Heat Reclaim Ventilator VKM
Heat Reclaim Ventilator VKM
Heat Reclaim Ventilator VKM
Supports both
50/60Hz power supply Equipped with DC motor
Power consumption reduced Approx. 29% increase
by about 51% in external static pressure
60 Hz power supply
1-phase, 220V
New model
560W
220Pa
Conventional
model
50 / 60 Hz
Air conditioning and outdoor air processing can be VRV Outdoor Units
accomplished using a single system.
Heat Reclaim Ventilator
with DX Coil
Outdoor Air
• Line up
Exhaust Air
MODEL VKM50GCVE VKM80GCVE VKM100GCVE Indoor Indoor
VKM Unit Unit
Capacity Index 31.25 50 62.5
Return
Connection Conditions Air Air
Air-Conditioning Air Supply
• When the VKM units are connected,
the total connection capacity index must be
50% to 130% of the capacity index of the outdoor units.
Specifications
MODEL VKM50GCVE VKM80GCVE VKM100GCVE
Refrigerant R410A
Power Supply (50/60Hz) 1-phase, 220–240 V / 1-phase, 220 V
Airflow Rate & External Static Pressure Airflow m³/h 500/500/440 750/750/640 950/950/820
(Ultra-high / High / Low) (Note 1) Static pressure Pa 210/170/140 220/180/125 170/120/90
Power Consumption Heat exchange mode W 270/230/170 390/335/220 440/370/260
(Ultra-high / High / Low) Bypass mode W 305/260/200 390/335/220 440/370/260
Fan Type Sirocco Fan
Motor Output kW 0.21×2
Sound Level (Note 2) Heat exchange mode dB 43/40.5/39 41.5/39/37 41/39/36.5
(Ultra-high / High / Low) Bypass mode dB 43/41/39 41.5/39/37 41/39/36.5
Temp. Exchange Efficiency (Ultra-high / High / Low) % 76/76/77.5 78/78/79 74/74/76.5
Enthalpy Exchange Efficiency Cooling % 64/64/67 66/66/68 62/62/66
(Ultra-high / High / Low) Heating % 67/67/69 71/71/73 65/65/69
Heat Exchanging System Air to Air Cross Flow Total Heat (Sensible + Latent Heat) Exchange
Heat Exchanger Element Specially Processed Non flammable Paper
Air Filter Multidirectional Fibrous Fleeces
DX-coil Capacity (Cooling / Heating) (Note 3) (Note 4) kW 2.8 / 3.2 4.5 / 5.0 5.6 / 6.3
Dimensions (Height×Width×Depth) mm 387 × 1,764 × 832 387 × 1,764 × 1,214
Machine Weight kg 92 113 115
Around Unit 0℃–40℃DB, 80%RH or less
Unit Ambient Condition OA (Note 5) -15℃–40℃DB, 80%RH or less
RA (Note 5) 0℃–40℃DB, 80%RH or less
Note : 1. Airflow rate can be changed over to Low mode or High mode. 2. The operating sound measured at the point 1.5 m below the centre of the unit is converted to that measured in an
anechoic chamber built in accordance with the JIS C 1502 conditions. The actual operating sound varies depending on the surrounding conditions (near running unit s sound, reflected sound and
so on) and is normally higher than this value. For operation in a quiet room, it is required to take measures to lower the sound. For details, refer to the Engineering Data. 3. Indoor temperature:
27℃DB, 19℃WB, Outdoor temperature: 35℃DB. 4. Indoor temperature: 20℃DB, Outdoor temperature: 7℃DB, 6℃WB. 5. OA: fresh air from outdoor. RA: return air from room.
Options
Item Type VKM50GCVE VKM80GCVE VKM100GCVE
Remote controller *1 BRC1H61W / BRC1H61K / BRC1E63
Controlling Wiring adaptor for electrical
device PC Board KRP2A61
appendices
Adaptor
For heater control kit BRP4A50
KDDM24B100
Silencer
Nominal pipe diameter mm φ250
Additional Air suction / White K-DGL200B K-DGL250B
function Discharge grille Nominal pipe diameter mm φ200 φ250
High efficiency filter KAF242J80M KAF242J100M
Air filter for replacement KAF241G80M KAF241G100M
1m K-FDS201D K-FDS251D
Flexible duct
2m K-FDS202D K-FDS252D
CO2 Sensor BRYC24B50M BRYC24B100M
*1 Necessary when operating a Heat Reclaim Ventilator (VKM) independently. When operating interlocked with other air conditioners, use the remote controllers of the air conditioners.
・Please inquire concerning optional accessories not listed above.
Specifications, designs and other content appearing in this brochure are current as of May 2020 but subject to change without notice.