Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

7XV5655-0BA00-Hub Manual A4 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 51

7XV5655-0BA00

Manual C53000-G1176-C174-4

Application Instructions
Serial Hub
Ethernet hub for transmission of serial data or protocols
from devices with an RS232, RS485 or FO interface via Ethernet
Manual 7XV5655-0BA00

CONTENTS

General Information ...................................................................................................... 3

Application .................................................................................................................... 8

Description of Interfaces, DIP Switches and Displays ................................................ 11

Mounting and Commissioning..................................................................................... 14

Mounting and Commissioning..................................................................................... 15

Practical Safety Information ........................................................................................ 18

Preparing the Operating PC or Service Notebook ...................................................... 19

The Configuration Tool ............................................................................................... 26

Optimising Data Transfer ............................................................................................ 39

Selecting a Password-Protected Serial Hub ............................................................... 40

Pin Assignment........................................................................................................... 42

Technical Data............................................................................................................ 45

Dimensions ................................................................................................................. 50

Ordering Information ................................................................................................... 51

C53000-G1176-C174-4 Page 2 of 51 SIEMENS AG


Manual 7XV5655-0BA00

General Information
0B

This manual contains the information that is necessary for proper and safe operation of
the products described. This manual is intended for technically qualified personnel
having received special training in, or having special knowledge of protection,
measurement and control engineering, hereinafter called automation engineering. The
knowledge and correct application of the warnings and instructions contained in this
manual are prerequisites to safe installation and commissioning of this product, as well
as to proper and safe operation and maintenance. Only qualified personnel as defined
overleaf have the special knowledge required for correct interpretation of the general
safety information and warnings given in this manual, and for their application to the
task in hand. This manual is included in the scope of delivery. For reasons of clarity,
however, it does not purport to contain every detail of all versions of the product
described, nor can it deal with all possible cases of erection, operation or maintenance.
If further information is desired or if special problems arise that are not treated
adequately in this document, it is possible to obtain additional details from your local
Siemens office or from the addresses stated on the back of this manual.
We should also like to point out that the contents of this product documentation are not
part of any previous or existing agreement or legal relationship, nor are they apt to
modify such an agreement or relationship. All obligations incurred by Siemens result
from the purchase contract, which also contains the complete and solely applicable
warranty conditions. Contractual warranty conditions are neither extended nor restricted
by the contents of this document.

Disclaimer of Liability Copyright


We have checked the contents of this document and Copyright © Siemens AG 2012. All rights reserved.
every effort has been made to ensure that the
descriptions of both the hardware and software are as The reproduction, transmission or use of this document
accurate as possible. However, since deviations cannot or its contents is not permitted without express written
be ruled out entirely, we do not accept liability for authority.
complete conformity or for any errors or omissions. Offenders will be liable for damages. All rights, including
The information given in this document is reviewed rights created by patent grant or registration of a utility
regularly and any necessary corrections will be included model or design, are reserved.
in subsequent editions. We are grateful for any Registered Trademarks
improvements that you care to suggest.
SIPROTEC, SINAUT, SICAM and DIGSI® are
Subject to technical modifications without notice. registered trademarks of Siemens AG. Other
designations in this manual might be trademarks whose
Release 4.00.00 use by third parties for their own purposes would
infringe the rights of the owner.

SIEMENS AG Page 3 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Statement of Conformity

This product complies with the directive of the Council of the


European Communities in accordance with the laws of the member states relating to
electromagnetic compatibility (EMC Council Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low Voltage Directive
2006/95/EC).
This conformity has been proven by tests performed according to the Council
Directives in agreement with the generic standards EN 61000-6-2
and EN 61000-6-4 (for EMC Directive) and with the standard EN 60255-6 (for Low
Voltage Directive) by Siemens AG.
The device is designed and manufactured for application in industrial environments. The
product conforms to the international standards of IEC 60255 and the German
regulations of VDE 0435.

C53000-G1176-C174-4 Page 4 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Instructions and Warnings


19B

The information and warnings in this manual must be observed for your safety and to
ensure an appropriate service life of the device.
The following terms and definitions are used:

DANGER
means that death, severe bodily injury or substantial material
damage will occur if the appropriate precautions are not taken.
U U

Warning
means that death, severe bodily injury or substantial material
damage could occur if the appropriate precautions are not taken.
U U

Caution
indicates that minor bodily injury or material damage could result if
appropriate precautions are not taken. This applies in particular to
damage on or in the device itself and resulting consequential
damage.

Note
contains important information about the product or a part of the
document to which special attention is directed.

Warning

The 7XV5655-0BA00 is specifically intended for installation in a switchgear


cubicle or distribution box.
After installation, the entire area around the terminals must be appropriately
covered. Only then is the device sufficiently protected against improper
contact with live parts.

SIEMENS AG Page 5 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Warning!
Hazardous voltages occur in this electrical equipment during
operation. Severe personal injury or property damage can result if
the device is not handled with the appropriate care.
Only qualified personnel should work on or around this equipment.
The personnel must be thoroughly familiar with all warnings and
maintenance procedures contained in this manual, as well as the
appropriate safety regulations.
Successful and safe operation of the unit depends on proper
transportation, storage, mounting and assembly as well as the
observance of the warnings and instructions contained in this
manual.
In particular, the general installation and safety regulations for work
in power current plants (e.g. ANSI, IEC, EN, DIN, or other national
and international regulations) must be observed.
Failure to observe these precautions can result in death, personal
injury, or serious material damage.
Never look into fibre-optic components or the ends of the fibres.

Qualified Personnel
20B

For the purposes of this manual, the warnings on the product itself,
only persons who are acquainted with the mounting, installation,
commissioning and operation of the device and who possess the
appropriate qualifications for their task, such as
ƒ training and instruction to energise, de-energise, clear,
earth and tag circuits and equipment in accordance with
established safety practice,
ƒ training or instruction in accordance with established safety
practice for care and use of certain safety equipment,
ƒ training in rendering first aid can be considered as qualified
personnel

C53000-G1176-C174-4 Page 6 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Scope of Supply
21B

• Serial Hub for DIN rail mounting


• Gender changer, 9-way, male-male
• CD with manual and configuration tool
• Installation Instructions

Unpacking and Repacking


2B

The devices are factory-packed to meet the requirements of IEC 60255–21.


Unpacking and re-packing must be performed with the required care, without force and
only with the aid of suitable tools. Visually check the device immediately upon arrival for
correct mechanical condition.
Please also always follow instructions if they are supplied with the device.
The shipping packaging can be re-used in the same manner for further shipment.
Note that the storage packaging of individual devices is not sufficient for shipping.
If other packaging is used, the shock requirements acc. to IEC 60255–21–1 Class II and
IEC 60255–21–2 Class 1 must be met.
The device should be stored in the final operating area for a minimum of two hours
before the power source is first applied. This gives the device time to acclimatise to the
temperature equilibrium, thus avoiding dampness and condensation.

Storage
23B

SIPROTEC® devices and associated parts should be stored in a dry and clean place.
The device as well as its replacement modules must be stored within the temperature
range, which is –10 °C to +55 °C.
The relative humidity is not allowed to lead to condensation or ice.
To avoid premature ageing of the electrolyte capacitors in the power supply unit, a
temperature range of +10 °C to +35 °C (+50 °F to +95 °F) is recommended for storage.
After extended storage, the power supply of the device should be energised,
approximately every two years for one or two days, to regenerate the electrolytic
capacitors in the power supply unit. This should also be done before the device is put
into service.

