Electric Controls: M P M e T e S Atr

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24
At a glance
Powered by AI
The document discusses different types of terminal units like parallel flow fan terminal units and series flow fan terminal units. It also describes different fan control codes and damper control methods for these units.

The document discusses parallel flow fan terminal units and series flow fan terminal units. Parallel flow units have the primary and secondary air mixed together before discharge, while series flow units have the air streams in series.

The document describes several fan control codes for electric parallel flow fan terminal units including CO (damper switch start/stop), JO (damper switch start/stop with electronic speed control), DO (damper switch start/stop with night setback), etc.

FORM AD2T-GEN (700)

CO
OL
ER

HE
AT WA
R ME
R
CO
OL
ER

CO
OL
WA
RM
E RM
50
R WA
60
70
80
OL
90 CO
90
80

Electric Controls 50
60
70

Te m p m a s t e r

A Controls Selection Guide for V.A.V. Terminal Devices


VOLUME III
70

10
0

SELECT FOR APPLICATION USING VAV COOLING &


80

70
90
VAV COOLING W/ HOT WATER OR ELECTRIC HEAT 80

0
10

90

4GROUND3

BGROUND
TABLE OF CONTENTS

MODEL GENERAL PAGE

ALL MODELS COVER & AD2T-GEN TABLE OF CONTENTS ........................................... 1, 2


ALL MODELS DISCUSSION ............................................................................................ 3 – 7
ALL MODELS MANUAL TABLE OF CONTENTS ............................................................ 8 – 10
ALL MODELS CONTROL SELECTION MATRIXES GENERAL INFORMATION ............... A.A1
ALL MODELS ELECTRIC CONTROL CODES ................................................................. A.A2

K.W. CHARTS AND SYMBOLS

ALL MODELS MAXIMUM K.W. CHARTS EXPLANATION .................................................. KW1


HSE HSE MAXIMUM K.W. CHARTS ................................................................... KW2
HMSRE HMSRE MAXIMUM K.W. CHARTS .............................................................. KW3
HFBE HFBE MAXIMUM K.W. CHARTS ................................................................. KW4
HVFBE HVFBE MAXIMUM K.W. CHARTS ............................................................... KW5
HVFSE HVFSE MAXIMUM K.W. CHARTS ............................................................... KW6
HFMLE HFMLE MAXIMUM K.W. CHARTS ............................................................... KW7
HFSLE, HLFSE HFSLE 7 HLFSE MAXIMUM K.W. CHARTS ............................................... KW8
ALL MODELS SYMBOLS LIST – ELECTRICAL SYMBOLS ............................................... SY1

2 YORK INTERNATIONAL
FORM AD2T-GEN

DISCUSSION
GENERAL thermostat is used for cooling with 2-stage heat, with
deadbands between both stages. The 1st stage
Tempmaster has subdivided the control into three func- deadband is 1.5°F and the 2nd stage is 40°F. This stat
tional areas. Damper operation, which is the same for may also be used in conjunction with an auxiliary damper
all units; fan operation, which is basically starting and switch to provide for 3 stage heat without 1st stage
stopping the fan at appropriate times compatible with deadband and is the only option available for 3 stage
the style of the unit; and the heating coil control, both heat.
water and electric heating coils. The 1st digit identifies
the box type. The 2nd and 3rd digits identify the damper ELECTRIC DAMPER CONTROL CODES
control. The 4th and 5th digits identify the fan control
(for fan terminal units). The 6th identifies landed voltage Damper Control Code - N0
and the 7th digit identifies electric heater control method
when electric heat is required. This is the basic electric control for terminal units. The
thermostat directly controls the actuator to provide the
required volume of air depending on space temperature.
DAMPER CONTROL AND OPERATION
Damper Control Code - R0
All electric control methods are of the pressure depen-
dent type. Pressure dependent controls are controlled This is the same control as code N0 above except a
directly by the thermostat. With this type of control the high limit control is used to provide a preset maximum
volume of air through the units is dependent upon the air volume independent of the thermostat signal. High
static pressure at the inlet of the unit. limit is achieved by use of a air pressure switch, with a
flow sensor mounted on the inlet of the unit. The high
An optional High Limit control is available for all units limit setpoint can be factory or field set and can be field
which limits the maximum primary air flow through the adjusted.
unit by use of an adjustable air pressure switch. All se-
ries type fan terminal units are supplied with High Limit Damper Control Code - 1R
control to prevent fan overload from excessive primary
This is the same control as code NO above except a
air flow.
auxiliary damper switch is provided for initiation of hot
water, or electric heat.
Dampers are controlled by Tempmaster’s new standard
.1 over the shaft” mounted, 24 volt, rotary damper actua-
Damper Control Code - 1S
tor. The actuator has a 5 minute-600 travel, and is rated
at 35 lb.-in. of torque. The actuator utilizes a magnetic This is the same control as code RO above except a
coupling providing a 45 lb.-in. stall torque which elimi- auxiliary damper switch is provided for initiation of hot
nates the need for mechanical stops or limit switches. It water, or electric heat.
can optionally be supplied with 1 or 2 auxiliary switches
for heat control or fan cycling. The actuator can also be Damper Control Code - X0
supplied with an optional minimum position adjustment
This is a cooling only unit control with changeover stat
to allow for minimum air flow requirements.
for central system heating. The stat is mounted on the
unit and has a 6 ft. long capillary and sensing bulb for
Damper actuator control is provided by the ES type float-
field insertion in the supply air duct. When supply air
ing thermostat which de-energizes the actuator when
above 750°F (adjustable) is sensed in the duct it switches
the space temperature is satisfied. The slow rotational
and reverses the actuator operation. In this condition if
time of the actuator in combination with this floating ther-
the space is calling for heat the damper will move to-
mostat control helps prevent “system hunting”. The ES-
wards its full open position. When the supply duct tem-
1 1 thermostat is used for cooling only applications; or
perature drops below 70°F (adjustable) the changeover
cooling with heating applications without deadband when
stat will switch the unit operation back to normal cooling
used in conjunction with an auxiliary damper switch to
mode.
control the heating mode. The ES-21 thermostat is used
for cooling with 1 stage heat when a deadband is re-
Damper Control Code - Y0
quired. The ES-21 has a deadband of 1.5°F between
cool and heat. This stat may also be used in conjunc- This is the same control as code X0 above except a
tion with an auxiliary damper switch to provide for 2 high limit control is used to provide a preset maximum
stages of heat without 1st stage deadband. The ES-31 air volume independent of the thermostat signal. High

