Architecture Building Services: Assignment-1
Architecture Building Services: Assignment-1
Architecture Building Services: Assignment-1
Architecture Building
Services
Semester IX
Submitted by
Name: Santhu Maji
Roll no:16SA20
CONTENT
1. DRAINAGE SYSTEM
2. PLUMBING SYSTEM
4. HVAC SYSTEM
HVAC
ELECTRICAL SYSTEM
2
DRAINAGE SYSTEM
Basically refers to All the piping within the private and public
premises which Conveys sewage ,rainwater and other liquid waste
to a point of disposal. A Drainage system does not include the
mains of public sewer systems or a private Or a public sewage
treatment or disposal plant.
Traps
- Traps catches water after each discharge from a fixture so as not
to allow unpleasant and obnoxious gases In a sanitary drainage
system to escape through the fixture
3
Types of traps
According to shape
1. ‘P’ trap
2. ‘Q’ trap
3. ‘S’ trap
According to use
1. Floor trap
2. Gully trap
3. Intercepting trap
4. Grease trap
Vents
Vents are the extension of soil and waste stacks through the roof
and a system of pipes largely paralleling the drainage system for
the admission of air and discharging of gases
4
Insception chamber
Inspection chambers are access points to underground pipework
which allow maintenance and the removal of blockages. When
installing any type of underground drainage there’s a very high
chance that you’ll need to install an inspection chamber.
Manhole
A manhole is an opening to a confined space such as a shaft, utility vault,
or large vessel. Manholes are often used as an access point for an
underground public utility, allowing inspection, maintenance, and system
upgrades
5
PLUMBING SYSTEM
1.Single stack system:
6
2. Two pipe System:
7
TYPES OF WATER DISTRIBUTION SYSTEM
1.Direct Pumping System :
-Tanks must be sufficiently elevated to achieve required pressure.
-This system is adopted when adequate pressure is available round
the clock at the topmost floor. With limited pressure available in
most city mains, water from direct supply is normally not available
above two or three floors.
-For proper operation of the system, the gravity tank is located at
least 30 ft or 10 m above the highest outlet or consumer.
-In tall buildings it's necessary to use pressure reducing valves in
the lowest floors before the fittings.
8
2.Overhead Tank System:
Overhead tanks ensure both water pressure and water supply in
case of power failure.
-This solution requires pressure reduction valves on each floor in
order to avoid undesired high static pressures at the tap, which
creates unacceptable noise while tapping.
-In this model the upper six floors require a separate booster
system in order to create sufficient pressure.
-The static pressure there is too low due to the insufficient
geometric height to the roof tank.
2. Hydro Pneumatic System:
-Is a modernization of the older gravity tank method of water
supply.
-Its main purpose is to control or boost a limited supply pressure
to a higher or more uniform value so that a continuous and
satisfactory water supply will be available at all fixtures within the
system.
-An airtight pressure vessel is installed on the line to regulate the
operation of the pumps. The vessel capacity shall be based on the
cut- in and cutout pressure of the pumping system depending upon
allowable start/stops of the pumping system.
2. Multiple Storage Tank System:
-In this System Bldg is divided into sub zones of 8-10 floors.
-Domestic and Flusing Tanks are provided for such zones
independently on Service Floors.
-Suction Tank Capacity is taken as 1 day’s Requirement.
-Connection to individual zones is either combined or separate.
9
HVAC SYSTEM
Heating, ventilation, and air conditioning (HVAC) system is designed
to achieve the environmental requirements of the comfort of
occupants and a process.
HVAC systems are more used in different types of buildings such as
industrial, commercial, residential and institutional buildings. The
main mission of HVAC system is to satisfy the thermal comfort of
occupants by adjusting and changing the outdoor air conditions to
the desired conditions of occupied buildings Depending on outdoor
conditions, the outdoor air is drawn into the buildings and heated
or cooled before it is distributed into the occupied spaces, then it is
exhausted to the ambient air or reused in the system. The selection
of HVAC systems in a given building will depend on the climate, the
age of the building, the individual preferences of the owner of the
building and a designer of a project, the project budget, the
architectural design of the buildings
Basic Component Of Hvac System
The basic components or equipment of an HVAC system that
delivers conditioned air to satisfy thermal comfort of space and
occupants and the achieve the indoor air quality are listed below
Mixed-air plenum and outdoor air control
Air filter
Supply fan
Exhaust or relief fans and an air outlet
Outdoor air intake
Ducts
Terminal devices
Return air system
Heating and cooling coils
Self-contained heating or cooling unit
Cooling tower
10
Boiler
Control
Water chiller
Humidification and dehumidification equipment
11
Some buildings can have multiple zones or have a large, single
zone, which needs central HVAC systems to serve and provide the
thermal needs However, other building may have a single zone
which needs equipment located inside the zone itself, such as small
houses and residential apartments. This type of system is
considered as local HVAC systems since each equipment serving its
zone without crossing boundaries to other adjacent zones (e.g.,
using an air conditioner to cool down a bedroom, or using an
electrical heater for the living room). Therefore, a single zone
requires only one-point control point connected to a thermostat to
activate the local HVAC system. Some buildings have multiple local
HVAC systems as proper equipment serving specific single zones
and controlled by the one-point control of the desired zone.
1.Window air-conditioner
12
This system is a packaged device consisting of a vapor compression
refrigeration cycle that contains a compressor, a condenser, an
expansion valve, and an evaporator, in addition to a fan, a filter,
control system and housing. Window air-conditioners can be
installed in a framed or unframed opening in building walls and in
window openings without any ductwork and distribution the
cooling or heating air effectively inside the conditioned space.