SIEMENS AG Page 7 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Application
1B

General scope of application


24B

The Serial Hub is designed for operation in industrial areas and substations.
The Serial Hub enables devices with serial interfaces (RS232, RS485, or FO) to convert
data to the UDP protocol and to transmit and receive data via a TCP/IP network. This
enables devices without dedicated network ports to exchange data via Ethernet.

Hamburg Berlin

Ethernet Ethernet

WAN, e.g. Internet


(LAN, e.g. Intranet)
TCP/IP
Ethernet 10/100 Mbps
Parameterisation, e.g.
with a notebook

Serial hub Serial hub Serial hub

Measuring
equipment Safety equipment
Munich

Fig. 1: General scope of application of the Serial Hub

C53000-G1176-C174-4 Page 8 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Application in Substations
25B

When using a 7XV5655-0BA00 Serial Hub with a fixed IP address, one or more
SIPROTEC® protection units can exchange serial data via an Ethernet network.
On the operating PC, a configuration tool is applied to link a virtual COM port with the IP
address of a Serial Hub. The use of DIGSI 4 enables the operation of all protection units
connected to the Serial Hub via the virtual COM port.
The protection unit is connected to the Serial Hub via its serial interface. The serial
interface types available are RS232 or RS485 (same connector), and FO (fibre optic
cable). The serial data is converted to the UDP protocol with error detection and
correction in the Serial Hub and transmitted via the TCP/IP Ethernet network.
The hub meets the requirements for standard compliance, uninterrupted transmission of
serial DIGSI® or IEC 60870-5-103/101 frames via the network by listening into the serial
frame traffic and sending the serial IEC telegrams via the Ethernet. packed into blocks.
Both full-duplex and half-duplex data transmission (RS485) is possible. Serial control
lines are not supported. The Serial Hub can be configured with password protection.
Configuration of the Serial Hub is performed using the configuration tool which is
included in the scope of supply.

WAN (Private Network)

Router / Switch
up 1 2 3 4 5 6

LAN Patch-Cable

Substation- Substation- FO-Cable 6XV8100


modem 1 modem 2
INPUT

Ethernet- Ethernet- Mini-Star- RS485-FO


Hub Hub coupler Converter
7XV5655 7XV5655 7XV5450 7XV5650

RS485-Bus-Cable 7XV5103 7XV5103

Config-Tool SIEMENS SIPROTEC SIEMENS SIPROTEC SIEMENS SIPROTEC


SIEMENS SIEMENS

RUN RUN
RUN ERROR RUN ERROR RUN ERROR
ERROR ERROR

DIGSI 4 L1 402,1A
L2 402,1A
L3 402,1A
Max450.1A
Max450.1A
Max450.1A
L1 402,1A
L2 402,1A
L3 402,1A
Max450.1A
Max450.1A
Max450.1A
L1 402,1A
L2 402,1A
L3 402,1A
Max450.1A
Max450.1A
Max450.1A
L2 402,1A
L3 402,1A
Max450.1A
Max450.1A
L2 402,1A
L3 402,1A
Max450.1A
Max450.1A

Anr. L1 Anr. L1
E 00.0A E 00.0A E 00.0A Anr. L2 Anr. L2

Anr. L1 Anr. L1 Anr. L1


Anr. L2 Anr. L2 Anr. L2
Anr. L3 Anr. L3 Anr. L3
Anr. Erde Anr. Erde Anr. Erde
Automat Automat Automat
7XV5101

Station-PC for
Remote control
SIPROTEC 4 Max. 31 SIPROTEC 4 Devices Max. 4 SIPROTEC 3 Devices Max. 31 SIPROTEC 3
and Configuration for
with Ethernet- with RS485-Interface with optical Interface Devices with
the Ethernet-Modems
Interface RS485-Interface

®
Fig. 2: Serial Hub, application in substations with SIPROTEC devices

SIEMENS AG Page 9 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Features
26B

ƒ Protocol detection according to EN 60870-5-101/103 and DIGSI protocol (similar


to IEC60870-5-103), UDP protocol with error detection and correction
ƒ A 10-Mbit Ethernet interface (10BaseT) for the 10/100 Mbit network.
ƒ RS232/RS485 (switchable port) or FO interface for data transfer.
ƒ Serial baud-rate and data format to the terminal devices is automatically set by
the application, e.g. DIGSI 4 at 2400 Bd to 57.6 kBd (115.2 kBd) with data
formats 8N1, 8N2, 8E1.
ƒ Re-set to default values (factory settings) with INIT button: 9600 baud, 8N1
ƒ DIP switch for RS232/RS485 selection and RS485 bus termination as well as FO
idle state
ƒ Enhanced security is possible with password protection
ƒ LED displays for operating voltage and data traffic are located on the front panel.
ƒ DIN rail module in the plastic housing with integrated wide-range power supply
unit (24 - 250 V DC and 60 - 230 V AC) which provides connection to all
conventional substation batteries or AC power systems.
ƒ Protective conductor (PE) connection
ƒ Easy configuration with the configuration tool
ƒ Configuration tool V15 for Microsoft Windows® XP Prof. 32-Bit SP3
Microsoft Windows® 7 Prof. 32-Bit SP1
Microsoft Windows® 7 Prof. 64-Bit SP1
Microsoft Windows® Server 2008 R2 / 64-Bit

C53000-G1176-C174-4 Page 10 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Description of Interfaces, DIP Switches and Displays


2B

The Serial Hub has the following connectors:


• A switchable RS232/RS485 interface (9-way SubD male connector)
• FO transmitter and receiver port with ST connectors
• 10-Mbit Ethernet connector (10BaseT) for a 10/100 Mbit network
• DIP switches for RS232/RS485 switchover and RS485 termination as well as
setting of the FO idle state
• AC/DC power supply and protective conductor (PE) connection via 3-way screw
terminals

Communications Interfaces
27B

The RS232/RS485 or FO interfaces are controlled internally by the same processor


interface. The electrical interface is selected via the DIP switches. A choice exists
between RS232 or RS485; the FO interface always operates in parallel with RS232 or
RS485 at the transmitter end and is OR’ed with RS232/485 at the receiver end, that is,
both streams of receive data are unlocked and are received and checked with equal
priority. To rule out data collisions, the connected protection units are addressed
selectively by DIGSI®. This is done via the interface address of the protection units.

RS232 Interface
59B

The terminal device (protection unit) (e.g. a


SIPROTEC® 4 unit) or a device from the
SIEMENS accessory program (e.g. a
7XV5300 or 7XV5450 star coupler for
operating two or more SIPROTEC®
devices) can be connected directly to the
RS232 port. The data is exchanged
between the protection unit and the Serial
Hub via this interface.
To operate the RS232 interface, DIP switch
S2-1 must be set to RS232 and DIP
switches S1-1+2 to (RS485 termination)
OFF. The DIP switch for the FO idle state
(S2-2) must be OFF (see Fig. 3).

Fig. 3: Connectors and DIP switch positions


RS232

Note: The factory settings for all interfaces are 9600 baud / data format 8N1. The
settings are automatically adapted to the terminal device's interface by the application
(e.g. DIGSI) on connection.