YORK INTERNATIONAL 3
limit is achieved by use of an air pressure switch, with a Damper Control Code - 1M
flow sensor mounted on the inlet of the unit. The high
This is a cooling and heating unit control with a deadband
limit setpoint can be factory or field set and can be field
between cooling & heating operation. It may be used for
adjusted.
hot water or 1 stage electric heat if a deadband is re-
quired.
Damper Control Code - 1J
This is a cooling only unit control with changeover relay Damper Control Code - 1N
for central system heating. The 24 volt changeover relay This is the same control as code 1M above except a
is activated by a remote signal (by others) it switches high limit control is used to provide a preset maximum
and reverses the actuator operation. In this condition if air volume independent of the thermostat signal. High
the space is calling for heat the damper will move to- limit is achieved by use of an air pressure switch, with a
wards its full open position. When the remote signal (by flow sensor mounted on the inlet of the unit. The high
others) is de-activated the changeover relay will switch limit setpoint can be factory or field set and can be field
the unit operation back to normal cooling mode. Damper adjusted.
Control Code - 1K This is the same control as code 1J
above except a high limit control is used to provide a Damper Control Code - 1W
preset maximum air volume independent of the thermo-
stat signal. High limit 1 is achieved by use of an air This is the same control as code 1M above except a
pressure switch, with a flow sensor mounted on the inlet auxiliary damper switch is provided for initiation of the
of the unit. The high limit setpoint can be factory or field 1st stage of electric heat for a 2-stage electric heater.
set and can be field adjusted. This control does not have a deadband between cooling
& heating mode. If 2-stage heat is required with a
Damper Control Code - T0 deadband between cooling and heating mode see con-
trol code 1P below.
This is a dual duct with mixing (constant volume) con-
trol. This control provides for hot duct and cold duct mix- Damper Control Code - 1X
ing at all times maintaining a constant volume of air to
This is the same control as code 1N above except a
the space in response to the thermostat signal. This
auxiliary damper switch is provided for initiation of the
type of control is not very practical due to the mixing of
1st stage of electric heat for a 2-stage electric heater.
hot and cold air at all times.
This control does not have a deadband between cooling
Damper Control Code - 1L
& heating mode. If 2-stage heat is required with a
This is the same control as code T0 above except 2 deadband between cooling and heating mode see con-
high limit controls are used to provide a preset maxi- trol code 1Q below.
mum air volume independent of the thermostat signal.
High limit is achieved by use of an air pressure switch, Damper Control Code - 1P
with a flow sensor mounted on both the cold air & hot air This is a cooling and 2-stage heating unit control with a
inlets of the unit. The high limits setpoints can be fac- deadband between cooling & heating operation and 1 st
tory or field set and can be field adjusted. and 2nd stage heat. It may be used for 2-stage electric
heat if a deadband is required.
Damper Control Code - 1T
This is a dual duct with out mixing (variable air volume) Damper Control Code - 1Q
control. An auxiliary damper switch on both the hot duct This is the same control as code 1P above except a
& cold duct is provided to insure that on a call for heat high limit control is used to provide a preset maximum
the cold duct damper is closed before the hot duct damper air volume independent of the thermostat signal. High
can start to open and on a call for cooling that the hot limit is achieved by use of an air pressure switch, with a
duct damper is closed before the cold duct damper can flow sensor mounted on the inlet of the unit. The high
start to open. limit setpoint can be factory or field set and can be field
adjusted.
Damper Control Code - 1U
Damper Control Code - 1Y
This is the same control as code TO above except 2
high limit controls are used to provide a preset maxi- This is a cooling and 3 stage heating unit control without
mum air volume independent of the thermostat signal. a deadband between cooling & heating operation. An
High limit is achieved by use of an air pressure switch, auxiliary damper switch is provided for initiation of the
with a flow sensor mounted on both the cold air & hot air 1st stage of electric heat for a 3 stage electric heater.
inlets of the unit. The high limits setpoints can be fac- This and code 2A are the only 3 stage electric heater
tory or field set and can be field adjusted. control methods available.

4 YORK INTERNATIONAL
FORM AD2T-GEN

Damper Control Code - 2A is the standard supplied volume control method. As an


option an electronic speed control can be furnished on
This is the same control as code 1Y above except a
all units with the exception of units requiring 277 volt 1/
high limit control is used to provide a preset maximum
10 hp motors. The low amp draw of these motors pre-
air volume independent of the thermostat signal. High
cludes the use of the electronic speed control for vol-
limit is achieved by use of an air pressure switch, with a
ume control.
flow sensor mounted on the inlet of the unit. The high
limit setpoint can be factory or field set and can be field
adjusted. ELECTRIC PARALLEL FLOW FAN CONTROL CODES

Fan Control Code - CO (Damper Switch Start/


FAN CONTROL AND OPERATION
Stop)
There are 2 basic configurations of fan powered terminal This control utilizes an external damper switch that is
units available, these are commonly referred to as paral- mounted on the rotary, primary air actuator. The fan is
lel flow and series flow. energized by the damper switch as the primary air
damper reaches its closed position. The damper switch
Parallel Flow Fan Terminal Units is adjustable to allow the fan to be energized at any
point as the damper is closing.
These units are configured with the primary air supply
(normally cooling only from a central conditioning sys-
Fan volume control is accomplished by the adjustable
tem) and the secondary air (generally available from the
manual backdraft damper provided.
return air plenum) in parallel with each other. The central
conditioning system provides the energy to move the
Fan Control Code - JO (Damper Switch Start/
primary air through the unit control damper. The second-
Stop)
ary air (from the return air plenum) is moved through the
unit by a forward curve centrifugal fan which is powered This control is the same as control code CO above, ex-
by a direct driven, permanent split capacitor, fractional cept an electronic speed control is supplied in place of
horsepower motor. The secondary air is introduced into the adjustable manual backdraft damper volume con-
the primary air path downstream of the primary air unit trol, to provide fan volume control.
control damper. A backdraft damper is provided on the
blower discharge to prevent primary air from escaping Fan Control Code - DO (Damper Switch Start/
back through the blower during normal cooling opera- Stop, Night Setback)
tion when the fan is not running. The motor blower on
This control operates in the same sequence as control
these units is only energized on a demand for heating.
code CO above, in normal occupied mode operation.
Tempmaster parallel flow fan terminal unit models can
This control also allows for night setback (unoccupied
be distinguished by the letters “FB” in the model desig-
mode) operation. During the unoccupied mode a unit
nation.
mounted thermostat senses the return air plenum air
temperature. If the air temperature falls below the night
These units are typically used in applications where
setback thermostat setpoint (adjustable) the fan is
perimeter VAV cooling with heating is required. With the
started and the supplemental heat (if applicable) is en-
space calling for cooling the central system conditioned
abled. Fan volume control is accomplished by the ad-
air is modulated by the unit primary air damper to sat-
justable manual backdraft damper provided.
isfy the space cooling load. As the space load is satis-
fied and the primary damper closes, the motor/blower is
Fan Control Code - KO (Damper Switch Start/
energized by an auxiliary damper switch. The blower
Stop, Night Setback)
supplies warm plenum air (assuming the plenum air tem-
perature is higher than the space thermostat setpoint) This control is the same as control code DO above, ex-
to satisfy low level space heating loads. The auxiliary cept an electronic speed control is supplied in place of
damper switch may be field adjusted to initiate the blower the adjustable manual backdraft damper volume con-
at any point in the reduction of primary damper airflow, if trol, to provide fan volume control. Fan Control Code -
desired. Supplemental heating may be accomplished NO (Damper Switch Start/Stop, Night Setback) This
by optional unit mounted hot water or electric heating control is the same as control code DO above, except
cools to satisfy higher level space heating loads. an air flow sensor is additionally supplied. This control
code is required when damper control code without high
Typically the motor/blower for parallel flow units is sized limit control is used. Fan Control Code - PO (Damper
for 50% of the unit primary air flow. Secondary air flow Switch Start/Stop, Night Setback) This control is the
(blower) volume control is accomplished by adjustment same as control code KO above, except an air flow sen-
of the backdraft damper volume control mechanism and sor is additionally supplied.

