Copyright (c) 2015 IEEE. Personal use of this material is permitted. MA, 02139, U.S.A.
However, permission to use this material for any other purposes must be J. Wu is with the College of Electrical Engineering, Zhejiang University,
obtained from the IEEE by sending a request to pubs-permissions@ieee.org. Hangzhou, 310027, P. R. China.
Y. Hu, J. Zhang and S. Finney are with the Department of Electronic & G. Tian is with the School of Electrical and Electronic Engineering,
Electrical Engineering, University of Strathclyde, Glasgow, G1 1XQ, U.K. Newcastle University, Newcastle upon Type, NE1 7RU, U.K.
1
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
fault diagnosis methods suffer from high costs or incapability experimental results of the faulty cell-unit that includes 24 PV
of locating fault modules. A model-based reconfiguration cells with one faulty PV cell; the experimental environment
algorithm is developed in [29] to realize the fault-tolerant parameters are 790 W/m2 at 24oC. The faulty cell is equivalent
operation. But it needs a large number of electrical relays to to a resistance. As the current increases, the corresponding cell-
reconfigure PV arrays. A similar technology, the in-situ unit output power is decreased dramatically. For instance, the
rearrangement strategy, can decrease the influence of shadow faulty cell-unit works at 0.96 A, and its output power is 4.75 W
[30]-[33]. However, its success depends on three conditions: i) (about 10% of the output at healthy condition) and this power
a large number of relays are used. ii) the health state of all PV reduces to nearly zero when the cell-unit current is higher than
modules should be monitored. iii) high computing resource of 1 A. In order to achieve a global MPP for the PV array, the
the controller is required to calculate complex optimal current is much higher than 1 A under the condition in Fig. 2.
arrangements. These increase the system cost and control Therefore, the output voltage for a faulty cell-unit is effectively
complexity. Paper [34] develops an improved strategy which negligible, as shown in Fig. 2.
combines power channels and relays to combat the shadow Therefore, when a PV module is subjected to partial shading,
influence but it also needs the healthy state of PV modules. its terminal output voltage is lower than the healthy module but
Paper [35] proposes a fingerprint curve of the PV array under higher than zero. In Fig. 2(b), the PV module loses one of the
shading conditions to find the key information (e.g. open-circuit 𝑛−1
cell-units and its output voltage is reduced to of the output
𝑛
and short-circuit points and MPP region) but it cannot locate the
voltage.
faulted modules. Paper [36] presents a fault diagnosis technique
PV string fault diagnosis can be achieved by measuring the
using current and voltage sensors but the system cost is quite
PV module voltage, which changes with the string working
high. Paper [22] presents a method to use the fault diagnosis
point. When the string works in the low voltage diagnosis
information for global MPPT without a need to trace I-V curves.
section, the faulty module can be located because its output
It becomes clear that online fault diagnosis is important because
voltage is zero (full shadow) or lower than the healthy module
i) it is the prerequisite for any array dynamical reconfiguration.
(partial shadow).
ii) it can provide crucial information for global MPPT; (iii) it
contains key state-of-health information useful for system B. PV array faults
maintenance. When a PV array is faulted, the faulty module has a lower
This paper proposes a low cost and online fault diagnosis effective illumination than healthy modules. Take a 3×3 array
method with optimized voltage sensor locations that can for example. Fig. 3(a) shows a multi-string faulty condition and
effectively locate the faulty PV strings and faulty modules. The Fig. 3(b) shows its I-V characteristics. In Fig. 3(a), the diodes
paper is organized as follows. Section II introduces PV fault are used to block the reverse current when a fault occurs. The
mechanisms. Section III illustrates the optimization of sensor output I-V characteristics can be divided into two sections: a
locations. Section IV describes the two-section PV array fault high voltage diagnosis section and a low voltage diagnosis
diagnosis method. Section V presents experimental results to section (constant output current). In the latter section, the faulty
verify the proposed method, followed by a short conclusion in module in the faulty string is shorted by bypass diodes where
Section VI. both healthy string and unhealthy string carry the same current.
