TABLE OF CONTENTS
2 YORK INTERNATIONAL
FORM AD2T-GEN
DISCUSSION
GENERAL thermostat is used for cooling with 2-stage heat, with
deadbands between both stages. The 1st stage
Tempmaster has subdivided the control into three func- deadband is 1.5°F and the 2nd stage is 40°F. This stat
tional areas. Damper operation, which is the same for may also be used in conjunction with an auxiliary damper
all units; fan operation, which is basically starting and switch to provide for 3 stage heat without 1st stage
stopping the fan at appropriate times compatible with deadband and is the only option available for 3 stage
the style of the unit; and the heating coil control, both heat.
water and electric heating coils. The 1st digit identifies
the box type. The 2nd and 3rd digits identify the damper ELECTRIC DAMPER CONTROL CODES
control. The 4th and 5th digits identify the fan control
(for fan terminal units). The 6th identifies landed voltage Damper Control Code - N0
and the 7th digit identifies electric heater control method
when electric heat is required. This is the basic electric control for terminal units. The
thermostat directly controls the actuator to provide the
required volume of air depending on space temperature.
DAMPER CONTROL AND OPERATION
Damper Control Code - R0
All electric control methods are of the pressure depen-
dent type. Pressure dependent controls are controlled This is the same control as code N0 above except a
directly by the thermostat. With this type of control the high limit control is used to provide a preset maximum
volume of air through the units is dependent upon the air volume independent of the thermostat signal. High
static pressure at the inlet of the unit. limit is achieved by use of a air pressure switch, with a
flow sensor mounted on the inlet of the unit. The high
An optional High Limit control is available for all units limit setpoint can be factory or field set and can be field
which limits the maximum primary air flow through the adjusted.
unit by use of an adjustable air pressure switch. All se-
ries type fan terminal units are supplied with High Limit Damper Control Code - 1R
control to prevent fan overload from excessive primary
This is the same control as code NO above except a
air flow.
auxiliary damper switch is provided for initiation of hot
water, or electric heat.
Dampers are controlled by Tempmaster’s new standard
.1 over the shaft” mounted, 24 volt, rotary damper actua-
Damper Control Code - 1S
tor. The actuator has a 5 minute-600 travel, and is rated
at 35 lb.-in. of torque. The actuator utilizes a magnetic This is the same control as code RO above except a
coupling providing a 45 lb.-in. stall torque which elimi- auxiliary damper switch is provided for initiation of hot
nates the need for mechanical stops or limit switches. It water, or electric heat.
can optionally be supplied with 1 or 2 auxiliary switches
for heat control or fan cycling. The actuator can also be Damper Control Code - X0
supplied with an optional minimum position adjustment
This is a cooling only unit control with changeover stat
to allow for minimum air flow requirements.
for central system heating. The stat is mounted on the
unit and has a 6 ft. long capillary and sensing bulb for
Damper actuator control is provided by the ES type float-
field insertion in the supply air duct. When supply air
ing thermostat which de-energizes the actuator when
above 750°F (adjustable) is sensed in the duct it switches
the space temperature is satisfied. The slow rotational
and reverses the actuator operation. In this condition if
time of the actuator in combination with this floating ther-
the space is calling for heat the damper will move to-
mostat control helps prevent “system hunting”. The ES-
wards its full open position. When the supply duct tem-
1 1 thermostat is used for cooling only applications; or
perature drops below 70°F (adjustable) the changeover
cooling with heating applications without deadband when
stat will switch the unit operation back to normal cooling
used in conjunction with an auxiliary damper switch to
mode.
control the heating mode. The ES-21 thermostat is used
for cooling with 1 stage heat when a deadband is re-
Damper Control Code - Y0
quired. The ES-21 has a deadband of 1.5°F between
cool and heat. This stat may also be used in conjunc- This is the same control as code X0 above except a
tion with an auxiliary damper switch to provide for 2 high limit control is used to provide a preset maximum
stages of heat without 1st stage deadband. The ES-31 air volume independent of the thermostat signal. High
YORK INTERNATIONAL 3
limit is achieved by use of an air pressure switch, with a Damper Control Code - 1M
flow sensor mounted on the inlet of the unit. The high
This is a cooling and heating unit control with a deadband
limit setpoint can be factory or field set and can be field
between cooling & heating operation. It may be used for
adjusted.
hot water or 1 stage electric heat if a deadband is re-
quired.
Damper Control Code - 1J
This is a cooling only unit control with changeover relay Damper Control Code - 1N
for central system heating. The 24 volt changeover relay This is the same control as code 1M above except a
is activated by a remote signal (by others) it switches high limit control is used to provide a preset maximum
and reverses the actuator operation. In this condition if air volume independent of the thermostat signal. High
the space is calling for heat the damper will move to- limit is achieved by use of an air pressure switch, with a
wards its full open position. When the remote signal (by flow sensor mounted on the inlet of the unit. The high
others) is de-activated the changeover relay will switch limit setpoint can be factory or field set and can be field
the unit operation back to normal cooling mode. Damper adjusted.
