Journal of Physics: Conference Series

PAPER • OPEN ACCESS

Heat Transfer Characteristics of Fan Coil Unit (FCU) Under The Effect of
Chilled Water Volume Flowrate
To cite this article: Putu Wijaya Sunu et al 2018 J. Phys.: Conf. Ser. 953 012058

View the article online for updates and enhancements.

This content was downloaded from IP address 181.214.211.147 on 06/02/2018 at 01:01


The 2nd International Joint Conference on Science and Technology (IJCST) 2017 IOP Publishing
IOP Conf. Series: Journal of Physics: Conf. Series 1234567890
953 (2017) 012058 doi:10.1088/1742-6596/953/1/012058

Heat Transfer Characteristics of Fan Coil Unit (FCU) Under


The Effect of Chilled Water Volume Flowrate

Putu Wijaya Sunu1,*, Daud Simon Anakottapary2, A.A.N.B. Mulawarman3, I D


M Cipta Santosa4, I Putu Sastra Negara5
1, 2, 3, 4, 5
Mechanical Engineering Department, Bali State Polytechnic, Badung-Bali,
80364 Indonesia.

*e-mail: wijayasunu@pnb.ac.id

Abstract. In this paper, the volume flowrate of chilled water in the water chiller simulation
apparatus was optimized using experimental studied. The experimental analysis was performed
on the fan coil unit (FCU) of the system. The chilled water flows in tube side and the air as a
hot fluid flows throughout the tube and fin of FCU. The thermal performance and analysis of
the heat transfer is examined using various chilled water flowrate e.g. 11, 12, 13, 14, 15 lpm.
The effect of the flowrate to the important parameter such as LMTD temperature, heat absorb
used for investigate the heat transfer characteristics. The result showed that the heat transfer
characteristics has been increased with the increased of chilled water volume flowrate.

1. Introduction
Air conditioning system is a sequence of air movement, air cleanliness, controlling temperature,
humidifying and dehumidifying in order to reach the human comfort.

Condenser

TEV
Compressor
Evaporator

Pump
FCU

Figure 1. Schematic diagram of water chiller

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution
of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.
Published under licence by IOP Publishing Ltd 1
The 2nd International Joint Conference on Science and Technology (IJCST) 2017 IOP Publishing
IOP Conf. Series: Journal of Physics: Conf. Series 1234567890
953 (2017) 012058 doi:10.1088/1742-6596/953/1/012058

All of the process mentioned use a refrigeration cycle system which uses heat exchanger as equipment
to absorp/reject heat from the conditioned room to the ambient. The heat exchanger play a major role
not only in HVAC [1,2,3,4] but also in other field of engineering such as power plant, chemical,
automotive, food processing etc. In refrigeration system, there are four major component e.g
compressor, condenser, expansion device and evaporator. For chiller system which use secondary loop
to circulate the chilled water as shown in figure 1, there are additional component namely pump and
fan coil unit (FCU). Auxiliary components, such as circulation pumps and fan coil units, can consume
a significant proportion of the total energy used [5]. The improper fan coil unit can result in
degradation chilled water temperature difference across the coils [6]. For fan coil unit, control the
speed of fan during on/off cycle using variable speed to reduce the energy consumption [6]. A
complex system using PID control used to maintain the water temperature [7, 8]. [9] Suggest
controlling either the chilled water temperature or water volume flow rate to reduce the supplied load
to the building at part-load to reduced unnecessary pump power consumption [10]. Volume flowrate
of chilled water through the FCU play an important role not only power consumption but also the heat
absorb in the FCU itself. Thus, this study fills an important gap in the literature by investigating the
phenomenon of chilled water volume flowrate in a secondary loop. The specific objective and the
scope of this presented work are to evaluate the energy absorbed by the fan coil unit (FCU) in the heat
transfer process between air ambient and the chilled water.

2. Experimental Apparatus And Method

The schematic test rig of the experiment shown in figure 2.

Figure 2. The sketch of experimental apparatus with the measurement point

Rotameter used to control the volume flowrate of chilled water. This measurement component
equipped with hand shut off valve for varying the flow. The spesification of the experiment list
components shown in table 1.

2
The 2nd International Joint Conference on Science and Technology (IJCST) 2017 IOP Publishing
IOP Conf. Series: Journal of Physics: Conf. Series 1234567890
953 (2017) 012058 doi:10.1088/1742-6596/953/1/012058

Table 1. Test rig specification.


No Equipment Description
1 Compressor Hermetically sealed, Rotary
2 pk, R22 refrigerant
2 Condenser Air cooled, finned coil.
3 Expansion device Thermostatic expansion
valve (TEV)
4 Evaporator (HX) Shell and tube heat
exchanger
5 Fan coil unit (FCU) Finned and tube
6 Chilled water pump Centrifugal, 125 W

The refrigerant temperatures and air temperatures were measured by k-type thermocouples which
placed at four point of refrigeration cycle system and chilled water loop. The temperatures data were
digitalized using data logger and recorded in computer memory.