2.Unitary air-conditioner
It is similar to window air conditioners from the equipment
perspective, but it is designed for commercial buildings. It is
installed on the exterior wall of the building and generally located
near the floor-wall intersection. Every single zone will contain one
unitary air-conditioner as in each guest room in many hotels
13
It consists of a vapor compression refrigeration cycle; heat source
such as heat pump and electric resistance; an air handler such as
dampers, filter, and fan; and control devices. This system may be
connected to ductwork and serve a large-size single zone that
cannot be served by unitary or window air conditioners.
4.Split systems
The split systems contain two central devicesthe condenser,
located outdoor, and the evaporator, located indoors. The two
devices are connected by a conduit for refrigerant lines and wiring.
This system solves some issues of small-scale single-zone systems
since the location and installation of window, unitary or rooftop air
conditioners may affect the esthetic value and architectural design
of the building. The split systems can contain one condenser unit
and connected to multiple evaporator units to serve multiple zones
as possible under same conditions or different environmental
conditions
14
ELEVATORS & ESCALATORS
Elevators
This are use to function efficiently and to provide access for the
elderly and disabled, modern offices and public buildings are
provided with suitably designed lift installations. Planning (as with
all services) should commence early in the design programme.
Priority must be given to locating lifts centrally within a building to
minimise horizontal travel distance. Consideration must also be
given to position, relative to entrances and stairs. Where the
building size justifies several passenger lifts, they should be
grouped together. In large buildings it is usual to provide a group of
lifts near the main entrance and single lifts at the ends of the
building. The lift lobby must be wide enough to allow pedestrian
traffic to circulate and pass through the lift area without causing
congestion. For tall buildings in excess of 15 storeys, high speed
express lifts may be used which by-pass the lower floors.
15
Requirements:
. Necessary in all buildings over three storeys high.
. Essential in all buildings over a single storey if they are accessed
by the elderly or disabled.
. Minimum standard -one lift per four storeys.
. Minimum walking distance to access a lift - 45 m.
. Floor space and lift car capacity can be estimated at 0,2 sq.m per
person.
16
17
Escalators
18
Escalator configurations vary depending on the required level of
service. The one-directional single bank avoids interruption of
traffic, but occupies more floor space than other arrangements. A
criss-cross or cross-over arrangement is used for moving traffic in
both directions.
19
FIRE FIGHTING SYSTEM
Fire fighting systems and equipment vary depending on the
age, size, use and type of building construction. A building
may contain some or all of the following features:
fire extinguishers
fire hose reels
fire hydrant systems
automatic sprinkler systems.
Fire extinguishers
Fire extinguishers are provided for a 'first attack' fire
fighting measure, generally undertaken by the occupants
of the building before the fire service arrives. It is
important that occupants are familiar with which
extinguisher type to use on which fire.
Most fires start as a small fire and may be extinguished if
the correct type and amount of extinguishing agent is
applied whilst the fire is small and controllable.
20
Fire hose reels
Fire hose reels are provided for use by occupants as a 'first
attack' fire fighting measure but may, in some instances, also
be used by firefighters.
When stowing a fire hose reel, it is important to first attach the
nozzle end to the hose reel valve, then close the hose reel
valve, then open the nozzle to relieve any pressure in the
wound hose, then close the nozzle. This achieves two
principle objectives:
A depressurised hose and hose reel seal will last longer
than if permanently pressurised.
When the hose reel is next used, the operator will be
forced to turn on the isolating valve, thus charging the
hose reel with pressurised water supply, before being
able to drag the hose to the fire. A potential danger exists
if the operator reaches the fire and finds no water is
available because the hose reel valve is still closed.
21
Because hose reels are generally located next to an exit, in
an emergency it is possible to reach a safe place simply by
following the hose.
22
Pipes are always filled with water. Heat from fire opens a
sprinkler head,
Usually only one or two heads open,
Water flows until it is shut off,
The open sprinkler head(s) is replaced and the system is
reset.
Deluge system
Pipes are not filled with water (or gas),
All sprinkler heads are pre-opened,
23
A signal from a detection device mechanically opens a water
valve,
-water fills the pipes and flows from all heads,
-water flows until shut off,
-system is reset.
24
Reliability and minimizing lost revenue
Minimizing maintenance costs
Minimizing energy costs
Adaptability
1 OPERATION ROOM
2 A.C UNIT
25
Negative pressure patient isolation room with HVAC Controls pop outs
26
IsolationAir® is a portable
contamination control system ideal for
hospitals, extended care facilities, and
emergency preparedness centers. This
system maintains a sterile environment
in an isolated room, which prevents
cross-contamination throughout the
rest of the facility— creating a better
environment for patients and staff.
27
The Type 1 EES consists of three separate branches capable of
supplying power considered essential for life safety and effective
facility operation during an interruption of the normal power
source.
Life Safety Branch
Critical Branch
Equipment Branch
28
CENTRAL MEDICAL GAS DISTRIBUTION SYSTEM
29
• Nitrogen (N2)
• Medical vacuum
1. Sources
2. Piping networks
30
3. Valves
6. Secondary equipment
Manifold systems
31
Medical Gas Distribution System
32
33
HOSPITAL WASTE MANAGEMENT SYSTEM
34
Medical Waste Management Flow Chart
35
SCHEME FOR WATER WASTE
36