Control Code - 1K This is the same control as code 1J
above except a high limit control is used to provide a Damper Control Code - 1W
preset maximum air volume independent of the thermo-
stat signal. High limit 1 is achieved by use of an air This is the same control as code 1M above except a
pressure switch, with a flow sensor mounted on the inlet auxiliary damper switch is provided for initiation of the
of the unit. The high limit setpoint can be factory or field 1st stage of electric heat for a 2-stage electric heater.
set and can be field adjusted. This control does not have a deadband between cooling
& heating mode. If 2-stage heat is required with a
Damper Control Code - T0 deadband between cooling and heating mode see con-
trol code 1P below.
This is a dual duct with mixing (constant volume) con-
trol. This control provides for hot duct and cold duct mix- Damper Control Code - 1X
ing at all times maintaining a constant volume of air to
This is the same control as code 1N above except a
the space in response to the thermostat signal. This
auxiliary damper switch is provided for initiation of the
type of control is not very practical due to the mixing of
1st stage of electric heat for a 2-stage electric heater.
hot and cold air at all times.
This control does not have a deadband between cooling
Damper Control Code - 1L
& heating mode. If 2-stage heat is required with a
This is the same control as code T0 above except 2 deadband between cooling and heating mode see con-
high limit controls are used to provide a preset maxi- trol code 1Q below.
mum air volume independent of the thermostat signal.
High limit is achieved by use of an air pressure switch, Damper Control Code - 1P
with a flow sensor mounted on both the cold air & hot air This is a cooling and 2-stage heating unit control with a
inlets of the unit. The high limits setpoints can be fac- deadband between cooling & heating operation and 1 st
tory or field set and can be field adjusted. and 2nd stage heat. It may be used for 2-stage electric
heat if a deadband is required.
Damper Control Code - 1T
This is a dual duct with out mixing (variable air volume) Damper Control Code - 1Q
control. An auxiliary damper switch on both the hot duct This is the same control as code 1P above except a
& cold duct is provided to insure that on a call for heat high limit control is used to provide a preset maximum
the cold duct damper is closed before the hot duct damper air volume independent of the thermostat signal. High
can start to open and on a call for cooling that the hot limit is achieved by use of an air pressure switch, with a
duct damper is closed before the cold duct damper can flow sensor mounted on the inlet of the unit. The high
start to open. limit setpoint can be factory or field set and can be field
adjusted.
Damper Control Code - 1U
Damper Control Code - 1Y
This is the same control as code TO above except 2
high limit controls are used to provide a preset maxi- This is a cooling and 3 stage heating unit control without
mum air volume independent of the thermostat signal. a deadband between cooling & heating operation. An
High limit is achieved by use of an air pressure switch, auxiliary damper switch is provided for initiation of the
with a flow sensor mounted on both the cold air & hot air 1st stage of electric heat for a 3 stage electric heater.
inlets of the unit. The high limits setpoints can be fac- This and code 2A are the only 3 stage electric heater
tory or field set and can be field adjusted. control methods available.
4 YORK INTERNATIONAL
FORM AD2T-GEN
YORK INTERNATIONAL 5
This control code is required when damper control code additional option to ensure that the damper is closed
without high limit control is used. prior to blower startup to eliminate any possibility of re-
verse blower rotation. Tempmaster offers a control op-
Series Flow Fan Terminal Units tion allowing a remote signal (by others) to start the
blower. If this option is used it is the responsibility of
These units are configured with the primary air supply
others to ensure that the fan starts before the primary
(normally cooling only from a central conditioning sys-
air damper opens, to prevent the possibility of the blower
tem) and the secondary air (generally available from the
stalling or blower reverse rotation.
return air plenum) in series with each other. The central
conditioning system provides the energy to move the
The motor/blower for series flow units is sized for 100%
primary air through the unit control damper. The second-
of the unit primary air flow. Blower air flow volume control
ary air (from the return air plenum) is moved through the
is accomplished by adjustment of an electronic speed
unit by a forward curve centrifugal fan which is powered
control. An adjustable high limit damper volume control
by a direct driven, permanent split capacitor, fractional
is also supplied, to limit primary airflow through the unit
horsepower motor. The secondary air is introduced into
to a preset maximum.
the primary air path downstream of the primary air unit
control damper and both are mixed in the unit blower
Electric Series Flow Fan Control Codes Fan
and discharged into the downstream duct. The fan oper-
Control Code - WO (Air Flow Switch Start/Stop)
ates continuously anytime the central conditioning sys-
tem is operating, providing constant volume air to the This control starts the fan any time airflow, at the inlet of
space at the required mixed air temperature to satisfy the unit, is sensed by an adjustable air flow switch.
the space load.