PV string current sensors cannot distinguish the unhealthy
II. FAULT MECHANISMS string from healthy strings. Nevertheless, the healthy modules
in the faulty string have a higher output voltage than the
Firstly, it is crucial to understand fault mechanisms prior to modules in the healthy string, as points A1 and A2 illustrated in
developing fault diagnosis techniques. Fig. 3(c). The voltage difference between the healthy module in
A. PV string faults the unhealthy string, and the module in the healthy string can
The PV string is the basic structure of a PV array. Fig. 1 be employed to locate the faulty module.
presents typical output characteristics of the PV string under
faulty conditions; the PV module parameters are listed in Table
I. The string includes three modules with non-uniform
illumination, the corresponding environment parameters are
850 W/m2, 25oC; 620 W/m2, 25oC; 400 W/m2, 25oC. Each
module has uniform illumination. It can be found that: i) The
multi-stage characteristics are caused by the differing output
current of each module; ii) In the low voltage diagnosis section,
the faulty modules are short-circuited, and the terminal voltage
of the corresponding faulty module is zero.
Fig. 1 Output characteristics of the faulty string.
In order to restrict the hot-spots in a PV module, a bypass TABLE I SPECIFICATIONS OF THE PV MODULE
diode is connected in parallel to PV cells. The corresponding Parameter Value
structure is named the cell-unit, which is composed of m PV Open-circuit voltage 44.8 V
cells. The PV module is connected in series by n cell units to Short-circuit current 5.29 A
achieve the high output voltage. Usually, partial shadow is also Power output 180 W
MPP current 5A
accrued in one PV module. Due to the cell-unit structure, even MPP voltage 36 V
though only one cell is faulty (0 W/m2), the output power of the Current temperature coefficient 0.037%/K
cell-unit will decrease dramatically. Fig. 2(a) presents Voltage temperature coefficient 4
2
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Power temperature coefficient 8 information.
Operating cell temperature 46±2°C
(a)
(a) 18
Istring/Iarray (A)
Faulty string 1
Faulty string 2
10
Low voltage fault
High voltage fault
section
section
(constant current)
6
0 40 80 120
Uarray (V)
(b) (b)
Fig. 2 PV string under partial shading conditions. (a) The PV cell-unit
output. (b) Partial shading illustration.
3
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
front-end DC-DC converter tracks the Fig. 5 Voltage sensor placement methods: (a) 1, (b) 2, (c) 3.
4
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
When the working point of a PV string moves to the high the first k modules in the r-th string (i.e. 𝑢𝑟1 + 𝑢𝑟2 +
voltage section, the output voltage of the healthy modules ⋯ 𝑢𝑟𝑘 ). Whenever there is current flowing in the r-th
increases until reaching 𝑈𝑜𝑐 . The faulted modules in the string string, there will be at least one module works at low
will equally divide the remaining voltage 𝑈array −( 𝑎𝑖1 + 𝑎𝑖2 + voltage working points (e.g., 𝑈array < 𝑈𝑜𝑐 ). At the low
⋯ + 𝑎𝑖𝑠 )𝑈𝑜𝑐 . The following relations hold for a string including voltage section, the reading of 𝑢𝑟1 + 𝑢𝑟2 + ⋯ 𝑢𝑟𝑘 is a
both healthy and unhealthy modules. function of 𝑈array and cannot remain constant.