3. Data Processing

The aim of this current investigation is to determine the Logaritmic Mean Temperature Difference
(LMTD) and the heat absorb in the fan coil unit (FCU).

∆ ∆
∆ (1)

with,

∆ (2)

∆ (3)

The heat transfer in the FCU define as,

. . ∆ (4)

4. Result and Discussion


Through the counter flow approach, the LMTD in the FCU for flowrate 11 lpm calculated below as:

= 28.93 - 18.1 (oC)


= 10.82 oC

= 19.58 – 13.1 (oC)


= 6.47 oC
∆ ∆


. .
= .
.

3
The 2nd International Joint Conference on Science and Technology (IJCST) 2017 IOP Publishing
IOP Conf. Series: Journal of Physics: Conf. Series 1234567890
953 (2017) 012058 doi:10.1088/1742-6596/953/1/012058

= 8.46

For various flowrate the LMTD presented in figure 3. 

LMTD

8,9

8,8

8,7
LMTD

8,6

8,5

8,4
10 11 12 13 14 15 16
Flowrate (lpm)

Figure 3. LMTD on various volume flowrate

Figure 3 shows the logaritmic mean temperature difference (LMTD) from the fan coil unit on various
volume flowrate of chilled water. LMTD is the driven of the heat transfer in the FCU. It is found that,
the LMTD increased with increased of chilled water volume flowrate and the 15 lpm flowrate gave
higher than those of other flowrate. Polynomial statistical approach applied into the data to find the
pattern of the data. The significant LMTD increased found at 14 lpm. Here, the chilled water have
enough time to contact with the wall and made the FCU more effective.

Q absorb FCU

4,40

4,30

4,20
Q (kJ/s)

4,10

4,00

3,90

3,80
10 11 12 13 14 15 16
Flowrate (lpm)

Figure 4. Heat absorp by FCU on various volume flowrate

4
The 2nd International Joint Conference on Science and Technology (IJCST) 2017 IOP Publishing
IOP Conf. Series: Journal of Physics: Conf. Series 1234567890
953 (2017) 012058 doi:10.1088/1742-6596/953/1/012058

The calculation of heat absorbed by the chilled water describe as,

. .∆
= 0.18 . 4.187 . 5 (kJ/s)
= 3.83 (kJ/s)

The correlation of volume flowrate and the total heat absorbed by the chilled water describe on figure
4. It is found that the heat absorbed by the FCU increased with the increased of chilled water flowrate.
Increased the flowrate of chilled water increased the mass flowrate of it. The momentum transfer
generated by increased of mass flow responsible for thinning the thermal boundary layer and made the
heat absorb by the chilled water higher.

5. Conclusions
An experimental investigation on air cooled chiller with various volume flowrate was carried out for
LMTD analysis for describing the heat transfer absorb characteristics at Fan Coil Unit (FCU). The
result can be summarized as,
a) The LMTD increased with increased of chilled water volume flowrate.
b) The heat absorbed by the FCU increased with the increased of chilled water flowrate.

6. List of symbols
LMTD Logaritmic Mean Temperature Difference
th temperature of hot fluid [oC]
tc temperature of cold fluid [oC]
Q heat absorb in FCU [kJ/s]
mass flowrate [kg/s]
ΔT temperature difference of chilled water in/out FCU [0C]
Cp specific heat [kJ/kg oC]

7. References
[1] Sunu P W, Anakottapary D S, Santika W G 2016 Matec Web of Conference 58, 04006
[2] Sunu P W, and Rasta I M 2017 Acta Polytechnica 57(2):125–130
[3] Liu M S, Mark C C L, Wang C C 2011 Nanoscale Research Letters 6:297
[4] Naik B K, Muthukumar P 2017 Energy Procedia 109 ( 2017 ) 293 – 305
[5] Albieri M, Beghi A, Bodo C, Cecchinato L 2008 International Journal of Refrigeration 32 (5)
1068-1076
[6] Teitel M, Levi A, Zhao Y, Barak M, Bar-lev, E Shmuel D 2008 Energy and Buildings 40 953–
960
[7] Zhang X J, Yu C Y, Li S, Zheng Y M, Xiao F 2011 Applied Thermal Engineering 31 3653-
3657.
[8] Wang S, Xu X 2002 Energy Conversion and Management 43 2569–2588.
[9] Fahlén P, Markusson C 2011 ASHRAE Transactions, ISSN 0001-2505.
[10] Henze G P, Floss A G 2011 Energy and Buildings 431820–1828.