YORK INTERNATIONAL 5
This control code is required when damper control code additional option to ensure that the damper is closed
without high limit control is used. prior to blower startup to eliminate any possibility of re-
verse blower rotation. Tempmaster offers a control op-
Series Flow Fan Terminal Units tion allowing a remote signal (by others) to start the
blower. If this option is used it is the responsibility of
These units are configured with the primary air supply
others to ensure that the fan starts before the primary
(normally cooling only from a central conditioning sys-
air damper opens, to prevent the possibility of the blower
tem) and the secondary air (generally available from the
stalling or blower reverse rotation.
return air plenum) in series with each other. The central
conditioning system provides the energy to move the
The motor/blower for series flow units is sized for 100%
primary air through the unit control damper. The second-
of the unit primary air flow. Blower air flow volume control
ary air (from the return air plenum) is moved through the
is accomplished by adjustment of an electronic speed
unit by a forward curve centrifugal fan which is powered
control. An adjustable high limit damper volume control
by a direct driven, permanent split capacitor, fractional
is also supplied, to limit primary airflow through the unit
horsepower motor. The secondary air is introduced into
to a preset maximum.
the primary air path downstream of the primary air unit
control damper and both are mixed in the unit blower
Electric Series Flow Fan Control Codes Fan
and discharged into the downstream duct. The fan oper-
Control Code - WO (Air Flow Switch Start/Stop)
ates continuously anytime the central conditioning sys-
tem is operating, providing constant volume air to the This control starts the fan any time airflow, at the inlet of
space at the required mixed air temperature to satisfy the unit, is sensed by an adjustable air flow switch.
the space load.
Fan Control Code - AO (Air Flow Switch Start/
Tempmaster series flow fan terminal unit models can be Stop, Damper Override)
distinguished by the letters “FS” in the model designa-
This control starts the fan any time airflow, at the inlet of
tion.
the unit, is sensed by an adjustable air flow switch. This
control also has an extra relay that interlocks with the
These units are typically used in applications where
primary air damper to insure that anytime primary air is
perimeter constant volume cooling with heating is re-
not sensed at the inlet of the unit, the damper will move
quired. With the space calling for cooling and the cen-
to its full closed position.
tral conditioning system supplying air to the unit, the
unit motor/blower is energized and the primary air damper
Fan Control Code - YO (Air Flow Switch Start/
modulates to satisfy the space cooling load. The unit
Stop, Night Setback)
motor/blower must be energized prior to central system
air being supplied to the unit to prevent backward rota- This control operates in the same sequence as control
tion of the motor/blower. As the space load is satisfied code WO above, in normal occupied mode operation.
and the primary damper closes, the motor/blower con- This control also allows for night setback (unoccupied
tinues to operate, supplying warm plenum air (assum- mode) operation. During the unoccupied mode a unit
ing the plenum air temperature is higher than the space mounted thermostat senses the return air plenum air
thermostat setpoint) to satisfy low level space heating temperature. If the air temperature falls below the night
loads. Supplemental heating may be accomplished by setback thermostat setpoint (adjustable) the fan is
optional unit mounted hot water or electric heating coils started and the supplemental heat (if applicable) is en-
to satisfy higher level space heating loads. These are abled.
initiated by an auxiliary damper switch or a cooling/heat-
ing thermostat signal. The auxiliary damper switch may Fan Control Code - 90 (Air Flow Switch Start/
be field adjusted to initiate heating at any point in the Stop, Night Setback, Damper Override)
reduction of primary damper airflow, if desired.
This control operates in the same sequence as control
Tempmaster recommends the use of an interlocking air
code AO above, in normal occupied mode operation.
flow switch to initiate the motor/blower anytime the cen-
This control also allows for night setback (unoccupied
tral conditioning system is in operation. We do not rec-
mode) operation. During the unoccupied mode a unit
ommend the use of backdraft dampers on the second-
mounted thermostat senses the return air plenum air
ary air inlet because tests indicate that if air is forced
temperature. If the air temperature falls below the night
through the blower, it will load up and possibly stall the
setback thermostat setpoint (adjustable) the fan is
motor, or even cause the blower to reverse rotation.
started and the supplemental heat (if applicable) is
Tempmaster can supply a damper override relay as an
enabled.

6 YORK INTERNATIONAL
FORM AD2T-GEN

Fan Control Code - SO (Fan Relay Start/Stop) Fan Control Code - 10 (Air Flow Switch Start/
Stop, Electric Heat Only)
This control starts the fan any time a 24 volt signal (by
others) is sent to the fan start relay. The fan must be This control operates in the same sequence as control
turned on at the same time, or prior to primary air being code WO above. This control also has an extra relay
supplied at the unit inlet. provided to prevent the electric heater from being ener-
gized unless the fan is operating.
Fan Control Code - I P (Air Flow Switch Start/
Stop, Night Setback, Damper Override, Electric Fan Control Code - 1Y (Air Flow Switch Start/
Heat Only) Stop, Electric Heat Only)
This control operates in the same sequence as control This control operates in the same sequence as control
code YO above, in normal occupied mode and unoccu- code AO above. This control also has an extra relay
pied mode operation. This control also has an extra re- provided to prevent the electric heater from being ener-
lay that interlocks with the primary air damper to insure gized unless the fan is operating.
that anytime primary air is not sensed at the inlet of the
unit, the damper will move to its full closed position. An
additional relay is provided to prevent the electric heater
from being energized unless the fan is operating.