(1−𝑎𝑖𝑗 )(𝑈array −(𝑎𝑖1 +𝑎𝑖2 +⋯+𝑎𝑖𝑠 )𝑈𝑜𝑐 )
𝑢𝑖𝑗 = 𝑎𝑖𝑗 𝑈𝑜𝑐 + 𝑠−(𝑎𝑖1 +𝑎𝑖2 +⋯+𝑎𝑖𝑠 )
B. Locating faulty PV modules in the low-voltage section
(𝑎𝑖𝑗 𝑠−(𝑎𝑖1 +𝑎𝑖2 +⋯+𝑎𝑖𝑠 ))𝑈𝑜𝑐 (1−𝑎𝑖𝑗 )𝑈array After locating the healthy string, the next step is to find the
= 𝑠−(𝑎𝑖1 +𝑎𝑖2 +⋯+𝑎𝑖𝑠 )
+ 𝑠−(𝑎 (6) faulty PV module. In the low voltage diagnosis section, the
𝑖1 +𝑎𝑖2 +⋯+𝑎𝑖𝑠 )
𝑅𝑖,𝑗,𝑟,𝑘 = (𝑢𝑖1 + 𝑢𝑖2 + ⋯ + 𝑢𝑖𝑗 ) − (𝑢𝑟1 + 𝑢𝑟2 + ⋯ 𝑢𝑟𝑘 ) faulty modules are shorted. The corresponding fault diagnosis
𝑗 𝑗 eigenvalue of the mono-string faulty is presented in Table III,
(𝑠 ∑𝑙=1 𝑎𝑖𝑙 − 𝑗 ∑𝑠𝑙=1 𝑎𝑖𝑙 )𝑈𝑜𝑐 (𝑗 − ∑𝑙=1 𝑎𝑖𝑙 )𝑈array
= + where the fully-faulty module indicates that all cell-units in the
𝑠 − ∑𝑠𝑙=1 𝑎𝑖𝑙 ∑𝑠𝑙=1 𝑎𝑖𝑙 module are faulty (0: healthy and 1: faulty). No. 7 (111) is the
(𝑠 ∑𝑘 𝑠
𝑙=1 𝑎𝑟𝑙 −𝑘 ∑𝑙=1 𝑎𝑟𝑙 )𝑈𝑜𝑐 (𝑘−∑𝑘
𝑙=1 𝑎𝑟𝑙 )𝑈array extreme case that all the modules in this string are faulty. Even
− 𝑠−∑𝑠𝑙=1 𝑎𝑟𝑙
− ∑𝑠𝑙=1 𝑎𝑟𝑙
(7) though the PV array works in the low-voltage diagnosis section,
The reading 𝑅𝑖,𝑗,𝑟,𝑘 at the high voltage section provides the modules are open-circuited when all modules are faulty.
extra equations to solve variable 𝑎𝑖𝑗 . There is a way to design Table IV shows the multi-string eigenvalues. From these, the
the optimal sensor placement for any 𝑝 × 𝑠 array with faulty module can be identified easily.
⌈𝑝 × (𝑠 − 1)/2⌉ sensors. If p is an even number, the 𝑝 × 𝑠
𝑝 TABLE III VOLTAGE OF THE MONO-STRING ALL FAULTED MODULES
array can be divided into elements of 2 × 𝑠 arrays. For each PV31~PV33 Ua Ub Uc
2
2 × 𝑠 array, it needs to apply the optimal sensor placement 100 Uarray/3 2Uarray/3 Uarray/6
𝑝 010 Uarray/3 Uarray/6 Uarray/6
method by using × 𝑠 sensors. If p is odd, the 𝑝 × 𝑠 array 001 Uarray/3 Uarray/6 2Uarray/3
2
𝑝−3 110 Uarray/3 2Uarray/3 Uarray/3
consists of one 3 × 𝑠 array and elements of 2 × 𝑠 arrays. It
2 011 Uarray/3 Uarray/3 2Uarray/3
needs to apply the sensor placement method for these elements 101 Uarray/3 2Uarray/3 2Uarray/3
and the number of sensors needed is equal to ⌈3 × (𝑠 − 1)/2⌉ + 111 Uarray/3 2Uarray/3-Uoc 2Uoc -Uarray/3
𝑝−3 000 Uarray/3 Uarray/3 Uarray/3
(𝑠 − 1). By considering both even and odd numbers,
2
𝑝−3 TABLE IV VOLTAGE OF THE MULTI-STRINGS FULLY FAULTED MODULES
⌈3 × (𝑠 − 1)/2⌉ + (𝑠 − 1) = ⌈𝑝 × (𝑠 − 1)/2⌉ (8) PV11~PV13/PV21~PV23 Ua Ub Uc
2
Therefore, the optimal number of sensors can be obtained. 100/100 Uarray/2 Uarray/6 2Uarray/3
010/100 Uarray/2 Uarray/6 Uarray/6
001/100 Uarray Uarray/6 Uarray/6
IV. TWO-SECTION PV ARRAY FAULT DIAGNOSIS STRATEGY 100/010 Uarray/6 Uarray/6 2Uarray/3
The proposed PV array fault diagnosis strategy is 010/010 Uarray/6 Uarray/6 Uarray/6