SIEMENS AG Page 11 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

RS485 Interface
60B

The bus-capable RS485 interface


provides a link with increased noise
immunity than the RS232 interface. The
data transfer rate is identical for both
interfaces. The terminal device (e.g.
SIPROTEC® 4 device) which is to be
applied, or up to 30 further bus-capable
SIPROTEC® devices can be connected
directly to the RS485 port.
To apply the RS485 interface, DIP switch
S2-1 must be set to RS485. The position
of DIP switches S1-1+2 is dependent on
the requirement of a RS485 termination
(the termination is set to ON as the first or
last device on the RS485 bus).
The DIP switch for the FO idle state (S2-
2) must be OFF for idle state = OFF (see
Fig. 4). For the RS485 mode, "half-
Fig. 4: Connectors and DIP switch positions duplex" mode it must be set using the
RS485
configuration tool (see p. 36 RS232
Interface Settings)!

FO Interface
61B

The FO interface has a transmitter and


receiver port with an ST connector. It is
a noise-immune link and is used
whenever especially high interference
levels are to be expected in the
operating environment, or when
equipotential bonding with the terminal
device must be avoided. The data
transfer rate is that of the RS232
interface. The terminal device (e.g. a
SIPROTEC® 4 unit) or a further device
from the Siemens accessory program
(e.g. 7XV5300 or 7XV5450 star coupler
for operating two or more SIPROTEC®
devices) can be connected directly to
the FO port.

Fig. 5: Connectors and DIP switch positions FO

Note: The FO interface is always active with the RS232 interface; the DIP switch (FO-
OFF/FO-ON) only sets the idle state.
C53000-G1176-C174-4 Page 12 of 51 SIEMENS AG
Manual 7XV5655-0BA00

To use the FO interface, DIP switch S2-2 must be set to match the FO idle state of the
communications partner (ON or OFF). DIP switch S2-1 for RS232/485 selection must
be set to RS232. DIP switches S1-1 and S1-2 must be set to OFF (see Fig. 5).
On SIPROTEC units, the idle state is pre-set to OFF. This is also the factory setting of
the Serial Hub.

The 9-way RS232 interface can be used in parallel. If it is not, please cover it with
the red protective cover included in the scope of supply !
If the FO interface is not used, it must also be covered with the protective covers
included in the scope of supply.

Ethernet Interface (10BaseT)


62B

The Ethernet interface 10BaseT (RJ45) is connected via an Ethernet patch cable (1:1,
not cross-over) directly to the output of a router or switch. The data packed in the UDP
protocol is transmitted to and received by the Ethernet via this interface. The Serial Hub
can be configured using the configuration tool on a PC connected to this network via an
ordinary patch cable.
By using the configuration tool on a PC with an Ethernet interface and a cross-over
Ethernet patch cable connected directly to the Serial Hub, it is possible to configure the
Serial Hub as well.
The configuration tool is included in the scope of supply.

Auxiliary voltage
28B

The auxiliary voltage Vaux (AC/DC) and the protective earth conductor are connected via
three terminals. The wide-range power supply unit has reverse polarity protection
(terminals L+ and L- could be exchanged to AC and DC operation) and can for example
be used in substations with substation batteries. It features double or reinforced
insulation and backs up the auxiliary voltage for >50ms.

GOK Contact
29B

The isolated GOK contact (device run) is for alarming faulty device states. The device
internally monitors the supply voltage and proper functioning of the device.
The contact is open in the normal operating state and closes on faults and auxiliary
voltage failure. It is connected via two terminals (GOK 1+2).

INIT button
30B

The INIT button is for resetting the Serial Hub to its factory (default) settings and should
only be operated by technically qualified personnel.
It can be used to set a defined baud-rate locally for service work. The default baud-rate
is 9600 8N1. The Serial Hub also outputs a reset string with the date and version
number of the firmware on its serial interface (RS232 / RS485 / FO).
This reset string can be read by a terminal program (e.g. HyperTerminal in Windows) on
a connected PC. The serial interface of the PC must be set to the default baud-rate.
You do not need to use the INIT button if you know the baud-rate!
Operating the INIT button does not alter any settings relevant to security such as IP
addresses or password!

SIEMENS AG Page 13 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Meaning of Displays
31B

The LEDs indicate the state of the device and have the following meaning:

Fig. 6: Connectors, displays (LEDs) and INIT button

• GOK Device run: switched on, operating voltage OK


(GOK) device operational
• System Slow flashing (approx. 1Hz):
no connection to the terminal device
fast flashing (approx. 2Hz) :
connection with the terminal device is running (CONNECT)
• LAN Physical connection with the network is operational
• LAN RxD Receiving data packets from the Ethernet
• LAN TxD Transmitting data packets to the Ethernet
• COM RxD Receiving data on the serial line
from the terminal device (RS232/485 or FO)
• COM TxD Transmitting data on the serial line
to the terminal device (RS232/485 or FO)
• ERROR Error on the serial line (RS232/485 or FO)

C53000-G1176-C174-4 Page 14 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Mounting and Commissioning


3B

This chapter is intended for experienced commissioning personnel. This personnel must
be familiar with the commissioning of protection and control systems, with the
management of power systems and with the relevant safety rules and standards.
Hardware modifications that might have to be made in certain cases are explained. For
primary testing, the connected protection unit must be switched on.
General

Warning of improper transport, storage,


installation or mounting of the device
Failure to observe these precautions can result in death, personal
injury, or serious material damage.
Problem-free and safe use of this device depends on proper
transport, storage, installation and mounting of the device. All
warnings and instructions in this manual must be taken into
account.
In particular, the general installation and safety regulations for
work with power current equipment (e.g. ANSI, IEC, EN, DIN, or
other national and international regulations) must be observed.

Mounting Instructions
32B

Devices for DIN rail mounting are only permitted for operation in enclosed housings or
cubicles, and may only be mounted in locations that are accessible to qualified
personnel only.
The DIN rail housing is intended for mounting on a symmetrical mounting rail according
to EN 60715.
For mounting, the device is swung downwards onto the DIN rail, pressed downwards,
and snapped on by pressing backwards. The connection is released by lifting the
locking element on the underside of the device using a flat screwdriver to loosen it from
the mounting rail. The device can then be lifted off the DIN rail in the opposite direction
to the snap-on movement.
The data lines for electrical interfaces, e.g. RS232 or RS485, must be encased in
screened, earthed cables.
The FO cables must comply with the connection standard of the device (technical data).

The mounting location should be as vibration-free as possible. The permissible ambient


temperature (operating and functional temperature) must be observed (see Technical
Data).
Operation outside the functional temperature range or in environments with increased
air pollution can lead to malfunctions, failure, and destruction of the device (note the IP
class of the device).

SIEMENS AG Page 15 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Connecting the Device


This describes the connection of all data and power supply lines that are necessary for
safe operation.
In the case of electrical installation, follow the rules governing mounting of power
current equipment.

Warning
Always use wire end ferrules for stranded conductors.

Warning
Never look into fibre-optic waveguide elements or the ends of the
fibres.
Please observe the permissible bending radii of the optical fibre waveguide
(manufacturer data).
Bending cables to a smaller radius than the minimum bending radius can destroy the
FO fibres.