YORK INTERNATIONAL 7
Te m p m a s t e r
R

TABLE OF CONTENTS

MODEL PAGE
GENERAL

ALL MODELS CONTROL SELECTION MATRIXES GENERAL INFORMATION A.A1

ALL MODELS ELECTRIC CONTROL CODES A.A2

SINGLE DUCT

S, V, CD, SL VAV COOLING ONLY - SELECTION MATRIX A.M1-A.M2

S, V, CD, SL VAV COOLING ONLY - CONTROL DIAGRAMS A1-A12

HSW, HVW VAV COOLING W/ HOT WATER REHEAT - SELECTION MATRIX B.M1-B.M2

HSW, HVW VAV COOLING W/ HOT WATER REHEAT - CONTROL DIAGRAMS B1-B8

HSE VAV COOLING W/ ELECTRIC REHEAT - SELECTION MATRIX C.M1-C.M2

HSE VAV COOLING W/ ELECTRIC REHEAT - CONTROL DIAGRAMS C1-C40

BYPASS

MSR VAV COOLING ONLY - SELECTION MATRIX D.M1-D.M2

MSR VAV COOLING ONLY - CONTROL DIAGRAMS D1-D6

HMSRW VAV COOLING W/ HOT WATER REHEAT - SELECTION MATRIX E.M1-E.M2

HMSRW VAV COOLING W/ HOT WATER REHEAT - CONTROL DIAGRAMS E1-E4

HMSRE VAV COOLING W/ ELECTRIC REHEAT - SELECTION MATRIX F.M1-F.M2

HMSRE VAV COOLING W/ ELECTRIC REHEAT - CONTROL DIAGRAMS F1-F20

DUAL DUCT

SX & VX VAV COOLING & HEATING - SELECTION MATRIX G.M1-G.M2

SX & VX VAV COOLING & HEATING - CONTROL DIAGRAMS G1-G8

INDEL1

8 YORK INTERNATIONAL
FORM AD2T-GEN

Te m p m a s t e r
R

TABLE OF CONTENTS

MODEL PAGE

PARALLEL FLOW FAN TERMINAL

HFB, HVFB VAV COOLING ONLY - SELECTION MATRIX H.M1-H.M2

HFB, HVFB VAV COOLING ONLY - CONTROL DIAGRAMS H1-H32

HFBW, HVFBW VAV COOLING W/ HOT WATER HEAT - SELECTION MATRIX J.M1-J.M2

HFBW, HVFBW VAV COOLING W/ HOT WATER HEAT - CONTROL DIAGRAMS J1-J32

HFBE, HVFBE VAV COOLING W/ ELECTRIC HEAT - SELECTION MATRIX K.M1-K.M6

HFBE, HVFBE VAV COOLING W/ ELECTRIC HEAT - CONTROL DIAGRAMS K1-K80

SERIES FLOW FAN TERMINAL

HFS, HLFS, HVFS, VAV COOLING ONLY - SELECTION MATRIX L.M1-L.M2


HFML, HFSL

HFS, HLFS, HVFS, VAV COOLING ONLY - CONTROL DIAGRAMS L1-L36


HFML, HFSL

HFSW, HLFSW, VAV COOLING W/ HOT WATER HEAT - SELECTION MATRIX M.M1-M.M4
HVFSW, HFMLW,
HFSLW

HFSW, HLFSW, VAV COOLING W/ HOT WATER HEAT - CONTROL DIAGRAMS M1-M40
HVFSW, HFMLW,
HFSLW

HLFSE, HVFSE VAV COOLING W/ ELECTRIC HEAT - SELECTION MATRIX N.M1-N.M8


HFMLE, HFSLE

HLFSE, HVFSE VAV COOLING W/ ELECTRIC HEAT - CONTROL DIAGRAMS N1-N100


HFMLE, HFSLE

INDEL2

YORK INTERNATIONAL 9
Te m p m a s t e r
R

TABLE OF CONTENTS

MODEL PAGE

K.W. CHARTS & SYMBOLS

ALL MODELS MAXIMUM K.W. CHARTS EXPLANATION KW1

HSE HSE MAXIMUM K.W. CHARTS KW2

HMSRE HMSRE MAXIMUM K.W. CHARTS KW3

HFBE HFBE MAXIMUM K.W. CHARTS KW4

HVFBE HVFBE MAXIMUM K.W. CHARTS KW5

HVFSE HVFSE MAXIMUM K.W. CHARTS KW6

HFMLE HFMLE MAXIMUM K.W. CHARTS KW7

HFSLE, HLFSE HFSLE & HLFSE MAXIMUM K.W. CHARTS KW8

ALL MODELS SYMBOLS LIST - ELECTRICAL SYMBOLS SY1

INDEL3

10 YORK INTERNATIONAL
FORM AD2T-GEN

Te m p m a s t e r
R

ELECTRIC CONTROL SELECTION MATRIXES


GENERAL INFORMATION

THE CONTROL SELECTION GUIDE IS BROKEN DOWN INTO 5 MAIN SECTIONS. EACH SECTION CONTAINS
MATRIXES & APPLICATION CONTROL DIAGRAMS RELATED TO THE TYPE OF TERMINAL DEVICE LISTED
FOR THAT SECTION (SINGLE DUCT, BYPASS, DUAL DUCT, PARALLEL AND SERIES FLOW FAN TERMINALS).
EACH OF THESE SECTIONS IS FURTHER BROKEN DOWN BY SEQUENCE CATEGORY (VAV COOLING ONLY,
VAV COOLING W/ HOT WATER HEAT & VAV COOLING W/ ELECTRIC HEAT). EACH OF THESE CATEGORIES
HAS AN ASSOCIATED SELECTION MATRIX(ES). THE MATRIXES ALLOW YOU TO SELECT THE TYPE OF
CONTROL OPTIONS, AND THEIR RESULTING CONTROL CODE AND SCHEMATIC DIAGRAM PAGE NUMBER.
EACH MATRIX HAS 3 MAIN CATEGORIES OF SELECTION, FAN TERMINALS HAVE AN ADDITIONAL CATEGORY
FOR FAN CONTROL. IF ELECTRIC HEAT IS REQUIRED A SELECTION CATEGORY IS ALSO PROVIDED FOR ITS
OPTIONS. FOLLOWING IS A BRIEF EXPLANATION OF THE MATRIX SELECTION CATEGORIES PROVIDED.

CONTROL TYPE (ITEM 1)


DETERMINES WHETHER THE CONTROL SEQUENCE IS PRESSURE DEPENDENT OR PRESSURE
INDEPENDENT. ALL ELECTRIC CONTROL SEQUENCES ARE PRESSURE DEPENDENT.

SEQUENCE OF OPERATION: (ITEM 2). SUB-CATEGORIES ARE:


DAMPER CONTROL: VAV COOLING ONLY, W/ CHANGEOVER, ETC;
TEMPERATURE CONTROL: ES-11, ES-21 OR ES-31 THERMOSTAT AS REQUIRED.
VOLUME CONTROL: AVAILABLE SELECTIONS FOR HI-LIMIT VOLUME CONTROL.

CONTROL TRANSFORMER: (ITEM 3)


ALLOWS SELECTION OF CUSTOMER OR FACTORY SUPPLIED/MOUNTED 24 VOLT CONTROL TRANSFORMER.
ALL CONTROLS WITH ELECTRIC HEAT WILL HAVE FACTORY SUPPLIED/MOUNTED OPTION ONLY.

FAN CONTROL (ITEM 4)


PROVIDES FOR SELECTION OF APPLICABLE FAN CONTROL OPTIONS INCLUDING STARTING METHOD AND
VOLUME CONTROL. ALSO PROVIDES FOR SELECTION OF FAN NIGHT SETBACK WHEN ALLOWABLE.

ELECTRIC HEAT CONTROL (ITEM 5)


AVAILABLE OPTIONS INCLUDE 1 PHASE, 3 PHASE AND 1 2 OR 3 STAGE HEAT.

1 2 3 4 5
SEQUENCE
OF OPERATION
HEAT CONTROL
CONTROL XFMR.
CONTROL TYPE

ELECTRIC
CONTROL
TEMP. CONTROL
DAMPER CNTRL.

FAN
CONTROL
VOLUME

TO USE THE SELECTION MATRIXES, SELECT THE APPROPRIATE MATRIX FOR YOUR UNIT TYPE AND
GENERAL SEQUENCE (VAV COOLING ONLY, VAV COOLING W/ HOT WATER HEAT OR VAV COOLING W/
ELECTRIC HEAT). SELECT THE REQUIRED SPECIFIC SEQUENCE OF OPERATION (ITEM 2 OPTIONS)
INCLUDING DAMPER CONTROL, TEMPERATURE CONTROL AND VOLUME CONTROL AND MOVE DOWN
THE MATRIX COLUMNS TO FIND A CODE AND DIAGRAM PAGE NUMBER THAT HAS A ROUND SYMBOL
IN THE COLUMNS WITH YOUR REQUIRED OPTIONS. CONTINUE TO MOVE UP OR DOWN COLUMNS TO
FIND A SELECTION WITH YOUR REQUIRED CONTROL TRANSFORMER AND IF REQUIRED FAN AND OR
ELECTRIC HEAT OPTIONS. WHEN YOU FIND A CODE & PAGE NUMBER THAT HAS ALL YOUR CORRECT
OPTIONS CHECKED WITH A ROUND SYMBOL GO TO THE SPECIFIED PAGE IN THE ELECTRIC CONTROLS
CATALOG TO FIND ANY OTHER DRAWING VARIABLES TO FINISH BUILDING YOUR 7 DIGIT CONTROL
CODE. USE THIS CODE AND SCHEMATIC DIAGRAM PAGE NUMBER WHEN ORDERING CONTROLS.
MTXSEL3

-A.A1-

YORK INTERNATIONAL 11
Te m p m a s t e r
R

BOX X XX XX X X ELECTRIC
1
2
COOLING ONLY
COOLING W/ ELECTRIC HEAT
CONTROL CODE
3 COOLING W/ HOT WATER HEAT
4 FAN TERMINAL - COOLING ONLY
5 FAN TERMINAL - W/ ELECTRIC HEAT
6 FAN TERMINAL - W/ HOT WATER HEAT
7 DUAL DUCT - W/ MIXING
8 DUAL DUCT - W/O MIXING
9 FAN TERMINAL - COOLING ONLY