001/010 Uarray/2 Uarray/6 Uarray/6
implemented in three steps: locating healthy PV string, locating 100/001 0 2Uarray/3 2Uarray/3
faulty module in the low-voltage diagnosis section, and in the 010/001 0 2Uarray/3 Uarray/6
high-voltage diagnosis section. 001/001 Uarray/2 2Uarray/3 Uarray/6
110/100 0 Uarray/6 2Uarray/3
A. Locating healthy PV strings 101/100 Uarray Uarray/6 2Uarray/3
011/100 Uarray Uarray/6 Uarray/3
The information of healthy strings is useful to identify a
faulty module. Thus the first step in fault diagnosis is to locate In practice, partial shading is a very common fault [2]-
healthy PV strings. Because of the absence of current sensors [3][5][12]-[14][22]-[33]. This is illustrated in detail in Table V.
in the string, the healthy string cannot be found directly. When Both Tables III and V are concerned with PV module faults.
a PV array changes from a healthy condition to an unhealthy Tables III deals with the fully-faulted module where all cell-
condition, the voltage sensor can pick up the change. units are faulted while Table V shows a partially faulted module
i) If the voltage sensor reading 𝑅𝑖,𝑗,𝑟,𝑘 always satisfies including some faulted cell-units. Their output voltages are zero
𝑗−𝑘
𝑅𝑖,𝑗,𝑟,𝑘 = 𝑈array despite any changes of the working and non-zero, respectively.
𝑠
point along the I-V curve, both i-th and r-th strings are C. Locating faulty PV module in the high-voltage section
healthy.
If all the PV strings are faulty, the eigenvalues of Tables III-
ii) If the i-th string is healthy, the sensor reading 𝑅𝑖,𝑗,𝑟,𝑘
𝑅𝑖,𝑗,𝑟,𝑘 𝑗 𝑎𝑟1 +𝑎𝑟2 +⋯+𝑎𝑟𝑘
V may be the same as other faulty conditions. This can lead to
satisfies − =− at low voltage misjudgment in locating faulty modules.
𝑈array 𝑠 𝑎𝑟1 +𝑎𝑟2 +⋯+𝑎𝑟𝑠
working points. This can be used to judge the number of For example, two types of the unhealthy 3×3 PV array with
faulty modules in the r-th string. the same sensor placement strategy are presented in Fig. 8.
𝑗 PV11, PV21, PV23 and PV32 are faulty at fault condition 1;
iii) If the i-th string is healthy, and (𝑅𝑖,𝑗,𝑟,𝑘 − 𝑈array ) remains
𝑠 PV12, PV21, PV31 and PV33 are faulty at condition 2. Two
constant for all working points, there is no current flowing fault conditions give the same voltage reading in the low-
in the r-th string, i.e., the r-th string is open circuited. This voltage diagnosis section, which is Uarray/2. In order to
𝑗
is because that (𝑅𝑖,𝑗,𝑟,𝑘 − 𝑈array ) is equal to the voltage of discriminate the two conditions, the high voltage diagnosis
𝑠
section is employed to find the actual faulty modules.