Auxiliary Power Connection


3B

The contacts for the operating voltage are established via the terminals on top of the
device. For the assignment of terminals please refer to the relevant sections of this
manual.
The supply voltage of the device must be protected with an external disconnection
device including a fuse, and identified as such. The fuse selected must be suitable for
the cross-section of the connection wires or for the cubicle wiring. (For the fuse value,
see the Technical Data.)
Screw terminal connection Solid or stranded conductors with wire end ferrules
for conductor cross-sections 0.25 mm2 to 2.5 mm2.
The dielectric strength of the connecting wires must
be at least 300 V AC.
Stripping length: up to 8 mm

Minimum cross-section of the 1.5 mm2


wires for auxiliary voltage and
earth (ground)

Nominal conductor cross-section 2.5 mm² , rigid conductor or with wire end ferrule

Tightening torque 0.5 Nm

C53000-G1176-C174-4 Page 16 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Connection to the Sub D connector


34B

The Sub D connector must be fastened tightly after connection. The pin assignment is
to be found in the relevant sections of this manual (page 41 ff).

Ethernet Connection
35B

The Serial Hub is connected to the network, i.e. a router or switch, by using a patch
cable, via the RJ45 (10BaseT) connector.
The dielectric strength of the Ethernet cable must be at least 300 V AC.
OR
The Serial Hub is connected directly to the LAN port of the operating PC using a cross-
over patch cable via the RJ45 connector.
The "link LAN" LED indicates correct connection with the Ethernet.
If that is not the case, check the network connection or network cable.
Cat5 cables (or better) must be used.

Commissioning
36B

Check whether the operating data match the values on the rating plate. Do not make
any changes on the device that are not described in this manual.
Plug in the connecting cable for the RS232/RS485 and fasten it tight or plug in the FO
cable and secure it. If you are not using the Sub D connector for RS232/RS485, attach
the red cover supplied.
Set the DIP switches for serial mode (RS232 / 485 / FO).

Maintenance and Cleaning


The device is maintenance-free. Use only a dry cloth for cleaning.
Never use liquid or aerosol cleaning agents.

SIEMENS AG Page 17 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Practical Safety Information


4B

As is the case for all electrical equipment, there are some basic safety precautions to be
taken. These safety precautions are primarily for your own protection but also prevent
damage to the device.
Settings not described in the manual, and changes to the device electronics can only be
carried out by an authorised vendor.
Read the device manual carefully and keep it close at hand.

Make sure that …


ƒ the device is always connected to protective earth
ƒ the device is never placed near a heating source or the outlet of an air-
conditioning unit.
ƒ the device is never exposed to direct sunlight.
ƒ the device never comes into direct contact with liquids of any kind. Never use
liquids in the vicinity of the device.
ƒ opening the housing can lead to electric shock and other damage. Never make
any changes to the device that are not permitted in this manual. Doing so could
damage the device. Any damage caused by unauthorised handling of the device
are done at own risk and own cost of repair or replacement.

Make sure that …


ƒ the rating of the supply voltage corresponds to the specification on the device
main plate If in doubt, contact your supplier.
ƒ the supply voltage is protected against surges and other disturbances.
ƒ the maximum power rating of the connected cables is not exceeded and
conductors have the required minimum cross-section.
ƒ all connected cables are protected against damage.
ƒ a damaged supply voltage cable is replaced immediately.
ƒ the line-side fuse is removed before cleaning the device to ensure complete
disconnection from the power source, and precautions are taken to prevent
unintentional reconnection.

C53000-G1176-C174-4 Page 18 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Preparing the Operating PC or Service Notebook


5B

Before commissioning the Serial Hub, the following precautions must be taken on the
on the operating PC or service Notebook:
Installation of the hub driver
To operate a serial hub from a WINDOWS® application in which an Ethernet link
is intended to be established, a driver providing a virtual serial COM port must
first be installed, using the configuration tool. This is done by installing and
setting up the configuration software.
In the application, the virtual COM ports look like interfaces integrated into the
PC/Notebook. Up to 255 virtual COM ports (minus the number of physical COM
ports) can be installed on a PC/Notebook.
This requires the following operating systems
Microsoft Windows® XP Prof. 32-Bit SP3
Microsoft Windows® 7 Prof. 32-Bit SP1
Microsoft Windows® 7 Prof. 64-Bit SP1
Microsoft Windows® Server 2008 R2 / 64-Bit
These Windows Operating Systems were used to test the installation as well as
the full scope of functionalities of the device.
• Installing the Configuration Software
For the installation of the configuration tool corresponding set-up files are
available for the various WINDOWS®-Operating Systems.
“ipEther.config.Setup_x86.exe” for Windows® XP SP3 and 7 SP1 32-Bit
“ipEther.config.Setup_x64.exe” for Windows® 7 SP1 64-Bit and Server 2008 R2
There are two ways of configuring the Serial Hub, using the configuration tool, via
the Ethernet interface.
1. The Serial Hub is connected directly to the operating PC/Notebook, using
a cross-over patch cable. After the configuration tool has been started, the
connected Serial Hub is automatically located and can be configured.
2. The Serial Hub is connected with a patch cable to a switch in an existing
network, to which the operating PC/Notebook is connected as well. After
the configuration tool has been started, all connected Serial Hubs are
located automatically and can be configured. To configure Serial Hubs
that are located in another network segment (e.g. behind a router), they
must be searched for in the network by manually entering the IP address.
• Configuring the Ethernet Interface of the Operating PC
In order to enable the operating PC to communicate with the Serial Hub, the
Ethernet interface of the operating PC/Notebook must be configured accordingly.

SIEMENS AG Page 19 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Configuring the LAN Interface of the Operating PC


14B

There are two ways of configuring the Serial Hub on a PC/Notebook using the
configuration tool via its Ethernet interface:

Direct PC <–> Serial Hub LAN connection with "cross-over patch cable"
37B

The Serial Hub is connected directly to the operating PC/Notebook using a cross-over
patch cable. A fixed IP address must be assigned to the LAN interface of the computer
for this purpose.
Note: If the computer is operated in a company LAN, a variable IP address is usually
assigned by the server (see next section). If the Serial Hub is to be configured directly
via the cross-over cable with this computer, a fixed IP address must be assigned to this
computer for this time.

Select the appropriate "Local area connection"


under "Connections".

In the "Local area connection status" window,


click the
"Properties"
button to switch to the local area connection
settings.

C53000-G1176-C174-4 Page 20 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Click the
"Properties"
button to set the IP address under
"Internet Protocol (TCP/IPvx)"
.

To assign a fixed IP address, select


"Use the following IP address"

Under "IP address:", enter a free IP


address for private networks, e.g.
192.168.10.100

Under "Subnet mask:" enter


the associated subnet mask
255.255.255.0
Under „Default Gateway“ enter
the associated Router address
192.168.10.1.

Confirm with "OK".

SIEMENS AG Page 21 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

If you want to check the settings of the LAN


interface In the "Local area connection
status" window, go to
"Details…"
.

Close the window again with the


"Close" button.

After you have started the configuration tool, the connected Serial Hub is located
automatically and can be configured (see Section "Configuration tool").

C53000-G1176-C174-4 Page 22 of 51 SIEMENS AG


Manual 7XV5655-0BA00

PC <–> Serial Hub LAN connection in an existing network


38B

The Serial Hub is connected with a patch cable (not cross-over cable) to a hub or switch
in an existing network to which the operating PC/Notebook is connected as well. The
PC usually automatically obtains a free IP address from the server.
The LAN connection of the operating PC to the network can be checked as described in
the previous section.

In the "Local area connection status"


window, go to
"General"
to display the status of the network
connection.

Under "Details" you can check at the


settings assigned to the connection.

Here, the network addresses are


automatically assigned by a DHCP server
in the network.

After you have started the configuration


tool, all Serial Hubs connected in the same
network segment are located automatically
and can be configured (see Section
"Configuration tool").