A
CONTROL XFMR BY OTHERS
FAN TERMINAL - W/ HOT WATER HEAT ELECTRIC HEATER CONTROL
CONTROL XFMR BY OTHERS 0 NONE
6 30A MAGNETIC DE-ENERGIZING CONTACTOR
7 50A MAGNETIC DE-ENERGIZING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR
E 30A MAGNETIC DISCONNECTING CONTACTOR
F 50A MAGNETIC DISCONNECTING CONTACTOR
DAMPER G
H
30A MERCURY DISCONNECTING CONTACTOR
50A MERCURY DISCONNECTING CONTACTOR
00 NONE
10 MANUAL
N0 ROTARY, ACTUATOR, ES-11 STAT
R0 ROTARY, ACTUATOR, HI-LIMIT, ES-11 STAT
T0 ROTARY, ACTUATORS, ES-11 STAT (DUAL DUCT)
X0 ROTARY, ACTUATOR, C.O. STAT, ES-11 STAT
Y0 ROTARY, ACTUATOR, HI-LIMIT, C.O. STAT, ES-11 STAT
1J ROTARY, ACTUATOR, C.O. RELAY, ES-11 STAT
1K ROTARY, ACTUATOR, HI-LIMIT, C.O. RELAY, ES-11 STAT
1L
1M
ROTARY, ACTUATORS, HI-LIMITS, ES-11 STAT (DUAL DUCT)
ROTARY, ACTUATOR, ES-21 STAT LANDED VOLTAGE
1N ROTARY, ACTUATOR, HI-LIMIT, ES-21 STAT
1P ROTARY, ACTUATOR, ES-31 STAT W/O ELECTRIC HEAT
1Q ROTARY, ACTUATOR, HI-LIMIT, ES-31 STAT 0 NONE V 208V/1Ø/60HZ
1R ROTARY, ACTUATOR, ES-11 STAT, DAMPER SWITCH A 24V/1Ø/60HZ (W/O XFMR) Q 240V/1Ø/60HZ
1S ROTARY, ACTUATOR, HI-LIMIT, ES-11 STAT, DAMPER SWITCH B 120V/1Ø/60HZ C 277V/1Ø/60HZ
1T ROTARY, ACTUATORS, ES-11 STAT, DAMPER SWITCH (DUAL DUCT)
1U ROTARY, ACTUATORS, HI-LIMIT, ES-11 STAT, DAMPER SWITCH
(DUAL DUCT) W/ ELECTRIC HEAT
1W ROTARY, ACTUATOR, ES-21 STAT, DAMPER SWITCH D 120V/1Ø/60HZ - 1 STAGE P 208V/3Ø/60HZ - 1 STAGE
1X ROTARY, ACTUATOR, HI-LIMIT, ES-21 STAT, DAMPER SWITCH E 120V/1Ø/60HZ - 2 STAGE R 208V/3Ø/60HZ - 2 STAGE
1Y ROTARY, ACTUATOR, ES-31 STAT, DAMPER SWITCH 5 120V/1Ø/60HZ - 3 STAGE 1 208V/3Ø/60HZ - 3 STAGE
2A ROTARY, ACTUATOR, HI-LIMIT, ES-31 STAT, DAMPER SWITCH F 208V/1Ø/60HZ - 1 STAGE S 240V/3Ø/60HZ - 1 STAGE
2B ELECTRIC, ACTUATOR, ES-11 STAT G 208V/1Ø/60HZ - 2 STAGE T 240V/3Ø/60HZ - 2 STAGE
2C ELECTRIC, ACTUATOR, HI-LIMIT, ES-11 STAT 4 208V/1Ø/60HZ - 3 STAGE 2 240V/3Ø/60HZ - 3 STAGE
2D ELECTRIC, ACTUATORS, ES-11 STAT (DUAL DUCT) H 240V/1Ø/60HZ - 1 STAGE U 480V/3Ø/60HZ - 1 STAGE
2E ELECTRIC, ACTUATOR, C.O. STAT, ES-11 STAT J 240V/1Ø/60HZ - 2 STAGE W 480V/3Ø/60HZ - 2 STAGE
2F ELECTRIC, ACTUATOR, HI-LIMIT, C.O. STAT, ES-11 STAT 6 240V/1Ø/60HZ - 3 STAGE 3 480V/3Ø/60HZ - 3 STAGE
2G ELECTRIC, ACTUATOR, C.O. RELAY, ES-11 STAT K 277V/1Ø/60HZ - 1 STAGE X 208V/3Ø/60HZ - 1 STAGE
2H ELECTRIC, ACTUATOR, HI-LIMIT, C.O. RELAY, ES-11 STAT L 277V/1Ø/60HZ - 2 STAGE W/O NEUTRAL (3 WIRE)
2J ELECTRIC, ACTUATORS, HI-LIMITS, ES-11 STAT (DUAL DUCT) Y 277V/1Ø/60HZ - 3 STAGE 8 208V/3Ø/60HZ - 2 STAGE
2K ELECTRIC, ACTUATOR, ES-21 STAT M 480V/1Ø/60HZ - 1 STAGE W/O NEUTRAL (3 WIRE)
2L ELECTRIC, ACTUATOR, HI-LIMIT, ES-21 STAT N 480V/1Ø/60HZ - 2 STAGE 9 208V/3Ø/60HZ - 3 STAGE
2M ELECTRIC, ACTUATOR, ES-31 STAT 7 480V/1Ø/60HZ - 3 STAGE W/O NEUTRAL (3 WIRE)
2N ELECTRIC, ACTUATOR, HI-LIMIT, ES-31 STAT
2P ELECTRIC, ACTUATOR, ES-11 STAT, DAMPER SWITCH
2Q ELECTRIC, ACTUATOR, HI-LIMIT, ES-11 STAT, DAMPER SWITCH
2R ELECTRIC, ACTUATORS, ES-11 STAT, DAMPER SWITCH (DUAL DUCT)
2S ELECTRIC, ACTUATORS, HI-LIMIT, ES-11 STAT, DAMPER SWITCH
(DUAL DUCT)
2T ELECTRIC, ACTUATOR, ES-21 STAT, DAMPER SWITCH
2U ELECTRIC, ACTUATOR, HI-LIMIT, ES-21 STAT, DAMPER SWITCH
2W ELECTRIC, ACTUATOR, ES-31 STAT, DAMPER SWITCH
2X ELECTRIC, ACTUATOR, HI-LIMIT, ES-31 STAT, DAMPER SWITCH

FAN
PARALLEL FLOW (EXCEPT LOW TEMP) ALL SERIES FLOW (AND LOW TEMP PARALLEL FLOW)
00 NONE 00 NONE
C0 FAN RELAY, DAMPER SWITCH, VOLUME CONTROL 10 FAN RELAY, AIR FLOW SWITCH, SPEED CONTROL (ELEC. HEAT ONLY)
D0 FAN RELAY, DAMPER SWITCH, AIR FLOW SWITCH, NIGHT SETBACK STAT, 90 FAN RELAY, AIR FLOW SWITCH, DAMPER OVERRIDE, NIGHT SETBACK STAT,
VOLUME CONTROL SPEED CONTROL
J0 FAN RELAY, DAMPER SWITCH, SPEED CONTROL A0 AIR FLOW SWITCH, DAMPER OVERRIDE RELAY, SPEED CONTROL
K0 FAN RELAY, DAMPER SWITCH, AIR FLOW SWITCH, NIGHT SETBACK STAT, S0 FAN RELAY, SPEED CONTROL,
SPEED CONTROL W0 AIR FLOW SWITCH, SPEED CONTROL
N0 FAN RELAY, DAMPER SWITCH, AIR FLOW SWITCH, NIGHT SETBACK STAT, Y0 FAN RELAY, AIR FLOW SWITCH, NIGHT SETBACK STAT, SPEED CONTROL
VOLUME CONTROL, FLOW SENSOR 1G 30A FAN RELAY, AIR FLOW SWITCH, 25A SPEED CONTROL
P0 FAN RELAY, DAMPER SWITCH, AIR FLOW SWITCH, NIGHT SETBACK STAT, (HFS-120V G,H,J)
SPEED CONTROL, FLOW SENSOR 1H 30A FAN RELAY, AIR FLOW SWITCH, NIGHT SETBACK STAT,
25A SPEED CONTROL (HFS-120V G,H,J)
1J 30A FAN RELAY, AIR FLOW SWITCH, NIGHT SETBACK STAT,
DAMPER OVERRIDE, 25A SPEED CONTROL (HFS-120V G,H,J)
1K 30A FAN RELAY, AIR FLOW SWITCH, DAMPER OVERRIDE,
25A SPEED CONTROL (HFS-120V G,H,J)
1L 30A FAN RELAY, 25A SPEED CONTROL (HFS-120V G,H,J)
1M 30A FAN RELAY, DAMPER OVERRIDE, 25A SPEED CONTROL
(HFS-120V G,H,J)
1P FAN RELAY, AIR FLOW SWITCH, NIGHT SETBACK STAT,
DAMPER OVERRIDE RELAY, SPEED CONTROL (ELEC. HEAT ONLY)
1Y FAN RELAY, AIR FLOW SWITCH, DAMPER OVERRIDE RELAY,
SPEED CONTROL (ELEC. HEAT ONLY)

REV. 1 (8-20-93)
PNMCLTR2

-A.A2-

12 YORK INTERNATIONAL
FORM AD2T-GEN

Te m p m a s t e r
R

USE OF MAXIMUM K.W. SELECTION CHARTS


BASIS FOR MAXIMUM K.W. CHARTS
THE MAXIMUM K.W. VALUES IN THE CHARTS ON THE FOLLOWING PAGES ARE BASED
ON THE FOLLOWING FACTORS: CURRENT RATING LIMITATIONS OF THE CONTROL
COMPONENTS SELECTED, 40° TEMPERATURE RISE ( T) ACROSS THE COIL FOR HVFSE
HFMLE, HFSLE, HLFSE AND HVFBE UNITS, 50° TEMPERATURE RISE FOR HFBE UNITS,
65° TEMPERATURE RISE FOR SINGLE DUCT AND BYPASS UNITS, PHYSICAL CONSTRAINTS
OF UNIT, OR 48 AMPS MAXIMUM TOTAL UNIT CURRENT INCLUDING FAN MOTOR.

FOLLOWING ARE THE COMPONENTS MAXIMUM CURRENT RATINGS:


30 AMP CONTACTORS (MERCURY OR MAGNETIC) = 30 AMPS @ ALL VOLTAGES.
50 AMP CONTACTORS (MERCURY OR MAGNETIC) = 50 AMPS @ ALL VOLTAGES.
TOTAL UNIT INCLUDING FAN MOTOR = 48 AMPS (WITHOUT SPECIAL SUBCIRCUIT FUSING.)

