UNIT-4 Part-1
UNIT-4 Part-1
UNIT-4 Part-1
HarisH Patil
HVAC Water System
►Refrigerant temperature in
evaporator is less than TC.
►Irreversible heat transfers
have negative effect on
Two-phase performance.
-vapor mixture
Refrigeration Cycle
►Heat transfers between refrigerant and cold and warm
regions are not reversible.
►Refrigerant temperature in
evaporator is less than TC.
►Refrigerant temperature in
condenser is greater than
TH.
►Irreversible heat transfers
have negative effect on
performance.
The Vapor Compression Refrigeration Cycle
Coefficient of Performance
TH
R
TL
The Vapor Compression Refrigeration Cycle
Coefficient of Performance
energy sought Q
ηE = = in = COPC
TH energy that costs Wcycle
Global Warming Potential (GWP) is a simplified index that estimates the potential
future influence on global warming associated with different gases when released
to the atmosphere.
Refrigerant Types and Characteristics
►Chlorofluorocarbons (CFCs) and Hydrochlorofluorocarbons
(HCFCs) are early synthetic refrigerants each containing chlorine.
Because of the adverse effect of chlorine on Earth’s stratospheric
ozone layer, use of these refrigerants is regulated by international
agreement.
►Hydrofluorocarbons (HFCs) and HFC blends are chlorine-free
refrigerants. Blends combine two or more HFCs. While these
chlorine-free refrigerants do not contribute to ozone depletion, with
the exception of R-1234yf, they have high GWP levels.
►Natural refrigerants are nonsynthetic, naturally occurring
substances which serve as refrigerants. These include carbon
dioxide, ammonia, and hydrocarbons. These refrigerants feature
low GWP values; still, concerns have been raised over the toxicity
of NH3 and the safety of the hydrocarbons.
Refrigerant Types and Characteristics
An ideal refrigerant should have the following properties:
1. low viscosity
2. low freezing point
3. low boiling point
4. low heat capacity
5. low specific volume
6. low saturation pressure
7. odorless
8. High latent heat of vaporization.
9. good thermal conductivity
10. high COP
11. Non inflammable and non explosive.
12. high critical pressure and temperature.
Refrigerant Types and Characteristics
Uses of Refrigerants:
Ammonia: Ice plants, large cold storages, etc.
Capillary tube
Thermal expansion valve (TXV)
Electronic expansion valve
Refrigeration System Components
Expansion Valve
Capillary tube
Cooling
tower
Chiller AHU
Plant
Chillers
AHU
Chillers
Chillers
What is a Chiller?
The refrigeration machine that produces chilled water is referred to as a “Chiller”.
A chiller is a water-cooled air conditioning system that cools inside air, creating a more
comfortable and productive environment.
Basically, there are two types of chillers based upon the refrigeration cycle:
1. Vapour Compression Chiller
2. Absorption Refrigeration Chiller
Based upon the condensation process of working fluid , there are two types of chiller:
1. Air-Cooled Chiller
2. Water Cooled Chiller
Working of Chillers
1. Chillers circulate chilled water to air-handlers(AHU’s) in order to transfer heat from air
to water.
2. This water then returns to the evaporator side of the chiller where the heat is
passed from the water to a liquid (LP) refrigerant .
3. The refrigerant leaves the evaporator as a cold vapor (LP) and enters the
compressor where it is compressed into a hot vapor (HP).
4. Upon leaving the compressor, the vapor enters the condenser side of the chiller
where heat is transferred from the refrigerant to the air/water side of the
condenser where it is circulated to an ACC/open cooling tower for the final
removal of heat from the refrigerant as a liquid (HP).
55ºF 170ºF
COMPRESSOR
68.5PSIG 226PSIG
Low Pressure, High Pressure,
High Temp Vapor High Temp Vapor
EVAPORATOR CONDENSER
R-22 refrigerant with, Evaporating Temp 4.4ºC & Condensing Temp 43.3ºC
Chillers Basics: Refrigeration Cycle
29
COP of chiller
Coefficient of Performance
Each Kg of refrigerant entering the evaporator will contain a
certain amount of heat and each Kg of refrigerant leaving the
evaporator will have a certain amount of heat. (Heat absorbed
in evaporator) Pressure
COP COOLING = Refrigeration Effect Work Done per unit time can be
Work Done expressed in kW
Chillers Components
EVAPORATOR COMPRESSOR :
Uses Refrigerant to absorb i. Centrifugal
Heat from Water . ii. Reciprocating
Types : iii. Screw
1. Shell and Tube : iv. Scroll
i. Direct Expansion
ii. Flooded Type
2. Plate Type EXPANSION VALVE :
i. Thermostatic Expansion
CONDENSER Valve
Uses Refrigerant reject Heat to ii. Electronic Expansion Valve
Water .
Cooling Towers:
i. Water Cooled
i. Water Cooling Towers
ii. Air Cooled
ii. Air Cooling Towers
iii. Evaporative
a. c.
a. Induced Draft Counter flow
b. Forced Draft Counter Flow
c. Induced Draft Cross Flow
(Single Flow Tower)
d. Induced Draft Cross Flow
(Double Air Entry)
b.
d.