SIEMENS AG Page 23 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Using "HyperTerminal" via the Serial Interface of a PC


39B

This terminal program is supplied as a standard feature of the operating system


WINDOWS® XP.
Start HyperTerminal under:
"Start Æ Programs Æ Accessories Æ Communications Æ HyperTerminal"

Enter a name for the new


connection, e.g. 9600 8N1.
The connection can be saved
on exiting.

Assign a PC interface to the


connection,
e.g. COM1.

For a new Serial Hub, select the settings


9600 bits per second,
8 data bits,
none for parity,
1 stop bit and
none for flow control

Continue with
OK

Note: The Serial Hub data traffic can only be monitored via the serial interface in the
currently set baud-rate and data format. If these settings were changed, the connection
settings in HyperTerminal will have to be adjusted.
It is advisable to note down these settings to avoid any problems accessing the
Serial Hub later.

C53000-G1176-C174-4 Page 24 of 51 SIEMENS AG


Manual 7XV5655-0BA00

For Windows XP and WINDOWS 7 the terminal program “DIGSI Terminal“ is available
on the included CD/DVD as well as in the Internet under www.siemens.com/siprotec.
H H

After starting of the program, this is self-explanatory.


- select COM-Port
- set baud-rate as well as the data format
- press the button “connect

Out-put of the Firmware after pressing in the INIT-key of the Serial Hub.

Note: Entered characters are not displayed. To enable this, the “Echo” has to be
activated with the command “ATE1“ on the connected device such as for example a
modem.

SIEMENS AG Page 25 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

The Configuration Tool


6B

Installation of the configuration tool V15


40B

Pre-requisite is one of the following operating systems:


Microsoft Windows® XP Prof. 32-Bit SP3
Microsoft Windows® 7 Prof. 32-Bit SP1
Microsoft Windows® 7 Prof. 64-Bit SP1
Microsoft Windows® Server 2008 R2 / 64-Bit
The configuration tool may be found on the included CD/DVD
as well as in the Internet under www.siemens.com/siprotec.
H H

• Selection of the set-up filing directory in the WINDOWS® Explorer


• Start of the installation on the operating PC by double-clicking on the file :
• “ipEther.config.Setup_x86.exe” for Windows® XP SP3 and 7 SP1 32-Bit
• “ipEther.config.Setup_x64.exe” for Windows® 7 SP1 64-Bit and Server 2008 R2.

Continue the installation with


“Next >“

C53000-G1176-C174-4 Page 26 of 51 SIEMENS AG


Manual 7XV5655-0BA00

With “Browse…“ the pre-set


installation path can be altered.

Select the installation folder here or


create a new folder

Continue with “OK”

By selecting “Install” the


configuration tool is installed
on the operating PC.

SIEMENS AG Page 27 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

When this window is displayed the


installation has been completed
successfully and the process is
completed with “Finish”.

The configuration tool may be


started on the desktop of the
PC/Notebook with the icon
“Configuration Utility”.

De-installation of the configuration tool


41B

The de-installation of the program may be carried out via WINDOWS®


System Control Panel-> Programs and Functions-> ipcas Ethernet Products.
Alternatively it may be done by starting the installation directory,
ipEther.config.Setup_xyy.exe.

For de-installation select „Remove“


in both windows and confirm the
entries.

C53000-G1176-C174-4 Page 28 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Configuring the Serial Hub with the Configuration Tool


42B

The configuration tool is used to install the basic settings. Start the configuration tool
and all serial modems and settings may be viewed in the displayed list.
For this purpose, the configuration tool is started and finds all Serial Hubs in the same
network segment which it then lists in a table.

Overview Window
43B

The configuration program locates all devices in its own network segment, even those
without a valid IP address.
If the settings (Properties) are to be carried out or changed under Windows 7, the
Configuration tool must be opened as Administrator. If the Tool has been started without
administrative rights this is displayed in the header.

Clicking on the column header in the overview, e.g. "IP address", sorts the devices in
ascending or descending order of the items in that column.

Items in the Overview Window:


63B

Name Serial Hub name for better identification by means of a self-


explanatory text.
IP Address Current IP address
Subnet Mask Current Subnet Mask
Gateway Current Gateway
MAC Worldwide unique MAC address
Device Type Device Type
Version Current firmware version
Info Currently configured COM port (not available for Serial
Hubs)
In Use If the entry is "YES", the device is in connection mode and
it is not possible to make changes to the settings.
UDP-Port 3497 If this entry is "NO", the device will no longer be found. It is
not connected, deactivated, or is behind a router that is
blocking the UDP port 3497.

SIEMENS AG Page 29 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

in local Net If this entry is "NO", the device is not in the local network
segment.
If the device is installed behind a router, the IP address
cannot be changed. This prevents the device from being
accessed unintentionally.
Password If this entry is "YES", the device is password-protected and
the password must be entered before configuration (by
right-clicking on "login").
If the password is forgotten, the device must be
submitted again (see last page).
Logged in If this entry is "NO", the password has to be entered before
configuration (by right-clicking "login").
CPU-ID Internal CPU ID (not relevant for users)

General Settings
4B

When the Serial Hub is delivered, no valid IP address has been set yet.
The default address is 10.10.5.1.
A unique IP address must first be assigned to each device.
To set the IP- addresses in the serial hub, the device must be connected in its own
network segment. Otherwise the device should be connected to the operating PC, using
a “cross-over patch cable”.
If the Serial Hub is integrated into a DHCP network the available IP addresses are
assigned automatically. The network administrator on the DHCP server must assign a
U U

fixed IP address for the Serial Hub.


U U

Right-clicking the device entry in the overview window displays a dialog box in which
further actions can be performed.

C53000-G1176-C174-4 Page 30 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Set IP Address
64B

Enter a fixed IP address, Subnet-Mask and Default-Gateway for


operation of the Serial Hubs in a network.
If the allocated IP-address and the Subnet-Mask are not compatible
the properties cannot be changed any longer. In this event please
change the settings.

Set Device Name


65B

Enter the name of the Serial Hub for a more transparent


overview in the table.

Change Password
6B

Before a password can be assigned or altered, the old password has


to be entered. Then enter the desired new password twice.
No password has been set on delivery, which means that the space
“Password” remains unfilled with the first change.
If the password protection is to be be deactivated, the old password
is entered and the empty spaces of the „New Password“ are
confirmed with “Return“.

In the case of a forgotten Password, the device must be sent in.


(For the relevant address, refer to the last page of this manual)

SIEMENS AG Page 31 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Upload Firmware
67B

Locate the new firmware version and import it with "Open" or


by double-clicking.
The firmware update re-sets the Serial Hub to its factory
settings (default settings). Passwords and IP-address are not
U U

re-set.
If the message: "Can’t upload Firmware. See Logging"
appears during a firmware update, please repeat the upload
until the message: "device is up again" appears.
The configuration tool may be found on the included CD/DVD
as well as in the Internet under www.siemens.com/siprotec
H

Delete
68B Currently marked entry is deleted.

Add Device Manually


69B

If the Serial Hub is connected behind a router, it is not located


automatically but must then be added manually ("Add Device
manually"). This is done by entering its IP address in the
required space. If the device can be accessed at this address,
it is imported into the list.
Note: If the device is installed behind a router, the IP address
cannot be changed. This prevents the device from becoming
unaccessible by mistake.

C53000-G1176-C174-4 Page 32 of 51 SIEMENS AG


Manual 7XV5655-0BA00

View Event Log


70B

View current log-file (internal trace)

Properties
71B Type-specific configuration user surface
For more information, see the relevant chapters in this manual.