USING CHARTS
IN ORDER TO USE THE CHARTS YOU MUST HAVE ALREADY SELECTED A TYPE OF UNIT,
ITS MODEL SIZE OR FAN SIZE, & REQUIRED K.W. FOR JOB. FIRST GO TO THE MAXIMUM
K.W. VS CFM CHART FOR THE SPECIFIC UNIT SELECTED TO CONFIRM THAT YOUR INITIAL
SELECTION FALLS WITHIN THE TEMPERATURE RISE VS CFM MAXIMUMS LISTED. IF IT
EXCEEDS THE LISTED LIMITS, THEN YOU MUST DECREASE THE K.W., INCREASE THE CFM,
OR BOTH. IF THE REQUIRED CFM IS NOT LISTED, USE THE FORMULAS BELOW CHART TO
CALCULATE ACTUAL TEMPERATURE RISE OR K.W.

ONCE YOU HAVE A SELECTION THAT FALLS WITHIN THE MAXIMUM K.W. VS CFM LIMITS,
PROCEED TO THE MAXIMUM CONTROL K.W. CHART. FIND YOUR REQUIRED HEATER
VOLTAGE & STAGES OF HEAT, AND SELECT THE HEATER CONTROL CODE (CONTACTOR TYPE)
DESIRED. CONFIRM THAT YOUR REQUIRED K.W. FALLS WITHIN THE HEATER CONTROL CODE'S
K.W. LIMITS. IF IT DOES NOT, SELECT ANOTHER HEATER CONTROL CODE (50A CONTACTOR)
THAT WILL MEET YOUR K.W. REQUIREMENTS.

SELECTION EXAMPLE #1
REQUIRED: HSE, MODEL D, HEATING CFM = 700, 4.0 K.W.- 2 STAGE HEAT, 277V/1Ø/60HZ
GO TO MAXIMUM K.W. VS CFM CHART. 700 CFM = 14.5 K.W. MAXIMUM, REQUIRED K.W. IS 4.0;
THEREFORE, WE ARE NOT LIMITED BY OUR TEMPERATURE RISE OR CFM.

GO TO MAX. K.W. PER STAGE CHART AND SELECT THE HEATER CONTROL CODE 6
(THIS IS THE LEAST EXPENSIVE 1Ø OPTION.)
REQUIRED K.W. = 4.0, CHART SHOWS 13.2 KW. MAXIMUM TOTAL K.W.; THERFORE, THIS IS A GOOD
SELECTION.

SELECTION EXAMPLE #2
REQUIRED: HVFBE, MODEL E, HEATING CFM = 750, 9.5 K.W.- 1 STAGE HEAT, 277V/1Ø/60HZ
GO TO MAXIMUM K.W. VS CFM CHART. 750 CFM IS NOT LISTED, REQUIRED K.W. IS 9.5
SINCE THE CHART DOES NOT LIST THIS CFM WE MUST CALCULATE OUR ACTUAL T.

3413 X 9.5
T= T = 39.8 39.8 IS LESS THAN 40° T MAXIMUM.
750 X 1.085

GO TO MAX. K.W. PER STAGE CHART AND SELECT THE HEATER CONTROL CODE 6
(THIS IS THE LEAST EXPENSIVE 1Ø OPTION.) LOOK AT COLUMNS FOR UNIT MODEL E.
REQUIRED K.W. = 9.5, CHART SHOWS 8.3 K.W. MAXIMUM; THERFORE, THIS IS NOT A GOOD
SELECTION. TRY HEATER CONTROL CODE 7. REQUIRED K.W. = 9.5, CHART SHOWS 11.2 K.W.
MAXIMUM TOTAL K.W.; THERFORE, THIS IS A GOOD SELECTION.

SELECTION EXAMPLE #3
REQUIRED: HVFSE, MODEL F, HEATING CFM = 2000, 25.3 K.W.- 3 STAGE HEAT, 480V/3Ø/60HZ
GO TO MAXIMUM K.W. VS CFM CHART. 1600 CFM = 25.4 K.W. MAXIMUM, REQUIRED K.W. IS 25.3;
THEREFORE, WE ARE NOT LIMITED BY OUR TEMPERATURE RISE OR CFM.

GO TO MAX. K.W. PER STAGE CHART AND SELECT THE HEATER CONTROL CODE 6
(THIS IS THE LEAST EXPENSIVE 3Ø OPTION.)
REQUIRED K.W. = 25.3, CHART SHOWS 24.9 K.W. MAXIMUM; THEREFORE THIS IS NOT A GOOD
SELECTION. TRY HEATER CONTROL CODE 7. REQUIRED K.W. = 25.3 3 STAGE, CHART SHOWS 35.4
MAXIMUM TOTAL K.W.; THEREFORE, THIS IS A GOOD SELECTION.

MKWEXPEL

-KW1-

YORK INTERNATIONAL 13
KW LIMITATIONS
SINGLE DUCT TERMINAL
MODEL HSE - ELECTRIC

MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 3.1 4.1 5.2 6.2 7.2 8.3 10.3 12.4 14.5 16.5 18.6 20.7 22.7 24.8 26.9 28.9 31.0 33.1 35.1 37.2 39.3 *39.4

* VALUE REPRESENTS 480/3/60


MAX. KW

HSE MAXIMUM CONTROL TOTAL KW


P UNIT MODELS UNIT MODELS UNIT MODELS UNIT MODELS UNIT MODELS UNIT MODELS UNIT MODELS
HEATER H A, B C, D E F G H J, K, M
CONTROL VOLTS A STAGES STAGES STAGES STAGES STAGES STAGES STAGES
CODE S
E 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

ALL CONTROL SEQUENCES


120 1 3.6 5.7 5.7 3.6 5.7 5.7 3.6 5.7 5.7 3.6 5.7 5.7 3.6 5.7 5.7 3.6 5.7 5.7 3.6 5.7 5.7
208 1 6.2 9.7 8.6 6.2 9.9 9.9 6.2 9.9 9.9 6.2 9.9 9.9 6.2 9.9 9.9 6.2 9.9 9.9 6.2 9.9 9.9
6-8-E-
240 1 7.2 9.7 8.4 7.2 11.4 11.4 7.2 11.4 11.4 7.2 11.4 11.4 7.2 11.4 11.4 7.2 11.4 11.4 7.2 11.4 11.4
G
277 1 8.3 9.1 8.1 8.3 13.2 13.2 8.3 13.2 13.2 8.3 13.2 13.2 8.3 13.2 13.2 8.3 13.2 13.2 8.3 13.2 13.2
480 1 9.7 9.4 N/A 13.4 13.4 11.9 14.4 15.8 15.8 14.4 19.5 19.5 14.4 22.8 22.8 14.4 22.8 22.8 14.4 22.8 22.8
120 1 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
208 1 9.7 9.7 8.6 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9
7-9-F-
240 1 9.7 9.7 8.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4
H
277 1 9.7 9.1 8.1 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2
480 1 9.7 9.4 N/A 13.4 13.4 11.9 15.8 15.8 15.8 19.5 19.5 19.5 22.8 22.8 22.8 22.8 22.8 22.8 22.8 22.8 22.8
208 3 8.6 8.4 N/A 10.8 10.8 8.9 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
6-8-E-
240 3 8.4 6.8 N/A 12.5 12.5 8.5 12.5 12.5 10.3 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5
G
480 3 8.1 N/A N/A 13.4 11.4 N/A 15.8 13.7 N/A 19.5 19.5 14.6 24.9 24.9 20.6 24.9 24.9 24.9 24.9 24.9 24.9
208 3 8.6 8.4 N/A 13.4 12.9 8.9 15.8 15.8 11.7 17.1 17.1 16.6 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1 17.1
7-9-F-
240 3 8.4 6.8 N/A 13.4 13.4 8.5 15.8 15.8 10.3 19.5 19.5 14.8 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7 19.7
H
480 3 8.1 N/A N/A 13.4 11.4 N/A 15.8 13.7 N/A 19.5 19.5 14.6 25.6 25.6 20.6 31.7 31.7 29.1 39.4 39.4 39.4

ELECTRIC HEATER ELECTRIC CONTROL CODES


CODE DESCRIPTION CODE DESCRIPTION

6 30A MAGNETIC DE-ENERGIZING CONTACTOR E 30A MAGNETIC DISCONNECTING CONTACTOR


7 50A MAGNETIC DE-ENERGIZING CONTACTOR F 50A MAGNETIC DISCONNECTING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR G 30A MERCURY DISCONNECTING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR H 50A MERCURY DISCONNECTING CONTACTOR