Fan Control Code - AO (Air Flow Switch Start/
Tempmaster series flow fan terminal unit models can be Stop, Damper Override)
distinguished by the letters “FS” in the model designa-
This control starts the fan any time airflow, at the inlet of
tion.
the unit, is sensed by an adjustable air flow switch. This
control also has an extra relay that interlocks with the
These units are typically used in applications where
primary air damper to insure that anytime primary air is
perimeter constant volume cooling with heating is re-
not sensed at the inlet of the unit, the damper will move
quired. With the space calling for cooling and the cen-
to its full closed position.
tral conditioning system supplying air to the unit, the
unit motor/blower is energized and the primary air damper
Fan Control Code - YO (Air Flow Switch Start/
modulates to satisfy the space cooling load. The unit
Stop, Night Setback)
motor/blower must be energized prior to central system
air being supplied to the unit to prevent backward rota- This control operates in the same sequence as control
tion of the motor/blower. As the space load is satisfied code WO above, in normal occupied mode operation.
and the primary damper closes, the motor/blower con- This control also allows for night setback (unoccupied
tinues to operate, supplying warm plenum air (assum- mode) operation. During the unoccupied mode a unit
ing the plenum air temperature is higher than the space mounted thermostat senses the return air plenum air
thermostat setpoint) to satisfy low level space heating temperature. If the air temperature falls below the night
loads. Supplemental heating may be accomplished by setback thermostat setpoint (adjustable) the fan is
optional unit mounted hot water or electric heating coils started and the supplemental heat (if applicable) is en-
to satisfy higher level space heating loads. These are abled.
initiated by an auxiliary damper switch or a cooling/heat-
ing thermostat signal. The auxiliary damper switch may Fan Control Code - 90 (Air Flow Switch Start/
be field adjusted to initiate heating at any point in the Stop, Night Setback, Damper Override)
reduction of primary damper airflow, if desired.
This control operates in the same sequence as control
Tempmaster recommends the use of an interlocking air
code AO above, in normal occupied mode operation.
flow switch to initiate the motor/blower anytime the cen-
This control also allows for night setback (unoccupied
tral conditioning system is in operation. We do not rec-
mode) operation. During the unoccupied mode a unit
ommend the use of backdraft dampers on the second-
mounted thermostat senses the return air plenum air
ary air inlet because tests indicate that if air is forced
temperature. If the air temperature falls below the night
through the blower, it will load up and possibly stall the
setback thermostat setpoint (adjustable) the fan is
motor, or even cause the blower to reverse rotation.
started and the supplemental heat (if applicable) is
Tempmaster can supply a damper override relay as an
enabled.
6 YORK INTERNATIONAL
FORM AD2T-GEN
Fan Control Code - SO (Fan Relay Start/Stop) Fan Control Code - 10 (Air Flow Switch Start/
Stop, Electric Heat Only)
This control starts the fan any time a 24 volt signal (by
others) is sent to the fan start relay. The fan must be This control operates in the same sequence as control
turned on at the same time, or prior to primary air being code WO above. This control also has an extra relay
supplied at the unit inlet. provided to prevent the electric heater from being ener-
gized unless the fan is operating.
Fan Control Code - I P (Air Flow Switch Start/
Stop, Night Setback, Damper Override, Electric Fan Control Code - 1Y (Air Flow Switch Start/
Heat Only) Stop, Electric Heat Only)
This control operates in the same sequence as control This control operates in the same sequence as control
code YO above, in normal occupied mode and unoccu- code AO above. This control also has an extra relay
pied mode operation. This control also has an extra re- provided to prevent the electric heater from being ener-
lay that interlocks with the primary air damper to insure gized unless the fan is operating.
that anytime primary air is not sensed at the inlet of the
unit, the damper will move to its full closed position. An
additional relay is provided to prevent the electric heater
from being energized unless the fan is operating.
YORK INTERNATIONAL 7
Te m p m a s t e r
R
TABLE OF CONTENTS
MODEL PAGE
GENERAL
SINGLE DUCT
HSW, HVW VAV COOLING W/ HOT WATER REHEAT - SELECTION MATRIX B.M1-B.M2
HSW, HVW VAV COOLING W/ HOT WATER REHEAT - CONTROL DIAGRAMS B1-B8
BYPASS
DUAL DUCT
INDEL1
8 YORK INTERNATIONAL
FORM AD2T-GEN
Te m p m a s t e r
R
TABLE OF CONTENTS
MODEL PAGE
HFBW, HVFBW VAV COOLING W/ HOT WATER HEAT - SELECTION MATRIX J.M1-J.M2
HFBW, HVFBW VAV COOLING W/ HOT WATER HEAT - CONTROL DIAGRAMS J1-J32
HFSW, HLFSW, VAV COOLING W/ HOT WATER HEAT - SELECTION MATRIX M.M1-M.M4
HVFSW, HFMLW,
HFSLW
HFSW, HLFSW, VAV COOLING W/ HOT WATER HEAT - CONTROL DIAGRAMS M1-M40
HVFSW, HFMLW,
HFSLW
INDEL2
YORK INTERNATIONAL 9
Te m p m a s t e r
R
TABLE OF CONTENTS
MODEL PAGE
INDEL3
10 YORK INTERNATIONAL
FORM AD2T-GEN
Te m p m a s t e r
R
THE CONTROL SELECTION GUIDE IS BROKEN DOWN INTO 5 MAIN SECTIONS. EACH SECTION CONTAINS
MATRIXES & APPLICATION CONTROL DIAGRAMS RELATED TO THE TYPE OF TERMINAL DEVICE LISTED
FOR THAT SECTION (SINGLE DUCT, BYPASS, DUAL DUCT, PARALLEL AND SERIES FLOW FAN TERMINALS).