Important Notes regarding the properties and storage file


as well as the correct start and termination of communication.
Only the „IP-Address“, „Name“ and „Password“ are stored in the Serial Hub.
The „virtual COM-Port“, the related „IP-Addresses“ and „all other settings“
(Properties) are only saved on the respective operating PC in an XML file.
The settings (Properties) of the operating PCs and the serial hubs are displayed in a
list or settings window in the Configtool. These settings (Properties) can be exported
from the Configtool and imported to a different PC or Notebook..
Each time the COM-Ports is opened “all other settings” along with the “baud-rate” and
“data format” are transferred from the application to the Serial Hub. After termination of
the communication, the application has to correctly terminate the application.
If more than one operating PC is used to access the same Serial Hub, then these
settings must be applied to all these operating PCs. The virtual COM-Port for a
particular Serial Hub may be the same or different on various operating PCs.
If the Serial Hub is “in use”, i.e. it is connected to an operating PC, it is barred for all
other operating PCs and the allocated COM-port for this Serial Hub is not shown in the
application. This avoids a data collision and is as such a “multi master system”.
The Configtool displays this under „In Use“ with „YES“.

SIEMENS AG Page 33 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Properties
15B

If the settings (Properties) are to be carried out or changed under Windows 7, the
Configuration tool must be opened as Administrator. If the Tool has been started without
administrative rights this is displayed in the header.

Double-clicking the device entry in the overview window displays a dialog box in which
additional settings may be made.
A detailed dialog box consisting of six setting tab cards opens:

TCP/IP Settings
45B

"Info" displays the


MAC address,
IP address and the
Device name

These settings can only be altered


under „General Settings“.

C53000-G1176-C174-4 Page 34 of 51 SIEMENS AG


Manual 7XV5655-0BA00

TC57 Settings (Ethernet)


46B

If a frame in TC57 format is received via the RS232 interface, it is immediately sent via
Ethernet without a "timeout". This procedure clearly increases the performance of the
connection and ensures uninterrupted transmission of frames.

The IEC 60870–5–1 and IEC


60870–5–2 standard defines four
standard frame formats for the data
link layer.
They are:
TC57 Format FT 1.1
72B

TC57 Format FT 1.2


73B

TC57 Format FT 2
74B

TC57 Format FT 3
75B

Frame formats FT 1.2, FT 2 and FT


3 have a frame of fixed length.
The frame with variable length for
FT 2 and FT 3 has a header of fixed
length. This contains "Start
character", "Length", "User data"
and "Checksum".

The user must select the required format and enter the values for "Fixed frame length"
and "Header length".
The value in the "Fixed frame length" edit box is in the range of 2 to 255 bytes.
The value in the "Header length" edit box is in the range of 2 to 14 bytes. The value only
refers to "User data" from the header.

Note: For the protocols IEC60870-5-103, VDEW or for the protocol used by DIGSI®,
the format FT 1.2 (Header length = 0 byte and Fixed Frame length = 2 byte) is required.

SIEMENS AG Page 35 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

RS232 Interface Settings (RS232 / RS485 / FO)


16B

These settings adapt the settings of the serial interface of the Serial Hub to that of the
terminal device. The terminal device may, for example, be a protection device with a
serial interface (SIPROTEC®). These settings apply to all possible connections (RS232
or RS485 or FO).

The RS232 settings are adapted to the


communication behaviour of the serial
terminal device.

Com port describes the virtual COM


76B

port to be used. (Up to 255 COM ports


minus the number of physical COM
ports are available.)

No Modem Signals has no effect here


and is not set.

Half Duplex (RS485). The RS485 can


be operated in the half-duplex or full-
duplex mode (RS232 and FO).

Under TotalReadTimeout,
it is usually in order to apply the default
value of 100 ms.
The ideal signal throughput time can be
ascertained with the "ping" tool (see
below) or the "INet Info" dialog box.
CharDistance (i.e. character interval)
with default value 5 ms should only be
changed in exceptional cases.

NOTE : The settings for baud-rate, data bits, parity and stop bits are done by the
application (e.g. DIGSI®). This establishes a link to the Serial Hub via the driver for the
virtual COM port and transfers the serial interface settings for communication to the
terminal device.

C53000-G1176-C174-4 Page 36 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Port assignment (Export / Import / Delete)


17B

In this selection the allocation of the


virtual Com-Ports of all Serial Hubs
to the MAC and IP addresses, as
well as the name of the
PC/Notebook are displayed.

If a device is marked, the allocation


of the XOM Port can be deleted with
the button “Delete“
The IP-addresses and names
remain stored in the serial hub, all
other settings are deleted in the PC
/Notebook.

With the buttons „Export“ und


„Import“ the „Device
Configurations List“ can be saved
on the PC and again imported onto
another PC.

With the button “Help“ further


information on this topic can be
obtained.

SIEMENS AG Page 37 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

INet Info
18B

This window provides up-to-date


network information.

The "Start" button transmits a ping


to the Serial Hub to ascertain the
throughput time of the telegrams in
the network.

About
47B

This window provides information about the


configuration- and driver version and the date of
issue of this configuration tool.

If the PC has Internet access, you can double-


click the image for direct access to our
Download Area.

All up-to-date documents, drivers and updates


for our products are available under
www.siemens.com/siprotec
H

C53000-G1176-C174-4 Page 38 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Optimising Data Transfer


7B

Great emphasis has been placed on compatibility in the design of this device.
Due to the Ethernet, there are, however, some minor restrictions. Data is not
transmitted in bytes to the network. This is done in data blocks via Ethernet.
This might result in minor delays. Block formation function does not directly
affect the application but might help to reduce the network load. Some fine
tuning might be necessary for time-critical applications. This involves the two
timeout parameters ("Total Read Timeout", "Character Distance").

Block Formation for Serial Data before Transmission into the Ethernet
48B

After the first byte has been received, "Total Read Time" starts. After the time
expires, all characters received so far are relayed to the Ethernet. The default
value is 50 ms.
"Character Distance" is the maximum interval between two received
characters. If this is exceeded, all characters received so far are transmitted
into the Ethernet. The default value is 5 ms.

Total read timeout Total read timeout

Character timeout

No transmission.
Gap is too small. Transmission Transmission Transmission
to PC to PC to PC
Transmission because
"Total Timeout" has
expired

Transmission because
the gap between the
characters is larger
than "Char Timeout"

Transmission because
the gap between the
characters is larger
than "Char Timeout"

SIEMENS AG Page 39 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Protocol Code TC57 for Transmission into the Ethernet


49B

This procedure considerably enhances transmission rates when TC57


compatible protocols are transmitted. If the RS232 interface detects a protocol
package of this type, it is transmitted as a block via the Ethernet immediately,
without waiting for a timeout to elapse.
The Serial Hub can be adapted to various standards.
The IEC 60870–5–1 and IEC 60870–5–2 standards define four standard frame
formats for the data link layer:
0 = Format FT 1.1 2 = Format FT 2
1 = Format FT 1.2 3 = Format FT 3
Frame formats FT 1.2, FT 2 and FT 3 have a frame of fixed length.
The frame with variable length for FT 2 and FT 3 has a header of fixed length.
This contains "Start character", "Length", "User data" and "Checksum".
The user must select the required format and enter the values for "Fixed frame
length" and "Header length".