Chiller Plant Configurations
1. Single chiller
2. Parallel chiller
3. Series chiller
4. Primary/Secondary system (Primary pump without VFD)
5. Primary/Secondary system (Primary pump with VFD)
Single Chiller System
Single Chiller System (Constant Flow)
For constant flow, chilled water temp range varies directly with the
load
Chiller is sized to meet load
1. Fewer % of time – 100%
2. Balance time = 50 to 60%
Advantages:
1. Easiest design
2. Require smaller mechanical room
Disadvantages
1. Least efficient
2. Provide no redundancy
Parallel Chiller System
Parallel Chiller System
Advantages
Provide a redundancy
Improve overall system load performance.
Reduce energy consumption
Disadvantage
1. Mixed flow issues
Series Chiller System
Series Chiller System
Sequence of Operation
As the chiller plant load increases, the lead chiller will load from 0 to 100%
capacity to meet it. Once the lead chiller is loaded (which is likely to be about
45% of plant capacity) the lag chiller is started.
Here are three ways to operate the lag chiller:
1. Set the upstream chiller chilled water setpoint to bring on the chiller once the
downstream chiller is fully loaded. This will preferentially load the downstream
chiller. The downstream chiller will operate at full load while the upstream chiller
will ramp up as the chiller plant load goes from about 45% to 100%. If the
downstream chiller is offline for any reason, the upstream chiller will not be able
to assume its role unless the chilled water setpoint is changed, either manually or
remotely.
2. Move the upstream chiller sensor downstream of both chillers. This will
preferentially load the upstream chiller. Once the upstream chiller cannot
maintain the chilled water supply temperature, the downstream chiller will start
and provide the balance of the load.
3. Modern chiller controllers can allow two chillers to communicate. In this
arrangement. Either chiller can be the first chiller on. Once the first chiller is fully
loaded, the second chiller will start and the load will be evenly balanced between
the two chillers. This can result in about a 2% improvement in annual chiller
energy usage. Where possible, this method is recommended
Series Chiller System
Advantages
1.No mixing issues
2.Optimize chiller performance
Disadvantages
1. Pressure drop through evaporates are additive
Primary/Secondary (Decoupled) Chiller System
(Constant flow)
Primary/Secondary (Decoupled) Chiller System
(Constant flow)
Decoupled Loop
The additional flow from the two primary pumps bypasses the building
through the decoupler. The bypassed water mixes with the return
water from the building and is returned to the chillers.
The decoupler allows the pumps to operate at different flow rates. This
is necessary because the primary pumps are fixed speed and the
secondary pumps are variable speed. Only on special occasions will
the primary pump flow and the secondary flow be equal.
Isolation Valve:
An automatic isolating valve is required for each chiller to stop short-
circuiting when the chiller and pump are off.
Primary/ Secondary Chiller System (Variable flow)
Bypass Line:
There is a bypass line to Maintain minimum flow through The chillers
only. Whenever the Chilled water flow is above Minimum, the bypass
is closed. Usually, the minimum flow rate of a chiller is 50% of the
design flow rate.
Bypass Line Valve Control:
It is recommended that each chiller should have a flow meter. The
meter can be used to recognize both minimum and maximum flow
constraints.
The bypass line control valve is controlled by a signal from the flow
meter of the operating chiller.
The control system should recognize the chiller and know the
minimum flow rate for that chiller.
The bypass line control valve is modulated to maintain the minimum
chiller flow. This must be done slowly. Fast changes in the bypass
line flow may cause the primary pump control loop to hunt as it
recognizes a change in total chilled water flow.
Waterside free cooling
Heat exchanger in
parallel with the chiller.
During free cooling the
chiller is off and isolated
by valves. The heat
exchanger rejects heat
into the condenser water
loop. For this to happen,
the condenser loop must
be colder than the chilled
water loop (the reverse of
chiller Operation).
This is “Non Integrated”
System
Series Waterside free cooling
Heat Pump
Heat pump is essentially an air conditioner with a few additions. A heat pump
has a reversing valve, two metering devices and two bypass valves. This
allows the unit to provide both cooling and Heating.
Heat pump in Cooling mode
a) The compressor (1) pumps the refrigerant to the reversing valve (2).
b)The reversing valve directs the flow to the outside coil (condenser) where the fan (3)
cools and condenses the refrigerant to liquid.
c)The air flowing across the coil removes heat (4) from the refrigerant
d)The liquid refrigerant bypasses the first metering device and flows to the second
metering device (6) at the inside coil (evaporator) where it is metered.
e)Here it picks up heat energy from the air blowing (3) across the inside coil (evaporator)
and the air comes out cooler (7). This is the air that blows into the home.
f)The refrigerant vapor (8) then travels back to the reversing valve (9) to be directed to the
compressor to start the cycle all over again (1).
Heat pump in Heating mode
The diagram above shows the heat pump in heat mode. The difference in the two
diagrams is the reversing valve (2) directs the compressed refrigerant to the inside coil
first. This makes the inside coil the condenser and releases the heat energy (3-4). This
heated air is ducted to the home. The outside coil is used to collect the heat energy (3-7).
This now becomes the evaporator.
Absorption Chiller