EACH OF THESE SECTIONS IS FURTHER BROKEN DOWN BY SEQUENCE CATEGORY (VAV COOLING ONLY,
VAV COOLING W/ HOT WATER HEAT & VAV COOLING W/ ELECTRIC HEAT). EACH OF THESE CATEGORIES
HAS AN ASSOCIATED SELECTION MATRIX(ES). THE MATRIXES ALLOW YOU TO SELECT THE TYPE OF
CONTROL OPTIONS, AND THEIR RESULTING CONTROL CODE AND SCHEMATIC DIAGRAM PAGE NUMBER.
EACH MATRIX HAS 3 MAIN CATEGORIES OF SELECTION, FAN TERMINALS HAVE AN ADDITIONAL CATEGORY
FOR FAN CONTROL. IF ELECTRIC HEAT IS REQUIRED A SELECTION CATEGORY IS ALSO PROVIDED FOR ITS
OPTIONS. FOLLOWING IS A BRIEF EXPLANATION OF THE MATRIX SELECTION CATEGORIES PROVIDED.
1 2 3 4 5
SEQUENCE
OF OPERATION
HEAT CONTROL
CONTROL XFMR.
CONTROL TYPE
ELECTRIC
CONTROL
TEMP. CONTROL
DAMPER CNTRL.
FAN
CONTROL
VOLUME
TO USE THE SELECTION MATRIXES, SELECT THE APPROPRIATE MATRIX FOR YOUR UNIT TYPE AND
GENERAL SEQUENCE (VAV COOLING ONLY, VAV COOLING W/ HOT WATER HEAT OR VAV COOLING W/
ELECTRIC HEAT). SELECT THE REQUIRED SPECIFIC SEQUENCE OF OPERATION (ITEM 2 OPTIONS)
INCLUDING DAMPER CONTROL, TEMPERATURE CONTROL AND VOLUME CONTROL AND MOVE DOWN
THE MATRIX COLUMNS TO FIND A CODE AND DIAGRAM PAGE NUMBER THAT HAS A ROUND SYMBOL
IN THE COLUMNS WITH YOUR REQUIRED OPTIONS. CONTINUE TO MOVE UP OR DOWN COLUMNS TO
FIND A SELECTION WITH YOUR REQUIRED CONTROL TRANSFORMER AND IF REQUIRED FAN AND OR
ELECTRIC HEAT OPTIONS. WHEN YOU FIND A CODE & PAGE NUMBER THAT HAS ALL YOUR CORRECT
OPTIONS CHECKED WITH A ROUND SYMBOL GO TO THE SPECIFIED PAGE IN THE ELECTRIC CONTROLS
CATALOG TO FIND ANY OTHER DRAWING VARIABLES TO FINISH BUILDING YOUR 7 DIGIT CONTROL
CODE. USE THIS CODE AND SCHEMATIC DIAGRAM PAGE NUMBER WHEN ORDERING CONTROLS.
MTXSEL3
-A.A1-
YORK INTERNATIONAL 11
Te m p m a s t e r
R
BOX X XX XX X X ELECTRIC
1
2
COOLING ONLY
COOLING W/ ELECTRIC HEAT
CONTROL CODE
3 COOLING W/ HOT WATER HEAT
4 FAN TERMINAL - COOLING ONLY
5 FAN TERMINAL - W/ ELECTRIC HEAT
6 FAN TERMINAL - W/ HOT WATER HEAT
7 DUAL DUCT - W/ MIXING
8 DUAL DUCT - W/O MIXING
9 FAN TERMINAL - COOLING ONLY
A
CONTROL XFMR BY OTHERS
FAN TERMINAL - W/ HOT WATER HEAT ELECTRIC HEATER CONTROL
CONTROL XFMR BY OTHERS 0 NONE
6 30A MAGNETIC DE-ENERGIZING CONTACTOR
7 50A MAGNETIC DE-ENERGIZING CONTACTOR
8 30A MERCURY DE-ENERGIZING CONTACTOR
9 50A MERCURY DE-ENERGIZING CONTACTOR
E 30A MAGNETIC DISCONNECTING CONTACTOR
F 50A MAGNETIC DISCONNECTING CONTACTOR
DAMPER G
H
30A MERCURY DISCONNECTING CONTACTOR
50A MERCURY DISCONNECTING CONTACTOR
00 NONE
10 MANUAL
N0 ROTARY, ACTUATOR, ES-11 STAT
R0 ROTARY, ACTUATOR, HI-LIMIT, ES-11 STAT
T0 ROTARY, ACTUATORS, ES-11 STAT (DUAL DUCT)
X0 ROTARY, ACTUATOR, C.O. STAT, ES-11 STAT