Protocol code for IEC 60870-5, VDEW and DIGSI®


50B

The IEC 60870–5–102 / 103, VDEW, DIGSI® V3 and DIGSI® 4


protocols are identical to or similar to this specification so that the protocol code
of this Serial Hub can be used.
This is done by activating the protocol code, selecting format FT1.2 and setting
a fixed frame length of 2 bytes.

Selecting a Password-Protected Serial Hub


8B

The password is used for activation of the configuration mode with the configuration tool
as well as for establishing the link. If no password is assigned, this must be entered in
the configuration tool under 'Password required'=false.

Entering a Password
51B

To enter a password enter 'Change Password' in the configuration tool and enter the
password under 'New Password' and then under 'Retype New Password' before
pressing "Enter". The password can have up to 8 digits.

To be able to access a password-protected Serial Hub


from the computer from which the application is to be
started, the password must be entered on this
computer.

C53000-G1176-C174-4 Page 40 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Entering the log-in


52B

To access parameter entry from the configuration tool, an assigned password must be
entered in 'Login'.

Entering an Incorrect Password


53B

If you enter the wrong password, the message "Invalid Password" is displayed.

SIEMENS AG Page 41 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Pin Assignment
9B

The cables for RS232 and RS485 are connected to the same port and selected
using the DIP switches.

RS232 Interface
54B

SERIAL PORT Pin Direction Definition


9-pin SubD connector
1 Screen

2 INPUT RXD Receive Data

3 OUTPUT TXD Transmit Data

4 not connected

5 GND Ground (ext)

6 not connected

7 not connected

8 Do not assign !

9 not connected

RS485 Interface
5B

SERIAL PORT Pin Direction Definition


9-pin SubD connector
1 Screen

2 Do not assign !
INPUT/
3 RS485 Data-A
OUTPUT
4 not connected

5 GND Ground (ext)

6 not connected

7 not connected
INPUT/
8 RS485 Data-B
OUTPUT
9 not connected

C53000-G1176-C174-4 Page 42 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Ethernet Interface
56B

Ethernet connector Pin Name Definition


RJ 45 1 TX+ Transmit Data+
2 TX- Transmit Data-
3 RX+ Receive Data+
4 n/c not connected
5 n/c not connected
6 RX- Receive Data-
7 n/c not connected
8 n/c not connected

Ethernet RJ45 connector

Auxiliary Voltage and Earth Connection


57B

3-way terminal block Pin Name Definition


Vaux
1 L+ Vaux+
Screen L- L+
2 L- Vaux-
3 Earth Protective Earth

The device features internal reverse polarity protection for Vaux.

DR Contact
58B

2-way terminal block Pin Name Definition


DR
1 DR Isol. DR
2 DR-NC Isol. DR-NC

SIEMENS AG Page 43 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Connecting Cable
RS232 connection options:

1) PC/Notebook to the protection unit Æ plug in serial DIGSI cable directly


2) Serial Hub to SIPROTEC 4 or Æ plug in serial DIGSI cable via gender
7XV5300, 7XV5450, 7XV5550, 7XV5652 changer (male-male) to Serial Hub

Serial DIGSI Cable

Notebook / PC 7XV5100-4/BB Notebook / PC


9-way female Length=3m 9-way male

2 RxD 3
3 TxD 2
5 GND 5
Housing Housing
4 7
6 8
7
8

For further cables and adapters, see: www.siemens.com/siprotec


H H

Serial RS485 Connecting Cable

7XV5103-0AAxx Further devices


From serial modem xx= length SIPROTEC or bus termination
SUB-D connector SUB-D connector SUB-D connector
9-way male 9-way male 9-way female

3 8 Housing
A A
3 3
B L=1/3/5/10 m L=0.2 m B
8 8

Housing Housing

For further RS485 cables and adapters, see: www.siemens.com/siprotec


H H

C53000-G1176-C174-4 Page 44 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Technical Data
10B

Auxiliary voltage 24 V – 250 V DC +/-20 %


60 V – 230 V AC +/-20 % , 45-65 Hz,

Power input 2.5 W DC


14 VA AC

Line-side fuse T 2A/250 V AC and 250 V DC


acc. to IEC 60127

Alarm relay (DR) Relays, 1 NC isolated


Connection 2-way screw terminal,
Switching current (continuous) 1A
Switching voltage 250V AC and DC
Switching capacity 20 W / 20 VA

3-way terminal
Minimum cross-section of the wires for auxiliary 1.5 mm2
voltage and earth (ground)
Nominal conductor cross-section 2.5 mm² , rigid conductor or with wire
end ferrule
Stripping length: up to 8 mm
Tightening torque 0.5 Nm

FO connection

Connection method ST connector receiver and transmitter


Wavelength 820 nm
Fibre Type Multimode fibre, 62.5/125 µm
Baud rate 2400 up to max. 115200 baud
Protocol full-duplex
Laser class 1 acc. to EN60825-1/-2 using glass
fibre 62.5/125 µm
Transmit power in dBm , peak (type), -12.0 (fibre type 62.5/125 µm)
NA = 0.275
Max. optical power for high level Max. -40 dBm peak
Min. optical power for low level Min.: -24 dBm peak
Optical power budget Min. 8 dB (62.5/125 µm)
NA = 0.275
Range Max. 2 Km (attenuation 3 dB / Km 62.5 µm)
Max. 2 m with plastic fibre

Ethernet interface 10BaseT (10/100 Mbits)


Connection RJ45, screened, 8-way
TCP/IP UDP Port 3497 (User Datagram Protocol)
ICMP (Internet Control Message Protocol)
ARP (Address Resolution Protocol)

SIEMENS AG Page 45 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

RS232 and RS485


Connection type 9-way SubD connector, 4/40 UNC screw
connection
Pin assignment See Pin Assignment
Cable length RS232 Max. 10 m / 3280 feet
Baud rate 2400 to 115200 baud, Rxd, Txd
Parity : None, Even, Odd, Mark, Space

Data : 7 or 8 bits
Stop : 1 or 2 bits
RS232 : full-duplex , RS485 : half-duplex

DIP switches RS232/485 switchover


Idle state FO ON/OFF
RS485 termination

LED displays DR (GN): Alarm (Vaux power o.k. and reset


o.k.)
COM-TxD (GN) : Transmit - RS232 or
RS485 or FO
COM-TxD (YE) : Receive - RS232 or RS485
or FO
System (GN) : Connection to the PC via
RS232 detected
LAN-TxD (GN) : Transmit Ethernet
LAN-TxD (YE) : Receive - Ethernet
LAN (GN) : Connection to the Ethernet
network
Error (RD) : hub error on RS232/Reset

Firmware Updatable
Driver Setup & configuration tool for
Microsoft WINDOWS® XP SP3 32-Bit,
Microsoft WINDOWS® 7 SP1 32/64-Bit,
Microsoft Server 2008 R2 64-Bit

Mechanical design
Housing Plastic
Dimensions See Dimension Drawings
Weight: Approx. 180 g

Degree of protection acc. to EN60529 IP20 (housing and terminals)


Protection class I Protective Earth

Safety
Acc. to DIN EN61010 Part 1
Overvoltage category III
Pollution degree 2
Fire resistance class (acc. to UL94) V0

C53000-G1176-C174-4 Page 46 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Standards: IEC 60255 (product standard)


IEEE Std C37.90.0/.1/
VDE 0435
For more standards, see each function

Insulation tests

Standards: IEC 60255-5 and IEC 60870-2-1


Voltage test (100% test) all circuits except 2.5 kV (rms), 50 Hz
auxiliary voltage and communication interfaces
Voltage test (100% test) on auxiliary voltage 3.5 KV DC
Voltage test (100% test) only locked 500 V (rms), 50 Hz
communication interfaces
Surge withstand capability test (type test) 5 kV (peak value); 1.2 / 50 µs; 0.5 J;
all circuits except communication interfaces, 3pos./neg. surges at 5s intervals
class III

Warning

The 7XV5655-0BA00 is specifically intended for installation in a switchgear


cubicle or distribution housing. After installation protective covering must be
placed around the entire area of the terminals. Only then is the device
sufficiently protected against impermissible contact with live parts.

