Models Available Power transducers measure AC power (active, reactive or both) either
EP12B Single Phase Watts
directly or through voltage and/or current transformers. The transducer
EP33B 3 Phase 3 Wire Bal. Watts
EP33U 3 Phase 3 Wire Unbal. Watts converts the AC power signal to either a DC mA or DC voltage output
EP34B 3 Phase 4 Wire Bal. Watts
which is directly proportional to the input signal value.
EP34U 3 Phase 4 Wire Unbal. Watts
Specification Connections
Reference Standard:
IEC 688, BS 6253, VDE/VDI 2191 Auxiliary
Power
Accuracy: ~/- ~/+
Class 0.25 (±0.25% f.s. max. error)
Input Voltage, Un:
16 15 14 13
50V to 550V direct connected (specify) - +
EP12B Output
or VT operated EQ12B
Input Current, In: EP34B
0-0.7A to 0-7.5A direct connected EQ34B Input
0-1A or 0-5A CT operated 11 3 2 1
Overload: S
L U
1.2 x Un, 2 x In continuous l k
O L K L1 P
1.5 x Un, 30 x In for 1 second A N P
Working Range: D L
0 - 120%Un (auxiliary powered) Y
80 - 120%Un (self powered) Auxiliary
0 - 120%In Power
~/- ~/+
Frequency:
50 or 60Hz
Burden: 16 15 14 13
- +
Current circuit < 0.3VA Output
Voltage circuit < 0.2VA (aux. powered) EP33B
EQ33B
Voltage circuit < 3VA (self powered)
Input
Weight:
9 8 7 3 2 1
EP12B, EP33B, EP34B 700g
S
EP33U, EQ33U 900g
L l k U
EP34U, EQ34U, All EPQ 1000g L K L1
O P
k L2
A l P
L K L3
D L
Y
Eltime Controls Email: sales@eltime.co.uk Web: www.eltime.co.uk Continued...
Connections
32 31 16 15
- + - +
EP33U Var Output Output (EP33U/EQ33U)
EQ33U (EPQ33U only) Watt Output (EPQ33U only)
EPQ33U
Input
14 13 8 6 5 4 3 2 1
S
L l k U
~/- ~/+ O l kL K L1
P
Auxiliary L K L2
Power A P
L3
D L
Y
32 31 16 15
- + - +
Var Watt
EPQ12B Output Output
EPQ34B
Input
14 13 11 3 2 1
S
L U
l k
~/- ~/+ O L K L1 P
Auxiliary A N P
Power D L
Y
32 31 16 15
- + - +
Var Watt
EPQ33B Output Output
Input
14 13 9 8 7 3 2 1
S
L l k U
~/- ~/+ L K L1 P
O
Auxiliary L2
A l k P
Power L3
D L K L
Y
16 15
- +
Output
EP34U
EQ34U
Input
14 13 11 9 8 7 6 5 4 3 2 1
S
l k
~/- ~/+ L
l kL K L1 U
Auxiliary O L2 P
l kL K
Power A L3 P
L K
D N L
Y
Continued... Eltime Controls Tel: +44 (0) 1621 859500 Fax: +44 (0) 1621 855335
10 Dimensions
100.0
Product Features
Isolated DC mA or DC voltage output
Accuracy class 0.25
Adjustable ‘span’ and ‘zero’
35.0
70.0
DIN rail mounting enclosure
4kV rms 50Hz 1 minute isolation
between input / output / case / auxiliary
1kVdc / 600Vac isolation between Watt
& Var outputs on Watt/Var transducers EP12B
EQ12B M3.5 DIN-EN 50022 / BS558
Screw type terminals
EP33B Terminals Rail Fixing
Fingerproof terminal cover included EQ33B
EP34B 112.0
EQ34B
Fixing
Clip
150.0
35.0
70.0
112.0
EP33U
EQ33U
EP34U
EQ34U
EPQ12B
EPQ33B
EPQ34B
EPQ33U Fixing
Clip
135.2
Alternative Surface
60.0
50.0
Fixing Dimensions
All dimensions in mm
Eltime Controls Email: sales@eltime.co.uk Web: www.eltime.co.uk Continued...