Y0 ROTARY, ACTUATOR, HI-LIMIT, C.O. STAT, ES-11 STAT
1J ROTARY, ACTUATOR, C.O. RELAY, ES-11 STAT
1K ROTARY, ACTUATOR, HI-LIMIT, C.O. RELAY, ES-11 STAT
1L
1M
ROTARY, ACTUATORS, HI-LIMITS, ES-11 STAT (DUAL DUCT)
ROTARY, ACTUATOR, ES-21 STAT LANDED VOLTAGE
1N ROTARY, ACTUATOR, HI-LIMIT, ES-21 STAT
1P ROTARY, ACTUATOR, ES-31 STAT W/O ELECTRIC HEAT
1Q ROTARY, ACTUATOR, HI-LIMIT, ES-31 STAT 0 NONE V 208V/1Ø/60HZ
1R ROTARY, ACTUATOR, ES-11 STAT, DAMPER SWITCH A 24V/1Ø/60HZ (W/O XFMR) Q 240V/1Ø/60HZ
1S ROTARY, ACTUATOR, HI-LIMIT, ES-11 STAT, DAMPER SWITCH B 120V/1Ø/60HZ C 277V/1Ø/60HZ
1T ROTARY, ACTUATORS, ES-11 STAT, DAMPER SWITCH (DUAL DUCT)
1U ROTARY, ACTUATORS, HI-LIMIT, ES-11 STAT, DAMPER SWITCH
(DUAL DUCT) W/ ELECTRIC HEAT
1W ROTARY, ACTUATOR, ES-21 STAT, DAMPER SWITCH D 120V/1Ø/60HZ - 1 STAGE P 208V/3Ø/60HZ - 1 STAGE
1X ROTARY, ACTUATOR, HI-LIMIT, ES-21 STAT, DAMPER SWITCH E 120V/1Ø/60HZ - 2 STAGE R 208V/3Ø/60HZ - 2 STAGE
1Y ROTARY, ACTUATOR, ES-31 STAT, DAMPER SWITCH 5 120V/1Ø/60HZ - 3 STAGE 1 208V/3Ø/60HZ - 3 STAGE
2A ROTARY, ACTUATOR, HI-LIMIT, ES-31 STAT, DAMPER SWITCH F 208V/1Ø/60HZ - 1 STAGE S 240V/3Ø/60HZ - 1 STAGE
2B ELECTRIC, ACTUATOR, ES-11 STAT G 208V/1Ø/60HZ - 2 STAGE T 240V/3Ø/60HZ - 2 STAGE
2C ELECTRIC, ACTUATOR, HI-LIMIT, ES-11 STAT 4 208V/1Ø/60HZ - 3 STAGE 2 240V/3Ø/60HZ - 3 STAGE
2D ELECTRIC, ACTUATORS, ES-11 STAT (DUAL DUCT) H 240V/1Ø/60HZ - 1 STAGE U 480V/3Ø/60HZ - 1 STAGE
2E ELECTRIC, ACTUATOR, C.O. STAT, ES-11 STAT J 240V/1Ø/60HZ - 2 STAGE W 480V/3Ø/60HZ - 2 STAGE
2F ELECTRIC, ACTUATOR, HI-LIMIT, C.O. STAT, ES-11 STAT 6 240V/1Ø/60HZ - 3 STAGE 3 480V/3Ø/60HZ - 3 STAGE
2G ELECTRIC, ACTUATOR, C.O. RELAY, ES-11 STAT K 277V/1Ø/60HZ - 1 STAGE X 208V/3Ø/60HZ - 1 STAGE
2H ELECTRIC, ACTUATOR, HI-LIMIT, C.O. RELAY, ES-11 STAT L 277V/1Ø/60HZ - 2 STAGE W/O NEUTRAL (3 WIRE)
2J ELECTRIC, ACTUATORS, HI-LIMITS, ES-11 STAT (DUAL DUCT) Y 277V/1Ø/60HZ - 3 STAGE 8 208V/3Ø/60HZ - 2 STAGE
2K ELECTRIC, ACTUATOR, ES-21 STAT M 480V/1Ø/60HZ - 1 STAGE W/O NEUTRAL (3 WIRE)
2L ELECTRIC, ACTUATOR, HI-LIMIT, ES-21 STAT N 480V/1Ø/60HZ - 2 STAGE 9 208V/3Ø/60HZ - 3 STAGE
2M ELECTRIC, ACTUATOR, ES-31 STAT 7 480V/1Ø/60HZ - 3 STAGE W/O NEUTRAL (3 WIRE)
2N ELECTRIC, ACTUATOR, HI-LIMIT, ES-31 STAT
2P ELECTRIC, ACTUATOR, ES-11 STAT, DAMPER SWITCH
2Q ELECTRIC, ACTUATOR, HI-LIMIT, ES-11 STAT, DAMPER SWITCH
2R ELECTRIC, ACTUATORS, ES-11 STAT, DAMPER SWITCH (DUAL DUCT)
2S ELECTRIC, ACTUATORS, HI-LIMIT, ES-11 STAT, DAMPER SWITCH
(DUAL DUCT)
2T ELECTRIC, ACTUATOR, ES-21 STAT, DAMPER SWITCH
2U ELECTRIC, ACTUATOR, HI-LIMIT, ES-21 STAT, DAMPER SWITCH
2W ELECTRIC, ACTUATOR, ES-31 STAT, DAMPER SWITCH