5
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
TABLE V VOLT OF THE MONO-STRING PARTIALLY FAULTED MODULES Monitor values from
PV11~PV13 Ua Ub Uc Comparison voltage sensor
Uarray/6<Ua< Uarray/3<Uc<
100 Uarray/3 —
Uarray/3 2Uarray/3
Uarray/6<Ua< Uarray/6<Uc<
010 Uarray/3 — Are all values normal?
Y
Uarray/3 Uarray/3
Uarray/3<Ua< Uarray/6<Uc<
001 Uarray/3 —
2Uarray/3 Uarray/3
Uarray/3<Uc<
110 Ua<Uarray/3 Uarray/3 2Ua Uc< Uarray
2Uarray/3 Is there a healthy
string? N
Uarray/3<Ua<
011 Uarray/3 Uc<Uarray/3 Ua 2Uc< Uarray
2Uarray/3 Y
Uarray/3<Uc< Low voltage area Low voltage area High voltage area
101 Ua<Uarray/3 Uarray/3 Ua 2Uc> Uarray
2Uarray/3 fault diagnosis fault diagnosis fault diagnosis
6
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
the rule for locating healthy strings. Therefore, string 2 is
diagnosed as being healthy which coincides with the fault
scenario in Fig. 12(a). Fig. 12(d) shows the sensor c output
curves. It can be seen that there is a healthy string, and the
values of Ua, Ub and Uc are Uarray/6, Uarray/6 and Uarray,
respectively, in the low-voltage diagnosis section. The faulty
modules identified are P11 and P33.
Tri-port
connector
(a) (b)
PV array
Two stage
converter
(a)
Fig. 10 Experimental platform.
(b) (c)
(a) (b)
8
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
conditions,” IEEE Trans. Power Electron. vol. 29, no. 11, pp. 5667-5672, Jiangfeng Zhang obtained his BSc and PhD in
Jun. 2014. computing mathematics and applied software from
[23] Z. Zou, Y. Hu, B. Gao, W. L.Woo and X. Zhao, “Study of the gradual Xi’an Jiaotong University, China, in July 1995 and
change phenomenon in the infrared image when monitoring photovoltaic December 1999, respectively. He is a senior lecturer at
array,” Journal of Applied Physics, vol. 115, no. 4, pp. 1-11, 2014. the Department of Electronic and Electrical
[24] T. Takashima, J. Yamaguchi, K. Otani, T. Oozeki, K. Kato, “Experimental Engineering, University of Strathclyde, Glasgow, U.K.
studies of fault location in PV module strings,” Solar Energy Materials He is also a member of the IFAC TC6.3 (Power and
and Solar Cells, vol. 93 issues. 6-7, pp. 1079-1082, Jun. 2009. Energy Systems). His research interests include
[25] R. A. Kumar, M. S. Suresh, J. Nagaraju, “Measurement of AC parameters modeling and control of energy systems, with a focus
of gallium arsenide (GaAs/Ge) solar cell by impedance spectroscopy,” on energy efficiency and demand side management.
IEEE Trans. Electron Devices, vol. 48, issue 9, pp. 2177-2179, 2001.
[26] A. Chouder, S. Silvestre, “Automatic supervision and fault detection of
PV systems based on power losses analysis,” Energy Conversion and Wenping Cao (M’05-SM’11) received the B.Eng in
Management, vol. 51, issue 10, pp. 1929-1937, Oct. 2010. electrical engineering from Beijing Jiaotong University,
[27] S. Silvestre, A. Chouder, E. Karatepe, “Automatic fault detection in grid Beijing, China, in 1991, and the Ph.D. degree in
connected PV systems,” Solar Energy, vol. 94, pp. 119-127, Aug. 2013.
electrical machines and drives from the University of
[28] N. Gokmen, E. Karatepe, S. Silvestre, B. Celik, P. Ortega, “An efficient
Nottingham, Nottingham, U.K., in 2004.
fault diagnosis method for PV systems based on operating voltage-
He is currently a Marie Curie Fellow with the
window,” Energy Conversion and Management, vol. 73, pp. 350-360, Sep.