TEMPMASTER CORP. JANUARY 92


- KW2 -

14 YORK INTERNATIONAL
FORM AD2T-GEN

KW LIMITATIONS
SINGLE DUCT TERMINAL
MODEL HMSRE - ELECTRIC

MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 3.1 4.1 5.2 6.2 7.2 8.3 10.3 12.4 14.5 16.5 18.6 20.7 22.7 24.8 26.9 28.9 31.0 33.1 35.1 37.2 39.3 *39.4

* VALUE REPRESENTS 480/3/60


MAX. KW

HMSRE MAXIMUM CONTROL TOTAL KW


P UNIT MODELS UNIT MODELS UNIT MODELS
H B, C, D E, F G
HEATER CONTROL CODE VOLTS A STAGES STAGES STAGES
S
E 1 2 3 1 2 3 1 2 3

ALL CONTROL SEQUENCES


120 1 3.6 5.7 5.7 3.6 5.7 5.7 3.6 5.7 5.7
208 1 6.2 9.9 9.9 6.2 9.9 9.9 6.2 9.9 9.9
6-8-E-G 240 1 7.2 11.4 11.4 7.2 11.4 11.4 7.2 11.4 11.4
277 1 8.3 13.2 13.2 8.3 13.2 13.2 8.3 13.2 13.2
480 1 13.4 13.4 11.9 14.4 19.5 19.5 14.4 22.8 22.8
120 1 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
208 1 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9
7-9-F-H 240 1 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4
277 1 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2
480 1 13.4 13.4 11.9 19.5 19.5 19.5 22.8 22.8 22.8
208 3 10.8 10.8 8.9 10.8 10.8 10.8 10.8 10.8 10.8
6-8-E-G 240 3 12.5 12.5 8.5 12.5 12.5 12.5 12.5 12.5 12.5
480 3 13.4 11.4 N/A 19.5 19.5 14.6 24.9 24.9 24.9
208 3 13.4 12.9 8.9 17.1 17.1 16.6 17.1 17.1 17.1
7-9-F-H 240 3 13.4 13.4 8.5 19.5 19.5 14.8 19.7 19.7 19.7
480 3 13.4 11.4 N/A 19.5 19.5 14.6 31.7 31.7 29.1

ELECTRIC HEATER ELECTRIC CONTROL CODES


CODE DESCRIPTION CODE DESCRIPTION

6 30A MAGNETIC DE-ENERGIZING CONTACTOR E 30A MAGNETIC DISCONNECTING CONTACTOR


7 50A MAGNETIC DE-ENERGIZING CONTACTOR F 50A MAGNETIC DISCONNECTING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR G 30A MERCURY DISCONNECTING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR H 50A MERCURY DISCONNECTING CONTACTOR

TEMPMASTER CORP. JANUARY 92


- KW3 -

YORK INTERNATIONAL 15
KW LIMITATIONS
PARALLEL FLOW FAN TERMINAL
MODEL HFBE - ELECTRIC

MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 2.4 3.2 4.0 4.8 5.6 6.4 7.9 9.5 11.1 12.7 14.3 15.9 17.5 19.1 20.7 22.3 23.8 25.4 27.0 28.6 30.2 31.8

HFBE MAXIMUM CONTROL TOTAL KW


UNIT MODEL UNIT MODEL UNIT MODEL UNIT MODEL UNIT MODEL UNIT MODEL UNIT MODEL
P A, B, C D, E D, E F, G F, G F, G H
HEATER H FAN SIZE FAN SIZE FAN SIZE FAN SIZE FAN SIZE FAN SIZE FAN SIZE
CONTROL VOLTS A 02, 03, 04 06, 08 12 06, 08 12 15 20
CODE S
E STAGES STAGES STAGES STAGES STAGES STAGES STAGES
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
ALL CONTROL SEQUENCES

6-8-E- 120 1 3.6 5.5 5.5 3.6 5.4 5.4 3.6 5.3 5.3 3.6 5.4 5.4 3.6 5.3 5.3 3.6 4.8 4.8 3.6 4.7 4.7
G 277 1 8.3 13.0 13.0 8.3 12.9 12.9 8.3 12.8 12.8 8.3 12.9 12.9 8.3 12.8 12.8 8.3 12.4 12.4 8.3 12.3 12.3
7-9-F- 120 1 5.5 5.5 5.5 5.4 5.4 5.4 5.3 5.3 5.3 5.4 5.4 5.4 5.3 5.3 5.3 4.8 4.8 4.8 4.7 4.7 4.7
H 277 1 13.0 13.0 13.0 12.9 12.9 12.9 12.8 12.8 12.8 12.9 12.9 12.9 12.8 12.8 12.8 12.4 12.4 12.4 12.3 12.3 12.3
6-8-E- 208 3 10.8 10.8 8.9 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
G 480 3 13.7 13.7 N/A 19.4 19.4 14.6 19.4 19.4 14.6 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9
7-9-F- 208 3 13.7 13.7 8.9 16.1 16.1 16.1 15.8 15.8 15.8 16.1 16.1 16.1 15.8 15.8 15.8 14.4 14.4 14.4 14.2 14.2 14.2
H 480 3 13.7 13.7 N/A 19.4 19.4 14.6 19.4 19.4 14.6 30.9 30.9 29.1 30.9 30.9 29.1 30.9 30.9 29.1 36.8 36.8 36.8

ELECTRIC HEATER ELECTRIC CONTROL CODES


CODE DESCRIPTION CODE DESCRIPTION

6 30A MAGNETIC DE-ENERGIZING CONTACTOR E 30A MAGNETIC DISCONNECTING CONTACTOR


7 50A MAGNETIC DE-ENERGIZING CONTACTOR F 50A MAGNETIC DISCONNECTING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR G 30A MERCURY DISCONNECTING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR H 50A MERCURY DISCONNECTING CONTACTOR

TEMPMASTER CORP. JANUARY 92


- KW4 -

16 YORK INTERNATIONAL
FORM AD2T-GEN

KW LIMITATIONS
PARALLEL FLOW FAN TERMINAL
MODEL HVFBE - ELECTRIC

MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 1.9 2.5 3.2 3.8 4.5 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.3 16.5 17.8 19.1 20.3 21.6 22.9 24.2 25.4

HVFBE MAXIMUM CONTROL TOTAL KW


P UNIT MODEL B & C UNIT MODEL D UNIT MODEL E UNIT MODEL F UNIT MODEL G
HEATER H
CONTROL VOLTS A STAGES STAGES STAGES STAGES STAGES
CODE S
E 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

ALL CONTROL SEQUENCES


120 1 3.6 5.5 5.5 3.6 5.4 5.4 3.6 5.3 5.3 3.6 4.8 4.8 3.6 4.7 4.7
6 - 8 - E- G
277 1 8.3 11.2 11.2 8.3 11.2 11.2 8.3 11.2 11.2 8.3 12.4 12.4 8.3 12.3 12.3
120 1 5.5 5.5 5.5 5.4 5.4 5.4 5.3 5.3 5.3 4.8 4.8 4.8 4.7 4.7 4.7
7-9-F-H
277 1 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 12.4 12.4 12.4 12.3 12.3 12.3
208 3 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
6-8-E-G
480 3 11.2 10.8 10.8 11.2 10.8 10.8 11.2 10.8 10.8 24.9 24.9 24.9 24.9 24.9 24.9
208 3 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 14.4 14.4 14.4 14.2 14.2 14.2
7-9-F-H
480 3 11.2 10.8 10.8 11.2 10.8 10.8 11.2 10.8 10.8 25.6 25.6 25.6 25.6 25.6 25.6

ELECTRIC HEATER ELECTRIC CONTROL CODES


CODE DESCRIPTION CODE DESCRIPTION

6 30A MAGNETIC DE-ENERGIZING CONTACTOR E 30A MAGNETIC DISCONNECTING CONTACTOR


7 50A MAGNETIC DE-ENERGIZING CONTACTOR F 50A MAGNETIC DISCONNECTING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR G 30A MERCURY DISCONNECTING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR H 50A MERCURY DISCONNECTING CONTACTOR

TEMPMASTER CORP. JANUARY 92


- KW5 -

YORK INTERNATIONAL 17
KW LIMITATIONS
SERIES FLOW FAN TERMINAL
MODEL HVFSE - ELECTRIC

MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 1.9 2.5 3.2 3.8 4.5 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.3 16.5 17.8 19.1 20.3 21.6 22.9 24.2 25.4