2X ELECTRIC, ACTUATOR, HI-LIMIT, ES-31 STAT, DAMPER SWITCH
FAN
PARALLEL FLOW (EXCEPT LOW TEMP) ALL SERIES FLOW (AND LOW TEMP PARALLEL FLOW)
00 NONE 00 NONE
C0 FAN RELAY, DAMPER SWITCH, VOLUME CONTROL 10 FAN RELAY, AIR FLOW SWITCH, SPEED CONTROL (ELEC. HEAT ONLY)
D0 FAN RELAY, DAMPER SWITCH, AIR FLOW SWITCH, NIGHT SETBACK STAT, 90 FAN RELAY, AIR FLOW SWITCH, DAMPER OVERRIDE, NIGHT SETBACK STAT,
VOLUME CONTROL SPEED CONTROL
J0 FAN RELAY, DAMPER SWITCH, SPEED CONTROL A0 AIR FLOW SWITCH, DAMPER OVERRIDE RELAY, SPEED CONTROL
K0 FAN RELAY, DAMPER SWITCH, AIR FLOW SWITCH, NIGHT SETBACK STAT, S0 FAN RELAY, SPEED CONTROL,
SPEED CONTROL W0 AIR FLOW SWITCH, SPEED CONTROL
N0 FAN RELAY, DAMPER SWITCH, AIR FLOW SWITCH, NIGHT SETBACK STAT, Y0 FAN RELAY, AIR FLOW SWITCH, NIGHT SETBACK STAT, SPEED CONTROL
VOLUME CONTROL, FLOW SENSOR 1G 30A FAN RELAY, AIR FLOW SWITCH, 25A SPEED CONTROL
P0 FAN RELAY, DAMPER SWITCH, AIR FLOW SWITCH, NIGHT SETBACK STAT, (HFS-120V G,H,J)
SPEED CONTROL, FLOW SENSOR 1H 30A FAN RELAY, AIR FLOW SWITCH, NIGHT SETBACK STAT,
25A SPEED CONTROL (HFS-120V G,H,J)
1J 30A FAN RELAY, AIR FLOW SWITCH, NIGHT SETBACK STAT,
DAMPER OVERRIDE, 25A SPEED CONTROL (HFS-120V G,H,J)
1K 30A FAN RELAY, AIR FLOW SWITCH, DAMPER OVERRIDE,
25A SPEED CONTROL (HFS-120V G,H,J)
1L 30A FAN RELAY, 25A SPEED CONTROL (HFS-120V G,H,J)
1M 30A FAN RELAY, DAMPER OVERRIDE, 25A SPEED CONTROL
(HFS-120V G,H,J)
1P FAN RELAY, AIR FLOW SWITCH, NIGHT SETBACK STAT,
DAMPER OVERRIDE RELAY, SPEED CONTROL (ELEC. HEAT ONLY)
1Y FAN RELAY, AIR FLOW SWITCH, DAMPER OVERRIDE RELAY,
SPEED CONTROL (ELEC. HEAT ONLY)
REV. 1 (8-20-93)
PNMCLTR2
-A.A2-
12 YORK INTERNATIONAL
FORM AD2T-GEN
Te m p m a s t e r
R
USING CHARTS
IN ORDER TO USE THE CHARTS YOU MUST HAVE ALREADY SELECTED A TYPE OF UNIT,
ITS MODEL SIZE OR FAN SIZE, & REQUIRED K.W. FOR JOB. FIRST GO TO THE MAXIMUM
K.W. VS CFM CHART FOR THE SPECIFIC UNIT SELECTED TO CONFIRM THAT YOUR INITIAL
SELECTION FALLS WITHIN THE TEMPERATURE RISE VS CFM MAXIMUMS LISTED. IF IT
EXCEEDS THE LISTED LIMITS, THEN YOU MUST DECREASE THE K.W., INCREASE THE CFM,
OR BOTH. IF THE REQUIRED CFM IS NOT LISTED, USE THE FORMULAS BELOW CHART TO
CALCULATE ACTUAL TEMPERATURE RISE OR K.W.
ONCE YOU HAVE A SELECTION THAT FALLS WITHIN THE MAXIMUM K.W. VS CFM LIMITS,
PROCEED TO THE MAXIMUM CONTROL K.W. CHART. FIND YOUR REQUIRED HEATER
VOLTAGE & STAGES OF HEAT, AND SELECT THE HEATER CONTROL CODE (CONTACTOR TYPE)
DESIRED. CONFIRM THAT YOUR REQUIRED K.W. FALLS WITHIN THE HEATER CONTROL CODE'S
K.W. LIMITS. IF IT DOES NOT, SELECT ANOTHER HEATER CONTROL CODE (50A CONTACTOR)
THAT WILL MEET YOUR K.W. REQUIREMENTS.