Ordering information
11
Model Code Description
EP Active Power (Watts)
EQ Reactive Power (Vars) Function Graphs
EPQ Active & Reactive Power (Watts & Vars)
100%
Wiring System Code Description
12B Single Phase
OUTPUT
EP
33B 3 Phase 3 Wire Balanced
EQ
33U 3 Phase 3 Wire Unbalanced
34B 3 Phase 4 Wire Balanced -100% IMPORT
34U 3 Phase 4 Wire Unbalanced (EPQ N/A) EXPORT 100%
OUTPUT
C1 1 Amp
C5 5 Amp EPQ
CX 0.5 to 7.5 Amps (specify)
-100% IMPORT
uxiliary Power
A Code Description EXPORT 100%
E0 Self Powered
E1 110Vac (±20%) LIMITS OF
VAR INPUT
E2 230Vac (±20%)
E3 415Vac (±20%)
-100%
E4 63.5Vac (±20%)
E5 24Vdc (±20%)
On EPQ combined Watt & Var transducers the
E6 48Vdc (±20%)
full scale Var input can be specified between
E7 110Vdc (±20%) 50% and 200% of the full scale Watt input.
Output Code Description e.g. If full scale Watt input is 200Watts, the Var
X1 ±1mA input can be specified anywhere between 100
and 400Vars.
X2.5 ±2.5mA
X5 ±5mA
X10 ±10mA
X10B 0-5-10mA Full
Input Scale 12B 33B/33U 34B/34U
X20 ±20mA Voltage Watts Single 3 Phase 3 Phase
XA 4-20mA & Current and/or Phase 3 Wire 4 Wire
Vars
XB 4-12-20mA
110V & 1A Standard 100 200 300
XV ±Voltage (specify up to 15Vdc) (P1-C1) On 50 to 100 to 150 to
Request 200 400 600
I nput Frequency Code Description 110V & 5A Standard 500 1000 1500
(P1-C5) On 250 to 500 to 750 to
F50 50Hz Request 1000 2000 3000
F60 60Hz 230V & 1A Standard 200 400 600
(P2-C1) On 100 to 200 to 300 to
Request 400 800 1200
Example EPQ - 33B - P1 - C5 - E1 - XA - F50 230V & 5A Standard 1000 2000 3000
(P2-C5) On 500 to 1000 to 1500 to
Request 2000 4000 6000
General Specification
Output
Response Time: < 400ms for 0-90% of input value
Warm Up Time: < 15 minutes
Residual Output Ripple: < 1% peak full scale
Long Term Drift: ±0.25% per year non-cumulative
Maximum Load: 1mA < 10kohm
2.5mA < 6kohm
5mA < 3kohm
10mA < 1.5kohm
20mA < 750ohm
Voltage output >1kohm
Self powered voltage and current transducers have an adjustable span while all
other units have an adjustable zero and span accessible from the front panel.
Auxiliary
AC: 110 / 230 / 415V (±20%) (others upon request)
DC: 24 / 48 / 110V (±20%)
Environmental
Operating Temperature: -20ºC to 65ºC
Storage Temperature: -40ºC to 75ºC
Variation With Temperature: 0.03%/ºC (±0.5% maximum)
Relative Humidity: 0 - 95% non-condensing
Burden
Input Circuits: See individual specifications
Auxiliary Power Supply: 7VA combined Watt/Var transducers (4VA all other transducers)
EMC Compliance
Directive 89/336/EEC: Electrostatic discharge IEC801.2 (8kV)
Electromagnetic fields IEC801.3 level 3
Fast transient bursts IEC801.4 level 4
Surge withstand IEC255-5
Enclosure
Enclosure: Grey ABS plastic with finger proof terminal covers
Enclosure Code: Case IP50, terminals IP10 to IEC529 and BS5490
Isolation: 4kV rms 50Hz 1min (to IEC 414) between input / output / case / AC auxiliary
(2kV rms 50Hz 1 min for EK energy transducers)
1kVdc / 600Vac between Watt & Var outputs (EPQ units)
Mounting: 35mm DIN rail (DIN-EN 50022)
Markings: CE marked
Options
Non Standard Calibration
All transducers are supplied calibrated to standard input values as detailed in the individual specifications,
however non-standard calibration input values can be specified (subject to technical viability).
Calibration Certificate
Calibration certificates traceable to national standards can be supplied on all transducers.
Conformal Coating
A conformal coating can be applied to the transducer circuitry during manufacture for transducers that will be
operating in harsh environmental conditions.