Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Description: Constant-Duty Power Supply

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

CDP8

Description Constant-Duty Power Supply


The Gamewell-FCI CDP8 Constant-Duty Power Supply is
a regulated, power-limited, 24 VDC, 8.0 amp. power supply
which can be used anywhere a constant 24 VDC source is
required. The CDP8 is suited and UL-Listed for fire alarm,
access control, and general power supply applications.

The Gamewell-FCI CDP8 provides four (4) power-limited,


24 VDC, 3.0 amp. outputs. Each output can be individually
configured to shed its load (turn off) during a power failure
to extend available standby battery power for designated
critical circuits.

Each output circuit is monitored for overload or shorted


conditions, with the trouble condition indicated by a specific
circuit trouble LED and activation of the common trouble
relay. Overloaded circuits will automatically restore when
the overload is removed.
CDP8
Engineer’s Specifications
The power supply shall provide four (4) output circuits Features
capable of up to 3.0 amp. continuous 24 VDC each to a
maximum of 8.0 amps. total. The output voltage shall be
regulated and power-limited. Each output circuit shall be
configurable to shed its load with the loss of the primary AC • Four (4) configurable monitored outputs
source. The Constant-Duty Power Supply shall include an • 8.0 A, 24 VDC, fully regulated full-load output
internal battery charger with charging capacity of 26 AH. It (power-limited)
shall also be operational from an externally charged bat- • Seven (7) trouble and status LEDs
tery. Operational troubles shall be indicated by seven LEDs • Common trouble Form-C relay
and a common trouble Form-C relay. The supply shall also • Isolated AC Fail Form-C relay
have a delayed AC Fail relay. The Constant-Duty Power • Selectable AC Fail notification relay
Supply shall be Gamewell-FCI, model CDP8. • Ground fault detection
• 26.0 A battery-charger capability
Specifications • Selectable internal battery charger disable
• Selectable internal ground fault detection disable
Primary Input Power: 120 VAC, 50/60 Hz, 3.5 A • Selectable load shedding on AC Fail per output
or 220 V, 1.9 A, jumper-selectable.
Secondary Power: 24-volt: two 7 – 26 AH batteries
Battery Charging
Capacity: Up to 26 AH batteries
Total Output Power: 8.0 A maximum
Standby Current: 0.03 A
Output Ratings: 24 VDC fully regulated, 3.0 A max-
imum per circuit, 8.0 A total
Cabinet Dimensions: 18.0" H x 12.5" W x 4.5" D An ISO 9000-2000 Company
(45.72 H x 31.75 W x 11.43 D cm) SIGNALING

S8240 7315-1288:163

GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com CS-2283 Rev. a page 1 of 2
Specifications (Continued) Ordering Information
Cabinet Battery Part Number Description
Space: Up to two 12 AH batteries CDP8 24 VDC, 8.0 amp. power supply with inte-
(maximum) inside cabinet. Larger gral battery charger
batteries require a separate
battery cabinet. BAT-1270 Battery, 12 VDC, 7 AH
Relative Humidity: 10 – 93% non-condensing (two required for 24 V operation)
Temperature Rating: 32°F – 120°F (0°C – 49°C) BAT-12120 Battery, 12 VDC, 12 AH
Common Trouble (two required for 24 V operation)
Relay: 2A/30 VDC or 120 VAC 30069 Power supervision end-of-line relay,
AC Fail Relay: 2A/30 VDC or 120 VAC 24VDC

GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2283 Rev. a page 2 of 2 www.gamewell-fci.com