SELECTION EXAMPLE #1
REQUIRED: HSE, MODEL D, HEATING CFM = 700, 4.0 K.W.- 2 STAGE HEAT, 277V/1Ø/60HZ
GO TO MAXIMUM K.W. VS CFM CHART. 700 CFM = 14.5 K.W. MAXIMUM, REQUIRED K.W. IS 4.0;
THEREFORE, WE ARE NOT LIMITED BY OUR TEMPERATURE RISE OR CFM.
GO TO MAX. K.W. PER STAGE CHART AND SELECT THE HEATER CONTROL CODE 6
(THIS IS THE LEAST EXPENSIVE 1Ø OPTION.)
REQUIRED K.W. = 4.0, CHART SHOWS 13.2 KW. MAXIMUM TOTAL K.W.; THERFORE, THIS IS A GOOD
SELECTION.
SELECTION EXAMPLE #2
REQUIRED: HVFBE, MODEL E, HEATING CFM = 750, 9.5 K.W.- 1 STAGE HEAT, 277V/1Ø/60HZ
GO TO MAXIMUM K.W. VS CFM CHART. 750 CFM IS NOT LISTED, REQUIRED K.W. IS 9.5
SINCE THE CHART DOES NOT LIST THIS CFM WE MUST CALCULATE OUR ACTUAL T.
3413 X 9.5
T= T = 39.8 39.8 IS LESS THAN 40° T MAXIMUM.
750 X 1.085
GO TO MAX. K.W. PER STAGE CHART AND SELECT THE HEATER CONTROL CODE 6
(THIS IS THE LEAST EXPENSIVE 1Ø OPTION.) LOOK AT COLUMNS FOR UNIT MODEL E.
REQUIRED K.W. = 9.5, CHART SHOWS 8.3 K.W. MAXIMUM; THERFORE, THIS IS NOT A GOOD
SELECTION. TRY HEATER CONTROL CODE 7. REQUIRED K.W. = 9.5, CHART SHOWS 11.2 K.W.
MAXIMUM TOTAL K.W.; THERFORE, THIS IS A GOOD SELECTION.
SELECTION EXAMPLE #3
REQUIRED: HVFSE, MODEL F, HEATING CFM = 2000, 25.3 K.W.- 3 STAGE HEAT, 480V/3Ø/60HZ
GO TO MAXIMUM K.W. VS CFM CHART. 1600 CFM = 25.4 K.W. MAXIMUM, REQUIRED K.W. IS 25.3;
THEREFORE, WE ARE NOT LIMITED BY OUR TEMPERATURE RISE OR CFM.
GO TO MAX. K.W. PER STAGE CHART AND SELECT THE HEATER CONTROL CODE 6
(THIS IS THE LEAST EXPENSIVE 3Ø OPTION.)
REQUIRED K.W. = 25.3, CHART SHOWS 24.9 K.W. MAXIMUM; THEREFORE THIS IS NOT A GOOD
SELECTION. TRY HEATER CONTROL CODE 7. REQUIRED K.W. = 25.3 3 STAGE, CHART SHOWS 35.4
MAXIMUM TOTAL K.W.; THEREFORE, THIS IS A GOOD SELECTION.
MKWEXPEL
-KW1-
YORK INTERNATIONAL 13
KW LIMITATIONS
SINGLE DUCT TERMINAL
MODEL HSE - ELECTRIC
MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 3.1 4.1 5.2 6.2 7.2 8.3 10.3 12.4 14.5 16.5 18.6 20.7 22.7 24.8 26.9 28.9 31.0 33.1 35.1 37.2 39.3 *39.4
14 YORK INTERNATIONAL
FORM AD2T-GEN
KW LIMITATIONS
SINGLE DUCT TERMINAL
MODEL HMSRE - ELECTRIC
MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 3.1 4.1 5.2 6.2 7.2 8.3 10.3 12.4 14.5 16.5 18.6 20.7 22.7 24.8 26.9 28.9 31.0 33.1 35.1 37.2 39.3 *39.4
YORK INTERNATIONAL 15
KW LIMITATIONS
PARALLEL FLOW FAN TERMINAL
MODEL HFBE - ELECTRIC
MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 2.4 3.2 4.0 4.8 5.6 6.4 7.9 9.5 11.1 12.7 14.3 15.9 17.5 19.1 20.7 22.3 23.8 25.4 27.0 28.6 30.2 31.8
6-8-E- 120 1 3.6 5.5 5.5 3.6 5.4 5.4 3.6 5.3 5.3 3.6 5.4 5.4 3.6 5.3 5.3 3.6 4.8 4.8 3.6 4.7 4.7
G 277 1 8.3 13.0 13.0 8.3 12.9 12.9 8.3 12.8 12.8 8.3 12.9 12.9 8.3 12.8 12.8 8.3 12.4 12.4 8.3 12.3 12.3
7-9-F- 120 1 5.5 5.5 5.5 5.4 5.4 5.4 5.3 5.3 5.3 5.4 5.4 5.4 5.3 5.3 5.3 4.8 4.8 4.8 4.7 4.7 4.7
H 277 1 13.0 13.0 13.0 12.9 12.9 12.9 12.8 12.8 12.8 12.9 12.9 12.9 12.8 12.8 12.8 12.4 12.4 12.4 12.3 12.3 12.3
6-8-E- 208 3 10.8 10.8 8.9 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
G 480 3 13.7 13.7 N/A 19.4 19.4 14.6 19.4 19.4 14.6 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9