EMC tests for immunity (type tests)

Standards: IEC 60255-6 and -22 (product standards)


EN61000-6-2 (generic standard)
VDE 0435 part 301DIN VDE 0435-110

High Frequency Test 2.5 KV (peak); 1 MHz;‫ = ז‬15 ms; 400 surges
IEC 60255-22-1, Class III per s; test duration 2s; Ri = 200 Ω
and VDE 0435 Part 303, Class III

Electrostatic Discharge 8 KV contact discharge; 15 KV air discharge


IEC 60255-22-2, Class III pos./neg. polarity, 150 pF; Ri = 330 Ù

Irradiation with RF field, frequency sweep 10 V/m, 80 MHz to 1000 MHz: 80% AM, 1
IEC60255-22-3, Class III kHz
IEC61000-4-3, Class III

SIEMENS AG Page 47 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Irradiation with RF field, single frequencies Class III: 10 V/m


IEC60255-22-3, IEC61000-4-3
- amplitude-modulated 80, 160, 450, 900 MHz; 80 % AM 1kHz;
duty cycle > 10 s
- pulse-modulated 900 MHz; 50% PM, repetition frequency 200
Hz
Fast transients / bursts
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
IEC 60255-22-4 and IEC61000-4-4
Repeat rate 300 ms; pos./neg. polarity;
Class IV
test duration 1 min.; Ri = 50 Ù

High energy surge voltages (SURGE) Pulse: 1.2/50 µs


EN61000-4-5 insulation class 3
- Auxiliary voltages common mode; 2 KV; 12 Ω; 9 µF
differential mode : 1 kV; 2 Ω; 18 µF

- Relay output common mode; 2 KV; 42 Ù; 0.5 µF


differential mode : 1 KV; 42 Ω; 0.5 µF

Conducted RF, amplitude-modulated 10 V; 150 KHz – 80 MHz; 80 % AM, 1 KHz


IEC61000-4-6, Class III

Magnetic field with power 0.5 mT; 50 Hz


frequency Class IV: 30 A/m continuous; 300 A/m for 3s;
EN61000-4-8 50Hz
IEC60255-6

Oscillatory Surge Withstand Capability 2.5 KV (peak); 1 MHz;‫ = ז‬15 µs; 400 surges
IEEE Std C37.90.1 per s; test duration 2s; Ri = 200 Ω

Fast transient surge withstand capability 4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
IEEE Std C37.90.1 Repeat rate 300 ms; pos./neg. polarity;
test duration 1 min.; Ri = 50 Ù

Damped oscillations 2.5 kV (peak value), polarity alternating 100


IEC 60694, IEC 61000-4-12 kHz,
1 MHz, Ri = 200 Ω

EMC tests for emission (type tests)

Standard: EN 61000-6-4/3 (generic standard)

Radio interference voltage on lines 150 kHz to 30 MHz


Auxiliary voltage only Limit class B
IEC CISPR 22

Interference field strength 30 to 1000 MHz


IEC CISPR 11 Limit value class A

C53000-G1176-C174-4 Page 48 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Mechanical tests, vibration and shock stress


- stationary use

Vibration Sinusoidal, 10 to 58 Hz : 0.075 mm ampl.


IEC 60255-21-1, Class 2 58 to 150 Hz : 1.0 g accel.
IEC 60068-2-6 20 cycles in 3 orthogonal axes

Shock Semi-sinusoidal, 5 g accel., 11 ms duration


IEC 60255-21-2, Class 1 3 shocks each in both directions of the
3 axes

Seismic vibration Sinusoidal, 1 to 8 Hz : 4 mm ampl.


IEC 60255-21-3, Class 1 horizontal
IEC 60068-3-3 1 to 8 Hz : 2 mm ampl. vertical
8 to 35 Hz : 1 g accel., horizontal
8 to 35 Hz : 0.5 g accel., vertical
1 cycle in 3 orthogonal axes

Mechanical tests, vibration and shock stress


- during transport

Vibration Sinusoidal, 5 to 8 Hz : 7.5 mm ampl.


IEC 60255-21-1, Class 2 8 to 150 Hz : 2 g accel.,
IEC 60068-2-6 20 cycles in 3 orthogonal axes

Shock Semi-sinusoidal, 15 g accel., 11 ms duration


IEC 60255-21-2, Class 1 3 shocks each in both directions of the 3
IEC 60068-2-27 axes

Shock Semi-sinusoidal, 10 g accel., 16 ms duration


IEC 60255-21-2, Class 1 1000 shocks each in both directions of the
IEC 60068-2-27 3 axes

Climatic tests
13B

Recommended operating temperature 0 °C to 55 °C


Limit temp. during operation -5 °C to +70 °C
Limit temp. during storage -25 °C to +55 °C (factory packing)
Limit temp. during transport -25 °C to +70 °C (factory packing)

Humidity 80 % at temperatures up to 31 °C,


Maximum relative humidity decreasing linearly down to 50 % at 40 °C

Installation altitude 2,000 m


Maximum height above sea level

All devices must be installed so that they are not exposed to direct sunlight, nor subject to great
fluctuations in temperature that may cause condensation.

SIEMENS AG Page 49 of 51 C53000-G1176-C174-4


Manual 7XV5655-0BA00

Dimensions
1B

C53000-G1176-C174-4 Page 50 of 51 SIEMENS AG


Manual 7XV5655-0BA00

Ordering Information
12B

Name Order No.


Serial Hub 7 X V 5 6 5 5 - 0 B A 0 0
10BaseT connection
10/100 Mbits, RJ45 connector
Serial RS232/485 interface
9-way Sub D connector
Gender changer (male-male)
FO interface, ST connection
DIN rail mounted device for 35mm rail

Aux. voltage 24-250 VDC / 60-230 VAC

If you have any comments or questions regarding this product please contact :
Siemens AG
Infrastructure & Cities Sector
Smart Grid Division
Energy Automation

Tel : +49 180 524 8437 (248437 correspondes to "cities" on telephone keypad)
Fax: +49 180 5242471
E-Mail: support.ic@siemens.com
H

Internet: www.siemens.com/siprotec
H H

Weitergabe sowie Vervielfältigung dieser Unterlage, Verwertung


und Mitteilung ihres Inhalts nicht gestattet, soweit
nicht ausdrücklich zugestanden. Zuwiderhandlungen verpflichten
zu Schadenersatz. Alle Rechte für den Fall der
Patenterteilung oder GM–Eintragung vorbehalten.

The reproduction, transmission or use of this document or its


contents is not permitted without express written authority.
Offenders will be liable for damages. All rights, including rights
Änderungen vorbehalten created by patent grant or registration of a utility model or design,
Subject to change without prior notice are reserved. Release 3.00.00

SIEMENS AG Page 51 of 51 C53000-G1176-C174-4

You might also like