HVFSE MAXIMUM CONTROL TOTAL KW


P UNIT MODEL B UNIT MODEL C UNIT MODEL D UNIT MODEL E UNIT MODEL F
HEATER H
CONTROL VOLTS A STAGES STAGES STAGES STAGES STAGES
CODE S
E 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

ALL CONTROL SEQUENCES


120 1 3.6 5.5 5.5 3.6 5.4 5.4 3.6 5.3 5.3 3.6 4.8 4.8 3.6 4.2 4.2
6-8-E-G
277 1 8.3 13.0 13.0 8.3 12.9 12.9 8.3 12.8 12.8 8.3 12.4 12.4 8.3 11.8 11.8
120 1 5.5 5.5 5.5 5.4 5.4 5.4 5.3 5.3 5.3 4.8 4.8 4.8 4.2 4.2 4.2
7-9-F-H
277 1 13.0 13.0 13.0 12.9 12.9 12.9 12.8 12.8 12.8 12.4 12.4 12.4 11.8 11.8 11.8
208 3 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
6-8-E-G
480 3 14.4 14.4 14.4 14.4 14.4 14.4 18.5 18.5 18.5 24.9 24.9 24.9 24.9 24.9 24.9
208 3 14.4 14.4 14.4 14.4 14.4 14.4 15.8 15.8 15.8 14.4 14.4 14.4 12.6 12.6 12.6
7-9-F-H
480 3 14.4 14.4 14.4 14.4 14.4 14.4 18.5 18.5 18.5 25.6 25.6 25.6 35.4 35.4 35.4

ELECTRIC HEATER ELECTRIC CONTROL CODES


CODE DESCRIPTION CODE DESCRIPTION

6 30A MAGNETIC DE-ENERGIZING CONTACTOR E 30A MAGNETIC DISCONNECTING CONTACTOR


7 50A MAGNETIC DE-ENERGIZING CONTACTOR F 50A MAGNETIC DISCONNECTING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR G 30A MERCURY DISCONNECTING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR H 50A MERCURY DISCONNECTING CONTACTOR

TEMPMASTER CORP. JANUARY 92


- KW6 -

18 YORK INTERNATIONAL
FORM AD2T-GEN

KW LIMITATIONS
PARALLEL FLOW FAN TERMINAL
MODEL HFMLE - ELECTRIC

MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 1.9 2.5 3.2 3.8 4.5 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.3 16.5 17.8 19.1 20.3 21.6 22.9 24.2 25.4

HFMLE MAXIMUM CONTROL TOTAL KW


P UNIT MODEL A UNIT MODEL B UNIT MODEL C UNIT MODEL D UNIT MODEL E
HEATER H
CONTROL VOLTS A STAGES STAGES STAGES STAGES STAGES
CODE S
E 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

ALL CONTROL SEQUENCES


120 1 3.6 5.5 5.5 3.6 5.4 5.4 3.6 5.4 5.4 3.6 5.3 5.3 3.6 4.8 4.8
6-8-E-G
277 1 8.3 11.2 11.2 8.3 11.2 11.2 8.3 11.2 11.2 8.3 11.2 11.2 8.3 11.2 11.2
120 1 5.5 5.5 5.5 5.4 5.4 5.4 5.4 5.4 5.4 5.3 5.3 5.3 4.8 4.8 4.8
7-9-F-H
277 1 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2
208 3 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
6-8-E-G
480 3 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2
208 3 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2
7-9-F-H
480 3 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

ELECTRIC HEATER ELECTRIC CONTROL CODES


CODE DESCRIPTION CODE DESCRIPTION

6 30A MAGNETIC DE-ENERGIZING CONTACTOR E 30A MAGNETIC DISCONNECTING CONTACTOR


7 50A MAGNETIC DE-ENERGIZING CONTACTOR F 50A MAGNETIC DISCONNECTING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR G 30A MERCURY DISCONNECTING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR H 50A MERCURY DISCONNECTING CONTACTOR

TEMPMASTER CORP. JANUARY 92


- KW7 -

YORK INTERNATIONAL 19
KW LIMITATIONS
PARALLEL FLOW FAN TERMINAL
MODEL HFSLE & HLFSE - ELECTRIC

MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 1.9 2.5 3.2 3.8 4.5 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.3 16.5 17.8 19.1 20.3 21.6 22.9 24.2 25.4

MAXIMUM CONTROL TOTAL KW


P UNIT MODEL UNIT MODEL UNIT MODEL UNIT MODEL UNIT MODEL UNIT MODEL
HEATER H HFSLE - A HFSLE - B HFSLE - C HFSLE - E HFSLE - F HLFSE - F
CONTROL VOLTS A STAGES STAGES STAGES STAGES STAGES STAGES
CODE S
E 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

ALL CONTROL SEQUENCES

6-8-E- 120 1 3.6 5.4 5.4 3.6 5.3 5.3 3.6 4.8 4.8 3.6 4.7 4.7 3.6 4.2 4.2 3.6 4.8 4.8
G 277 1 8.3 12.9 12.9 8.3 12.8 12.8 8.3 12.4 12.4 8.3 12.3 12.3 8.3 11.8 11.8 8.3 12.4 12.4
120 1 5.4 5.4 5.4 5.3 5.3 5.3 4.8 4.8 4.8 4.7 4.7 4.7 4.2 4.2 4.2 4.8 4.8 4.8
7-9-F-H
277 1 12.9 12.9 12.9 12.8 12.8 12.8 12.4 12.4 12.4 12.3 12.3 12.3 11.8 11.8 11.8 12.4 12.4 12.4
6-8-E- 208 3 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
G 480 3 14.4 14.4 14.4 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9
208 3 14.4 14.4 14.4 15.8 15.8 15.8 14.4 14.4 14.4 14.2 14.2 14.2 12.6 12.6 12.6 14.5 14.5 14.5
7-9-F-H
480 3 14.4 14.4 14.4 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6

ELECTRIC HEATER ELECTRIC CONTROL CODES


CODE DESCRIPTION CODE DESCRIPTION

6 30A MAGNETIC DE-ENERGIZING CONTACTOR E 30A MAGNETIC DISCONNECTING CONTACTOR


7 50A MAGNETIC DE-ENERGIZING CONTACTOR F 50A MAGNETIC DISCONNECTING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR G 30A MERCURY DISCONNECTING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR H 50A MERCURY DISCONNECTING CONTACTOR

TEMPMASTER CORP. JANUARY 92


- KW8 -

20 YORK INTERNATIONAL
FORM AD2T-GEN

Te m p m a s t e r
R

SYMBOL LIST

ELECTRICAL SYMBOLS

SPEED CONTROL SC RELAY COIL K1

SW1
C NC RELAY CONTACTS
K1-1
DAMPER SWITCH
NO

C N0
AIR FLOW SWITCH CONTACTOR COIL C1

S1
NC

CONTACTOR CONTACTS
C1-1
TRANSFORMER X1

24V

R B Y
ELECTRIC THERMOSTAT
FAN MOTOR FM ES-11
ELECTRIC T-STAT

ELECTRIC ACTUATOR E.A. ACTUATOR 24V


C NC
HOT WATER VALVE
CW

OPEN

ELECTRIC ACTUATORS
COM

LSE NO N.C. HW VALVE


C NC SPRING RETURN
CCW

CLOSE
LSR NO

L1 N R1 R2
CHANGEOVER
DISCONNECT T-STAT
SWITCH
DISCONNECT SWITCH CHANGEOVER THERMOSTAT SENSING BULB
LOCATED IN
FUSING Y1 B1 B2 Y2 DUCTWORK

OPTIONAL DISCONNECT SWITCH


AND OR FUSING

GROUND LUG G
8 7 CHANGEOVER
RELAY

CHANGEOVER RELAY
K1-2

K1-1

ELECTRIC HEATER
5 1
1 PH ELEMENT 2 4

ELECTRIC HEATER
3 PH ELEMENT
C NC

TC
HI-LIMIT SWITCH
S2
NO
THERMAL CUTOUT

UNIT TERMINAL 3

NSB
R B
NIGHT SETBACK STAT ELECTRIC HEATER TERMINAL A

ELSYM1

-SY1-

YORK INTERNATIONAL 21
NOTES

22 YORK INTERNATIONAL
FORM AD2T-GEN

NOTES

YORK INTERNATIONAL 23
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele. 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 2000 www.york.com ALL RIGHTS RESERVED