7-9-F- 208 3 13.7 13.7 8.9 16.1 16.1 16.1 15.8 15.8 15.8 16.1 16.1 16.1 15.8 15.8 15.8 14.4 14.4 14.4 14.2 14.2 14.2
H 480 3 13.7 13.7 N/A 19.4 19.4 14.6 19.4 19.4 14.6 30.9 30.9 29.1 30.9 30.9 29.1 30.9 30.9 29.1 36.8 36.8 36.8
16 YORK INTERNATIONAL
FORM AD2T-GEN
KW LIMITATIONS
PARALLEL FLOW FAN TERMINAL
MODEL HVFBE - ELECTRIC
MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 1.9 2.5 3.2 3.8 4.5 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.3 16.5 17.8 19.1 20.3 21.6 22.9 24.2 25.4
YORK INTERNATIONAL 17
KW LIMITATIONS
SERIES FLOW FAN TERMINAL
MODEL HVFSE - ELECTRIC
MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 1.9 2.5 3.2 3.8 4.5 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.3 16.5 17.8 19.1 20.3 21.6 22.9 24.2 25.4
18 YORK INTERNATIONAL
FORM AD2T-GEN
KW LIMITATIONS
PARALLEL FLOW FAN TERMINAL
MODEL HFMLE - ELECTRIC
MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 1.9 2.5 3.2 3.8 4.5 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.3 16.5 17.8 19.1 20.3 21.6 22.9 24.2 25.4
YORK INTERNATIONAL 19
KW LIMITATIONS
PARALLEL FLOW FAN TERMINAL
MODEL HFSLE & HLFSE - ELECTRIC
MAXIMUM KW vs CFM
CFM 150 200 250 300 350 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
KW 1.9 2.5 3.2 3.8 4.5 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.3 16.5 17.8 19.1 20.3 21.6 22.9 24.2 25.4
6-8-E- 120 1 3.6 5.4 5.4 3.6 5.3 5.3 3.6 4.8 4.8 3.6 4.7 4.7 3.6 4.2 4.2 3.6 4.8 4.8
G 277 1 8.3 12.9 12.9 8.3 12.8 12.8 8.3 12.4 12.4 8.3 12.3 12.3 8.3 11.8 11.8 8.3 12.4 12.4
120 1 5.4 5.4 5.4 5.3 5.3 5.3 4.8 4.8 4.8 4.7 4.7 4.7 4.2 4.2 4.2 4.8 4.8 4.8
7-9-F-H
277 1 12.9 12.9 12.9 12.8 12.8 12.8 12.4 12.4 12.4 12.3 12.3 12.3 11.8 11.8 11.8 12.4 12.4 12.4
6-8-E- 208 3 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8
G 480 3 14.4 14.4 14.4 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9 24.9
208 3 14.4 14.4 14.4 15.8 15.8 15.8 14.4 14.4 14.4 14.2 14.2 14.2 12.6 12.6 12.6 14.5 14.5 14.5
7-9-F-H
480 3 14.4 14.4 14.4 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6 25.6
20 YORK INTERNATIONAL
FORM AD2T-GEN
Te m p m a s t e r
R
SYMBOL LIST
ELECTRICAL SYMBOLS
SW1
C NC RELAY CONTACTS
K1-1
DAMPER SWITCH
NO
C N0
AIR FLOW SWITCH CONTACTOR COIL C1
S1
NC
CONTACTOR CONTACTS
C1-1
TRANSFORMER X1
24V
R B Y
ELECTRIC THERMOSTAT
FAN MOTOR FM ES-11
ELECTRIC T-STAT
OPEN
ELECTRIC ACTUATORS
COM
CLOSE
LSR NO
L1 N R1 R2
CHANGEOVER
DISCONNECT T-STAT
SWITCH
DISCONNECT SWITCH CHANGEOVER THERMOSTAT SENSING BULB
LOCATED IN
FUSING Y1 B1 B2 Y2 DUCTWORK
GROUND LUG G
8 7 CHANGEOVER
RELAY
CHANGEOVER RELAY
K1-2
K1-1
ELECTRIC HEATER
5 1
1 PH ELEMENT 2 4
ELECTRIC HEATER
3 PH ELEMENT
C NC
TC
HI-LIMIT SWITCH
S2
NO
THERMAL CUTOUT
UNIT TERMINAL 3
NSB
R B
NIGHT SETBACK STAT ELECTRIC HEATER TERMINAL A
ELSYM1
-SY1-
YORK INTERNATIONAL 21
NOTES
22 YORK INTERNATIONAL
FORM AD2T-GEN
NOTES
YORK INTERNATIONAL 23
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele. 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 2000 www.york.com ALL RIGHTS RESERVED