Massachusetts Institute of Technology, Cambridge,
2013.
MA, U.S.A, and a Senior Lecturer with Queen’s
[29] X. Lin, Y. Wang, D. Zhu, N. Chang and M. Pedram, “Online fault detection
University Belfast, Belfast, U.K. Dr. Cao received the
and tolerance for photovoltaic energy harvesting systems,”
“Best Paper Award” at the LDIA’13 Conference, the
the 2012 IEEE/ACM International Conference on Computer-Aided Design
“Innovator of the Year” Award from Newcastle
(ICCAD), San Jose, USA, pp. 1-6. 2012.
University in 2013, and was the Winner of the “Dragons’ Den Competition” at
[30] D. Nguyen, B. Lehman. “An adaptive solar photovoltaic array using
Queen’s University Belfast in 2014. He serves as an Associate Editor for IEEE
model-based reconfiguration algorithm,” IEEE Trans. Ind. Electron., vol.
TRANSACTIONS ON INDUSTRY APPLICATIONS, IEEE INDUSTRY APPLICATIONS
55, no. 7, pp. 2644-2654, Jul. 2008.
MAGAZINE and IET Power Electronics, the Chief Editor for two Special Issues,
[31] J. P. Storey, P. R. Wilson, and D. Bagnall, “Improved optimization strategy
an Editor for Electric Power Components & Systems Journal and nine other
for irradiance equalization in dynamic photovoltaic arrays,” IEEE Trans.
International Journals. His research interests are in fault analysis and condition
Power Electron., vol. 28, no. 6, pp. 2946-2956, Jun. 2013.
monitoring of electric machines and power electronics.
[32] G. Velasco-Quesada, F. Guinjoan-Gispert, R. Pique-Lopez, M. Roman-
Lumbreras, and A. Conesa-Roca, “Electrical PV array reconfiguration
Jiande Wu (M’11) received the B.Sc. and the Ph.D. in
strategy for energy extraction improvement in grid-connected PV
power electronics from Zhejiang University in 1994
systems,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4319-4331, Nov.
and 2012, respectively. He has been a faculty member
2009.
at Zhejiang University since 1997 and is currently an
[33] Y. Wang, X. Lin, Y. Kim, N. Chang, and M. Pedram, “Architecture and
associate professor. From Oct. 2013 to Oct. 2014, he
control algorithms for combating partial shading in photovoltaic systems,”
was an academic visitor at the University of
IEEE Trans. Comput.-Aided Design Integr. Circuits Syst., vol. 33, no. 6,
Strathclyde, Glasgow, U.K. His research interests
pp. 917-929, Jun. 2014.
include applications of power electronics and network
[34] S. Jonathan, R. W. Peter, and B. Darren, “The optimized-string dynamic
communication.
photovoltaic array,” IEEE Trans. Power Electron., vol. 29, no. 4, pp. 1768-
1776, Apr. 2014.
[35] P. L. Carotenuto, P. Manganiello, G. Petrone, and G. Spagnuolo, “Online
Gui Yun Tian (M’01–SM’03) received the B.Sc. in
recording a PV module fingerprint,” IEEE J. Photovolt, vol. 4, no. 2, pp.
metrology and instrumentation and the M.Sc. in
659-668, Mar. 2014.
precision engineering from the University of Sichuan,
[36] Y. Hu, H. Chen, R. Xu, R. Li. “Photovoltaic (PV) array fault diagnosis
Chengdu, China, in 1985 and 1988, respectively, and
strategy based on optimal sensor placement,” Proceedings of the CSEE,
the Ph.D. degree from the University of Derby, Derby,
vol. 31, issue 33, pp. 19-30, 2011.
U.K., in 1998. He is currently a Chair Professor in
[37] B. Yang, W. Li, Y. Zhao and X. He, “Design and analysis of a grid-
sensor technologies at Newcastle University,
connected photovoltaic power system,” IEEE Trans. Power Electron., vol.
Newcastle upon Tyne, U.K. He is also with the School
25, no. 4, pp. 992-1000, Apr. 2010.
of Automation Engineering, University of Electronic
[38] P. Guerriero, V. d’Alessandro, L. Petrazzuoli, G. Vallone, and S. Daliento,
Science and Technology of China, Chengdu, China. He
“Effective real-time performance monitoring and diagnostics of individual
has coordinated several research projects from the Engineering and Physical
panels in PV plants,” the 4th International Conference on Clear Electrical
Sciences Research Council, Royal Academy of Engineering and FP7. He also
Power (ICCEP), Alghero, Italy, pp. 14-19. 2013.
has collaborative links with leading industrial companies, such as Airbus, Rolls
[39] P. Guerriero, G. Vallone, M. Primato, F. Di Napoli, L. Di Nardo, V.
Royce, BP, nPower, and TWI.
d’Alessandro, S. Daliento, “A wireless sensor network for the monitoring
of large PV plants,” the International Symposium on Power Electronics,
Electrical Drives, Automation and Motion (SPEEDAM), Ischia, Italy, pp.
Stephen J. Finney obtained the M.Eng in electrical
960-965, 2014.
and electronic engineering from Loughborough
University of Technology in 1988; and the Ph.D.
Yihua Hu (M’13) received the B.Sc. in electrical
degree from Heriot-Watt University, Edinburgh, U.K.,
motor drives in 2003, and the Ph.D. in power
in 1995. He worked for the Electricity Council
electronics and drives in 2011, both from China
Research Centre before joining the Power Electronics
University of Mining and Technology, Jiangsu, China.
Research Group at Heriot-Watt University in 1990.
Between 2011 and 2013, he was with the College of
From 1994 to 2005 he was a member of academic staff
Electrical Engineering, Zhejiang University as a
at Heriot-Watt University. Since 2005 he is with the
Postdoctoral Fellow. Between November 2012 and
Institute of Energy and Environment, University of
February 2013, he was an academic Visiting Scholar
Strathclyde, Glasgow, U.K., where he is currently a
with the School of Electrical and Electronic
Professor in power electronic systems. His research interests include the power
Engineering, Newcastle University, Newcastle upon
electronics for high power applications, power transmission and distribution.
Tyne, UK. He is currently a Research Associate with the Department of
Electronic & Electrical Engineering, University of Strathclyde, Glasgow, U.K.
His research interests include PV systems, DC-DC/DC-AC converters, and
electrical motor drives.
9
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
James L. Kirtley Jr. (LF’91) is a Professor of
electrical engineering at the Massachusetts Institute of
Technology, Cambridge, MA, U.S.A. He was with
General Electric, Large Steam Turbine Generator
Department as an Electrical Engineer, and with Satcon
Technology Corporation as Vice President and
General Manager of the Tech Center, and Chief
Scientist and Director.
Dr. Kirtley attended MIT as an undergraduate and
received the Ph.D. from MIT in 1971. He was
Gastdozent at the Swiss Federal Institute of Technology, Switzerland. He
served as Editor in Chief of the IEEE TRANSACTIONS ON ENERGY CONVERSION
from 1998 to 2006 and continues to serve as Editor for that journal, and as a
member of the Editorial Board of the Electric Power Components & Systems
Journal. He was awarded the IEEE Third Millennium medal in 2000, and the
Nikola Tesla prize in 2002. He was elected to the United States National
Academy of Engineering in 2007. His research interests are electric machinery
and electric power systems.
10